Professional Documents
Culture Documents
Electrical Component Specification for Switchboards, Motor Control Centre and Automation Panels
Prepared for
Wellington Water
11 May 2015
simon.cartwright@cardno.co.nz
www.cardno.com Version Number 1
Document History
Version Effective Description of Revision Prepared by: Reviewed by:
Date
1 11 May 2015 For Tender Alex Rowe Simon Cartwright
© Cardno. Copyright in the whole and every part of this document belongs to Cardno and may not be used, sold, transferred, copied
or reproduced in whole or in part in any manner or form or in or on any media to any person other than by agreement with Cardno.
This document is produced by Cardno solely for the benefit and use by the client in accordance with the terms of the engagement.
Cardno does not and shall not assume any responsibility or liability whatsoever to any third party arising out of any use or reliance by
any third party on the content of this document.
Note
This specification should be read in conjunction with:
A) General Electrical Specification – Part 1 – Design and Construction of Switchboards, MCCs, and
Automation Panel Components
B) General Electrical Specification – Part 3 – Electrical installation
C) General Electrical Specification – Part 4 – Electrical building services electrical installation
D) Scope of works and particular specification
Definitions
ACB Air Circuit Breaker
Client Wellington Water
CT Current Transformer
Engineer Project engineer acting for the Client
ICA Instrument, Control and Automation
Manufacturer Manufacturer or supplier of switchboard/MCC
MCB Miniature Circuit Breaker
MCC Motor Control Centre
MCCB Moulded Case Circuit Breaker
RCCB Residual Current Circuit breaker
VSD Variable Speed Drive
Table of Contents
2.1 General Error! Bookmark not defined.
2.2 Din Rail 1
2.3 Terminal Blocks 1
2.4 Panel Mounted Instrumentation 1
2.5 Current Transformers 2
2.6 Hour-Run Meters 2
2.7 Isolators & Fuse Switch Disconnectors 2
2.8 Fuses 2
2.9 Circuit Breakers 3
2.10 Contactors 3
2.11 Overloads 4
2.12 Integrated Motor Starters 4
2.13 Variable Speed Drives (VSD) 4
2.14 Harmonic Filters 6
2.15 Softstart Units 6
2.16 Thermistor Protection Relays 7
2.17 Voltage Sensing Relays 7
2.18 Control Relays 7
2.19 Extra Low Voltage Power Supplies 7
2.20 Push Buttons 8
2.21 Signal Lamps 8
2.22 Pushbuttons (illuminated) 9
2.23 Power Factor Capacitors 9
2.24 Surge Protection Devices 9
1.1.1 The selection of electrical components for Switchboards, MCC or ICA panels should comply
with the requirements of this specification unless otherwise defined by the project ‘Particular
Project Specification’.
1.1.2 Component selection shall be selected from the latest list of ‘Approved Electrical Components’
supplied by the Client. If the component is not listed in the ‘Approved Electrical Components’
an alternative by a New Zealand supplier will be offered for approval in writing by the Engineer.
1.1.3 In the absence of a relevant and consistent AS/NZS standards, the IEC standards apply.
General standard for ‘Low-voltage switchgear and controlgear’ IEC 60947 applies to all
components.
1.1.4 Motor starter components shall be designed to meet ‘Type 2’ co-ordination as defined in IEC
60947-4-1
1.1.5 Unless otherwise stated, all motor starters and VSD units will be suitable for centrifugal pump
application.
1.3.2 Terminal blocks for PLC inputs and outputs shall be supplied by the PLC supplier.
1.5.4 Test links shall be provided in switchboards for all current transformers.
1.7.2 Isolators and fuse switch disconnectors shall have a rated short circuit capacity not less than
the maximum prospective short circuit capacity available from the upstream device. Where
designated for incomer or feeder duties, they shall have utilisation category AC22 for the
switching of mixed resistive and inductive loads and moderate overloads. Where designated for
starter duties, they shall have utilisation category AC23 for the switching of motor loads or other
highly inductive loads. Isolators and fuse switch disconnectors shall be suitable for fault-
make/load-break operation.
1.7.3 Isolators and fuse switch disconnectors rated up to a maximum of 400A frame size may be
fitted.
1.7.4 Where designated for feeder duties, fuse switch disconnectors shall be of the 3-pole type, with a
separate neutral link where necessary.
1.7.5 All switch disconnectors and fuse switch disconnectors shall have provision for locking in the
‘OFF’ position.
2.8 Fuses
1.8.1 Fuse type and size shall be selected to suit the application and be of the high rupturing capacity
type conforming to BS88 unless an alternative is agreed with the Engineer.
1.8.2 Control circuit fuses of 6.3A and below shall be installed in suitable fuse terminal holders with
LED blown indication.
1.8.3 Control fuses for PLC and telemetry RTU shall be fitted as recommended by the manufacturer.
1.9.2 MCBs for the protection of wiring installations of buildings and similar applications (‘domestics’)
shall comply with AS/NZS 61009-1.
1.9.3 Residual Current Devices (RCD) shall comply with AS 3190, AS/NZS 3175 or AS/NZS 61009-1.
1.9.4 As a minimum, C-Curve 6KA breakers shall be fitted for general and control purposes.
1.9.5 MCBs shall be fitted with thermal overload and instantaneous magnetic short circuit protection
with a maximum rating of 63A.
1.9.6 Circuit breakers of 63A or more shall be of the moulded case type with clear indication of the
open, closed and tripped positions.
1.9.7 Incomer and feeder ACBs and MCCBs shall be suitable for fault-make fault-break operation,
and have a rated service short circuit breaking capacity (Ics) not less than the maximum
prospective short circuit capacity.
1.9.8 Incomer and feeder MCCBs shall be fitted with standard thermal-magnetic or electronic trip
units with adjustable short circuit protection (rating permitting) and adjustable thermal
protection. Generator MCCBs shall be fitted with generator thermal magnetic or electronic trip
units with adjustable short circuit and thermal protection, suitable for protection against typical
generator low short circuit currents. Motor starter MCCBs shall be fitted with motor starter
magnetic or electronic trip units for short circuit (but not thermal) protection.
1.9.9 ACBs and MCCBs shall be assembled within the enclosures in accordance with manufacturers’
recommendations, ensuring that the fault rating of the device and assembly is maintained. All
control and power connections to the devices shall be accessible without removing internal
shrouding. For withdrawable devices the minimum internal protection shall be to IP 2X with the
device removed or in the test position. Where an ACB trolley is required, there shall be one
provided for each switchboard/MCC room and for each type of ACB, be capable of reaching
each ACB, and be purpose made by the ACB manufacturer. Tools for withdrawing the ACB or
spring charging shall be provided for each ACB. Motorised spring charging shall be provided
where necessary. All ACBs shall be of the withdrawable type.
1.9.10 Where designated for feeder duties, breakers shall be of the 3-pole type, with a separate neutral
link where necessary.
1.9.11 All breakers shall have provision for locking in the ‘OFF’ position.
2.10 Contactors
1.10.1 Contactors shall comply with IEC 60947-4-1
1.10.3 Be fitted with changeover type auxiliary contacts, rated at 230Vac 10A as necessary, but not
less than one set.
1.10.5 Have wiring from the coils and auxiliary contacts brought out to accessible terminals.
1.10.6 Be rated for making and breaking short-circuit current in coordination with their associated
short-circuit protection devices.
2.11 Overloads
1.11.1 Fixed speed starters shall provide overload protection in accordance with the following:
> up to and including 15kW, thermal overloads
> above 15 kW, electronic overloads
1.11.2 Softstart and VSD motor starters shall be provided with ‘built-in’ motor protection overload
facility.
1.11.3 Overloads shall be ‘direct mounted’ to the contactor or (with the agreement of the Engineer)
mounted beside the contactor on the din rail.
1.11.4 The overload ‘Reset’ facility will be selectable for manual or automatic reset.
1.11.5 The overload shall display status through an indicator and auxiliary contacts.
1.11.6 All three phases will be monitored and a phase imbalance of greater than 10% will activate the
overload.
1.13.2 As a minimum, each VSD shall have the following hardware functions and features;
> Short term rating of 150% of maximum continuous rating for 1 minute,
> All components shall be protected against external short circuits, and internal short circuits,
> Motor protection including over current, ground fault, over and under voltage, phase
imbalance and motor thermal protection,
> Internal voltage surges and external voltage surges. Operation of the VSD shall not be
affected by spurious noise emanating from adjacent electrical switchboards,
> VSD fault conditions or over temperature shall initiate a safe shutdown of the VSD. Manual
reset shall be necessary prior to restart,
> The VSD internal control equipment shall automatically correct the VSD output voltage for
variations in mains voltage over a +10%, -15% range,
> The VSD equipment shall withstand, without damage, any motor regenerative voltages that
may occur on the load side terminals,
> The rate of rise of output voltage shall be limited to a value that does not cause long term
degradation of the motor insulation,
> The VSD shall be controllable from either a 4-20mA signal for automatic control or from a
raise and lower switch or speed dial for manual speed control,
> A remote mounted control panel (where the VSD is installed inside a switchboard).
> All VSD faults, alarms and control signals are to be available from the VSD faceplate.
> All VSDs shall incorporate internal filters to reduce harmonics and RFI to comply with the
relevant Supply Rules and New Zealnd standards,
> All VSDs shall accept inputs from PTC directly.
1.13.3 As a minimum, each VSD shall have the following programmable functions and features;
> Speed control over the range 0-120% of the driven electrical device,
> Acceleration/deceleration ramp time 0 – 600 seconds,
> Selection of up to 2 ‘Preset’ speeds,
> The ability to skip ‘problem’ frequencies,
> The ability to adjust switching frequency,
> Automatic or manual fault reset,
> Minimum and maximum speed settings,
> Output filters where the VSD is an older style motor and insulation may be questionable.
1.13.4 As a minimum, Variable speed drives will meet the following input and output requirements;
> Digital Inputs (provide by clean contact inputs)
Start/Stop
Start Inhibit/Interlock
3 additional programmable inputs.
> Digital Outputs (240V AC 5 amp, 100V DC 2 amp changeover contacts)
Motor running
VSD fault.
> Analogue Inputs
1.14.2 Active filters shall measure and analyse the harmonics induced by the VSD or other load, and
inject an appropriate harmonic load to neutralise these harmonics. The filter unit shall be sized
appropriately to meet the requirements to neutralise harmonics to the specified levels in Section
1.19. plus 25%.
1.14.3 Whilst the overall aim of filters is to limit harmonics and RFI to the specified levels at the Point of
Common Coupling to the electricity network, in some cases high levels of harmonics may cause
interference to other equipment that share the MCC. In such cases the harmonics shall be
reduced so that there no detrimental effect on other equipment at the MCC.
1.14.4 The proposed manufacturer/model and location of filter units to be provided shall be subject to
approval by the Engineer.
1.15.2 A separate by-pass contactor shall be provided if not incorporated into the softstart unit.
1.15.4 As a minimum, each softstart unit shall have the following functions and features;
> The maximum starting current can be adjusted from 200% to 700% of the nominal motor
current.
> Accelerating ramp time shall be adjustable from 1 to 30 seconds.
1.15.5 After the motor has stopped or the starter has been switched off, the thermal state of the motor
is calculated (even if the control circuit is not energised) and thermal control prevents the motor
from restarting if the temperature rise is too high.
1.15.6 In addition to the necessary digital inputs to operate the softstart unit, the following digital
outputs will be available in the form of ‘volt-free contacts’;
> Softstart unit at full speed.
> Spare – (programmable)
1.15.9 If the motor is fitted with Thermistor devices, the softstarter unit shall be capable of
incorporating these, thus avoiding the use of an external thermistor relay.
1.16.2 As a minimum, each thermistor protection relay shall have the following functions and features;
> Automatic reset facility.
> Display status through an indicator and auxiliary contacts.
> DIN rail mounted
1.18.2 Control relays shall have the following functions and features;
> Plug in flat pin type, with 8 pin, 11 pin or 14 pin configuration.
> Socket shall be ‘top-hat’ DIN rail mounting.
> Relay shall incorporate label legend.
> Provide indication of the status of the contacts by mechanical means or LED.
> Guaranteed for more than 1 million mechanical operations
1.18.3 The relay contact rating shall be suitable for the connected load.
> have the ability to monitor the state of the low voltage output,
> where required, shall be capable of charging back-up batteries,
> the negative of a DC power supply shall be connected to earth.
1.20.2 Emergency stop push-buttons shall be of the ‘latching’, mushroom-headed type and comply
with AS/NZS 3947.5.5:2000. They shall be of the quarter-turn or pull-to-release type. Key type
release buttons shall not be used.
1.20.3 Push button switches shall have the following colour designations;
Function Colour
STOP / OFF RED
START / ON GREEN
OPEN BLACK
CLOSE BLACK
RESET BLUE
1.21.2 In compliance with IEC 60947 or similar approved equivalent standard for all indicator and
operator colours:
Function Colour
ON / RUNNING GREEN
FAULT AMBER
AVAILABLE WHITE
OPEN WHITE
CLOSED WHITE
1.22.2 Indicating pushbuttons shall be 22 mm in diameter with illumination from light emitting diode
(LED).
1.23.2 Where required, PFCs shall be installed in the switchboard for each pump. The PFCs size shall
be selected, based on the pump manufacturers data sheets, to correct the full load power factor
to the value specified by the Power Supply Company to avoid any reactive power charges
(normally no less than 0.95PF).
1.23.3 Capacitors 2kVAr and above shall have an overpressure disconnect system for use in the event
of internal faults. The capacitors shall be manufactured and tested to comply with IEC 60831-
1/2.
1.23.4 The connection of power factor connection capacitors shall be switched by a contactor
connected to the line (upstream) side of the motor starter protection and CT modules.
1.23.5 Fit air cored inductors to each capacitor phase to limit capacitor inrush current. Capacitor
contactors shall be rated for capacitor switching. Rating of the capacitor contactor(s) is to be
verified by the designer.
1.23.6 Power factor correction capacitors shall be installed outside the switchboard multi-boxes as
follows:
Indoor pump-stations - in stainless steel enclosures mounted on the wall away from the multi-
box switchboard.
Outdoor pump-stations - in the ventilated cable base of the outdoor enclosure. The capacitors
shall be installed in stainless steel containers.
1.23.7 Power factor capacitors 2kVAr (at 400V) and above shall be 440 Volt rated Schneider brand
mounted in stainless steel enclosure with air chokes and cable terminations - Supplier, Lees
Technology.
1.23.8 Power factor capacitors below 2kVAr (at 400V) shall be 440 Volt rated epoxy-cased capacitors
mounted in stainless steel enclosure with air chokes and cable terminations - Supplier,
Schneider.