Professional Documents
Culture Documents
CONTENTS
SYLLABUS
UNIT I
Power System Network Matrices
- 1: B.E. VIll Semester (Electrical)
Definitions of Graph theory
P.5
Incidence Matrices
Primitive matrices
P. UNIT I
P.10
Calculation of Network matrices by Singular Transformation cidence and etwork Matrices: Graph
incidence
Methods
P.15 Matrices, Primitive network, formation of network
UNIT -II
Power System Network Matrices -2: matrices by Singular transformations.
Derivation of addition of branch and addition of link P.49,55
Formation of ZBus and YBUs by algorithms
UNIT II
P.60, A-1
Modification of Zeus for changes in power system Algorithm for formation of Bus Impedance and Bus
P.59
UNIT III
Admittance matrix for system without mutual coupling.
Three Phase Network Matrices:
Three phase balance and unbalanced network elements for UNIT
balance and unbalance excitation. P.87
Formation of sequence impedance matrix. Three phase Networks: Three phase balance network
P.93
Short Circuit Studies: elements with balanced and unbalanced excitation,
Short circit calculation for Balance three phase network using
ZBUs (Three incidence and network matrices for three phase element.
phase to ground fault and Line to ground fault)
P.185 to 199 Algorithm for formation of three phase bus impedance
UNIT-IV matrices without mutual coupling.
Load Flow Analysis:
Power system load flow equation .118 UNIT N
Solution technique: Newton-Raphson method in rectangular
equations,
Load Flow Studies: Power system load flow
form without PV bus P.129, 124, A-2
Transient Stability Studies Newton-Raphson and
SOution technique, Gauss-Seidel
Modlling of synchronous machine P.222
fast
Power system network for transient stability studies P.227 231
to
voltage control
Numerical solution of swing equation by Modified Euler method decoupled technique with and without
P.233 and phase shifting8
OUSes. Representation of tap changing
K' = A
B=AK
-
(e) Augmented cut-set Incidence matrix (B):
This is a non-singular square matriX with rank (n -1)
Fictitious cut-sets, called tie cut-sets, can be introduced in order
d) Basic cut-set Incidence matrix (B); -
The incidence of elements to basic cut-sets of a connected that the number of cut-sets equals the number of elements. Each tie
c'y+C'a
=
c'[z]i ---Gi) Table (1): Formation of network matrices by singular
the incidence of elements to transformations
Since the matrix C shows basic
algebraic sum of the voltage around each ho. Ndwork matrices
loops, C7 gives the
loop. In accordance with
Krichhoff's voltage law, the algebrain sum Primilive Loop Ba Branch
loop is zero. Hence,
of the voltages around a
c'v= ---(ii)
sum of the source voltao. ClaC
Similarly, C'e gives the algebraic tages LOOP ZB.
powers in the primitive network is interconnected network. The performance equation of the primitive
(j*)'v. The power in the
primitive and interconnected networks must be equal, network in admittance form is premultiplied by B° to obtain
that is, the
transformation of variables must be power-invariant.
Hence B'i+B'j=B'Iy - -(1)
TBUS)'EBUS =
G'v ----- Since the matrix B shows the incidence of elements to basic
Taking the conjugate transpose of equation
(3), Cut-sets, B'i is a vector in which each element is the algebraic sum
BUs)
Since A is
=
''A
areal matrix
of thecurrents through the elements incident to a basic cut-set.
The elements of a basic cut-set if removed divide the network
BEBR --------(V)
4
0 1 O-1
IBR B'[y]BE BR Drawing the basic sample network from the above
---(vi)
The relation between the branch currents and the branch
voltage is
IBR YBR EBR --(Vii)
lt follows from equations (vi) and (vii) that
YBR
B
y]B
The basic cut-set matrix B is a singular matrix and theretore
B'ly]B is a singular transformation of [y].
The branch impedance matrix can be obtained from
ZBR YBR = (B'[y]B)
AD COMP. APP. IN ELECT. ENGG. (B.E, VIII Sem. Elect.) 21
04 PUU 06 PU
1025 PU
-
0
0 1025 PU
O
Basic cut set matrix B
elcs (A) (B) (C)
0 0
B_20 1
B 4
0
0 0 1
-1 1
a-1
1 0 0-1
B 0 10 -1
0 01
As YBR B ly]B
Now from the given data
22 ABD COMP. APP. IN ELECT. ENGG. (B.E.
VIl S Elect.) 23
IN ELECT. ENGG. (B.E. VII Sem.
0.1025 0 0. 0 WD
COMP. APP. IN
0 10
Z =
0.4 0 0
0 0.6 0
0 0 0.1025
0.4 0 0 20 0 22
0 0.1025
=yl= 0 0
0.1025
o L3
0 0.6 30
0
10 0 -1 0.4 0 0
YBR =0 10 0.1025 0
-1
0 0 1 1 0.1025 0
0 0.6
1 0 0 0.12
0 1 0 Soln. (i) Corresponding Oriented Graph.
0 01 3
-1 -1 1
1
0.6 0.6
0.60.7025 -0.6
2
L-0.6 -0.6 0.7025
Prob.3. A four Bus sample system is shown in figure
Consider ground as reference and the values mentioned as self
impedances in p.u., obtain the following :
(i) Oriented Graph, Tree and Co-Tree.
Gii) Basic loop incidence matrix.
(iii) Basic cut-set incidence matrix. Where Branch (tree)
0 0 0 0 0.12
(iii) Basic cut-set Incidence Matrix Now Loop impedance matrix ZLoop
B D
0
ZLoop =C'[z]C
20 1
0 0 01 0 0 0 0 0
0 1 0
U 0 02 0 0 0 0
B
0 0 0 1
10 0 -1 1
0|| 0 0 022 0 0 0 0 1
5-1 0 0 1
B 11 1-1 -
10 0 0 03 0 0
4-1 -1 -1 1
0 0 0 0 043 01 0
0 0 0 0 0 012] 0 1
iv) Impedance matrix 0.83 0.4
10.10 0 0 0 0 0
0.4 0.94|
0.2 0 0 0
0
0 0.0 0.22 0 0 (IV) C = 0
0 0 0.30 0 0 0
5 0 0 00 0.43 0 -1-
-1 0
6 0 0 0 0 0 0.12
B-1-1 -1
-
0
Therefore B=
-1 -1
which is equal to Cb
1.e. The primitive impedance matrix of the given network
Hence proved that Ch =- B
26 VBD COMP. APP. IN ELECT, ENGG.
(B.E, VIl Sem 27
Sem. APP. IN ELECT, ENGG. (B.E,
VII Sem. Elect.)
Prob.4. Find YBR for a power system Elec VIWD cOMP,
shown in gure
Positive sequence reactances of the comp. are markoa 1 00 1
diagram. B,-0
1
0 1
(W.03)
00 1
1
04 PU 0 6 PU
Now y= z
networkk
impedance matrix of the given
and the primitive
O.1025 0 0 0
0.1025 PU
0.4 0
0-1025 PU Z 0 0 0.6 0
0 0 0.1025
Soln. YBR = ? find out [y).
Using partitioning method of matrices to
Now as YpR = (B' [y]B) 9.75 0 0 0
First we will evaluate the Basic cut set matrix B. 2.5 0
Corresponding oriented graph (with branches and links, i.e. we get, y= 1.67 0
0 0
tree
and co-tree) 0 9.756|
0 0
975 0
o 25 0
0 01 0 0
YBR 0 10 1
0 0 1
0
0 01 1J|o
0 167
o 975
00 0 1
o |1 1
B =0 0 1
[o -1 0
A =0 1
-1
0 0
-1 0 0
(i) Bus Incidence Matrix; K' =-1-1 0
-1 -1-1
1-1 0
o -1 0 [-1 0 11 0 01
-i-1 -1-1 o-0
0
=0 1
A K 1
2 -1 0 Ab
-1-1 -111
1
1
A 01
0 0
6 0 0 -1 0 0.23 0 0 0 0
(ii) Branch Path Matrix 0 0 0.4 0 0 0
00
Z
elpath
0 0 0.13 0
0 0 0 0.6 0
1-1-1 -
0 0 0 0.14
K =2 0 -1
-1 9.09 0 0 0 0 0
30 0
0 4.35 0 0 0 0
ii) Basic cut-set Matrix
elb y=z 0
0
0
0
2.5
0 7.692
0
0 0
10 0 00 0 1.67 0
2 01 0
0 0 0 0 7.142
00 1
Ub
B= Now A [y]A
1 0
-1 1
0 0 0
0
0 0 1
B =0 -1 1
-1 1
0x
6 1 1
00 -1 0-1 -1]
30 31
VBD COMP. APP. IN ELECT. ENGG. (B.E.
E. VIl
VIll Sem
Sem. ENGG. (B.E, VIl
Sem. Elect.)
Elec INELECT.
9.09 0 0 cOMP
MP. APP.
0 0 0 -1 0 VID
00 Incidence Matrix (A)
4.35
0
0
2.5
0
0
0
0
0
0
1-1
10
() Bus
0 0 0
1-
0 0 0 7.692 0 0
0-1 0 0 0
0 0 0 0 1.67 0 0
1 0
I0
0 0 0 0 0 7.142 0 0 A =4 0
0 -1 0 0
13.44 -
4.35 0
0 0
2 0 1
3 0 0
1
0
B 4| 0 0 0 1
7 0 1
0 1
5 C 4 0 -1 -1
10 0
3 ref, node
01 0
70 0 1
32 33
BD COMP. APP. IN ELECT. ENGG. (0.E. ELECT. ENGG, (8.E. VII Sem, Elect.)
sem.t
Vi Bem APP. IN
Prob.7. Consider the following given power Elea DD
COMP
power
network. systen
ot
Calculate the incidence matrices.
-7
s-5
Solution: -
The corresponding single line and orient
nted b-4
connected graph is drawn below (with 0 as reference node) Branch 1-3
-- Link
cotree of the orien ted connected graph.
Fig. Tree and
(6)
1
3
-
O A 4
(c)
Figure: Power system representation
(a) Single line diagram
(b) Positive sequence network diagram
(C) Oriented connected graph
35
(B.E. VII Sem.
Elect.)
BD a.E. VIll Sem.
COMP. APP. IN ELECT. ENGG. (B.E. Sem cOMP.APP IN ELECT. ENGG.
Ele D and. Tie cut-set
(b) Bus Incidence matrix (A) cut-set Incidence matrix (B)
(d) Basic
(B)
Incidence matrix
bus
bus Buses
As
AL
Basic cut-set
Tie cul-set
Fig. Basic and tie cut-gets of the orien ted connec ted graph.
(c) Branch path Incidence matrix (K)
path
Us
B 4
2 -
5
6 B
36
BD COMP. APP. IN ELECT. ENGG. (B.E. VI som.
Eleu ELECT. ENGG. (B.E, VII Sem. Elect.)
31
Basio cut-aeta Tie eut-eote COMP. AP
APP. IN
C
8- 3
- C
5
U
Basic cut-sets Tie eut-sets
Us 0
The matrix (a) can be partitioned as follows
Open loops Basic loops
B C D E G
B U
1
3
(e) Basic loop Incidencè matrix (C) and Augmented 1
1 -1
Incidence matrix (C) C4
U C
Basic lop
- Open loop
0 U
39
IN ELECT. ENG0, (8.E. VIf Sem. Elec1.)
38 D cOMP, APP. IN ELECT. ENGa. (B.E. vIl Gem.
Sem. cOMP. APP.
EleuVD
Prob.8.
TO
(1)
(2)
Fig. Sample netuwork.
-- -Dranch
Linh Fig. Tree and cotres
of the oriented eonnacted
sroph of sampla natioork,
a. Form the incidence matrices A, A, K, B, B, C, and connected graph of
a. The branches and links of the oriented
for the network shown in Fig. above. network are shown in figure above. The element-node incidence
the
b. Form the network matrices YBUS» YBR, and ZLonn0op
h
matrix is
singular transformations.
Soln.
The impedance data for the sample network is given in Tahl e
below: 2
The network contains four nodes and five elements, that is,
=
n=4 and e 5. The number of branches is
b=n-1=3
A
-1
and the number of basic loops is
l=e- n+ 1
=2
41
VBD COMP. APP. IN ELECT. ENGG. (B.E. VIll APP IN ELECT. ENGG. (B.E. VIl Sem. Elect.)
Sem. Elect VBD COMP.
.
El
The branch-path incidence matrix is
path
3 -
The basic and tie cut-sets of the oriented connected graph
ph
the network are shown in fig. below. The basic cut-set incidenes
Basic loop
Open loop
D
loops
Fig. Basic and open
of the oriented con-
nected graph of sample
network.
matrix is
A BC The augmented cut-set incidence matrix is
AB C D E
2
B 3
The basic and open loops of the oriented connected graph are
shown in Fig. below. The basic loop incidence matrix is
D E
O
-
Fig. Basic and tie
C- 3
Basic cut-set cut-sets the oriented
Tie cul t connected graph of sample
network.
42 VBD COMP. APP. IN a.E. VIl
ELECT. ENGG. (B.E. VIl Sem.
Ser 43
Elee
ELECT. ENGG. (B.E. VIl
Sem. Elect.)
The augmented loop incidence matrix is aND COMP. APP. IN
obtained by singular
admittance matrix
The bus
N B C D E ransformation is
C = 3
7
of the sample networkkis
b. The primitive impedance matrix :
12 3 4 5
2 0.1 0.5
le] =3 0.5
0.2 0.4
0.2
2.083-0.417 -1.042
-0.417 2.083 0.208
0
ul3 2.000
5.000
44
VD COMP. APP. IN ELECT. ENGG. (B.E.
VIl Sem. ENGG. (B.E, VII Sem. Elect.)
45
38
E
ENGG. (B.E.VIl
VIL (B.E, VII Sem. Elect) 7
46 D COMP. APP. IN ELECT. Sem.Elec COMP,APP,IN ELECT. ENGG.
D Consider
OUESTION A four Bus sample system is shown in figure.
REPEATEDLY ASKED UNIVERSITY ONS Prob.3.
primitive ne ence and the values mentioned as self impedances in
referen
Q.1. Show the representation
of network ground as following
impedance and admittance form. IS-02 the
p.u, obtain
Refer Q.3,P.10] ) Oriented Graph, Tree and Co-Tree.
obtain loop from singula incidence matrix,
Q.2. Derive the relation to singu (ii) Basic loop
[S-00, 03, W-03 incidence matríx.
transformation. (iii) Basic cut-set
[Refer Q.5,P.13] =-B
matriv (iv) Verify the relation Cb
Q.3. Derive the relation to obtain Bus admittance Ax irom
matrix. IS-03)
singular transformation. [S-02 (v) Form loop impedance
Refer Q.6,P.15) [Refer Prob.3,P. 22]
Q.4. Derive the relation to obtain Branch Impedance
nce matrix Prob.4. Find YBR for a power system shown in figure.
from singular transformation. S-01, W-00, 021 sequence reactances of the comp. are marked on diagram.
Positive
Refer Q.7,P.17] (w.03)
Prob.1.For a particular power system element-node incidenos
[Refer Prob.4,P.26]
matrix A is given by,
|1 -1 0 0
1 0 -1 0
A =0 0 -1 1
1
0-1
0 1-1 0
Find
) Branch-path incidence matrix.
(i) Basic cut-set matrix.
(ii) Loop incidence matrix. (W.03)
[Refer Prob.1, P.19]
Prob.2. Find YBR for a power system
shown in fig.Q 10).
Positive sequence reactances
of the comp. are marked on diagram.
(W.03)
IRefer Prob.2,P.21]
UNIT-II COMP, APPL. IM ELECT, ENGG.(B.E. VIl Sem, Elect)
49
aD
ALGORITHMS FOR FORMATION x
m+l) x (m+1). The
new voltage and current vectors are a dimension
OF NETWORK MATRICES o 41)x1, To determine the new bus impedance matrix requires
elements in the new row and column.
the calculation of the
Q.1. Show the representation of partial networl And onl partial network
If p-q is a link, no new bus is added to the
Write down the performance equation of the same.
case, the dimensions of the matrices in the performance
Ans. Performance equation of a partial network: The Ia this
elements of the bus impedance
representation of partial network is shown in figure below, equation are unchanged, but all the
Assume that the bus impedance matrix ZBUs is known Tor
for matrix must be recalculated to include the effect of the added link
a
partial network of m buses and a reference node 0. The performa
nance Q.2. Derive equations useful for formation of ZBUS
equation of this network, is element p-q is a branch to the exísting partíal
when the added
EBUS = ZBUSIBUS network
network Start from performance equations of a partial
and its representation.
Ans. Addition of a branch
The performance equation for the partial network with an
Partial E2
Ne twork
E1 added branch p-q is written below
P m
E Z Z12 Z1p
Zm 14
Em
E2 Z21 Z22 Lap Zam Z2a l2
Reference.
Ep
=P
Zp Zp2 Lpp Zpm Lpa p
where EBUS = an m xl vector of bus voltages measured
with respect to the reference node.
IBUS = an mxI vector of impressed bus currents. Zml Zm2 Zmp Lmm mq
Em m
When an element p-q is added to the partial network it may
be a branch or a link.
Eq Zgl Zg2 Lqp Zqm Laa
If p-q isa branch, a new bus q is added to the partial
network and the resultant bus impedance matrix is of dimension
1
48 VBD COMP. APPL. IN ELECT. ENGG. (VIll Sem. Elecl
UNIT-II
ALGORITHMS FOR
FORMAT
ATION WwDCOMP. APPL,
IN ELECT ENGG.(8.E. VIl Sem, Elect) 49
NETWORK TRICE Iont:1) X (m+1). The new voltage and current vectors are a dimension
OF (m )xl. To determine the new bus impedance matrix requires
+1)x1,
netu
representation of partial twork only the
calculation of the elements in the new row and column.
Q.1. Show the
performance equation
of the same. If p-q is a ink, no new bus is added to the partíal network.
write down the
equation of a partial netwe etwork: this case, the dimensions of the matrices in the performance
Ans. Performance figure below
The fa
Zpm
where EBUS = an m xl vector of bus voltages measured
Ep p2 Lpp **
48
VBD COMP. APPL. IN ELECT, ENGG. (VII Sem. Elecy
IN ELECT, ENGG. (B.E. Vil
Se
50 BD COMP. APPL. 51
The representation of
partial network with ded branch
added wwD cOMP. APPL. IN ELECT. ENGG.(B.E. VII Sem, Elect.)
shown below.
i E=Zili
E2 Zzili
*******
Partial E, Zpili
ne twor k Element@
P-9
Em2mil ii)
Eg-Zqili
Re ference
Letting I =Iper unit in equation Gi), Zgi can be obtained
and therefore, The voltages at buses p and q are related by equation (iii)
pq.pa Vpo and the current through the added
element is
pq
Ypa.pq pq- =-1 x)
Substituting for Vpo from equation (vi) The voltages across the elements of the partial network are
elements by (iv)
given by equation (vi) and the currents through these
Vpg
Ppa(Ep-E) .(Vil) From equations (iv) and (x), we have
pq.pq
pqYpapq pg tYpq.pa Vpa =-1
Substituting for vpg in equation (ii) from (vii)
and therefore,
(Ep -Ea)
Eg =Ep +9po
pq.pq tpa.pa Ypo
pq Y pq.pg
Finally, substituting for Eq,Ep,Ep and Eo from equation
(ii) with Ii Substituting for Vpo from equation (vi)
=l
Pa.pa piZoi) l+Ypq,pa (Ep-Eo)
Zg pq (xi)
Ypa.pq
i 1,2..., m
Ypq.pq
V
i#9
ABD COMP. APPL. IN ELECT. eVIlSem.
ENGG. (B.E, VI
Elhea 55
APPL. IN ELECT, ENGG.(8.E, VII Sem, Elect)
Substituting for vpg in equation
(ii) form (xi) aMyD COMP.
ZgUs when
(Ep-Ea) 0.3. Derive equations useful for formation of
1+ papo added element of p-q is a link to the existing partíal network.
Eg=Ep+ Ypap
the
iart from the pertormance equations of partial network and its
weDresentation including modification after elimination of
Eq.Ep,Ep, Ea from equation
equation (ix) [W-03]
Finally, substituting for wilh fictitious link.
Ans.[Student are requested to go through Q.2 before
oceeding further)
(Zpq Zoq) Addition of a link :
99Zpo +*P9po pa XI
The representation of a partial network
pa
added brane
If there is no mutual coupling between the and
elements Or
other elements of the partial network, then of Ypq.po are
Partial Element
Networkk
zeroand Lpq.pq
D-
pqpq
It follows from equation (vii) that
m
Zqi =Zpi i=1,2,.. Reference
i#q
As the added element p-q is a link, the procedure for
and from equation (xi) that recalculating the elements of the bus impedance matrix is to connect
in series with the added element a voltage source e; as shown in
Zgg=pq t Zpapg figure below. This creates a fictitious nodel which will be eliminated
Furthermore, if there is no mutual coupling and p is
later. The voltage source e is selected such that the current through
the
reference node,
the added link is zero.
pi 0 i=1,2......, m The performance equation for the partial network with the
added element p-I and the series voltage source e is
iq
and
Zgi =0 i
=1,2.., m
i+9 Partial Element p-q
Also Network
6Ti=1
Zpg =0 per unit
and therefore,
Zgg Zpap
VI
IN ELECT. ENGQ. (8.8. Sem.
Eleo COMP, APPL
APPL IN ELECT, ENGG (,E, VII Sem, Elect.) 57
ARD cOMP. APPL. WD
P Y p! t Ypl po Vpo
Zm Zu
where
Vpl
yplpo pa
Zpp pm Zpl Yplpl
Zp
Since
and Ypl.pl Ypqpa
**
Yplpapq.pg
**
Lmp mm Lml
Zm
***
Zm2 **
then
Zip ZIm pq.pa Vpo
Z Zi2 Vpl 4)
pq.pq
Since Substituting in order from equations (4), (vi) and (2) with
..(1) =1 into equation (3)
yields
e =
E-Eq I
can be determined by injecting current at the
th
P9po(Zpi -Zai) ,
ZnZpi Zgji+
a
the element Z i=1,2.. m
Ypa,pa 5)
the node with respect to bus a
bus and calculating the voltage at
Since all other bus currents equal zero, it follows from equation
(1) i#l
that The element Zij can be calculated by injecting a current at the
E = ZI k =
1,2.., m (2) 1
th bus with bus q as reference and calculating the voltage at the
e = Z,I bus with respect to bus q. Since all other bus curents
equal zero, it
Letting I=l per unit in equation (2) Zjcan be obtained follows from equation (1) that
directly by calculating e Ek = Zkll k=1,2,. m (6)
The series voltage source is e =Znl
e =Ep -Eq-Vpl .(3) Letting l =lper unit in equation (6) Zu can be obtained
Since the current through the added link is directly by calculating e.
'pq0 The current in the element p-l is
the element p-l can be treated as a branch. The current in this pl-I =-1
element in terms of primitive admittances and the the voltages
voltages across u This current in terms of primitive admittances and
elements is
COMP. APPL. IN ELECT. ENGG. (B.E
a,E.VIW
58 D Som.Ela COMP.APPL IN ELECT, ENGG.(B.E, VIl Sem, Elect.) 59
ND
across the element is therefore,
plYpl.p t
Vpl pl.poa Vpa-1 and
Zu qltpq,pq
Again, since The elements in the row and column of the bus impedance
network are found from equations
plpo-Pq.po and ypl.plpqpq
gmented partial
matrix for the
(8). It remains calculate the required bus impedance matrix
to
(5) and
then aclude the effect of the added link. This can be accomplíshed by
(o inc
I+pqpa Vpo 4ifving the elements Zij, where i,j= 1,2,.,
m, and eliminating
p pq.pq
.th row and column corresponding to the fictitious node.
Substituting in order from equations (7), (vi) and (6) with the I is eliminated by short-circuiting the series
The fictitious node
= l into (3) yields e.
I voltage source From equation (1)
=Zpl-Zql
+ppa (Zpl-Zat)
EBUS = ZBUS IBUS + Zill ..(9)
e
Zu
Ypq,pq 8 = ZijlBUs +Znl =0 ...(10)
and
elemo
the added element
If there is no mutual coupling between ang where ij =1,2,....,m. Solving for I from equation (10) and
network, the elements of
other elements of the partial PLpo substituting into (9)
Zi
atre
It follows from equation (5) that which is the performance equation of the partial network
Z-Zpi-qi i= 1,2,.., m including the link p-q. It follows that the required bus impedance
i#l matrix is
ZI2=-0.23 = Z2
Thus ZpUS = O0.13 0.13
Zy3=-0.47 = Zg
2 0.13 0.36
Zu= 0.95
1s a Dranch from p = .
i) Again adding element 3, Wnich Thus,
Z31 Z32
2 0-0.23 -0.47 0.95
Now eliminating the l row and column
Z 0.95
Z32Z22 0.36 = Z23
Z33 = 0.6
Zi2-Z12 Zi12 - 0.13 (0-023) = 0.13 = Z21
Zu 0.95
=0.13- (0-0.47)=0.13-Z31
Thus,
Z13 =Z13-
ZBUS = O 0.13 0.13 0.13 0.95
0.13 0.36 0.36 0.36-0,23)(-0.23) - 0.304
30.13 0.36 0.6
Z22
=Z22Z 0.95
(-0.47)(-04)=0.367
33 =Z33-4313
Zu 0.95
1
(-0.23)(-0.41)
iv) Now adding and element 4, which is a link fro P Z23-Z23- 0.36- -0.246=Z32
9=3. Z 0.95
Vi
IN ELECT. ENGG. (B,E,
E. VIl
VBD COMP. APPL. Sem. APPL. IN ELECT. ENGG.(B.E. VI1 Sem. Elect.)
COMP. APP
64 Elea VBD 65
ement 2 which is a branch from
Thus,
O (i) Adding p = 3 to q = 1.
0-25 0.2
0-25 ZBUS 3 0.25 0.25
1
0.25 0.4
0.15
(iii) Now again adding element 3 which is a branch from p = 1
Z23Z21 Z22
O Z23 Z3 0.25
=
Z32
Z21Z11=0.4= Z12
Z22 0.6
Thus, 3 O
30.25 0.250.25
1) Starting with element a branch fromp=o
1
which is
3 where p =
0 is reference node
ZBUS= O 0.25 0.4 0.4
0.25
ENG
ELECT. ENGG. (B.E.VIl DD IN ELECT.
ELECT. ENGG. (B.E. VIll SEM. ELECTRICAL) 67
COM. APP.
IN VIl Se
55 WBD COMP. APPL. Sem.Elec sMMD
is a link node p
rom node p == 00 t
(iv) Now adding element 5 which to q= Thus,
matrix.
The augmented impedance 0.153 0.096 0.096
Z3
ZBUS |
0.096 0.153 0.153
0.25 0.25 0.25
0.096 0.153 0.353
O0.25 04 04 Z similar fashion, solving for element 6 which again is
(v) In the
2 0.25 04 0.6 Z2 q =2.
a link from P=O to
Z3 1 42 Z After final elimination,
we get
Now eliminating the 1" row and column O 0.0716 0.114 0.063 Z
B=0,25-0.25)(-0.25) _ 0.039 0.063 0.146 Zal
Z33 Z33- 0.153
Z 0.65 Z13 Z1 Z Z
Z31-231-L_0.25- (-0.25-0.4) _0.096 =Z13 ZI3 0.0326 = Za
0.65 ZI1 = 0.051 = Zil
Zs2 Z32- 2=0,25-25)-04)-0.096-Z Z12 =-0.083 = Z2
0.65
-04--04)-0.4) -) Z = 0.334
Zi1=Z-
0.0716| 0.039 0.0326
3) 0.137
Z22 =Z22- Za20.6 U.4)-0.4)-0.353 0.071 0.114 0.063 0.051
Zu 0.65 6
Zi2=Z2-Z12=04-0.4)(-0.4) = 0.153 0.039 0.063 0.1460.083
Zu 0.65 0.032 0.051| 0-083 0.334
68
VBD COMP. APPL. IN ELECT. ENGG. (B.E
E.VIlSem.Ele oMP.
COMP.
ELECT ENGG.(B.E. VIll Sem. Elect.)
IN ELECT,
APPL. IN
69
Zayai2 0.039-526-
(0.0326)(-0.083)
3232 0.334
= 0.047
(0.051)-0.083)
Zi2 Z2
=Z12-
0.063 = 0.075=2
Z 0.334
Zi=Z-L=0,114-0051)(0.051) i) Starting
with element which is a branch from p = 3 to
0.106
=
41.ZBUS
Z 0.334
O 0.4
Z22-2=0.146--0083) = 0.125
Z22 0.334
-
0-3
=4. This again adds to a new bus.
0-4 0-3 0.8 0.4 0
ZBUS = 0 0.3 Z4
0.4
ZAZ41 42 Z44
71
APPL,
INVELA
IN ELECT, ENGG.(B.E, VII Sem, Elect.)
VD COMP. APPL. IN a.E.VIlSerm,
ELECT. ENGG. (B.E.
VIl COMP,
MP,
APPL.
Elec WD
Z41= Z2i =0= Z14 iminating the /h, row and column
Elim
Z42 =Z22 =0.3 = Z24 Z1-Y41_
ZL = 0,4
Zi1= Zu
Z44= 1.1
ZL12= 0-0= 0 = Z21
Thus, Zí2 =Z12 Zi
Z22
=Z22-NI2a (-0.3)(-.3) -0.235
1.4
a
(iv) Now adding element 4 which is link
from node n- Zu
O04 0 0 Z
O 0.4
00 0.3 0.3 Za 0 0.235 0.064
00.3 1.1 Za ZBUS
0 0.064 0.235
IZZi2Zu Z (v) Adding element5 which is link fromp=I to q=4.
Z =-Z41 =0 =Z
The augmented impedance matrix
ZI2= -Z42 =-0.3 = -Z2
Z14=-Z44 = 1.1 =-Z4
O
0.4 0 0 ZIl
Z Z2 Z14 Z
=
O04 0 0 0 Z1= Z11-Z41 = 0.4-0= 0.4 Z
0 0.3 0.3 -0.3 Z12 -Z42 = 0-0.064 = -0.064 Z2
Z12
0 0.3 1.1-1.1 =
Z14= Z14-Z44 = 0-0.235 -0.235 = Z4!
I 0
-0.31.1 14 Zu= Z- Z4+0.4-(-0.235) +0.4 = 1.035
IN ELECT. ENGG. (8.E Vit
72 BD COMP,APPL. Sem.E
APPL. IN ELECT. ENGG.(B.E. VIl Sem. Elect)
73
MP.
=
=0,245-0,09 = 0.155 Z
0 0.4 Z Z1Z41
O04O 0
0.234 0.064 -0.064 Zp =
Z12-Z42 = 0.062 -0.049
= 0.013 = Z
Zi2 =Zp
Z142-0 1.035
=Z2 10.155 0.013| -0.092-0.153
Z
Z1Z4=0-(0.4-0.235)0.09 =Z41 Now, eliminating
the row and column
Zi4 =Zy4
Z 1.035
- =0.245_(0.155)2
= 0.402
Za14-0.064 (-0.064)(=-0.235) Z1 = Z1 0.153
= 0.049 Z -
Z 1.035
2=0.062_0.155)(0.013) = 0.075 = Z21
ZAL14=0.235- -0.235) Zi2 =Z12 -
0.182 -0.153
Z 1.035
=
(0.155) (-0.092)3,.2x10
Thus, Zbi4 0.09-
14L14 Z - 0.153
0.062 0.231
0.09
0.049
0.049 0.182
Z2 -3-3.2x103 0.041 0.237
Z4
NaG. (8.E,
Prob.4. E.VIL
Sem.
B APPL ELECT. ENGaa.(B.E, VIl Sem Elect.) 75
COMP,
WD
Starting with element
I
which is a branch from p=0 to
0.3 )
ZBUS O0.3
0.1
0.4 i) Adding element 2, which is a branch from p =
1
to q = 2.
This adds a
new bus.
O
O 0-3
0.5
ZBUS O0.3 Z12
Z21 Z22
Z21 =Z11 =0.3 = Z12
Obtain ZBUS using building algorithm
system shown above. The values
indicated in figure
figure are
n
for the power
Z22 =Z21 +0.1
=
0.4
reactance's. sel.
Soln. Corresponding oriented graph.
0.3 0.3
ZBUS
0.3 0.4
ii) Adding the element 3, which is a branch from p = I to
O0.30.3 Z13
0.5
ZBUS O 0.6 0
0-2 0 0.5
0-6
0
ii) Adding element 4, which is a link from p = to q =2. The
1
(a) Form the bus impedance matrix of the above network 0.6 0 -0.6
using algorithm. ZBUS 0 0.5
(b) Modify the bus impedance matrix obtained to include
-0.6
the addition of an element from bus 2 to 4 with an impedance of
0.3.
Eliminating the e" row and column.
Modify again the bus impedance matrix so obtained to
remove the new element from bus 2 to 4. Z22 =Z22
- O.6-(0.6)2
0.24
Verify the magnification done in part (c). Zu
Soln.
Z23 =Z23- 3 -0.6)00-Z32
Corresponding oriented graph
Z 1
ZBUS
3 0.24 0
0.5
IN ELECT. ENGG. (B.E.
(B.E. VIll
Vn
80 VBD cOMP. APPL. Sem,E 81
a branch from
m APPL. IN ELECT, ENGG.(B.E. VIll Sem. Elect.)
soD COMP.
element 3, whicn p=3to
1S
Z22 =Z2
Z142-0,24 (0.24) = 0.2 0.197 0.088 0.176
1.44
0.088 0.316 0.132
ZBUS
4)-0.5)0.084=Z32 0.176 0.132 0.264
Z23 Zz3 23 =0_
Zu 1.44
Z24 ZaZ40(0.24)(-1) 0.167 =Z42 c) Now removing the new element added in part (6)
from the
1.44 2 q = 4 with an
bus impedance matrix. Adding a link from bus
p = to
a,b,c
E- E-E u$E6-E
pq
Fig.2. Representation of three-phase network componentin
admittance form.
pE-Eä upq -Eß-E
E-E
Fig.1. Representation of three-phase network component in The performance equation of a three-phase element in
impedance.
impedance form is
ipgipqipq are the currents through the element p-q for phase
aa
epq ab ac
epa
a, b and c respectively pq
Jpg pg pq are the source currents in parallel with phases a, b pq + epq ba
pq bb
pq bc
P pq
and c respectively, of the element p-q cb
Vpg Ca
pq Cpq
Zp is the three-phase impedance matrix for the element p-q
.i)
Ypq is the three-phase admittance matrix for the element p-q
where Zpa = self-impedance of phase a of the three-phase element
connecting nodes p and q
84 V BD COMP. APPL. IN ELECT. ENGG. (B.E. VIll Sem. Elect)
86 BD COMP. APPL. IN ELECT. ENGG. (B.E. VIlI Sem.Elect
Ser
IN ELECT. ENGG. (B.E. VIl Sem. Elect.) 87
aNBD COMP. APPL.
zp mutual impedance between phases a and b in the admittance matrix
The corresponding relations are true
Zpmutual impedance between phases a and c pq
,
,b,c
i +.b.cya.b.ca,b.c
pq a.bc+ab.c =[ya,b.cj va.b4
The vectors representing the variables are
composed of 3 x1
where
P be submatrices corresponding to the variables of a particular three-
The parallel three-phase source current in matrices are composed of 3 x
admittance form and phase network element. The parameter
the three-phase series source voltage
in impedance form have the 3 submatrices. These submatrices correspond to the self and mutual
relationship, as is the case in single-phase
representation, three-phase impedance or admittance matrices of the network
p -ya.b.cea.b.c elements.
Q.2. Derive an expression for performance equation of 30
The impedance matrix z and the admittance matrk stationary and rotating element in impedance and admittance
yp of a stationary bilatera element form when excitation is balanced and unbalanced.
(W.03)
are symmetric. If, in addition,
the three-phase element is Ans. Balanced excitation
balanced, then the diagonal elements
zpdesignated by zpg. are equal and o The excitation of any three-phase element is balanced when
all phases are equal
the
in
the off-diagonal elemeny sOurce voltages or source currents of
designated by zpq, are equal,
magnitude and displaced from each other by 120. For
balanced
that is,
excitation,
and
= zp=
epq and
ppz
ea,b,c
epa Cpq
Zpa
B.E. VIl
ENGG. (B.E.
VBD COMP. APPL. IN ELECT. Vie Sem.
89
Elect COMP PPL. IN ELECT. ENGG. (B.E. VIll Serm. Elect.)
VBD
that S,
Jpq
a
to obtain
3vp+3pspzP -***.*....(3)
It follows that a =1, as +atl=0 and a =a. The phase where pgZpg is the positive sequence impedance, which is
voltages and phase currents are balanced if the excitation of a designated by zpg Thus, a balanced three-phase element with
balanced three-phase element is balanced. Then, the perforn
ormance
can be treated as a single phase element in
balanced excitation
equation, in impedance form, fora stationary element is element is equal to three times
network problems. The power in the
the power per phase.
pa 2pq pq In a similar manner, equation (2)
can be reduced to
1 +azpq t azpq
pq Zpg ,m
pg aP +pgPp Pp
a Zpq pq where
zpag +a
zpg +az m2 is the positive sequence impedance.
form, for a stationary
The performance equation, in admittance
..(1)
and for a rotating element is element is
n2
and for a rotating element is
m2
pq n
2Pq ipa +Jpap +aypq taypg
, m2
Unbalanced excitation
pq p When the excitation is unbalanced, the
performance equation
...(2) reduced to three independent
Both sides of equation (1) can of a three phase element can be
be premultiplied by matrix zp.Using a
conjugate transpose of equations by diagonalizing the impedance
the phase variables are
complex transformation matrix T then
as follows:
expressed in terms of a new set of variables
vD=
P.9
Tvb
.(4)
ep.g = TelJk
Iepq
91
90 BD COMP. APPL. IN ELECT. ENGG. (B.E.
E.VIIl
V COMP, APPL.
IN ELECT, ENGG. (B,E. VIll Sem. Elect.)
Sem.Elec D
30 components, stationary and rotating can
p-Ti .3. Show how
epresented y diagonalized matrix form by non-diagonalized
The complex power in the element
is
be (S.00,01, W.00)
matrix form,
Symmetrical components
SpPptjp = a,b,c
P
Ans.
particular transformations for three-phase balanced
Two
three-phase
Substituting from equations (4), dlements are of
interest. One of these transforms the
positive and negative sequence quantities, know
antities into zero, this transformation is
Symmetrical components. The matrix for
) as
a
Thus T is a unitary matrix. Zpa pq pq
Substituting from equations (4) the
performance equation (2) z1,2
becomes
2pg
T+zpT (7)
pa 2pa
2p=(T' zabcr
pq ....(8) where the zero sequence impedance is
Similarly for admittance
zpzpg +22pq
pq the positive sequence impedance is
92 VBD COMP. APPL. IN ELECT. ENGG. (B.E.VIl
VIL
Sem.
Elect 93
impedance is IN ELECT. ENGG. (B.E. VIlI Sem. Elect.)
the negative sequence COMP. APPL,
PL.
VBD
zpa-P zpg +2tpa
and zp refers to the transformed impedance matrix atrix,
P
element.
which
is 0,c.P pa pq
diagonal for a balanced three-phase pq
The transformation matrix Ts also alizes the impedance
diagonalizes pa-pq
,a,b.C
matrix for a rotating element, even though Zp is not c.
is not symmetric,
impedance
suhere the
diagonal elements are the zero, alpha and beta
This diagonalized matrix is
respectively, and zp refers to the transformed
components,
m2
pq
impedance matrix which is
diagonal for a balanced three-phase
0.1,2
zp tap +azp
pq element.
Zpgtazp+az The transformation matrix 1, does not diagonalize the
+a
Clarke's components
0,0.
pq
p P+zp 3-2p)
Another transformation matrix transforms the three-phase ,mI
pm2
zpq p + zp
quantities into zero, alpha, and beta sequence quantities, known as
Clarke's components. The matrix for this transformation
is
Q.4. Starting from the performance equations (of a partial
0 30 network), derive equations useful for formations of bus
T -V1/23/2 impedance matrix when
i) the added element is a branch. (W.01)
-1/2-3/2 and (ii) the added element is a link.
Consider no mutual coupling between the elements.
which is an orthogonal
matrix, that is, TT. =U. ThererOrc Ans. Incidence and network matrices for a three-phase
Te = Te. Using this transformation balanced or unbalanced network can be formed by the same
the impedance matrix 1ora
procedures as those described for single-phase networks. The entries
stationary element z from equation (8) becomes. 1, -1 and 0 in the incidence matrices for a single-phase networks.
IN ELECT. ENGG. (B.E.
(B.E. VIl
VBD COMP. APPL. Sem.Ele IN ELECT. ENGG. (B.E. VIlI Sem. Elect.) 95
94 cOMP. APPL.
vill be composed of 3 x
will a,b.e
components. The network matrices E
to the phase or sequence
submatrices whose elements also refer 72.b,c 74,0,
components.
za,b.czC
21
2m 29
a three-phase network.
Performance equation of partial
cquation for a three-phase *** ******
a,D,c
vector of the three-phase bus voltages measured with
** *****
where ERIIS *
7a,b,C
,C 74,0,
mq
respect to the reference bus a,b,c m ,b,C7a,b,c
Zml m2 mp
m
I = Vector of impressed three-phase bus currents
z4D,C 7a,b,C 74,b,C ZA,0,
9 ZD,C qm 99
E q 9P
BUS = three-phase bus impedance matrix.
Three-pha se
EbC=Zb.ca.b.c
..(7)
element p-9
Eab =Zabca.be
and at any bus k,
ED=Z.D.CTa.bc
Partial equation (7) and (6) and solving
network Using the relationships from
for Z.1a.b.c
qi i
ZaDCa.b.c =Z.b."a.b.e +yab)yabcZ.bc -Za.b.abe
I, it follows
all values of
Since equation (8) is valid for
that
b.cZa.b.e Zab.c 9)
Fig. Injected three
Reference za.b.c
qi
za.b.e ab.c
pi +V
pq.p
ypq popi
phase current for calculation
of z4,D, and
aud u
z8,b,c
IN ELECT. ENGa. (B.E.
(B.E. VIT e OMP. APPL,IN ELECT. ENGG, (8.E, VIll Sem. Eledt.)
ARD COMP, APPL. VIl
Som.Eioct
Substituting from cquation (16) into (10), it follows that
let the current at the qth bus be 1Abe
To calculate Z, And
wn17)
added elements p.
It the p-q were
all other bus currents equal zero, no
the elements of the partial network, th voltage
the From the matrix equation
mutually coupled to
E= =
However, the element p-q is assumed to be mutually coupled to
he
7a,D,C a,b,c a. a,b,c
s18)
po,pa) po.pg
therefore,
one or more elements of the partial network;
ELDC=ZD14D=D1.DC+AEa,b.e Premultiplying by a,b.c J and postmultiplying by
T0) po,pa
where, AE.b is the change in voltage at bus i due to the effect of pg,pq cquation (18) becomes
E =Z0za,b,c
q
ip
gg
Z,CZa,b,c
pq ,a,b,c
P9 pq
(0 Reference
source in series with added link for
Fig. Three-phase voltage
It, in addition, p is the reference node,
Z4and Z4D, C
the elements of Zi calculation of Z,
a,b,c
and are zero. Also 2 P m
7a,b,cZa.b,c 14,0C
Z,0, 73,b,c Ea,b.cl7a,b,c 24b,c 7a,b,c
lm
P9 P 12
74,b,c Ta,b,C
Z4,b.c ,D,C
21
If the network elements are balanced,
Z 2m 2
then 7a,b,c74,0, and Ea.b,c12 2P
iq
either equation (9) or (20) can be used.
****
******
***
*****
73,b.c Ta,0,C
Addition of a link a,b,c 74,0,C pm
,0,c
pl P
E,D,CPZ p2 PP
As in the case of single-phase P
networks, when the new eleme ***
terms of the primitive admittances and as in the case where the added
The current inin Following the same procedures
then
voltages across the elements is element is a branch,
a,b,ca,b,cC =-(Z.b,©-Zb,c)ab.czab.c1a.b.c 34)
ya,b,C,a,b,C
pqYpl.ppl pl.pa pa (28) AEb, io
Since,
Ta,b,C
Ypl.popq,pa
a,b,C va,D,Cy3,D,C
pl.plp9.pq and from equation (19)
a,b,c a.b,c ya,b,c
and the elements of a,0,C are zero, then the voltage va, from -po,po ]po,pq -YYpo.pq pq.pa
-
zB-zD +ac
If, in addition, p is the reference node,
Link
zBC -z; -z i= 1,2,...m i= 1,2,.,m
i#l
z.D,C-7a.
ql
b,c,a,b,c
tpq.p4
Furthermore, if the elements are balanced, Z D.C-Za.bc
P
i= 1,2,.... i= 1,2,..sssnrgn
i+l itl
The fictitious node l is eliminated
by short circuiting the lmn
7d,D,C-74,D,C, a,b,c
voltage source
e. From equation (25),
Zab.c
=Z-7a +pa.Pq
node
Tpq.pq
ezbe
1
and Z2,b.c
=
"ij(modified)ij(before elimination)
ab.e-ZTs+Z. =
0 (42) i.j = 1,2,....m
IN ELECT. ENGG. (B.E. VIll
106 ABD COMP. APPL. V
Sem, ELECT. ENGG. (B.E. VIlI Sem. Elect.) 107
Elet COMP.APPL IN
The same procedures as those used for 2-4 0.6 0.2 0.2
single-phase networks
0.2 0.6 0.2
can be employed to derive an equation
for modifying the submatrices 1.6
0.2 0.2
of the three-phase bus impedance matrix
when mutually coupled 4-3
0.9 0.3 0.3
elements are removed or their 0.3
impedances are changed. This 0.3 0.9
equation is 0.3 0.3 1.9
zp---7Mhe4yeZ-
where Ay
(a) Form the bus incidence
matrix A with ground as ref.
yb.e (b) Form the bus admittance
matrix YBUS by transformation. /
Mhu-Aherp1-11-2 (c) Form the bus impedance
matrix ZBUS using algorithm.
Soln. Part (a) The bus incidence matrix
VBD COMP. APPL IN ELECT. ENGG. (B.E. IN ELECT. ENGG. (B,E. ViIll Sem. Elect)
108 VIl Sem. aMBD COMP. APPL. 109
Eléct
bus 3 Part-b
matrix
The primitive impedance
e
A= -U
U
U
U -U
where U is a matrix (unit) of dimension 3 x 3.
3
-1
A-4
-1 HL
-1
IN ELECT. ENGG. (B.E. VI Sem. ELECT. ENGG. (B.E. VI1 Sem, Elect.) 111
110 BD COMP. APPL. Elect aD COMP. APPL, IN
4 6
a bCabCaDCaboab
-BAAEAR
OEE
EEREEE
(B.E. VIl
IN ELECT. ENGG. (B.E. VI
112 VBD COMP. APPL. Sem. Elect)
aNBD CoMP. APPL. IN ELECT. ENGG. (B.E. Vil Sem. Elect.) 113
c
Part
Will be tormed y first adding
by
The bus impedance matrix
ad
al
branches and then adding the links. irom p = 1 to a
with element 1, the branch
Step 1. Start
matrix of the partial networ. are
The elements of the bus impedance
a
0.080 -0.025 -0.020
a,b.C 2
b -0.020 0.080 -0.025
ZBUS
-0.025 -0.020 O.080
Step 2: Add element 2, the branch from p
matrix is
= 1 to q = 3. This
adds a new bus and the bus impedance
2
a b b
0.080 -0.025 -0.020
-0.020 -0.025
-
B 0.080
ZBUS C
-0.0250.020 O.080
O.080 -0.025-0.020
-0.020 0.080 -0.025
-0.025 -0.020 0.080
Step 3. Add element
4, the branch from p = 2 to q 4. Thi1s
element is not
connected to the reference node and its additiOn
creates a new bus. Using the formulas
given in Q.5.
Zgi ZCi =2,3
zab.c
iq
=
za.bc i=2,3
and
Zabc Za = +z
P9-P
The bus impedance matrix is
114
VBD COMP. APPL.
IN ELECT.
ENGG. (B.E. 115
Step 4 Vill IN ELECT.
ENGG. (B.E, Vill Sem. Elect.)
Add element 5, S 1D APPL.
the link from p COMP
element is not connected
to the reference node
=4 to = T q3. VBD
rows and columns
corresponding to the fictitious node I
zD= za.b.cza.b.c
pi qi il
Za.b.c_za,b,c
ZC= "ip iq i#l
and Z =Z
Zl+pq.p
The augmented impedance matrix
EBUS(F)BUSO)ZBUS BUS(F
The unknown voltage vector is
- (1)
Fa,b.c
EIF)
Loods
Eb,c
BUS(F) EpFb.c
Fig. Three-phase representa tion of a power
ayetem. ***
Mochines
a, b.c
n(F)
w Transmission syslem
where the elements of ERUS(E) are the three-phase voltage vectors
E 1,2,..., n
The known voltage vector prior to the fault is
m E E3,b.c
E 1(0)
,a, b,c
Fa.b.c
Ea.b,c
EBUS(O) p0)
Fig. Three-plose represen tation
of a power aya tem
for short circus
studies.
Eb.e
n(0)
ELECT. ENGG. (B.E. VIl Sem, Ele
188 BD COMP. APPL. IN APPL. IN ELECT. ENGG. (B.E, VIII Sem. Elect) 189
VBDCOMP.
during a fault at bus pis
The unknown bus current vector elements of za are matrices of dimension 3x3.
bhere the
where
of BUS
Equation(1) can be written as follows:
0
E1P pCF)
7a.b,c
BUSE)
a, b,c a,b.C-Z20pF)
p(F) -2)
E2(F)
. /....
Ea,b.c Ea,b.Cza, b, C a,b.c
0 Eo)Ep(0)pp P(F)
****
figure above E
pCF) = Z.b,Ca,b.c -..)
p(F)
Za,b,c 73.b.c
a.b.c
LBUS Lpp pm where Z is the three-phase impedance matrix for the fault. The
PCF) a.b.c7,b.Ca.b.c
ZD,Ca, b.C
p(0) pp p(
Solving equation (4) for InE yields
P(F
-(4)
a= (Z,c +Zab)-Ebe
Bue impedanoe matri
(tranemision syetem and Ep(0)
machine reacdances)
p(E)
Eun
Substituting for IE in equation (3), the three-phase voltage
(8
Y is the three-phase admittance matrix for the The elements of the voltage vector are
where
Vij(F
Substituting InE from equation(8), the pth equation of v,b,c
Vij(F)
becomes
Y.b.C a.b.c
pF) =Ep(0Zp p(F) ----- (9)
and the elements of the primitive admittance matrix are
aa
Solving equation (9) for Eo( yields
ij. kl
ab
Yij.kl
-----(10) .a,b,C ba bb bc
Ep(F) =(U+Za.b.Cya.b,C)-lga.b.c y ,
ij.kl ij, k ij, kl ij,kd
P(0)
yCa cb
Yijk
Substituting for EE in equation (8), the three-phase cue
where y is the mutual admittance between phase b of network
at the faulted bus p is
. The three-phase
element i-j and phase c of network element k
1
,b.c Zab.cy2.b.clE.b.c
-
a,b.
E2 (T)' Ej0) then
Zpa
EL.23
Ei0)
This matrix can be diagonalized by the transformat
(T)2T, into
The fault impedance matrix
Z can be transfomed by
(0)
p T. into the matrix ZF The resulting matrix is diagonal if the
p 0.1.2
fault is balanced. The fault impedance and admittance matrices in
components for various types
terms of three-phases and symmetrical
if faults are given in
table(1).
where zg zg and zpa are the zero, positive, and negative
equations for calculating fault cuments and
Similarly, the
sequence impedances respectively. The positive and negative can be written in terms of symmetrical component The
voltages
sequence impedances for a stationary balanced three-phase elemem
current at the faulted bus p is
are equal. In addition, it is generally accepted that positive and
negative sequence impedances for rotating elements can be assumed 1=
pF)
(ZL.2 +Zo EL2 -(1)
equal for short circuit calculations.
In a similar manner, each y2,b,c in the primitive admittanc
or pYp-(U+zp pO)
-2)
+ where yozp
+37g
t+| V-VVe-VVo+2y
where vo 0 0 00 0
Three-phase-to s+3 YF
0 1o
o
ground
0 ZF o01
Not defned
Not defined E1
3T1
Three-phae
Line-to-ground
-I
t +2p,+2
0
Line-to-line-to-
ground +2p +2
erms of symmetrical components, into equations(1), (3), and (5)
Line-to-line
Not defined
pF) are
The voltages at buses other thanp
which reduces to
)
)
EEiF)
p(F)
3 (9) i EE) Zip 1
----
ZF +Zp
p(F) 7()
ZF + Zpp E 0
pF) 0
which reduces to
The phase components of the fault current at bus p can be
obtained by pre-multiplying both sides of equation (9) by Ts. These EO
Pi(F)
0
currents are = V51-
i(F)
Tp(F E2) ZF + Zpp
a2 0
p(E)ZE + Zp a
p(F) In phase components,
1.2 3 zEp(0) fault current and the bus voltages are obtained
Fa,b.c zpEp pCF)
The
by
ZF + Z PP
ZF +Zp hctituting from equation (10) for YFin
equations(2), (4), and
(6). The current at the
faulted bus p is
zZp37F
1be o
p70)+2Z+32F 0
3E p(0) 0.1,2
p
z+27+32
3Ep(0)
Ep
p
z22+3z -Zpp
E EpO
EQ12 3 Ep)
The phase components of the fault voltage are 3ZF EpP pp+ 22pp +3Z
3ZF Z+2Zp +3Z
Z
Z+2Zp +3ZF Zp- - Z
p pp +Zpp +3Zp
E
gb
p
z-Z
Z+2Zpp +3Zp
22+32
Z-Zp
7)
-Tpp
7(0)
Zp+2Zpp +3ZF
PP 22+32
E0.12
E(0
The voltages at buses other thanp are EP-E0) a-Ep)
EO)
i( 0) 0 3 Ep(0)
0 ip
E z+2z z+2+3
P
EiE 0
z0 27+32 z+2Z +3Z
which reduces to z-z
Zp+2Zo+3ZF
EO)
Ei(F
0 z-z ip
O0 z+2+3ZF 70
ip Z+2 +3ZF i#P
i(E2) PP
i#p
ELECT. ENGG. (B.E. VIl Sem. IN ELECT. ENGG.(B.E. VIll Sem. Elect.) 203
202 VBD COMP. APPL. IN
Elece COMP APPL.
VBD
NUMERICALS: bus pedance matrix in terms of sequence quantities
a) The
Prob:1 Consider the following determined to calculate three-phase and line-to-ground fault
mustbe
currents, using
etrical components. Table given in problem
the ree-phase impedances of the network elements.
nit-3 shows
positive ànd negative sequence impedances of the network
The zero,
ments can be obtained by means of the transformation matrix Ts
(o)
that 1s,
Zpu=(T,)pb.cT
pq
Assuming the impedance matrices of the generators are
svmmetric and using the average value -0.0225
for the off-diagonal
ahead.
elements,the sequence impedances are shown in Table
sequence impedances for
Table Zero, positive, and negative
(6)
Ground Branch samplesystem.
Mutual
Link
Element Bus Self
Figure: Sample system for short circuit calculations. number Code
(a) Single line diagram of three-phase system;
(b) Oriented connected graph.
p-9
Bus Impedance
a. Using symmetrical components, calculate the following Impedance
z0.1,2 Code 70,1,2
for a three-phase fault at bus 4: pq.p p.q.r.s
i. Total fault current r-s
i. Bus voltages during fault
1-2 0.035
ii. Short circuit currents in lines connected to the faulted
bus. 0.1025
b. Using symmetrical components, 0.1025
calculate the following
for a line-to-ground fault at bus 4:
1-3 0.035
i. Total fault current
0.1025
ii. Bus voltages during fault
0.1025
ii. Short circuit currents in lines connected
to the faulted
bus. 3 2-3
2.50
C. Determine the maximum
three-phase short cireu 1.00
current that circuit breaker A must
interrupt for a fault on me 1.00
line side of the breaker.
Soln.
204 VBD COMP. APPL. IN .E.VIl
ELECT. ENGG. (B.E. VIll Se- COMP. APPL. IN ELECT. ENGG. (B.E. VIll Sem. Elect.) 205
Sem. 'BD
Ele
Step4.Add element 5, the link from p =4 to =3. The
2-4 2-3 q
1.00 0.60
elements ofthe row
0.40 and column corresponding to the fictitious node
0.40 are
4-3 2-3 Zi2 =Z21=Z42-Z32
|1.50 0.90
0.60
Z13=Z3= Z42 -Z33
0.60 Zy4=Z41= Z44 -Z34
Z=Z41-Z3y +Z43,43
Since there is no coupling between the sequence impedance
nces, and the augmented matrix is
the bus impedance matrix in terms of sequence quantities can
h
obtained by forming the positive, negative, and zero sequence bu
2) 0.1025 0.1025 0.1025
impedance matrices independently. First, the positive sequence bu
impedance matrix will be formed.
3 0.1025 -0.1025
Step 2. Add element 2, the branch from p =l to q =3. Then, Z22-Z22 a1Z Z12
7)
LBUS F
Zi3=Za3-ZsaZ Z12
2 3
0.1025 Z4=Z44-ZaZ Z14
Step 3. Add element 4, the branch from p = 2 to q = 4. Thus, Z24Z42 = Z24-Z21Z Z14
Z24=Z42=Z22 Z34=Z43 =0
Z44=Z24+Z24,24
Z'34
Z43 =Z34-Za1Z Z14
and
Thus,
2 (3 4)
BUS = (2) 0.1025 0.1025
BUS 0.938 0.0087 0.0598
0.1025 0.0087 0.0938 0.0427
4 0.1025 0.5025 4) 0.0598 0.0427 0.2930
206 9ABDCOMP. APPL. IN ELECT. ENGG. (B.E. VIm Sem.
e aMRD COMP.
APPL. IN ELECT. ENGG. (B.E. VII Sem. Elect.)
p= 2 to q =3. As in the
Step 5. Add element 3, the link from he Step 5. Add element 3, the link from p = 2 to q =3 which is
previous step, coupled with the elements 4 and 5. The elements of the row and
Z=Z=Z2 -Z32 column coresponding to the fictitious node 1 are
Zs-Zy=Zas-Z33
Zi2=Z2-Z32 +22422-L42)+Y23, 43 (Z2 -Z-)
Z=Za=Z24-Z34 Y23, 23
Z-Z2-Zy +Z23.23
y23,24(Z23-Z43) +y23,43 Zs-Zss)
Zy3= Z23-Z33 +
4 Y23.23
0.0938 0.0087 0.0598 0.0851
0.0087 0.0938 0.0427-0.0851 +23,2424Z44)+y2343 (Z44 -Z)
Z4 Z24-Zaa
=
Y23.23
0.0598 0.0427 0.2930 0.0171
0.0851-0.0851 0.0171 1.1702
=Z2Z3 +1+
y23,24 (Zqi -Z4) + yz3,43 (Z4 -Za)
ZI
y23,23
Eliminating the row and column, the final positive sequence
The zero sequence primitive impedance matrix is
bus impedance matrix is
1-2 1-3 2-3 2-4 4-3
2 1-2 0.035
ZBUS 0.0876 0.0149 0.0586
1-3 0.035
3 0.0149 0.0876 0.0439
2-3 2.500 0.600 0.900
0.0586 0.0439 0.2928
2-4 0.600 1.000
Since positve and negatve prmtive sequence impedances are
equal to positive and negative sequence bus impedance matrices are 4-3 0.900 1500
equal.
The procedure for forming the zero sequence bus impedance
The new element 3 is coupled only to elements 4 and 5 and it is
matrix is identical for the first four steps. The zero sequence Dus
sufficient to invert the sub-matrix containing the coupled elemen
impedance matrix of the partial network, before adding element 5, 15
2-3 2-4 4-3
0.0149
0.0876 O.0439
E9.12
3--Z44+2F 02928
L
0.0209
0.0141
0.6182
(4)1 0.056
0.0439
0.2928
voltages are
he phase components of the
0.0586
00139 0.3928
Sem
9ABD COMP. APPL. IN ELECT. ENGG. (B.E. Vil Sem.
210 Elect) wBD COMP.
APPL. IN ELECT. ENGG. (B.E. VIll Sem. Elect.)
211
1
E-TE =0 ;43(F)
a,b.C =Ti -1.42 a2
a
bus are
0.833
0 = 0.83 3
:0,1.2
43F) y4343 (E4E)-3E) 0.85/3) 0.83/3
0 0.60 are
The phase components of the total fault current
0
2.49
1ab.c =TI 0
-1.423 0
0
Bus voltages during the fault are
)E
:0.1,2
EE
24(F)Y24,242F)-E4(F) (0.80V3-0) (0) -0.6182
E 0.40
E1,2
4(F)
3 z+Z =0.833 0.9110
-0.2928
0 z+2Z4 +3zF-z
2.00/3
0
-0.51313
0.7561 3
The phase components of these
currents are
-0.2430 3
COMP. APR IN ELECT. ENGG. (B.E. VII Sem. Elect.)
213
VBD COMP. APPL. IN ELECT. ENGG. (B.E. Vill Sem, E BD
212 3ZF
V3
20 42
(1)
) +2Z+3ZF
44
E2 3 2+2z+37FZL42 Ea,b.c =
EAF)
a
7Z44-44
Z
a2
0.6182-0.2928
0
Z+2Z
z-z
0.6182+0.5856
44 +3z
a
0.6182-0.2928
0.0209
0 a - 0.6182 +0.5856
3-0.83 V3 0.0586 70+2Z
44 +3ZF
0 0.0586
-0.0173 3
3
0.9514
-0.77-j0.866 |
-0.0486 3
-0.77+ j0.866
0 LA3
L43
0 z+274 +3zFZ
43
z+2Z47
42
1
z+27
z
+3zF
Ea.b.c a 42 Z42
2F)
0 0.0141
z+2Z+3ZF
A4
3-0.83/30.0439 a z0-z4
42
0 0.0439
z+2Z+32F
0.0209 +0.1172 0.8853+j0
0.6182+ 0.5856
-0.01173 a2 0.0209-0.0586 -4.687-j0.866
0.6182+0.5856
0.9636 3 a 0.0209-0.0586 0.4687+j0.866
0.6182 +0.5856
-0.0364 3
z+24 0.0141+0.0878
y24 E2F)-E4F)t Y24,43(E4P)-Esp)
z27+3z 0.6182+0.5856 (0)
+Y24,23
E2)- 0)
)
Z-Z a2 0.0141-0.0439 y24.24(E2P)-E4F)
E
:0,1.2
0.6182+0.5856 43(F)
Z+2+37F
z-z 0.0141-0.0439
0.6182+0.5856
Y 24,24
(E2F-E4F)
[1.225(-0.0173 +0.5131) +0.225 (-0.5131+0.0117)
z+27+ 32p
+-0.375)-00173+0.0117)
0.9154+j0 (0.9514-0.7561)
=v3 0.4
-0.4752-j0.866
-0-4752+10.866 -0.0486 +0.2430)
0.4
Short circuit currents in the lines connected to the faulted bus
2re 0.50/3
Y4343(E 4 E3+Y43,23(2(F)-E3( 0.49 3
+y EF
E 0)
4F) 0.49 3
y43 (E- Esp)
EE-E3(F-FX) The phase components of the currents in the lines coanegfed
top
-
1.5 2.02 3
0,1.2
42,42(2) -0.60
Z=Z4-Z31+Z43,43(2)
and the augmented positive sequence
matrix is
2 3 4
0.0876 0.0149 0.0586 0.0437
3 0.0149 0.0439-0.0437
0.0876
0.0586 0.0439 0.29280.2489
0.0437-0.0437 0.2489-0.3074
218 VBD COMP. APPL. IN ELECT ENGG. (B.E. VIl Se
VIlI Sem.
Elect
REPEATEDLY ASKED UNIVERSITY QUESTION
ONS
P --- (2)
2
The frequency f in cycles per second 1s
rpm ---(3)
1f 60
angle in radians is
Ihen from equations (2) and (3) the electric
60f ---(4)
rpm
0m
the rotor with
angular position ð, in radians, of
Ihe electric
Spect to a synchronously rotating reference axis
Is
WR 27T(rpm0.746
H d Tm-Te --(7)
Tf dt2
f 60 550 d
T= (5) Since the torque and power in per unit are equal for small
base kva dt2
deviations in speed, equation (7) becomes
The inertia constant H of a machine is defined as the kinetc
energy at rated speed in kilowatt seconds per kilovolt-ampere. The
kinetic energy in N-mis
d dt
1t(Pm-Pe
IN ECT. ENGG. (B.E. VII Sem. Elect)
.E.VIl OMP. APPL. 223
222 VBD COMP. APPL. IN ELECT. ENGG. (B.E. VIIS
Sem.Ele PD representation of the synchronous machine used for
The
where Pm=mechanical power solutions and the corresponding phasor diagram are shown
below.
air gap power
Peelectric figure
written in Saliency and changes in field flux linkages can be taken into
equation can be written
This second-order differential astwg representir the effects of the three-phase ac quantities of
equations: unt by
simultaneous first-order synchronous machine by components acting along the direct and
axis is along the centerline of the
ds do Pm-Pe) uadrature axes. The direct
and the
he quadrature axis leads the direct axis by 90
dt dt H achine pole
degrees. The
he position of the quadrature axis can be
and lectric
determine by calculati a fictitious voltage located on this axis.
dodee 8 Thisis a voltage
back of quadrature-axis synchronous reactance and
dt dt determined from
Since the rated synchronous speed in radians per second : is
(6) aris
transient reactance is shown in figure ahead.
The quadrature component of voltage back of transien
reactance from the phasor diagram is
Fig. Representation of a sunchronous machine for determining E
E-E-j(Ng -Na)la (a) Equivalent circuit; (b) phasor diagram.
where Eq is the voltage proportional to the field flux linkages
resulting from the combined effect of the field and armature current
Since the field flux linkages do not change instantaneously following
a disturbance, E also does not change instantaneously. The rateof
dt To XF Xs t Xm
where the rotor open circuit The blocked rotor reactance is approximately
XmXr
time constant To in seconds
is
w- 000 X'= Xst
Xm tXr
Q.3. Write down the equations for the representation of
To X +Xm
loads for transient stability analysis.
2xfr representation of
Fig. Simplifed Ans. Representation of loads
and the terminal current is induction machine for transient analy loads, other than motors represented by
Power system
equivalent circuits, can be treated in several ways during the
I, = (E, E') -
Tat jX transient period. The commonly used representations are either static
The reactances X and X' can be obtained from the conventional impedance or admittance to ground, constant current at fixed power
in factor, constant real and reactive power, or a combination of these
steady state equivalent circuit of an induction machine as shown
figure below, where representations.
The constant power load is either equal to the schehuled real
r is the stator resistance in per unit
and reactive bus load or is a percentage of the specified values in the
xs is the stator reactance in per unit
COr a combined representation. The parameters associated with
228 E. VIll APPL. ELECT. ENGG. (B.E. VIl Sem. Elect)
VBD COMP. APPL. IN ELECT. ENGG. (B.E. Sem,
VIll Sem.
Elect COMP.
PPL. IIN 229
I9D Using the bus admittance matrix with ground as
static impedance and constant current representations are obtain. Hohenstein, 1959).
from the scheduled bus loads and the bus voltages calculatedfrom
fro voltage equation for bus p is
ed
load flow solution for the power system prior to a disturbance. T
the
-jQp)p YLpg Eg
initial value of the current for a constant current representation
)
is Ep= Ep q=1
obtained from q#p
po Sp0 Jbp0 Fig. ahead which was used also to illustrate the load
system shown in
a
SOution techniques in chap-(4) has two machines and load at
for
Q.4. Write down the network performance equation
ca Dus. Representing all loads as static admittances to ground, the
transient stability studies. voltage equation
for bus 1 is
Ans. Network Performance Equations:
The network performance equations used for load flo EI-YL12E2 -YL13 E3 -YLj4 E4 - YLioEo
calculations can be applied to describe the performance of here Y L12 = Y12 Li
an
network during a transient period (Stagg, Gabrielle, Moore, YLi3 = Y13 Li
IN ELECT. ENGG, (B. VIl
BD COMP. APPL. Sem.E APPL. IN
ELECT ENGG. (B.E. VIIl Sem. Elect) 231
230 cOMP
YL4=Y4L1 9D YL2sE
Y14 from the bus k+l-YL21E - Y La, E YLaEs
E
-
-
Y12, 13. and mittan
The elements load flow representatio
kl=-Y L31E-YL3sE
the same as in the
network are
matrix of the
- YL47E,
However, L Y kl-Y
E4 L4E"-YL46 E
+ +Y14 Y10 -YLs2 k+1 - Y Ls,Ek+1
Where, Yu = Yi2 Y13 E
YLgsEk"1
EX =-Y L62E, " -
T n+m
E 22pa'a p=1, 2,..
q=l
pf
calculations for transient
o.5. Write down the preliminary
stability study.
Ans. Preliminary
Calculations: -
is the load flow
The first step in a transient stability study
the disturbance. Then
calculation to obtain system conditions prior to
Reference
the network data must
be modified to correspond to the desired
Network elemenis Elements repreentin machines and loads representation for transient analysis. In addition, the machine
currents prior to the disturbance are calculated from
Single line diagram of power system for transient analysis.
Pi-jQi i= 1,2,..., m
includes the static admittance representing the load. Since E ti
Ei
is zero, the line parameter Y Lj0 does not have to be calculated.
where m is the number of machines and P and Q are the
E2=-YL21E -
YL25 Es - YL26 E6 YL28 Eg
scheduled or calculated machine real and reactive terminal powers.
where bus 8 is a new bus. In this case the diagonal admitane The calculated power for the machine at the slack bus and- the
element for bus 2 is terminal voltage are obtained from the initial load flow solution.
Y22y21t y25 + Y26+ y20+ y28 Finally the voltages back of machine impedances must be calculated.
where y20 is the static admittance representing the load an When the machine i is represented by a voltage source of
Constant magnitude back of transient reactance, the voltage iss
Y28 is the machine equivalent admittance. The formulas 10
obtained from
Gauss-Seidel iterative solution of the network shown in Fig. abo
are, then,
i0)Ei t Taili+ je.xdilti
where E'io) = e'i)+ J i0)
E -
YLi2 E - Y Lj3 Es -
YLi4E
IN EL
ELECT. ENGG. (B.E. VII Sem. Elect.)
APPL.IN 233
232 VBD cOMP. APPL. IN E.VIll
ELECT. ENGG. (B.E. VIll S. COMP.
Serm.Elea
BD equations. Finally, the initial field voltage E rdi(0) is equal
and Ei(0) is the initial value used in the solution of the
the ditferent tial
difs difterentia/
saturation is neglected.
if
to EiThe new volta
equation. the internal bus is obtained by calculating
The initial internal voltage angle is
terminal current from
machine te
-F-E)
new
Oi(0) = tan -i0) 1
.
and the voltage proportional to field flux linkages E qi(0)
ôj and
required also for this representation. These voltage are obtainedfro equations toobtain the changes in the internal voltage angle
= Ei+ Taidi t jxaildi t jNqilqi
Er machine speed Thus for an m machine problem where
all
equations are
where E gi(0) is the initial value used in the solution of m solve 2m simultaneous differential equations. These
COMP APPL. IN ELECT. ENGG. (B.E. VIII Sem.
234 VBD COMP. APPL. IN ELECT. ENGG. (8.E.
(B.E. VIl
VIl Se Elect.)
Sem.Elect VBD 235
Oi(t+At) Oi(0)+
O) do dt l)
At i= 1,2, . m
where
where the derivatives are evaluated from equations (1) and
Pei(t) are the machine powers at time t. When t = 0, the machine
do = i(t+At) 27tf
dt (+At)
powers Pei() are obtained from the network solution at the instant
is scheduled, the
dus of the fault is to bë changed. If an operâtion
0A
0)
At)=(;+ A) i(t+ At) Ppropriate changes are made in the network parameters or varables,
rai+
Tai
t jxdi
and machine powers from
ELECT. ENGG. (B.E. VIl Sem Elect)
APPL. IN EL 237
236 VBD COMP. APPL. IN ELECT. ENGG. (B.E. VII Sem. Eleet cOMP.
Develop a flow char for modified Eulers method for
or both. Then the network equations are solved to obtain sSves ystem Q.7.
stability studies. (W.02)
conditions at the instant after the change occurs. In this calculas.
ation ansient
the internal voltages are held fixed at the current values, T Then Ans.
estimates are obtained for the next time increment. The
procese
s is Flow chart
repeated until t equals the maximum time T(max) specified for the he Colcalate load flow
diburbance
prior w
study.
Modify netuork data
The sequence of steps for transient analysis by the modifed or new
represenlation
ground. Bi(o)at'ilatiru' m
i-1,2. Calculale initial estimates of pouer
When the effects of saliency and the changes in field flux angles and machine aperds at 1+ Al
.
(2)
dt Hi Modily syatem data
iaE1sinito)
Setj- i-1,2.
m
.
- -
dEgi
T (Erdi-E1,) I=1,2, m Solue netuork performanot equations
Setj-1
dt Tdo
5-
Again, if no governor action is considered, Pmi remains fixed -p-1,2 n p/(uhen faulon bus)
Calculate final estimales of pour
and Caleulate machine currenta agla and machine Bpeeds al t+A
( d
Pmi Pmi (0) -8-)
i-12...,m
If the effects of the exciter control system are not included
Caleulate machine terminal
Efdi remains constant and powe -
Pa--sB4 i-1,2... m
i-1,2.. m
Efdi Efdi(0)
If each machine of the system is described by equation (2), 1g. Transient calcula tions using the modified Euler method.
Not opual
Bqul Calculate
fnal eatimates ofso
behind machine
inpedances att
k k
+2Ar
Lgual í-1,2...
(Pmi PeAt i= 1, 2, ...., m
Setj-2
liHi
Not
re P are the machine powers when the internal voltage
Aduanor ime
4A-t
i()
angles are +(ki /2). Thus, before l2; can be calculated, new
Equal or les omponents for the voltages
for the internal machine buses must be
Greoer Print result
calculated from
Q.8. Discuss the algorithm to be used for transient stabilt lcos 8i)+
study of power system, which employs Runge Kutta method. e=E 2
voltage angles and machine speeds, again for the simplified machine to obtain bus voltages
Then, the network equations are solved
representation, are determined from calculation of machine powers P
for the
Aoi+a)Ki +2k2 +2k3i +kai) The third set of estimates are obtained from
Pmi -P)At
Ttf m
The k's and l's are the changes in 0 and o; respectively i= 1,2,..,
H
obtained using derivatives evaluated at predetermined points. Then,
where Pare obtained from a second solution of the network
Oit+a0)Oc)t ki +2k 2i + 2k3i +k4i)
equations with the internal voltage angles equal to ôi) + K2i /2
and voltage components equal to
Oi(t+ At)=Oi) t(i +2l2 +23i +l4i) ...
Ecos80) +
The initial estimates of changes are obtained from 2
kp =(Oi(0) -27tt) At
e=Elcos Sc)+
k2
=E Isin
i+ i=1,2,..
South
El
voltage components equal to Determine the effects on the sample power system shown in
figure of a three-phase fault on bus 2 for a duration of .1 sec.
e=E cos(ô,() +k3i)
r=
Soln.
E sin( +ki) The results of the load flow calculation prior to the fault are
The final estimates of the internal voltage angles and machine given in table (1). The inertia constants, direct-axis transient
speeds at time t + At are obtained by substituting the k's and I's into reactances, and equivalent admittances of the generators at buses
1
equations. The internal voltage angles 8ii+At) are used to calculate and 2 in per unit on a 100,000 kva base are given in table (2).
the estimates for the components of voltages for the internal macine Table (1) Bus voltages, generations, and loads from load flow
buses from calculations prior to fault.
ei+At)=1 E; |cos o(t+At) Bus Bus voltages Generation Load
Code
fi(t+At) =|E; |sin Oi(t+At) i=1,2,.. m (p)
(Ep)
The network equation are solved then for the fourth time to Megawatts Megavars Megawatts Megavars
obtain bus voltages for the calculation of machine currents and 1.06000+j0.00000 -7.480 0.0 0.0
129.565
a 10.0
power and network power flows. The time is advanced by At and 1.04621-j0.05128 40.0 30.0 20.0
network solution is obtained for any scheduled switching operatio 1.02032-j0.08920 45.0 15.0
0.0 0.0
1.01917-j0.09506 40.0 5.0
and change in the fault condition. The process is repeated untl 0.0 0.0
1.01209-j0.10906 60.0 10.0
equals the maximum time Tmax 0.0 0.0
IN ELECT. ENGG. (B.E. VIl Sem. Elect.)
ELECT. ENGG. (B.E. VIl Sem. COMP. APPL. 243
242 VBD COMP. APPL. IN
IBD
Elec admittance matrix is YBUS
Table(2) Inertia constants, direct-axis ent
transient reactances,
reactancee The bus
and
equivalent admittances for generators of sample system
Bus code Inertia constant Direct-axis transient Equivalent
p-i H reactance Xd Admittance
ypi
E= YL52E YL54E -
OJTt
Reference
YLpYY PP
The YLpq
s for all elements are given
in table
The voltages behind the equivalent admittancs
The modified line parameter for element 1
-2 is presenting
machines re obtained from the equati
machine
E=Etjxdiliii =n+n+2
the
be
YL2YY+Y16 n +2,..., n
+m
1-3 -0.16769-jo.00890
YL2-y21 0.16383+j0.045 12
Y22Y22 + Y27 + Y20 1-6
2-1 -0.45235-j0.00052
where Y22 and Y21 are elements in
the bus admittance 2-3 -0.15078-jo.00017
matrix: y27 is the equivalent admittance representing
the machine at 2-4 -0.15078-j0.00017
bus 2 and y20 is the equivalent admittance 2-5 -0.22618-j0.00026
to ground representing
the load at bus 2. The equation for the load 2-7 -0.01810+ j0.00601
equivalent admittance is
PLp-JQp 3-1 -0.09625+j0.00089
Ypo
2 +f 3-2 j0.00119
-0.12833+
3-4 -0.77000+j0.00711
and for bus 2 -0.12866 +j0.00115
4-2
Y20
0.20-j0.10 = 0.18228-j0.09114 4-3 -0.77198+j0.00687
1.04621) + (0.05128)2 4-5 -0.09650 +j0.00086
where the bus voltage is obtained from the load flow solution and is 5-2 -0.65236 +j0.02866
-0.32618 + j0.01433
given in table. The line parameter YE21 is 5-4
COMP APPL. IN ELECT. NGG. (B.E. VIll
E
BD Sem. Elect.)
IN ELECT. ENGG. Sem
(B.E. VIl Sem.
246 VBD COMP. APPL. Elect 10.50335+ j0.49981)
=|(1.50 247
and 172 (0.0+j0.0))(0.0-j0.66667)
-
the
machine at bus 2 is obtained in a similar manner and is = 0.22134
E7= 1.50335 +j0.49981 The real power of the machine at bus 2 is zero since
bus 2 is
The voltage magnitude is the faulted bus and its oltage is zero. Calculating the real
power as a
E7= 1.58426 check,
5 0.01226-j0.00093 At=0.02.
IN ELECT. ENGG.(B.E VIl Sem.
RDco
p. APPL.
248 VBD COMP. APPL IN ELECT. ENGG. (B.E. VIl Sem. i Elect.)
249
These oltage
components replace the previous values
Then, for the machine at bus
1,
solution obtained
load flow prior to the fault and again
60.02)=2(3.1416) 60+(4.05006) 0.02 omhe
theJoad
e soly the
solved. In this calculation the new voltage network
ations are behind the
= 376.992+0.08100 4a
chine
equivalent admittances as well as zero voltage
at the faulted
377.07300 constant
held
usare e
Similarly, for the machine at bus Sind there is no change in the internal voltage angle
2,
for the
(0) 07 2(3.1416) 60+(75.3984)0.02 imatC. the system voltages and machine
estim
inital currents and
powersare the same as those obtained from the network solution
376.992+ 1.50797 at
378.49997 de
the
instant fault occurs. Consequently, the rates of changes
in the
eod of the machines at t+ At=0.02 will be the same. Therefore,
The rates of change of the internal voltage angles are calculated
next from dolg
o.02)= 4.05006 and do
dr 0.02) =75.39484
dojou-2nf The final estimate for the speed of the machines at t+At is
dt
Since O at t = 0 is cqual to 2nf, then for the machines calculated from
drlo+ddr +t)
do20)00 do
0)0.0 and
d 0)
dt At
The initial estimates of the internal voltage angles of the
machines are calculated from
db ar
Then, for the machine at bus 1,
(0)
'iCt+at) |E;| sin 80 d t+de)2
Then, for
the machine at bus 1,
B.E. VIl Se
ELECT. ENGG. (B.E. VIl Sem.
250 VBD COMP. APPL. IN Elect COMP APPL IN ELECT. ENGG. (B.E. VIll Sem. Elect)
IBD 251
= 1.21152 -j3.39816
At t+At 0.02 the final components
=
of voltages behind and the real power
is
machine equivalent admittances are
Pe
e6(0.02)= (1.21152) (1.042 12) -(3.39816)
(0.30641)
= 0.22132
252 VBD COMP. APPL. IN .E.VIll
ELECT. ENGG. (B.E. VII Sem.
Se
Elect
The current of the machine at bus 2 is
1
P-jp-yE
-ypEp
the same.
Ans. Gauss iterative method using
YBUSs
Ep
is initiated by assuming
The solution of the load flow problem
where yp is the total admittance at the bus and ypEp is the shunt voltages for all buses except the slack bus, where the voltage is
calculated for all
current flowing from bus p to ground. specified and remains fixed. Then, the currents are
buses except the slack bus s from the bus loading equation
(ii) Line Flow Equations:
After the iterative solution of bus voltages is completed, line
p p
=
1,2,.., n
1)
flows can be calculated. The current at bus p in the line connecting EP
bus p to q is P #s
where n is the number of buses in the network. The
performance of
)Ypq + Ep
'P(Ep-Eq 2 the network can be obtained from the equation
IBUS = YBUs EBUS ..(2)
118 VBD COMP. APPL. IN ELECT. ENGG. (B.E. VII Sem. Elect.)
120
BD cOMP. APPL. IN ELECT. ENGG. (B.E. Vl Sem. Elect.) aMD COMP. APPL.
IN ELECT. ENGG, (B.E. VIl Sem. Elect.)
121
qp )
P*S s(3) Letting
The bus currents calculated from equation (), the slack bus (Pp-jp)Lp = Klp
voltage, and the estimated bus voltages are substituted into equation and Ypap= YLpq
(3) to obtain a new set of bus voltages. These new voltages are used
then, the bus voltage equation (5) becomes
in equation (1) to recalculate bus currents for a subsequent solution
E
KLp
of equation (3). The process is continued until changes in all bus
voltages are negligible. After the voltage solution has been obtained, YE q=l
p=1,2,., n p#s
the power at the slack bus and line flows can be calculated.
The network equation (3) and the bus loading equation (1) can *****6)
be combined to obtain
The normal procedure for a load flow study is to assume a
E,YE q#p
p1,2,. to the positive sequence network. Since there is no mutual coupling,
the bus admittance matrix can be formed by inspection and many of
its elements will be zero. Selecting bus 2 as the slack bus in the
P#s system shown in figure below, the formulae for the Gauss iterative
4) solution are
-
which involves only bus voltages as variables. Formulating
the load
flow problem in this manner results in a set
of nonlinear equations
that can be solved by an iterative method.
A significant reduction in the computing Stack
time for a solution
will be obtained by performing as many
arithmetic operations as
possible before initiating the iterative calculation.
Letting
-
Yp
Ypq
vo qua
equaon for bus p
Ek+1KL3
Solue uollage
(E -YL2E- --2 7
YL3sEs
Ek+l
(E)
- YL31Ej-YL46E6
Calculale change in uoltage of bus p
AE,-E, E
Teat
Jor marimu
Ek
-YLs2E2 - YL53E3
A
change in vollage
:mar AE
Grealer
mas Ar-1aE,
| Equal or less
Ek1
E- (E) YLg2E2 -
YL64E Aduance bus count
P+I-
al or Test
where the superscript k refers to the
iteration count. less Drend
ideration
of
P:n
The corresponding flow chart is as
follows
124 YBD COMP. APPL. IN ELECT. ENGG. (B.E, 125
VIl
VIue APPL. IN ELECT. ENGG. (B.E.
VIlI Sem. Elect.)
Sem.
Elect.) OMP. AP
COMP.
BD
The
sequence of steps for the load flow solution by the Gauss-
|Grealer
Ceidel iterative
method is shown in figure.
Aduance Reploor 8 by E,"
iterabion coan Form bus admittanae matris
+1-k P-12n p*s
E+I_ KL5YLsE--YLs3E3
Es= k+1 Reploce
Eby5
(E
Advance bus count
E6
(E) -YLE,
p+l-
-
YL64E
126 VBD COMP. APPL. IN ELECT. ENGG. (B.E. VIIL
S Sem.
Elect. VBD COMP. APPL. IN ELECT. ENGG. (B.E. VII Sem. Elect.) 127
Equal or le for end of bus currents are calculated from equation (1) (see Q.1) and then
iteration
bus residuals are calculated from equation (A). A voltage correction
Aduanee
ilerabion cound Greater is obtained for that bus at which the residual Rp is a maximum. If
h+1-
Tesl Equal or
Grealer for conuergence Calculale line
flows and pouer
the current at bus p remained constant, the residual R, would be
mar 4E" :
al alack bu
reduced to zero by the voltage correction
Fig. Load ffow solution by the Gauss-Seidel itera tive method
using Ymus.
AE Rp
Ypp
Relaxation method using YBUS
The equations for bus currents are used for the solution the An improved estimate of voltage for bus p is then
of
load flow problem by the relaxation method (Jordan, 1957). + AE
From Ep=Ep
the network performance equation, the current at bus p is
and the new current is
Ip=YpE + Yp?E2.. .+ YppEp-.+YpnEn
This equation can be rewritten as I+=Pj0p
k+1
Yp1E +Yp2E2.+YppEp+YpnEn-Ip Rp = (Ep
where R, is a residual and represents the error in current at bus p As a result of the change in the current, the actual residual at
resulting from the assumed voltage solution. For the system shown bus pis Rp=Ip-Ip
in figure, the formulae for the relaxation method
are
Using the voltage E,**", the new residuals for buses other
Y1E+Y2E2 + Y13E3" +Y14E4* -1 =Ri*
than p and the slack bus are calculated from
Y31E +Ya3E+ YasEs-15=R
YajE+ YasE4 + Ya6Eg*
R =Rg+YgpAE q=1,2,...., D
-14* =R4* 9#P,9#S
Ys2E2" + Ys3E3* +YssEs-1s=R This process is repeated, each time correcting the voltage
Y62E2 +Y4E4 +Yo6E -16* =R* .. (A) corresponding to the largest residual, until all residual are less than
where the equation for the slack bus has been excluded since E2 or equal to a specified tolerance. The sequence of
steps for the load
specified and remains fixed. flow solution by the relaxation method is shown in figure ahead.
With the set of bus voltages The sequence of steps for the load flow solution by the
Pp -ep q,Gpa+,Bpg)+fpG,Gpq-egBpq))
AQ
A
Equations for determining the elements of the Jacobian can be
from
derived from the bus power equations. The real power
Qp fp e,Gpa +fqBpq)-epq Gpq qBpq)).)
equation (3) is
This formulation results in a set of nonlinear simultaneous PpCp Cppp +pBpp)+pppppBpp
equations, two for each bus of the system. The real and reactive
powers Pp and Q, are known and the real and imaginary 2e, CqGpg tqBpq)+1pCqGpq-CqBpq)
q=l
components of voltages ep and fp are unknown for all buses qFP
p =1,2,.........n-1 .(5)
except the slack bus, where the voltage is specified and remains
fixed. Thus, there are 2(n-1) equations to be solved for a load flow Differentiating, the off-diagonal elements of Jj are
solution. SPp
The Newton-Raphson method requires that a set of linear epGpq-fpBpq 9P
òeq
equations be formed expressing the relationship between the changes
in real and reactive powers and the components of bus voltages as and the diagonal elements of Jj are
follows:
AP OP
oP dP1 oP Ae
2Gpp
oep
+ fpBpp -fpBpp t 2eGpq
9=1
t fqB pq) .(6)
õe q#p
*.****
Sen-1 of
****
of n-1
****
*******
**A***************
** ******
However, the equation for the current at bus p is
+tpBpp
**********
Pp
2E,Ea
p-l
Ypa cos(pq +op®q) (12) Ep Yp Isin pp + IE,Ypg Sin (pq +ôp -8q)
|Epl
9P
Qp
E,E, Ypg l
sin (pq+ôp-8,) p= 1,2..-1
Then the equation relating the changes in power to the changes
The elements of the Jacobian are calculated from equations
(12) and are in the voltage magnitudes and phase angles for the Newton-Raphson
For J1 method is
B-EHH
From bus admittance matrix
BUS
Set interation
Advance
iteration count
+Ae
count k =0 K* k
P1,2 ps
Test
AQ
0J4 E
Successful solutions can be obtained also by reevaluating the
A
Equal
for coverage or less Calculate line
Jacobian in only the first few iterations.
Imax Apk= flows and power
max AQ1 =E at stock bus When using rectangular coordinates, a solution to the load flow
problem also can be obtained by neglecting the off-diagonal
Greater elements of the submatrices Jj,J2,JJ3 and J4 of the Jacobian (Ward
Calculate bus currents
and Hale, 1956). This results in the following equations for the
changes in real and reactive power at bus p.
dPp dPp
p=1,2,3..n ps AP, = Ae, + Af,
dep ofp
Calculate elements for jecobian AepepGpp fpBpp +Cp) +Afp (CpBpp +fpGpp + dp)
-
(
Aduance Reploice
1by1
ileration count
po -1,2.n paa
P-1,2.n +1-
+a(e-e)
change in voltage Greater
AEI AE eKtl
P (accelerated)p
mar
qual or le
-
K and C
i 7
Replace i by and by to obtain
Set current flowe i0 and
bus currenis Ipus0 ñew current vector i or all elements
Calculate new bus voltages
Assume bus voltages
E
Ei-E, +K'l=i
p-1,2 p
-ep fqGpq-eqBpq) 1)
BD COMP. APPL. IN ELECT. ENGG. (B.E. VIll Sem, E
where ep and fp are the components of voltage at bus p. The Val. WBD COMP. APPL. IN ELECT. ENGG. (B.E. VIll Sem. Elect.)
alues 143
of ep and fp must satisfy the relation In the Newton-Raphson method, the equations for
a voltage -
controlled bus p are
p+p(|Ep l(scheduled)
(2)
in order to calculate the reactive bus pOwer required to provide
the Pp2 Gpa *igBpa)+1p",GpaCqBp))
scheduled bus voltage. The present estimates of ep and f,
be adjusted, therefore, to satisfy equation (2).
ust
and |Ep P=ep+f,
The phase angle of the estimated bus voltage is where equation (5) replaces the equation for the reactive power. The
arctanf
matrix equation relating the changes in bus powers and the square of
voltage magnitudes to changes in real and imaginary components of
p voltage is
Assuming that the angles of the estimated
ep
and scheduled AP JJ2 |Ae
voltages are equal, then adjusted estimates for and fp are AQ
J3J4 Af
p (new) |Ep l(scheduled) cos p AEP
reactive power.
144 VBD COMP. APPL. IN ELECT. ENGG. (B.E. VIl Sem. Elect ELECT. ENGG. (B.E. VIll Sem. Elect.)
M9D COMP. APPL.
IN 145
In the Gauss-Seidel method using ZBUS a correction to the Q.10. Explain how voltage control is achieved at a remote
reactive bus power can be calculated in order to provide the
bus.
scheduled voltage (Brown, Carter, Happ and Person, 1963). From the
Ans. Voltage control at a remote bus
performance equation, the voltage at bus p is
It is the practice in the operation of many power systems to
p +fp =Zpilf". t pp'p2paa control the voltage at a bus other than the terminal of a reactive
The current at bus p can be corrected by Alp to obtain source. This makes it necessary in the load flow
solution to
satisfy the equation. Subtracting the two magnitude specified for bus q, as shown in figure below.
where e, and f,
A procedure developed to accomplish this assume scheduled
voltage equations,
approximation is
A-pp)-+jr") Zpp
voltage magnitude for bus p. A reasonable first
Ep lecheduled)
0)=|Eqlscheduled)
During the iterative solution, the reactive power at bus p
isS
or Ar- +"9_p +jf calculated in the usual manner using this assumed scheduled
voltage.
Lpp
After the calculation of the voltage at bus q, however, the deviation
Assuming that the phase angles of the scheduled voltage and
from the scheduled voltage magnitude is determined from
ET are equal, then lscheduled)-Eg
A|EqEq
(el+j ||Ep lecheduled)
is
where E is the calculated bus voltage. If the value of A|E,
Lpp E
is
The corresponding correction in the reactive power is greater than a specified tolerance, the scheduled voltage for bus p
re-estimated from
AQ- Im|(E") *Ar
If the new reactive power Ep lscheduledy=(|Ep loscheduled)+A|EG
This procedure has been employed in the Gauss-Seidel method
is within the capability limits of the reactive source, then the
using YpUS
. During the iterative solution a change in the assumed
new bus current is
Scheduled voltage at bus p does not affect immediately the calculated
1k1pJ0" voltage at bus q. It is necessary, therefor to complete a number of
CE) iterations before re-estimating the scheduled voltage for bus p. Tests
If QT is not within the reactive capability, the appropriate have shown that five iterations are required to obtain sufficiently
limit replaces the calculated value in the determination of the bus accurate changes in the calculated voltage at bus q for re-estimating a
current. The new bus current is used in subsequent bus voltage new scheduled voltage for bus p. A voltage tolerance of 0.005 per
calculations.
unit provides acceptable results.
147
146 D COMP. APPL. IN ELECT. ENGG. (B.E. VIIl Sem. Elect) qhBD COMP. APPL.
IN ELECT. ENGG. (B.E. VIll Sem. Elect.)
-
AE I is less than the tolerance.
Escheduled )
(a)
Ypg
Qp A
Fig. Single line diagram of reactive power source and
remote voltage controlled bus
q(aEg E.) pg
current flowing from t to q, is
- .4)
irg =(E -
Eq)Ypg a
148 149
AD COMP. APPL. IN ELECT. ENGG. (8.E. VIll Sem, Eloct COMP. APPL. IN ELECT, ENGG. (B.E. VII Sem. Elect.)
ND
The corresponding terminal currents for the equivalent
pq
circuit shown in figure (b) are (Ep -atg)-E-E) a
p(Ep-Eq)A+E,B ) B- Ep
A-P
a Ypl +yp2
pq
2tYpn
Similarly, substituting E, =0 and Eg =1 in both equations
The mutual admittance from p to q is
(4) and (6),
= A +C Ypa
pq
qYpq and Iq a
Again, since the terminal currents for the transformer and its The self-admittance at bus q is
P+
equivalent must be equal,
pq A +C
Yqg =Yql
a
Yqn +|
P
Substituting for A from equation (7) and solving for C, Yql Tpq.. Yqn
IEG-1E lsheduled>e
DZ pg - a(a Aa+Aa)-Z pq
The standard change in tap setting of TCUL transformers is requires that every
The change in tap setting of any transformer
+5/8 percent per step. This value has proved satisfactory for Aa recomputed. To avoid these
element of the ZBUS matrix be
since it obviates, in general, additional iterations to obtain a voltage
be used, in
extensive calculations, an alternative equivalent can
solution. It is not necessary to check the voltage magnitude of those
original transformer
which the series impedance is made equal to the
buses controlled by TCUL transformers every iteration. Performing
correspond to tap
this check in alternate iterations has proved sufficient. A voltage
impedance and the shunt elements are varied to
changes (Gupta and Humphrey-Davies, 1961).
magnitude tolerance E of 0.01 per unit has given acceptable results.
terminal
Letting A =Ypg and equating the corresponding
The self-admittance Ypp and the mutual admittances
Q.11) for the
currents from equations (2) and (5) (refer
YpgYqp must be recalculated for every change in the tap setting
transformer and its equivalent, respectively, then
of the transformer connecting buses p and q. In the Gauss and
= -
Ep-Eq)ypq + E,B (Ep aEq)
Gauss-Seidel iterative methods using YBUS, the paranmeters
)
ipt
sq Ep as-jbs
Similarly, equating the terminal currents q from equations (a
Since
and (6) (refer previous questions) with A = Ypq isq=(Es-Eq)Ypq, then
=/1-g :
-1-E Og+ibg 1
(1i)
The shunt admittances, at buses p and q. respectively, are a Z M
pq
function of the voltages E, and Eq. The bus loading equations are, pr 'sq
Fig. Phase shifting transformer representation
then,
Similarly, the transformer current at bus q. igs is
Pp-jQp
Ep Epg Ep iqs (Eq -E,)Ypg
-y,Eg-1-pEp
Substituting again for E,
L pq
Eq
iqs ={(as + jb, )Eq -Epl + jb,
a,
Q.13. Write in short about the phase shifting transformers When a phase shifting transformer is connected between buses
in load flow studies. P and q, the self-admittance at bus p can be determined
by letting E,
Ans. Phase shifting transformers buses.
equal tO one per unit and short-circuiting all other network
A phase-shifting transformer can be represented in load flow
Then
studies by its impedance, connected in series with an idecal
autotransformer having a complex turns ratio, as shown in figure pp1pl t1p2.. pr. pn
below. Then the terminal voltages Ep and Eg are related by Substituting for i,pr from equation (1ii) and since
'plYpl
P =a, + jbs
E .(1)
ip2=yp2
Since there is no power loss in an ideal auto-transformer, ********* **
pp .. T-
pa Tpn aMD COMP.
0.14. What is the
significance of inter-connected power
2
a,+b system.
The current flowing out of bus to bus is-Isq
q p Theref
Dre Ans.
the mutual admittance is
Ygp
System Pe2
D
Then Yap-Ypgs
and from equation (1) 5ystem A
L
Yqp pq System C
as +jbs PFL
Similarly, letting E, equal one per unit and short circuiting all System B
has the advantage that the tolerances are specified for the net real and to obtain
With bus 1 as the slack, use the following methods
reactive powers at a bus. The tolerances, therefore, are given
directly in quantities that are meaningful to the engineer who a load flow solution.
acceleration factors of
specifies the desired accuracy. Tolerances of 0.001 per unit for the (a) Gauss-Seidel using YBUS, with
the real and
real and reactive bus powers used in the test calculations and 1.4 tolerances of 0.0001 and 0.0001 per unit for
produced comparable results. The initial bus voltages were assumed
imaginary components of voltages.
equal to 1.0+j0 forall tests performed. tolerances of 0.01
(b) Newton-Raphson using YBUS, with
The time required for the iterative solution was least for the
reactive bus powers.
Newton-Raphson method using the bus admittance matrix. per unit for the changes in the real and
When voltage-controlled buses are represented, the Gauss (c) Gauss-Seidel using ZBUs,
with voltage tolerances of
Seidel method using the bus admittance matrix usually requires
0.001 and 0.001 per unit.
fewer iterations to obtain a solution. However, a few more iterations
(d) Gaus using YLoop, with loop voltages tolerances of
usually are required for the Newton-Raphson method using the bus
admittance matrix and for Gauss-Seidel method using the bus 0.01 and 0.01 per unit.
impedance matrix. The time per iteration for the Gauss-Seidel impedances and line charging
Soln. The transmission line
method using the bus admittance or bus impedance matrix increases are given in Table (i)
admittances in per unit on a 100,000 kva base
as a result of the added computations. The time
per iteration for the per unit bus
Newton-Raphson method decreases slightly, because The scheduled generation and loads and the assumed
the number of
arithmetic operations is reduced for the voltage
controlled buses. voltages are given in Table (11)
VBD COMP. APPL. IN ELECT. ENGG. (B.E.
VI
SemElect
Sem. 161
160 APPL. IN ELECT, ENGG. (B.E, VII Sem. Elect.)
for sample system aMD COMP.
Table ) Impedances and line charging In order to calculate
the parameters for these equations, it is
Impedance Line charging
Bus code ssary, first, to determine the elements of the bus admittance
P- Zpa pq/2 atrix from the transmission line and line charging admittances with
orOund as reference. Ihe transmission line admittances, obtained
0.0+j0.030 by
1-2 0.02+ j0.06
0.08+j0.24 0.0+j0.025 oking the reciprocal of the line impedances, are shown in Table (iii)
1-3 with the total line charging admittance to ground at each bus.
2- 0.06+j0.18 0.0+ j0.020 lang
5.00000-j15.00000
Ek
(E4 4-
= YL4p E,k+l - YL43E3** - YL45E5* 1.25000- j3.75000
0.0 + j0.05500
Ek =
-YL52 E2*-YLs4E4k+1 6.25000-j18.69500
(E)
VBD COMP. APPL.
162
E.
IN ELECT. ENGG. (B.E. VI
VII
Sem.E PPL. IN ELECT.
COMP. APPL
ENGG. (B.E. VIll Sem. Elect.)
163
The off-diagonal elements associated with bus lare BD in per unit at the p" bus. For bus 2
here Pp
-jQp is the net load
Y12 = Y21
=-Y12 =-5.00000 jl5.00000
+
j0.20)-
Y13 Y31
=-Y13 =-1.25000 + j3.75000 KL2 = (0.20- 10.83334 -j32.41500
The bus admittance matrix with ground as reference
erence = 0.00740 + j0.00370
for in following Table (iv)
sample system is
The KL,'s for all buses are given
s are obtained from the equation
The YLpq
= -0.80212 + j0.00071
are given in Table(v)
The YLpg S for all elements
with
It is not necessary to
calculate the parameters associated
particular load flow. For actual
the slack bus for the
solution of a
frequently
planning and operating studies, however, the slack bus is
cases. This type of change can be
changed in subsequent load flow stored
all buses are calculated and
made readily if the parameters of
in the appropriate data lists.
is to calculate a new
The first step in the iterative solution
The new estimate from the
estimate of the voltage for bus
2.
equation.
system
Table (iv) Bus parameters for sample
Bus code KLp
P
0.0 + j0.0
0.00740+ j0.00370
-0.00698-j0.00930
-0.00427-j0.00891
-0.02413-j0.04545
The KL S are obtained from the equation
= 0.888 + j0.086
The flow megawatts and megavars is
in
-6.3
5-4 = -0.30000
lines terminating at the slack bus. The real slack bus power i1s
QS 0.0{1.06(-5.00000) +0.0(-15.00000))
megawatts and the reactive power is -7.5 megavars.
129 and
=
- {0.0-5.00000) -1.06(-15.00000)}
1.0
b. The matrix equation for the solution of a load flow
h.the +0.0 1.0(10.83334) + 0.0 (32.41500)
{
This equation does not include the slack bus. The changes + 0.0
{ 1.0 (-2.50000) +0.0 (-7.50000)}
es in 1.0 (-7.500000)}
bus powers are obtained from -1.0 {0.0(-2.50000) -
(-7.50000)}
(1.0(-2.50000) + 0.0
This equation does not include the slack bus. The chane
anges in +0.0 (-7.500000))
bus powers are obtained from - 1.0 {0.0{-2.50000) -1.0
APp -Pp(scheduled) - Pp = -0.98500
remaining buses are
The powers for the
AQ =p(scheduled)p
P=-0.07500
where Pp(scheduled) and p(scheduled) are the net bus powers in per
unit. The calculated bus powerS are obtained from the equations P0.0
P-eopg +Bp)+oGp -eBp)} p=0.0
=-0.28000
o-reGp +Bp)-eGGGp-eB) Q-0.05500
using the initial bus voltages and the elements of the bus admittance Q-0.04000 bus 2 are
matrix. and reactive power for
The real and reactive power for bus 2 are The changes in the real
0.20000-(-0.30000) 0.50000
=
P=1.0(1.06(-5.00000) + 0.0(-15.00000)) AP
2
T0)030000- j(-0.98500)
P 1.0(-2.50000)-0.0(-7.50000) -2.50000
=
=-0.30000+ j0.98500
1.0-j0.0 des
from the equation
The components of the current for bus 2 are, then, in the first row of J2*
The diagonal element
c 0.30000
d=-0.98500 dep
Bpe+fp Gpp +dp*
The components of currents for the remaining buses are
OE2 =1.0(32.41500) +0.0(10.83334)
+0.98500
cO-0.07500 1S
of2
d0.28000 33.40000
from the equation
and the off-diagonal elements
c0.0
d0.05500 dr-e Bpa +fp Gpa
c0.0 =
are 2=1.0(-5.00000) +0.0(-1.66667) -5.00000
d0.04000
5 of 3
The elements of the Jacobian =
=1.0(-5.00000) +0.0(-1.66667) -5.00000
are calculated using the bus
voltages and currents and elements
of the bus admittance matrix. The of 4
diagonal elements in the row
of Jj from the equation
dp =1.0(-7.50000)+0.0(-2.50000) = -7.50000
dep
=epGpp-fp Bp+ep is dfs
first row of J3 from the equation
The diagonal element in the
172 RD COMP APPL IN ELECT ENGa. (8.E. JIl Be
VII Gem.
Lleca APPL, ELEGT EMGG. (B.E. VIH Sem. Elect.) 173
wn GOMP.
0020.0-1.50000)-1.0-2.50000)=2.50000
ofs
00
=1.0(32.41500) +0.0(10.83334)-0.98500 31.430m
31.43000 Repeating the process to obtain the elerments for the remaining
k = 0 is,
rows, the Jacobian when
and the off-diagonal elements from the cquation
are
=0.0(-1.66667) + 1.0(-5.00000)=-5.00000
des
3Q2
=0.0(-2.50000) + 1.0(-7.50000) = -7.50000
des
0Qp
ofp
Bpp +c is
Q
=0.0(-5.00000)
Of -1.0(-1.66667) = 1.66667
4
IM ELECT EHGG. (8.E, VIl Sem, Elect)
174 COMP. APPL. IN ELECT. ENGa. (0.E.
VI Sem, Eioe o APPL. 175
AD
The solution of the matrix equation for Aep nd Alp p23 able (ix): Changes in bus voltages from the Newton-Raphson
YBUS
4,5, can be obtained directly fromn
solution using
Change in bus voftages
APk
Ae teration Bus 3 Bas 4 Bus 5
art
Bus 2
4ok Count k
0.0 +0.0 00
0.03176-j0.00123
00 +00
G.03136-5747
0.D
00
0.05505-j0.05084 9.2652-0.1234
0.00876-0.00014-.01133+j0.00/201 -001206+p239 9.01424+0.00375
the Newton-Raphson
Table (xi): Changes in bus powers from
09188 05559 -01302 -02597 -03148 -01930
03752 .07551
-01529 -0.1687 -0.1930-04357
solution using YBUS
04846 05559 .12796
04428
E-E +AE
0.04365O8+j0. 1309524
E =1.05505- j0.05084
process it is necessary to
Prior to initiating the iterative
E =1.03176-j0.09123 Calculate the bus currents with the scheduled
net bus powers and
= 0.17544-j0.028887
The currents for all buses, except the reference,
are
This new value of bus current replaces the previously
0)0.20-j0.20
(0.0+ j0.085)(1.0+ j0.0) = 0.200- j0.28s calculated value for bus 2 in subsequent calculations.
A new estimate of the voltage for bus
1.0-j0.0 3 is obtained next by
o.05112-40.0asso9 002777-j0.09581
0.02521-j0.09920 001913-j0.1403
-0.00693+j0.00562
C=4 1
0.00736-j0.00744 -0.005974j0.00466
.0490ej0.O8313 0.00008-j0.00067
-0.0006-j0.00087 0.00006-o.0054
0.0330-50.00043
-ZF 22
g
-ZF
+ 32g)
Not defined zF 2p+32
The loop admittance matrix
is
3a+ 27pg)-z-zp +376)27p + 57g
O0 0 A B C
--
-1
1h-P(Ep) -y,E
K These curents, identical to the initial bus currents calculated in
the bus impedance method, are
=0.200- j0.285
1 -0.450+ j0.095
COME IN ELECT. ENGG. (B.E, VIl
IN aE. VIll
ELECT. ENGG. (B.E. VIl Sem.
Sem. VWD Sem, Elect.) 181
180 D COMP. APPL. Elect)
1
1450-j0.150
1=-0.400- j0.005 2 1.000-j0.055
0.600-j0.060
1=-0.600+j0.060 i= 4 0.200 + j0.285
are calculated from 5 0.0 +j0.0
The changes in bus currents
6 0.0+ j0.0
a-1-1 0.0+ j0.0
Since the bus currents prior to initiatng the
iterative proced.ure
Ar=0.200-j0.285
Eoop-C'[2]i
the loop voltages are
Ar -0.450 + j0.095
Aib =KAI(0)
BUS
are
2 3 4
From the loop performance equation the balancing loop
currents are
-1-1 0.200 j0.285 A B
Aib= 2 -0.450+ j0.095 1.07143-j3.21429 -0.47619 +jl.42857 -0.23809 +j0.71429
+ j0.060 Loop
4
5-0.600 -0.23809 +j0.71429 -0.30159 + j0.90476 0.68254-j2.04762
1.450-j0.150
0.24286-j 0.04786
1.000 - j0.055
2 0.17310 +j0.34230 A
23
are 2 T.064J00
ABC 0.24286-j0.04786 EpUs T6ej00
A
1450-j0.150 02742)-j00
0.27429-j0.04020 1.06+j00
B
4
0.200+j0285
= 2 0.02+j0.064 085428+j0.13671
0.06286+j0.00014
0.85428+j0.13671
1.05112-j005399
2 |
|
1.02793 -j 0.09483
the equation
The new link currents from 1.02741-j0.1095
1.02241-j0.11604
are The new bus voltages replace the initially assumed voltages. If
5 0.24286-j0.04786
all loop voltages are within specified tolerance, the line flows are
61027429-j004029
calculated. If any loop voltage is greater than the tolerance, the new
currents. The
0.53174-j 0.06014 bus voltages are used to calculate new estimates of bus
second estimate for the bus voltages. The bus voltages for each
The new currents in all elements are, then,
iteration are shown in Table (1) and changes in bus voltages are
1 0.39572-j0.00171
shown in Table (2). The loop voltages for each iteration are shown
in
2 0.18857+j0.04543
Table (3)
3 0.06286 +j0.00014
Table (1) Bus voltages from the Gauss iterative solution using
0=4 0.85428+j0.13671
YLp
5 0.24286-j004786
6 0.27429-j004029 Bus voltages
Bus 5
Iteration Bus 2 Bus 3 Bus
7 0.53714-j0.06014 Count (k)
1.0+j00 1.0+j00
1.0+j0.0 1.0+j00
1.02741-j0.10095 1.02241-j0.1l604
1.05112-j0.05399 1.02793-j0.09483
These values replace the previous estimated flows. 1.02046-j0.08826
1.01932-j0.09495 1.01229-j0.10778
1.04826-j0.05073
1.01925-j0095111.0121-j0.10912
1.04624-j0.05131 1.02038-j008925
The new bus voltages from the equation
G
hf1
Tr 3
2
Fig. 1
0-
5
2
-0
Fig.
Reference node
is 0 node.
vD COMP. APP. IN POWER SYSTEM
(B.E. VIll Sem. EE) 543
544 BD COMP. APP. IN POWER SYSTEM
TEM(R
(BE.
VIlSom.a IN POWER SYSTEM (B.E, VIl Sem. EE) 545
COMP APP.
BD
2 0 0 0 0
0 0
0 0
Fig. 0 0
links {2,3,4) 0 0 1
0 0
Node 0 0
Element
For [C
[A]=
O@O
0
1
0
0
A
4 0 -----*
R S B
0 -1
0 -1
6 0 0 0 -1 0
A C=
0 0 0
0
0 0
Fig
0 0
IN POWER SYSTEM (8.E.
VIl Sem,
E)
wwD cOMP APP. IN POWER SYSTEM (
VI 547
Bem.
t I
Table
Fo
TementNa
Meslanee
0.5 0.5
0.5
0.4
Fig.
Fig.
(1,3,3
I-(2,4)
1-1 -1 -1
0
1
0
0 0
K
YBUs
Q.2/a) For the system shown in Fig.2 obtain
O000
Of05 0
000
0 040 0 0
00 02
00
00o050
Fig. 2 O0 0
00 03
POWER SYS
YSTEM (B.E V oem. EE) 549
APP, IN
APP
coMPWrite
OMP.
the per
down the
performance cquation of three phase element in both these
548 VRD COMP. APP. IN POWER SYSTEM (8.E. VIl
Sem.EE form?
20 0 00 12M
forms
0 25 0 0 0 IP.84, Q11
IY]-121-0 0 00 SECTION-B
00 20
000 1.25
How buses are classified on the basis
neçessity
ity of load flow studies?
of of
1 0
Ypus-A 10YI[A]=|00-10-1
110 n40
What 15
load flow
problem?
fications in
0-1 001 IP.272, Q4b)a (©]
-00
o -1
-1 0 0 -5 0
0 01 J 2 0
O
0-1.25 1.25
T2
1
[2+2.5+2 -2.5
0 5+125 -1.25 Line
-2.5 -125 2.5 +1.25
6.5 0 -2.5
YBUS 0 6.25 -1.25
-2.5 -1 25 3.25
(b) Derive an expression for the elements of the bus impedance matrix for addition of a Fig.
new branch to the existing partial network. 10M
G: X=X2 = 0,2
xo = 0.08 Xg = 0.03
IP.49,02)
02: X =X2 =0.3
Xo =0.1 Xg0.05
Q.3./a) Show that three phase stationary and rotating components can
by
be represenicd
diagonalised matrix form. 8M and T2: X = X2 =
0.1
Xo = ; Xg =0.03
IP.91, Q3 Ane,
X= X2 =0.4 Xo =0.7
au
e phase network component is represented in impedance and 1L-G fault takes
place at bus 3
cOMP, APP. IN POWER SYSTEM (B.E. VIII So
SSO ARD
Find a Total fault cument
Buas voltase during ault pu.
and prefault bus voltage of 1.O
assunme System to be mloaded
IPA38, Q.31
made for transient stabilitY sudies. Derive the swi ion
Q6a) Staate the assumption
r pOwer system.
IP.284, 219, Q26(), e1/
with the help of now chart, discuss the algorithm toT transicnt stability studics
ies of
rive the
expression for Loop USing Singular
transformation.
SM
IP.13, 0.51
Define 2M
path (i) Tree
0 Branch
(ii) Connected graph (iv) Basic loop IP.5, Q.11
() Form loop impedance matrix if the valves given are p.u. valves.. Consider the
0.1
TO
0.2
T 0.22
o
0.3
O.12
Fig. 1
Assume ground as reference
() Derive useful equations for formation of bus impedance matrix when the 8M
added element
is a
branch for 3 phase network. IP.185, 0.21
10M
s [P.93,041
rar a three phase to ground 1ault at bus Pn a power system, derive an expression
SECTION-B for
(i) Fault current.
Q4.) What is the necessity of load fiow analysis in power system?
3M (Gi) Faulted bus voltage.
IP.272,
0.40
D) What do you mean by bus loading equations?
(Gii) Voltages at other buses during fault.
12M
2M
IP.187, 0.31
IP.118, Q.10
Draw and explain the flow chart for load 1low analysis by Newton Raphson
(iv) Current through network elements during fault.
method using bus
admittance matrix.
as Fault current in 3- element (i, j) is
10M
-EF
(d) What are the diflerent types of buses named in load flow analysis? Mention
IP.136, 04
-E
the known and
unknown quantities on each bus.
SM
IP.272, 0.-40 YEn Q
-En)
Q5. The power transfer curves for a power system are described by equations given
below.
power output
prelault 15 1.0 p.u, compute the variations in '8' and 'o' with time. Assume unat
the lault is cleared at 0.15 sec. from its inception. Assume At =0.05, the magnitude o inertia
Pe-2sin
sUMMER EXAMINATION
B.E. VIl SEM. (ELECTRICAL) (CBS)
cOMPUTER APPLICATIONS L
IN POWER SYSTEM
20 , coP
Deve the
APP. IN WER
wansformation
SYSTEM (B,E. VIll
wauation
Sem, EE)
OR
of loop mpedance
matrix
Zogl
567
using singular
6M
IP.13,251
networ raph shown in Fig 206) obtain YBR,
(Elective I1) For
thie Zg and Yus by singpalar
transformation,
05
(n Augmented cut set incidence matrix [B].
0.4 pu pu
() Augmented loop incidence matrix [C].
ref.
OTTL Fig. 2 (b)
IP.333, Q.1@
031) Derive the equation useful 1or formation of ZBUS when added element is a link,
b) The bus impedance matrix ZBUs for the sample power system is given below.
Fig.1 (a) )If include the addition of an element from bus 2' to bus '3 with an impedance ot
0.4 pu.
P.533, 0.1a
0b) Explain in brief the following
terms ;
8M 0)
1if
include the addition of an element from bus 4' to bus "2 with an impedance
(9 Network graph.
of 0.5 pu in given matrix. 10M
() Tree of a graph.
2 3 4
(üi) Primitive network.
2 0.271 0.126 0.329
(iv) Basic cut set
BUS-3 0.126 0.443 0.188
4 0.329 0.188 0.380
IP.10,5,0,
IP.337, Q.2(a)]
556 VBD COMP. APP. IN PoWER SYSTEM (B.E. VII Sem. EE)
gARD COMP. APP. IN POWER SYSTEM (B
M(B.E.
VMSom. IN POWER SYSTEM (B.E. VIl| Sem. EE)
558 OR
te coMP APP. 559
of Ypus by
direct inspection method with s
example,
bn04
Q4(0) Eplain the fomation
0.25 0.25
Zpus0.25 0.4J
nethod for powe
building algorithm method for power system shown
IPh
Obtain ZBUS using in FipAr elemen 3 which is a branch p-1, q-2
AD) Adding
31 2
Z32
0.2 3 0.25 0.25 Z
Zpus=1025 04
Za1 Z2
2 Z
025 0.25
=Zj2
0.2 Zz=Z13 =025
0.15 =0.15=Zj2
Za=Z11
Z22 = 0.4+
0.2=0.6
Fig. 4 (b)
0.25 0.25 025
0.4 0.4
Ans. Oriented graph is
ZBUS
.25
0.25 0.4 0.6
4)
Add element 2 whichn is link fromp=0 to q=1
3 2
D
SYSTEM (B.E.V
0.153 0.096 0.096
Zyn-0.3530096) 0.553
ZBUS =0.096 0.153 0.153
0.096 0.153 0.353
0.336
Zn=-Z =-0.153 Write down the performance equaion or tne 5-phase element in both these
form
0.069
(ii) Voltage of each bus during fault.
-
0.047
= 0.11
0.13 0.13
0.22
0.11
Z11=Z1- =0.153-(0.153)2
Z 0.553
Fig.(6)
=0.11
VIlI Sem. EE)
POWER SYSTEM (B.E. 563
562 WBD COMP. APP. APP
IN TEM(B.E.
POWER SYSTEM (B.E.
Ans.
VIN
VIlls. EE
Som. CoP
(0.18 0.35+0.11
ZBus
(3) 0.46
=
link between p= 2 and q=3
(4) which
ent (4)
15
0.22 0.11 Ciement
:Adu
Step
0.13 ( (6/0.13 Z=pi-2a
tpa,pq
y pal
I step: Add element (1) in network (p= 0, q =1) =-0.13
Z-31
Zpi
Z =0=Z
=-32
=-0.35
Zi2
ZBUS 0.13, Z =
0.13
Zq=2pa tLpa,pa
(-0.13)(-0.15)--0.103
Z
1
2 3 0.64
Z =-0.158
Z=-0.12
Voltage at faulted bus during fault is given by
Z =-(-0.12) +0.13=0.25
Modifying
=0.103-0.103)(-0.13)
Z11 -0.06
0.25
Z33=0.12-(0.12)2
-= 0.06
0.25
POWER SYSTEM (B.E VIl Sem. EE)
APPIN
IN PO 567
cOMP perlormance f
Gauss-Seidal and NewMon Kaphson
method for
load
S66 VBD COMP. APP. IN PoWER SYSTEM
(.E, VII Som
he
the
Conpare
.EE) solulion, 5M
fow IP.344, 0-4(b
flowchart of Gauss 7M
neaw the
[P.119, 124,
22, 31
EP-T, EP-lo Pu
o OR
gener
generator circuit delivers 18 MW over a double circuit line to
MVA 50 C/s
Cls
Voltage at bus 2 during fault n
an
A20
The generato bus kinetic energy is 2.52 MJMVA at rated speed. The
0 infinite bus.
0.05
EF-V5 0.06 transient. reactance 15 X=0.35pu . Each transmission circuit reactance is
0 orator
0
0.288 hus voltage 1.0 pu. A 3-phase short circuit occurs at the mid point of one of the
0
transmission lines at t=0 and t Is cleared in 0.05 sec. Find the swing of the rotor
E=T, EP upto 0.15. Taking time step of 0.05 sec. Use modified Euler's method 20M
IP.298, 346, Q, 6))
a ag L 0J
[11
=0.288 a2 PU
||0
1T19= a2 a34.64
w31 a a2]| 0
a
WINTER E AMIATTON.-20163
ON.- 2016
wVIl SEM. (ELECTRICAL) (CBS)
COMPUUTER APPLICATIONNS
IN POWER SYSTEM
rive the
relation to obtain Zop from singular sformation,
IP.13,051
uences reactances of the components are marked on diagram. Select ground node
reference and element 4 as link.
as
12M
0.4pu 0.6pu
3
0.1025pu O 2 3 0.1025pu
Fig.1
IP.26, Prob.4
OR
8
02) Define
(a) Graph (b) Element (c) Node (d) Path
IP.5, Q.1
3
Fig. 2
ABC
POWER SYRTEM D
Clelste (8V
K
Be incldece maris
(Ref)
1-(3,4,5)
A BC D
b-(1,2,6,7),
Bus Incidence B]
matrix= -10
00
0 0
20
1
0-11
000
010
0 0
0-
-
1 -1
0 1+
Branch path -K Basic loop incidence matrix
CoO /3
EE) 573
572 SYSTEM (B,E. VII Sem.
VBD COMP. APP. POWER
IN POWER
SYSTEM oIM
(0.E. VL orientedgraph
Coresponding
0.22
3
0.2t 140.3
-1 -1
1
0
0 1
C-B'I
1-14, 5}
RH.SBt b-(1,2,3, 6},
YBsAYA
11 [A]
Nodes
O0
b/ll
Q3.(a) Derive the equation usefül for formation of LBus when added element is link
a -1 0
Start TOM 2
performance equations of a partial network Also derive
equation for removal of link 15M 0
IP.55,
03 0 00-1
(b) For the given power system shown in Fig.3 the impeda nces of elements are given
inP.0
Find Bus admittance matrix by direct inspection method.
-1
5M
0 0-1
O.1
-110 0
o
IA'j=-l
[A'O 0
1
0 0
0.2 0.22 -1 0 1
0
0.43
0 0 -1 -1 -1
0.3 10 0 0 0 0
0 50 0 0
Z=[Y]=00 00 4.5 0
0 3.34
0
0.12 O 0 0 0 0 2.32
Fig. 3 0 0 0 0 0 8.33
POWER SYSTEM
POWER (B.E. Vill Sem. EE)
NPO
IN $75
574 I
APP.
APP N
RD COMP. APP. IN POWER SYSTEM pcoM
OMP,
relerence
us,s
2-
(B.E, VIll
VIlSom.
YRaA YA=AlY-
-110
-10
00 0
01
0
s
EE)
0 0-1 01
0
00-1 -1
10
0
0
5
0 0 4
0 0
00 4.5 0
0
(1,2,3), 1=
(4,5)
0 00 3.34
0
be .
0 00 0 2.32
0 dhe element
Connectthe
1which is branch (p = 0, q= 1)
0 0 0 0 ;
0 8.33 Bus0.4
-10 5 0 0 0
0
ent 2 which is branch, p
element =0,
q=2
1 -1 0
-5 4.5 0
0
0 sep2:
Connect the
0-4.5
1
-10
00 references bus
0 2.32
0 0 -3.34-2.32 -8.33
0 0 pis
ZZpi =0
0
-5 9.5 4.5 0
YBus0-4.5 -2.18-2.32 Of04 Z12
0 -2.32 13.99
OR Zg =Zo2, 02 =0.3
04 For the system shown below, form
: lauo 03
the bus impedance matrix
using an algorithm.
Selt 0.4 01
impedances of different elements are
given in Fig. 4 select bus
3 as reference bus.
Explin
how the bus impedance matrix so
formed can be modified if an element
connected between Step3:Connect the element 3 which is branch p = 0, q=4
bus 3-4 is removed from the above system.
20M
,
0.4 0 Z14 Z=Zpi =0
0.3
0 0.3 Z =Z4 =0
0.4 0.3 Z44 Z42-Z24 =0
0.8 ZA1 Z42
Fig. 4
576
RD COMP. APP. IN POWER SYSTEM VER SYSTEM (B.E. V
Sem. EE)
(B.E. VIl APP 577
0.4 0 0 VIlSem. MP, p 1,q-4
EE which is link,
element55 wh
Zus0 0.3 0 ,Connect
element
0.3
Step 4: Connect element no 4 which
is link p-2, q-4 Zgus O 04 0 0
0.23 0.064
Z
ZBus
O 04 0 0 0.064 0.23
La
0 0.3
Z14
0 0.3
Za
Zn Zi2 Z14 ZZpi-Zqi =Z-Z4i
-Z41 =0.4-0= 0.4,
ZaZpi-Z. i-1, Zn =Zu
Modification,
Z1 =0.4- (0.4)= o
=0.244
1.03
Z = 0.4-0= 0.4, Z12 =
0-0=0, Z14 =0-0=0
Z12 0-0.4)(0.064) = 0.024
Z220.3- (0.3)-
1.40.23 1.03
Z14=0-.5)-0,23) = 0.111
Z4=0 1.4
=0.064 1.03
22=0.23-C0.064) 0.22
Z44-0.3-F0.5) (-0.3) = 0.23 1.03
1.4
mo
0,111
j011
0.049 0.178
j023 j0.13
000
0.5() Write down the performance equation
of the three phase element in
impedan
impedance
and admit
imittance
j0.11
form.
are
bus impedance
[P.34,011
elements
-
I5M
0.6 Step
3: Add element 3, p- 2,9=3
Fig.5 Zg Zg tZ33
POWERSYSTEM (B.E, VIl Sem, EE) 581
APP IM
COMPelement 5 p-0, q-3
RD cOMP. APP. IN POWER SYSTEM (B.E. wct
Vl Bom,
te)
ha O 0.11 0.11 01 Zp O0.1 0.11 011
z
0.11 0.34 0.34 0.11 034 034
Z
O0.11 0.34 0.74
0.11 034 038 Zy
Connect element (4) p-2, q-3
Za-Z-Z 0-(0.38)+0.11
=
Zg =Zy-Za = 0.11-0.11 =0
= 0.49
=
Zy =Z-Z = 034-0.74 -0.4 =0.11--0.1)2
Zq = 0.08
0.49
Zy =Zp-qi +Zp P4= Zz1 =Zs +Z2.2 -0,74
Z12=0.11-C01)-0.34)
Modification = 0.03
0.49
Za =0.11-0=0.11, Z2 = 0.11-0 = 0.11, Z13 = 0.11
Z3
=0.11-E.D-0.38)_
0.49
Zza-034, Z2 =034, Zgy = 0.74
0.38
2=0.34C034) = 0.104
0.49
Za-0 4.32
Zn-0.08, Z2 =-0.07, Zs-0.08
1b=T, I2 =0
Z-0--.08)+0.13 voltages
Bus
=0.21
-z
Modification,
z2+Z2
EZ+27,+32 -2
Z1=0.08--0.08)2
0.21
-0.61 |-0.9333
Z12=0.08-F0.08)-0.07) = 1.533 0.056
0.21 L-0.04 -0.063
1.0033
connected to
infinite
e bus has following parametes
7, A
single m/c
=0.25 p.u. line
reactance 0,1 pu dislly the bus voltags
was 1A pa
OR
Q.6() Derive equation for shot circuit curent and oltage it athree phase to ground fault o
Occurs at
bus p
141
[P.193,
04
Show how the primitive impedance matrix for a
balanced three phase rotating element yields
matrix [T,].
6
P87,0
Q.74) Give and explain flow chart for load flow solution in power system
by Gauss-Seidel iterative
IP.119,
0
b) Derive the swing equation 4NM
IP21,0
( State the assumption, made for trans ient stability studies. 4M
IP.284, 06)
APP WER SYSTEM (B.E. VII Sem. EE)
COMP. 587
SUMMER
2017
EXAMINATIO - D 2 A B C |D E
B.E. VIIl SEM. (ELECTRICAL) 0 0
(CBS
COMPUTER APPLICATIONS 5 0
IN POWER SYSTEM 0
IP-15,
06
(b) For Fig. 1(6) shown, determine matrices A, B, C and K. Select
node. 1 nsreference
raf
and
elements 2 and 5 as links prove A.k° B for given network.
12M
A B C|D
io 0-1
3 0 0 01
5 0 0 0l0 1
-1
LAJ-20
-1
10
0 -1
-1
4
0
00-1
0 0 1 ref.
I-21-
Fig
A]- -1
AKT -B
3
0 0 -1
0 1
0
588 VED cOMP. APP. IN POWER SYSTEM (B.E. Vil1 Sem. Ee)
IN POWER SYSTEM (B.E. VIlI Som. EE)
588 VRD COMP. APP. IN POWER sYSTEM cOMP APP.
589
(B.E. VIl VID 2
Sem Ee. 3
0
OR 0 0
0.5
Q.2 For the system shown in Fig. 2. Obtain 0 0.4 00
BUS And YLoop by singular
0 02 0 0
ransformation,
transfe 0
Also obtain YBr from YBUS Fositive
5 0 0 0.5 0
sequence reactance of
different elements
are shown 0 0 0 0.8
in Fig. 2 in brackets.
20 0 0 0 0
(0.5) 2.5 0 0 0
50 o
2 Y-Z=0 0
5 0 0 0 2 0
(0.5) (0.2) 0 0 0 0 125
3
=[A JIYILA]
(0.4) (0.8) YBUS
2 0 0 0 0|1 0 0
0 01 1|0 25 0 0 0l0 0
00 0
1
-1 -1|| 0 0 0 0 1
0 01 12.5 0 -2.5
-0o 0 -1 -1|0s
o o o
-1 -1 2 0
0 -1.25 1.25
Zloop=CZC
b {3,4, 53
I-{1,2}
YBUS [A']Y[A]
31
LA]-0 0 -1
2 -1
Fig
POWER SYSTEM (8.E.
RD cOMP APP IN POWER SYSTEM(8.8.V OMPAPPM
H VI sen. E)
000
591
11-1
-05-05 100
0.4-0.4
IC-0 020 02 02 o 01-1 -1
o
-0.5 0
o ujlo 1 0.8 0 0
2 0
-05 -0.5 0 25 0 00
-0.4 0.4 YIB]=00 500
cIRg- -1-111
CA -1 101 0.2 0.2 o0 0 2 125J|1 1-
05 0 00 00 1-1
0.8
LuL 19 6
[B']EY (B]=0 0
000 1 1
0.625 0.909 2 2
-2001 -1 -1
Yu0909 05s23) 1.25 1.25 -125
5.25 3.25-325
4-9.25 125 Ypr3.25 5.75 0.75
YBUS-2.-3.75 125 825
-25 5 25 -3.25-3.25
is showa below. Obai
Q30) The power system represented by single line diagram
Y-B JYIB)
(0 YpUs by direet inspectioa
O-
Fig
Fig. 3(a)
APP IN POWER STEM
(B.E.
VISom.EE)
coMP
592
RD COMP. APP. IN POWER SYSTEM 2.5 0 000
Positive sequence
reactance of the elements
(B.E. VIlSem 0 3.23 0
00 o0-I00 0 593
00 0
2 00 -11
Reactance
U.4
3
0 0
0, 0 0
1 -1 0
.3 0.4
0.5
0.2
Ans
2.5
0
0
3.23
0
00 0
0 0 0 0
0 0 3.33 0 00
YIIA
25 0 0 oA
5 0
0 20 00
0 0 00 0
[-2.5 0
0
0 0 3.33
3.33-3.33 0
-2.5 0 2.5
-2 2
Fig.
b-{1,2,5)
0-5 0
I-0,46) 2.5 0
0
-10 1
-1 0 1 00 333
Ypus-LA1Y]A
A'YA=00 -1 0 -] -13.53-33 0
25
o5
0
L0 10 1 1
2 3 4 0-2 2
0 -5
1-1 0 0
20 01
A=5 0-1 0 3.33-8.33 -2.5
YgUs=-3.33 10.33 7.83
3-1 0 1
6 1
-1 0
0) Derive the equations for the addition of branch to partial network 101
-1 2 5 3 4 6 IP.49, 02
1 04 0 000 0
20 0.30 0 0 0
OR
Z=5 0 0 03 0 00 044)Form bus impedance matrix using algorithm for the power system shown if
3 0 0 0 04 0 0
1211
400
6 0
00 0.5 0 Fig. 4(a). Select bus 1 as Ref.
0 0 0 0 02
COMP. APP. 595
594 RD COMP. APP. IN POWER SYSTEM (B.E. VIll
Sem, EE VDZaspa.pq0.23
3 2
-2[0.13 0.13]
ZpUs
0.13 0.23]
Add
clement (5). p=1 and q =4
Step3
3 4
3 2
2
0.13 0.13 Z24
Fig. 4(a) ZpUS3 0.13 0.23 Z34
Z4z Z43 Z44
4
Reactance of the elements are shown in table.
Z42-Z24 =Z
Element No.
2 3 4
2 0.13 0.13 0.13 Z2
ZBUS3 0.13 0.23 0.23 Za
4 0.13 0.23 0.37 Zar
3 Z12 Zs Z14 Zu
ZBUS2O.13]
2
Zu-Zp +Z14,14 = -(0.23) +0.15 =
--0.37) 0.52
Step 2: Add element (2). p-2, q-3
Modification
3 2
ZBUS=2 0.13 Z23
3 Z2 Z33
ZBUSZj newZj (old) Zya
Za
Z4 = Z34-
0.128
Z4 ZZ
old Z
Za
2 3 4
0.2875 0.08
Zu Zu
0.52
=026 0.08
0.1282 0.102
ZBUs3 0.2875
0.102 0.245
3 4 4 0.08
2 0.097 0.0725 0.0975
ZBUS3 0.0725 0.1282 0.128 if the impedance of the element connected between bus 2 and bu5
Modify
4 0.0975 0.128 0.26
Add element 3 between p-3 and q=4 a fe required reduce to 50% of the original value. (Refer Fig. 4a). 4
(6) Modify LBUS if the element connected
between bus 2 and 35 removed. (Refer Fig.
4(a).
0.15 0.15
Ans. 4M
50.14 5
0.14
0.05
Fig.
Siep I: Add element which is link betweenp=2 and q=3 with 0.09
Fig
2 4
b-{1,3,5)
2 0.08 0.2875 0.08 - 0.2875
- {4)
BUS= 3 0.2875 0.1282 0.102-0.1282
Removing the element between (2) and (3) 4 0.08 0.102 0.245 - 102
ie. p -2 and q- 3(ie. -0.1) -0.2875 -0.1282 -0.102 0.295
Prefault: 0.65
IP.87,
OR
0
Duringfault: 4.0
Q.6. For the power system shown in Fig. 6, if L-G fault
takes place at bus 3.
Postfault:2.0
Determine
T T2 Determine variation of rotor angle and velocty versus t using modífied Eulers
Line method.
G G2
Take time step of 0.05 sec.
Fault is cleared at 0.1 sec. carry out calculations upto 3 iterations 2011
IR.S13,
06
Fig.6
Sequenee reactance data is given belowW
Fig. 1
3
5
4 4 O 4
b-(1,2,4)
I-(3.5)
COMP,
APP. IN POWE
SYSTEM (B.E. VIll Sem. EE) 601
POWER SYSTEM (B.E. VIl Sem, EE)
APp IN 603
602 RD COMP. APP, IN PoWER SYS
TEM
(DE.VI1 yooMP A B C D
Sem.
E
A 0 0
0 0
0 5 -1 0
[A] 0 0 --
1 5
B
-
B
Basic cutset
2
0
A B C D E B
[B) 0
C]
1 0 0 -1
b
1 0
2 0 0
0 0
4 0 0 0
+1 0
0 0 0
APVMPO
POWER TEM (B.E. VIlSem. EE)
) COMP APP. IN POWER 605
Zs y
BYATEM gOMP,
(8V shown in Fig form Algrithm method
I rk
04
0.8 02
04
Fig. 3
P.71,251
K
OR 2
Q24a) For network shown in Fig 2 obtain and Zloop
BUS BR and Z10op by singula
by Singular
transformation
0.5 PU
5 PU
1
l=(2,5)
(0.4 PU) OR
2
0.4 PU -- 0.5 pu
L Fom BUS
impedance matrix Zgus using algorithm for a given power system network
j0.56
j0.4
IP.10,03 jo.35
Q.34a) Derive expression for formation
of ZBUS when added element p q is a link to the exísting
IP.55, 0 form? Write down the performance equation in both the foms 10M
IP.84,Q.11
UIMIVMER XAMINATION
608 RD COMIP. APP. IN POWER SYSTEM(8.0.V 2018
Uking tasfomation malrik '1 transform the three phase inpedance
Nedance ba
Bem
EE g.E. 1l SEM.
VIII ECTRICAL)(CBS)
in 0 1,2 sequence quantities Assume stationary elements
ak ta g equv MPUTER PPLICATIONS
IPAT
IN POWER SYSTEM
OR
0
Q6) Represent three phase power system lor short cireult studies
for a fault at bus p ression for branch admittance matrix using singular transfomation
expression
Deive 8M
P.185,0.1 IP.17,271
For three phase to ground fault at bus
P in a power system derive an expression G
Ssio for: sequence
cequence reactances for the network are shown
O Fault current. () Faulted bus voltage. (ii) Voltages at other buses durino positive in figure Q.1b).
The
fault.
() Curent through network elements during fault. Indicate
ic the clements
A - B and D-Fas links and form
1417 incidence matrix.
IP.187,031 () Bus 2
Q.7.(a) Draw the flow chart for Gauss-Seidal iterative method using YBUS
for load n. m)
Branch path
incidence matrix
2M
T004
M
P.272,0-40 002
OR
Q.8.(a) Why the study of transient stability 15 needed' What are the assumptions considered
in its stut 0,05 0.10
5M
P.284, 06()
(b) A 4 pole, 60 MVA synchronous machine
running at 1500 rpm delivers 55 MW power 0.03 0.07
at an
infinite bus through transmission line, Generator
has inertia constant of 4 MJ/MVA and voltage
Fig. Q.1 (b)
behindtransient reactance E' =1.05 . Voltage at infinite bus is
1<0 P.U.
P-421, Q.1(6
Find variation of and against time by modified Eulers method. Assume preaut
po ansmission system reactance of 0.3 PU. Take time step of 0.05 sec. Assume fault s) Obtain ZBUS using singular transformation for power system in fig Q2a). 1he
0.3 Renctance
(pu)
0.4
0.3 0304 05
P.591,
0.1 0.4 OR 0.3a)
ce reactanco of different
sequence ments are
tive
Poslive shown
in fig, 4 obtain
0.5
m. Use
algorithm. Use Node 1 as reference node.
0.3 us by
(0.1)
Fig. Q. 2 (a)
[P.434,0.26
02
(0.1)
() YBUS by algorithm.
2
-0- 5
Fig. 3(b)
b(2,3,5)
={1,4)
INAPOWER STEM (B.E. VIll
P. IN
APP Sem. EE)
COMP
610 ABD COMP. APP. IN POWER SYSTEM (B.E, VIle
Sem.
Starting with element 2 whieh is a braneh with p-1 and q- 2 EE)
Zn = =Z-Z2=0.1-0.1= 0
BUS [0.1) 1,
:Zj4-Z24=0.1-0.1=0
(2) Add element is a branch p= and q=4 Zy4 =
3' which
1
jed,
Zin=Z12-Z22 =01-03--02
ZBUS
0.1 js2,
t2o1,01=0.3+0, = 0.4
4 Z41 Z44 Zy=--Zau
Modification
Z4 Z =0.1 = Z41
ZBus
4 0.1 0.5
L
3) Add element '5' which is a branch p=2 and q=3 Z14 = .1
i 1,j=4
14 2
1 0.1 0.1 Z3 Z12 =02-42 =01
i= 1,j=2
LBUS
4 0.1 0.5 Z4 Z
2 Z1 Zsa Zs3
i4,j=2 Z42 = Za2
-4 2=0.1
Zi2 =Z2 = 0.1 =Z1
1
4 2
Zz4 =Z4p =0.1 = Z4
1
0.1 0.1 0.1
Z33 = 0.1+ 0.2=0.3
ZBUS
4 0.1 0.35 0.1
ZunewZucok)
0263
R
-
0.1 0.1 0.1
ZBUs-0.1 065 0.1
IP.87,0.21
b) How three phase network component is representca n puancc ana admittance
form? w..
Write
down performance equations in both forms.
10M
IP.84, 0.1) p=0 and q=1
Adding branch between
OR
Q.6. For the power system shown in fig. 6, if L-G ault takes place at Bus 3, determine : ZooZ100
(a) Total fault current.
Z11=0.25
(b) Voltage of each bus during fault.
(c) Current through phase C of trans1ormer element. Assume prefault bus voltages
ges aare
1 pu. ZBUS = 0 0
20M
O0 0.25
Fig. 6
Zsus
O 0.25 0.25
Z-Z=0.25 (-0.65)
1,j=3 Z13 = 0,25 -0.25)(-0.65) 0.0875
-0.25)
Za=Za =0.35
i-
ZZg3 0.65
0.25
(-0.25)-0.75) 0625
Z14 = -
i-2,j =4
Z =0.65+0.1= 0.75
Z22 =
0.35-035)-035) 0.2275
i-2,j=2
O 025 025 025 025
0.35-0.55)-0.65)
-0.35) 0.65) - 0.1225
Zpus-025 035 0.35 035 Z23 =
i-2,j=3
025 035 0.65 0.65
0.75) -
025 035 0.65 0.75 -0.65)F075)
=0.35-0.65)(- 0.1375
Z24
i-2,j =4
Addition of eiement 'S' which is a link between p - 0 and q- 4
Zp-Z4 =-0.65
Zero sequence network
Zy4=-Zu =-0.75
o 00.1 OR
LG auh A50
MV Hz synchronous generator cireuit delivers 20 MW
25
3YF
3Z+Zp0+ZLP ear ble circuit line
doub
to an infinite bus. The generator bus kinetic
enery 1s
IMVA
MVA at rated speed. he generator transient reactance
2.52 MJ is
0.835 0.35pu. Each transmission circuit reactance is 0.2 pu on 25 MVA base.
0.83 5 X'd=
generator bus voltage was pu & infinite bus voltage is 1.0 pu.
0.833 Initially
1.l
A
(b) Voltage of each bus during faut chort circuit occurs at the midpoint of one of the transmission lines att
3 pha
La it is cleared in 0.05 sec. Find the swing of rotor upto 0.15. Take time
-
Zr - 0 and it
Ep
02+Z +Z +3ZF
Zpp +Zpp + 3ZF step of 0.05
sec. Use modilied Euler's method. 20%
-LPP X= 0.2
-0.515 3 X=0.2 V=140
Xd = 0.35
0.7561
3
-0.2430
3
AIs. P 20 MW =
*=
25
0.8 PU
)-3.42-1.42 =2
E-1.1, V=120°
0 Sep 1: Prefault condition/ calculation
0.4942.02V3 0.2
0 0 0000
Q.7.(a) Explain the significance
of load flow studies. Give classification
of buses for load flow studies.
0.2
0.35
SM O1200
[P.272, 369, 0.4(6),
(b) Derive the equation
(C), (a))
1.10
used to calculate real and reactive bus
powers for load flow olution o
using Newton Raphson
Method with YBUS
8M
X=0.35+ 0.45
IP.133, Q.4
INA oWER SYSTEM (B.E. VIl Sem, EE)
APP
616 AD COMP. APP. IN POWER SYSTEM (B.E. coMP perfo
Gauss
rformance of Gauss Siedel and Newton 617
the Raphson
VIs
Som.EE Cnpan
methods
for load
005 0 soution
BUS0
00
01 0.02
0.1
ow
M
P.34,046)1
OR
LG. fault
MVA, 50 Hz synchronous generator circuit delivers
3YEI 20 MW
over
32 +Zp0+ ZZppl circuit lin an infinite bus. The generator
to
double bus kinetie
energy is
20
(c) HL-03.42a-1.42a2=2 s,P=20 MW==0.8 PU
25
-
E-1.1, V=120°
| 0.4942.02 5 0.2
0 0 0 000
Q.7.(a) Explain the significance
of load flow studies. Give classification
of buses for load flowstudies 0000
0.2
0.35
M O1409
IP.272, 369, 0.46), (o), (a))
(b) Derive the equation used
to calculate real and
reactive bus powers for load
flow solution oy
using Newton Raphson Method
with YBUS
8M
X=0.35 045
P.13, 0.41
POWER SYSTEM (B.E.
APp N VIll Sem.
EE)
oOMP
818 RD COMP, APP. IN PoWER SYSTEM (D.E. VIl
VIll
619
So
Sem,
EE)
PE sin8o aloos
L62.5
5, =19.08 M
0.35
Xa o(0)+(At)
1.1
01 o(0.05)=
xa =315.72-314.15
do
Pmeax
EV
= 1.1x10.91
1.2
8(0.05)= o(0)-,
dt lo.0s
At
=2.92 rad/sec
relation
relation tto obtain YBR by singular transformation
81
S(0.1)= 8(0.05) o Gt lo.1
x At
lo)
Derive lhe
the
IP.17,07
=23.58+2.92x 0.05x
80 for a power ystem using singular transformation shown in Fig (1).
Find Ypus
Positive
sequence reactances of the components are marked on diagram. Select
8(0.1)= 31.97
and element 4 as a link 121
ground as a relerence
Att 0.1, the fault is clear
Pet)=Pmax 1 Sin ð
(0.1025)pu
0
O04 0. (0.1025) pu
Step 3:t=0.1 sec and t+l =0.15 sec
YBUS[A]' [Y][A]
=-16.13 rad/ sec Ans
do
o(0.15)=o(0.1)+At)
dt
-
= 317.07+(-16.13) (0.05)
do
t lo.15
=o(0.15)-2 Tf ref.
=316.26 -2(7) (50) b={1,2,3} and I= 4
= 2.11 rad/ sec 3
T0.1025 0 0 0
do Z= 2 0 0.4 0 0
60.15)=8(0.1) x At
dt lo.15 3 0 0 0.6
4 0 0 0.1025
0 25 00 Find:
0 167 0 Element-1Node incidence matrix
00 9.756 (1)
Branch Path incidence matrix
(2)
incidence matri
Basic cut-set
0)
Basic loop
incidence matrix
(4)
A -1
L TO
TO
-10 0
A-1 0 o
oo-1
Ysus=A. YAA
a9.75 0 0
-110 011 0
-10
0 0 -1
25 0
0 167 o00- Fig. 2
0 0 0 9.75|0 0 1
Select node 1
as reference and elements 1,4 and 5 as links. P.30, 0.6
-9.75 250 0) Explain the following terms
=9.75 25 0
TT 0.43
0.2 0.22
b-(1,2,3) /= (4, 5)
----- ---
0.3
... eauation
equation for short circui
circuit current and faulted bus voltages
Derive if a three- phase to
)
Q4.(a) For the system shown below, form the bus impedance matrix using building algorithm. OR
Selr
impedances of different element are given in Fig 4. Sclect bus -3 as reference. Akla) For the system shown in Fig. 6 consider zero sequence bus impedance matrix
121
IP.$74, 0-44
element are 15
Modify bus impedance matrix if an element between 3-4 is removed from the =
() above system. Z110=0.054, Z120 Z210 0.005
4
Z230Z320=0.014,Z220 = 0.035
0.4 0.3
0.8 variable as well as symmetrical components.
ply
.13
Fig.6 P.13, 0.51
IP.579, Q.506)
ot
is 2.52 MJ/MVA at rated speed. 1he generator transient
bus. The generator bus kinetic energy
Initially the generator bus voltage was 1.1 pu and infinite bus yoltage is 1.0 pu. A 3 phase short
circuit occurs at the mid point of one of the transmission line at t = 0 and it is cleared in 0.05
sec. Find the swing of the rotor upto 0.15 sec. Taking time step of 0.05 sec. Use modified Euler's
method 201
Xe = 0.2
0.35
E Xe 0.2
Fig. 1(b)
IP.298, 06)
627
V3D COMP.
APP. IN POWER SYSTEM (B.E. VIll Sem. E)
wER SYSTEM (8.6 VINSem.
t) 629
w cONe APR IN POowER SYSTEM (8E. Rrasck (Flementy
V Bm t
0.1025
A 05
012
0hrw sitm ri (
0 0.1025
0B sdi erh (
-
() npedanoe matria (Z-)
00 0.1025|
nong[0.825)
igelane matrix
to bus
fhom bus 2 1o wilhan
bus 33 with
the aklhion of an element an inpedanee
( ilode
of 04p
P.337,2.20)
OR
= 3 [0.5]
Bus by building the algorithm. The val
Q4 For the system shown below, obtain es of
is a branch fromp=3 to q= 1 this adds a now bus.
impedance in per unit are given as- 20M
.2 which
0.4
0.25
TausZ Z1
0.25
0.3
0.4
:1, Z Z
=0.5=Z31
0.5 :Z =Zg
: pP
Ans. To find: Zpus =?
.Z1*y131
0.4 = 0.5+0.3
0.25
0.4
25 =0.8
0.3
0.5 : f0.5
Ol05 08
0.5
632 RD COMP. APP. IN POWER
SYSTEM (B.E.
Vis IN POVWER YSTEM (B.E. VI1 Sem.
IP. APP,
Now again adding 3 which cOMP. EE)
ele. is a branch fom p-1 to q-2.
q-2. This
This agni
again
Sem.
anewb EE
yRD
adds to
-Z for i-11
-0.8-Zl,
0.5 0.5 Z3
ZUS- 0.5 0.8 Z2 Z2-Z12-0.8=Zz1. for i=2
Z -Zat +pqpq 11 +Zo101 0.8+ 0.25-1.05
O
ZZ O.5
0.5
0.5
0.8
0.5
0.8
-0.5
-0.8
for i-3. Z -Zi3 -0.5 = Z32 ZpUS O..5 0.8 1.2 -0.8
for i-1. Z21 =Z1 = 0.8= Z12 -0.5 -0.8 0.8 1.05
Modification of ZBUS
Of0.5 o.5 0.57
ZUSO0.5 o.8 0.8
ZBUS(new) BUS(old) ZiZi
ZZiu
lo.5 0.8 Z2J
Z pa+Zpapa ijold) ZZ
Zijncw)
Z
Z2 =Z12 +Z1212 =0.8+0.4 = 1.2
Z'33Z3 Z3Z13
Z
30.5 o.5 0.5
ZpUS D 0.5 0.8 0.8 S E0.5) CO.8) - 0.1190
lo.5 o.8 12] 1.05
Z -0.8)CO8)-o.1905
1.05
0.5 0.5 0.5 Z3
O0.5 0.8 0.8 Z Zi2 = 0.8- (-0.8)C0.8) -0.1905
ZBUS 1.05
O.5 0.8 1.2 Za
Z11 Z22 0.8)C0.8)-0.5905
1.05
Z= Zp-Zqi Zoi Z=-Z O
Zi, =-Z1 O0.2619 0. 1 19 0. 119
= Z31. ZBUS O
Z13-Z13=-0.5 for i=33 0.119 0.1905 0.1905
Z-2-Zqi-7-Z-23
0.11
0.15
Z-Z2-0119-Zyr for i=3 Fig. 6
Zn-Z2-0.1905=Z. for i =1
following':
Calculate the
Z2-=-0.5905= Z2. for i= 2
short circuit current.
) Total
Z-Z*2pp Z+Zo202=0.5905+0.25 =0.8405
at Bus 3 during fault.
(i) Voltage
Voltages of bus and during
1 2 fault.
(i)
0.2619 0.119 0.119 -0.119
current in phase "b' of the network element i.e. transformer.
O 0.119 0.1905 0.1905-0.1905 iv) The
BUS 0.119 0.1905 0.5905 - 0.5905 The self impedance are given in per unit. Take
pre fault voltage as 1.0 pu and
O-0.119 -0.1905-0.5905 0.8405 2011
fault impedance 0.38 pu.
Modification of ZgUS
Aas. Given:
Soive the modification like step (iv) and find BUS (new)
Again following the procedure for addition of link ie. element 4 fromp- 1 to q-2 find 0.16
Zys=? Z=?, Z12=? and the modification of ZBUS
0.11 0.
Note : Piease try your own and find ZBUs 0.15
Fig. 6
Q51a) Show that T is a unitary matrix
51
IP.541, 0.30 Positive sequence network
(b) Show that the impedance matrix for a three phase balanced stationary element can be diagonalized
IP.91,4
(c) DEE a equation i general which shows that transformation matrix T is useful tor ne
0.11 0.16
transformation of 3-phase a, b, c variable into any J, k variable. 8M 0.14
1,
0000
P.507, Q.J(©J
0.15
POWE YSTEM (B.E. VIll Sem. EE)
IN
PP,
636 RD io SYSTEM
COMP. APP. IN POWER SYSTEM (B.E. VIll CO 011
VIl Sem.EE) 011-0-
O- 0.14 0.16
( -0.25, 2= 025
t (0.15
0.11 0.15 Zy041-5)
(0.15) (0.15)-0,338
0.31
oref.
0.11
Applying step by step method for ZBus (tve sequence) O.11 0.11
0.25
=0.11 0.25
Step 1:Connect element (1) between p-0 g 0.338
0.11 0.25
and q1 it is a branch
z 0.11 0.11
0.11 025
t-61-,-6
Step 3:Connect element (6) between p -2 and q = 3 it is a branch
044+j0.338
0.11 0.11 0.11
0.11O.11 025 025
0.25 0.41
6.8445
Step 4: Connect element (4) between p =2 and q = 3 it is a branch
s
O 0.11 0.11 0.11 Z
1 1
=[6.842125]
.Z =ZZ st 1Z120 x 6.3825)
=
Z=Za-Z3 0.11-0.11 = 0
3)-3.969 2125
ZyZz2-Zy2 = 0.25-0.25 = 0
-Zpp
Z13Z23-Z33 = 0.25- 0.41 = -0.16 +Zpp +Zpp
PO3Z,+Zpp +Zpp + Zpe32
Eo=
Zu=Z-Z31 + Z22 = 0--0.16) + 0.15 - 0.31 -Lpp
Zy = 0.11-0= 0.11
1
EP(f)
3 0.727
)3x (0.15)+0.11+0.25+0.333-0.75
IN POWER SYSTEM (B.E.
eOMP. APP. VIl Sem. EE)
639
99D cOMP, APP. IN PoWER SYSTEM (0,E,
m
VI Bem
Sp 6iCem in phase b
EE) NOTES
-IW3/044 p38)
4-326
3.261
D-096-3421
9.74) Compare the performance of Gaus- Seidel and Newton Raphson methods for load fow
solution.
IP.344,
0.46)
Draw the flowchart for calculation of reactive power at voltage controlled bus
in the Gau
Gauss-
Seidel iteative method when maximum and minimunm limits are specified for reactive power
7M
IP.124, Q.31
( Derive the equation use to calculate real and reactive bus power 1or 1oad tiow solution by using
IP.129, 0.41
OR
Q.8. A 20 MVA 50 c's generator circuit delivers 18 MW over a double circuit line to
an infinite bus.
The generator bus kinetic energy 1s 2.52 MJIMVA at rated speed. The generator transient
reactance is
X0.35 pu. Each transmission line circuit reactance is 0.2 pu on 20
MVA base.
Initially the generator bus voltage was I.l pu and infinite bus voltage 1.0 pu.
A 3-phase short
circuit occurs at mid point of one of the transmission line at t= 0 and it is cleared in 0,1 sec. Find
the swing of the rotor upto 0.2 sec. Taking time step of 0.05 sec. Use modified Euler's method.
201
elements 22 and 5
as links. Also prove relation A [K] =B for fig. 1
reference and
12M
Fig.1
P.601, Q.1(b
OR
021a) Define 6M
(a) Oriented Graph (b) Element
e)Branch () Tree
P.5, Q.1
- 25
(0.E. element
Seleet ground as feferenee and element 4 as link
VIl Som
u) How d
admittances of each
0.1025 pu
0.4 pu 0.6 pu
- yY14 Z Z4
1
j04
j2.5
y"Z03-33
0.1025 pu
Fig. 2(b)
IP.26,041 y 24 Z4 j03J333
Q3() For the power system shown in fig.3 obtain
34
-js
diagonal elements
2 Now, calculate
1:
Step
Fig. 3
self admittances of the elements are given For calculating diagonal elementS, add all the admittances connected to particular
in Table below. )
node i.e. 2, 3, 4.
Element No.
. network graph
Yss -Ya+Ys+Yg = Yas
+ y+y
will become
=-j2.5-j2-j5=-j9.5
j0.3
Oll-diagonal elements are Yz3, Y32, Y24, Y42. Y34 and Y43
SYSTEM (B.E, VI| Sem. EE) 645
APP. IN
POER . Tree diagram
644 AND cOMP, APP. IN PoWER SYSTEM (8.E. VII 8om e,
8om. LE) Yaph
Netwonk 0.3
Ofdaguaal elements can be eskulhiel by taking the () ve admiltane
of the admittanee
connected (0.3) 2
tetween hwo nodes (huses) 2
-
YYy-Y n-Yy j25
(0.6)
110.5 0
YsNo-Y-YJ.3 /05 3
0.2
4
YYay-0s+Y)-(0 v)-(-2-j5)=17 (0.2)
4
StepI
n=4,
b=n-]=3
/=e-b=4-3=1
Y Yas Y P.16 j25 j3.33
element 1
YsUSD-3)- Y Yss Ysu25-ps j7
Step1:
Connect
YYs Ya
333 7 -jil2.83
p=, 9=I
9.16 25 3.33
--J0-25 95-7
-3.33 -7 1283
Step I1:
Connected element 2
IP.49,
OR
0.2
O 05 Z
Zgus Za
Q4. For the power system shown in fig. 4, consider nodes 3 as reference Z22
(a)Obtain Lbus by algorithm. 12M
() Modify Lbus if self impedance of element between bus 3 and bus 4 is mode 0.1 using
Lbus formed in part (a), Self impedances of the elements are shown in fig. 4.
ZggZpa+papa
4M
3 (0.6)
1 (0.5)
:. Zaus 05
O05
0.5
4 (0.2)
0.8
Fig. 4
SYSTEM (B.E, VIll Sem. EE)
SYS 647
POWER
PP. IN
APP (branch)
YSTEM (B.E coMP elementno, 4
gABD COMP. APP. IN POWER SYSTEM
646 (B.E.
VIlSom,EE onnect
111: Connect element no,
3 (link)
Step
g=4 pis connected to ref. bus
pZpi=0
O05 05 Z =0
41=Zo1
Zus0508 2 il
=0
Za2 =Zo2
=
9-2
tpqp=0+0404 0.2
P0,
Zus 05 08-08
-05-0.s 14 p 0, qF4
Modification of ZBUs 0.3
2
. LBUS(new) = BUS(old)
110.5 .6
. ZxZ12
Lp(ncw) =L12(old) 0.2
4
0.5-05)x(-0.8) = 0.2143
1.4
(-0.5)
(new) = 0.5-0.5) 0.3214
1.4
(-0.8) (-0.3)
12 (new)= 0.8- -0.3429
.4 O0.321 0.214 0 Zu
aUs
0214 0.343
Z2
lBUs
O0.321 0214
0 02
0214 0343
POWER YSTEM (B.E, VII Sem
INA
POWER SYSTwEM
APP IN 649
648 RD cOMP. APP. IN
(0.E. COMP tween node.
and 4 is made 0.1
VIlSem Impedance
Connect element 4 with, 2-0.2 (link)
t 0.3
10.5
il 2y-Z4 =0
01
i2ZpZa-Z4 =0
O 001
O 0321 0214
0 ) To
prove that perfor
performance equation of 3 phase balanced element where excited
0214 0.343
00 balanced xcitation in
impedance form can be represented on single phase
02 0.2-0.2
by
O00-02 0 excitation:
Ans.
30 Balanced
Modification of Zgus
equation for 30 stationary elements
is,
: The performance
Z1(new) =0.321-0 =0.321
12 (new)L21(ncw) =
0.214-0 =0.214
12(1+a+a)+ (a+a
1) Zpm +a?)
Performance equation
of 36 balanced rotating elements +Zpa (+a +a )). 1pa
Performance equation
of 3o primitive network
is,
[Z(1+1+1)+2p (5a")+Z (a +a +a)]. 2g
Z Z Zpa
If m = m2 =m
Representing in 1o
form
(: a+a' =-1)
Lp Zpg Zp ;aDc
P4
p pq 4N
D) To show that the transformation matrix TS is unitary matrix.
Premultiplying by [1 P.541, Q.3(
a a] on both the sides
1 a
aaV+[1 when excited by
other for balanced stationary and rotational element
a
a-]|ap
8M
unbalanced excitation.
au
a a
ZP+22p Z(a+a)Z Z +(a +a )Zm
h.
pq +Z+ Z+azm
Zg +
Zp +a
+Z +a'z
3Z+62 0 0
2p+2p) 3(2pq +a
0
2pd +azp)
0 3(2p-2p 0 0 0
0 3(2pg-Zp)
zO2 =Zp
ZpZp+Zp+Zp
Zpa-Zp-Zpg=Zp Zpg=Zpg +a
Zpq +a Zp
p-2pq +a Z =a 7p
Sequence Impedance of
30 rotating elements)
mi = m2 = m (stationary
elements: lI
We know that,
Zpa Zp+22p
Zp-(T).Zp.T
654 PRD COMP. APP, IN Sem.
POWER SYSTEM (B.E. VIlI Sem
EE)
OR
IP.187, 031
0.7. A single machine connected to infinite bus bar has the following paranmeters.
H-3 mJ/MVA
Xd'0.25
Initially bus voltage was 1.4 pu and generator delivered a power of 75 MW at t = Q There s
three phase short circuit at generator bus which is cleared in 0.1 sec. The base MVA is 100 an
infinite bus voltage is 120. Find swing curve upto 3 iterations. Take time step of 0.05 sec.
modified Euler's method. 29
IP323. Qsal
OR
Q80) What is necessity of load flow studies? How buses are classified on the basis of specificatios
loud flow problem?
& (N
P272 40)
() Draw the flow chart for Gauss Seidel iterative method using YBus
for load tlow studics