CONCERTED
DISTRIBUTION
APPROVALS
Space for stamp of the EMPLOYER Space for stamp of the CONTRACTOR
Space for stamp of ICS Space for stamps of the DESIGN SUPERVISOR
REGISTER OF CHANGES
- SS-R10-WD-ELE-R09-D112
- SS-R10-WD-ELE-R09-D151
2 20.04.2018 - SS-R10-WD-ELE-R09-D172
- SS-R10-WD-ELE-R09-D201
- SS-R10-WD-ELE-R09-D211
- New positions are added in document SS-R10-WD-ELE-R09-A1
3 30.11.2022 Changes based on Client comments:
- AP-R10-WD-ЕLE-R09-D021
- AP-R10-WD-ЕLE-R09-D031
- AP-R10-WD-ЕLE-R09-D051
- AP-R10-WD-ЕLE-R09-D061
- AP-R10-WD-ЕLE-R09-D071
- AP-R10-WD-ЕLE-R09-D110
- AP-R10-WD-ЕLE-R09-D111
- AP-R10-WD-ЕLE-R09-D112
- AP-R10-WD-ЕLE-R09-D113
- AP-R10-WD-ЕLE-R09-D114
- AP-R10-WD-ЕLE-R09-D115
- AP-R10-WD-ЕLE-R09-D151
- AP-R10-WD-ЕLE-R09-D152
- AP-R10-WD-ЕLE-R09-D161
- AP-R10-WD-ЕLE-R09-D162
- AP-R10-WD-ЕLE-R09-D163
- AP-R10-WD-ЕLE-R09-D171
- AP-R10-WD-ЕLE-R09-D201
- AP-R10-WD-ЕLE-R09-D202
- AP-R10-WD-ЕLE-R09-D203
- AP-R10-WD-ЕLE-R09-D211
- AP-R10-WD-ЕLE-R09-D212
- AP-R10-WD-ЕLE-R09-D213
- AP-R10-WD-ЕLE-R09-D221
- AP-R10-WD-ЕLE-R09-D222
- AP-R10-WD-ЕLE-R09-D223
- AP-R10-WD-ЕLE-R09-D231
- AP-R10-WD-ЕLE-R09-D232
- AP-R10-WD-ЕLE-R09-D233
- AP-R10-WD-ЕLE-R09-D241
- AP-R10-WD-ЕLE-R09-D242
- AP-R10-WD-ЕLE-R09-D243
- AP-R10-WD-ЕLE-R09-D251
- AP-R10-WD-ЕLE-R09-D252
- AP-R10-WD-ЕLE-R09-D253
- AP-R10-WD-ЕLE-R09-D261
- AP-R10-WD-ЕLE-R09-D262
- AP-R10-WD-ЕLE-R09-D263
- AP-R10-WD-ЕLE-R09-D271
- AP-R10-WD-ЕLE-R09-D272
- AP-R10-WD-ЕLE-R09-D273
- AP-R10-WD-ЕLE-R09-D293
CONSTRUCTION OF PHASE 1 OF NATIONAL DISPOSAL FACILITY
- AP-R10-WD-ELE-R09-D111
- AP-R10-WD-ELE-R09-D112
- AP-R10-WD-ELE-R09-D113_1-13
- AP-R10-WD-ELE-R09-D151
- AP-R10-WD-ELE-R09-D152_1-8
- AP-R10-WD-ELE-R09-D161
- AP-R10-WD-ELE-R09-D162_1-6
- AP-R10-WD-ELE-R09-D171
- AP-R10-WD-ELE-R09-D201
- AP-R10-WD-ELE-R09-D202_1-6
- AP-R10-WD-ELE-R09-D211
4 27.02.2023
- AP-R10-WD-ELE-R09-D212_1-7
- AP-R10-WD-ELE-R09-D221
- AP-R10-WD-ELE-R09-D222_1-8
- AP-R10-WD-ELE-R09-D232_1-7
- AP-R10-WD-ELE-R09-D251
- AP-R10-WD-ELE-R09-D252_1-6
- AP-R10-WD-ELE-R09-D261
- AP-R10-WD-ELE-R09-D262_1-4
- AP-R10-WD-ELE-R09-D272_1-2
- Attachment 3: Power balance
- Attachment 4: Cable lists
CONSTRUCTION OF PHASE 1 OF NATIONAL DISPOSAL FACILITY
CONTENTS
CONTENTS.............................................................................................................................5
LIST OF DRAWINGS..............................................................................................................6
LIST OF ATTACHMENTS......................................................................................................8
LIST OF ABBREVIATIONS....................................................................................................9
1. GENERAL...................................................................................................................10
1.1. Grounds for Design.....................................................................................................10
1.2. Scope of the design part.............................................................................................10
2. POWER TRANSFORMERS L-EA-MT, L-EE-DTR И L-EE-DTR-DG........................11
3. LV SWITCHGEAR L-EB-LVS....................................................................................11
4. LV POWER STARTER BOARDS..............................................................................11
5. FIRE FIGHTING PUMPS. POWER STARTER BOARD L-DA-PSB-01....................12
6. LV DISTRIBUTION PANELS L-EE-ADS AND L-EE-ADS-DG.................................12
7. ELECTRICAL DISTRIBUTION PANEL L-EE-EDP-01..............................................13
8. LIGHTING DISTRIBUTION PANEL L-EE-LDP-01....................................................13
9. UPS ELECTRICAL DISTRIBUTION PANEL L-ED-EDP-01.....................................13
10. ELECTRICAL CONTROL PANEL L- GG-ECP.........................................................13
11. CABLE RACEWAYS..................................................................................................13
11.1. General.......................................................................................................................13
11.2. Main cable raceways..................................................................................................13
11.3. Cable leads to individual consumers and power socket panels.................................14
11.4. Cabling of lighting and current socket installations and HVAC peripheral components
....................................................................................................................................14
12. LIGHTING SYSTEM AND SOCKETS NETWORK....................................................14
13. EARTHING AND LIGHTNING PROTECTION SYSTEMS........................................15
13.1. Earthing system..........................................................................................................15
13.2. Equipotential bonding system.....................................................................................15
13.3. Lightning protection system........................................................................................16
14. MEMO ON SAFE WORK CONDITIONS, FIRE AND EMERGENCY SAFETY........16
14.1. Evaluation of possible hazards for staff......................................................................16
14.2. Measures for protection of the personnel against possible hazards..........................16
14.3. Possible harms and hazards......................................................................................17
14.4. Planned actions..........................................................................................................17
14.5. Healthy and safe working conditions..........................................................................17
CONSTRUCTION OF PHASE 1 OF NATIONAL DISPOSAL FACILITY
LIST OF DRAWINGS
LIST OF ATTACHMENTS
LIST OF ABBREVIATIONS
LIST OF DOCUMENTS
1. GENERAL
3. LV SWITCHGEAR L-EB-LVS
The following Motor Control Centers (MCP) are subject of this section:
Powered by "EB" power supply system:
HVAC Motor starter board L-VA-PSB-01
HVAC Motor starter board L-VA-PSB-02
Powered by "EE" power supply system:
HVAC Motor starter board L-VA-PSB-03
HVAC Motor starter board L-VA-PSB-04
The design basis and main ratings are according to document EQEB-11207-TD-ЕLE-
R01, section 4.2.7 from the Technical Design.
For the purpose of Working Design is developed configuration based on PrismaSet P
series by Schneider Electric with fixed motor protection thermo-magnetic circuit breakers
directly attached to contactors. Other possible configurations shall provide similar functions.
CONSTRUCTION OF PHASE 1 OF NATIONAL DISPOSAL FACILITY
In case of selection of other types of circuit breakers the discrimination with upstream
and downstream protections shall be checked.
This configuration has been preferred to more sophisticated modular systems for the
following reasons:
All motors are comparatively small and are started in direct mode. This
refers also to the motors operated by frequency converters, as the solutions
developed in design part HVAC anticipate the solutions with frequency
converters built in the units.
The total power of the motor starter boards is small and correspondingly
comparatively simple molded case circuit breakers are sufficient as
incomers.
As the system is designed for operation exclusively in automatic mode, no
other control means are anticipated for these panels except status indication
lamps. The motor control for the common systems – hot water and chilled
water systems shall be done from the panel L-VA-PLC-01. Means for
manual operation for testing purposes shall be provided in the latter panel.
The buildings’ air handling system shall be controlled by the local HVAC
control panels x-VA-PLC01. Start/stop push buttons for starting and
stopping of each Air Handling system, including motors, fed from L-VA-PSB-
01/2 are provided at each building’s local HVAC control panel x-VA-PLC01.
This report provides as well functional diagrams for control of the following HVAC
systems:
Hot water system
Chilled water system
Fan coils for building L
The following Power Starter Boards, anticipated for NDF shall be complete delivery
with the equipment, therefore no separate design is necessary:
Fire protection motor starter board L-DA-PSB-01
Motor starter board L-AA-PSB-02
This report provides functional diagrams for control of the fire fighting pumps.
According to three separate feeders are provided to L-DA-PSB-01 panel – for each of
working and back-up pumps and for the jokey pump.
The design basis and main ratings are according to document EQEB-11207-TD-ЕLE-
R01, section 4.3.3 from the Technical Design.
CONSTRUCTION OF PHASE 1 OF NATIONAL DISPOSAL FACILITY
The design basis and main ratings are according to document EQEB-11207-TD-ЕLE-
R01, section 5.3 from the Technical Design
11.1. General
The design basis and main ratings are according to document EQEB-11207-TD-ЕLE-
R01, section 7 from the Technical Design
11.2. Main cable raceways
The main cable routes consist of concrete cable ducts and wire mesh cable trays with
a bar of electro-welded steel installed on galvanized steel supports.
Vertical cable trays shall lead from main cable trays to each electrical or control panel.
The vertical trays shall be equipped with protective metallic covers.
At each wall crossing the cable trays shall be interrupted. The cables shall cross the
walls through penetrations with fire resistance not less than EI120.
The cable ladders for building L are shown on drawing AP-R10-WD-ELE-R09-D031.
The power cables connecting the power transformers and the diesel generator to the
MV and LV main switchgear will be laid in a cable duct under the floor of the room, closed
with concrete covers, shown in drawing AP-R10-WD-ELE-R09-D021. To pull the cable from
the diesel generator to the concrete cable duct in the room, a special cable tray with a cover
for floor installation, secured with suitable supports, is provided.
11.3. Cable leads to individual consumers and power socket panels.
Shall be laid in rigid metal protective conduits will be made of electro-welded steel with
a zinc cover whose thickness will be not less than 0,02 mm, with threaded ends in
accordance with EN standards.
The conduits shall be installed on the wall surface.
Each cable shall be installed in separate conduit.
11.4. Cabling of lighting and current socket installations and HVAC peripheral
components
In rooms with gypsum board walls and suspended ceilings:
The cables shall be laid in flexible (corrugated) conduits inside the walls, respectively
above the ceiling where the conduits shall be attached to the ceiling suspension elements.
The flexible corrugated conduits will be of LHC type, halogen free, without toxic gases,
corrosive gases and opaque smokes, for operating temperatures of up to 105 oC and in
accordance with the standards: EN 13501, EN 50086 and EN60423.
The auxiliary and junction boxes for this type of flexible conduits will be made of
material with similar characteristics to the ones defined for the conduits.
Each cable shall be installed in individual conduit.
In technical rooms with concrete walls:
The cables for individual consumers and commutation devices shall be installed in
rigid metal conduits
CONSTRUCTION OF PHASE 1 OF NATIONAL DISPOSAL FACILITY
The cables for lighting fixtures installed in lines (the premises L-1-01 ÷ L-1-05) shall
be laid in perforated galvanized steel cable trays which serve in the same time as supports
for the fixtures.
The design basis and main ratings are according to document EQEB-11207-TD-ЕLE-
R01, section 9 from the Technical Design.
In the present revision, new calculations of the lighting in the technical building are
presented. They were made by the Contractor company due to the accepted replacement
of fluorescent lighting fixtures with LED lighting fixtures. The lighting installation shown in
drawing AP-R10-WD-ELE-R09-D071 has been adjusted according to the new lighting
fixtures.
This part of the project is according to the previous revision of the project.
13.1. Earthing system
Earthing system consists of the following components:
Foundation electrode.
Constitutes of a ring installed on the periphery of foundation with cross-
connections at each 20 m approximately. Solid copper conductor 50 mm 2 (
8) shall be used. The foundation electrode shall be attached to the
reinforcement thus providing grounding of the whole building structure.
Potential equalizing ring.
Buried in the soil at 1 m depth and 1 meter away from the building. Stranded
copper conductor 50 mm2 shall be used.
Connections to other earthing electrodes – as shown on the drawings.
Stranded copper conductor 50 mm2 buried in soil shall be used.
Tap-offs for down-conductors and connections from foundation electrode to
potential equalizing ring.
Both the tap-offs to lightning protection down conductors and connections to
the potential equalizing ring shall be made connected to the foundation
electrode in one and the same points at each 10 m along the building
periphery. Solid copper conductor 50 mm 2 ( 8) shall be used.
The tap-offs to the lighting protection down-conductors shall end with test-
boxes installed on external walls surface. The function of the test boxes is to
provide dismountable bolt connection to the down-conductor. Specially
certified products shall be used.
All connections between elements shall be made with materials specially certified for
use in earthing systems.
13.2. Equipotential bonding system
CONSTRUCTION OF PHASE 1 OF NATIONAL DISPOSAL FACILITY
The following hazards are likely to occur during the implementation and operation
stages of the project:
• During operations it is possible to get an electric shock if contact is
made with exposed current wires or burns due to breakthroughs of
insulation or short circuits.
• Affecting of adjacent power cords during work.
• Contact with parts, which are normally not on voltage.
• Ignition of exposed cable fragments due to overload or breakthroughs.
14.2. Measures for protection of the personnel against possible hazards
The following measures are envisioned in order to ensure safety and work hygiene, as
well as fire safety during operations on the site:
The building has a monolithic construction.
The dimension of the premises allows for correct placement and installation
of all facilities and installations.
The switchgear units use IP-31 and IP-44 degree of protection. The
connection between incoming and outgoing current wires in the switchgear
is made via cable shoes, and in the smaller sections – via cable loops and
screw links.
All electrical equipment is technically secured, whereby the non-conducting
metal parts are connected to the zero bus of the switchgear or to the ground
loop.
The grounding installation is executed via the third and fifth conductor of the
power cord.
14.3. Possible harms and hazards
The following hazards may occur during the installations foreseen in this project:
Uncoordinated actions by the work force.
Lack of any of the following: tools necessary for safe operations, safety
equipment for work at high altitudes, suitable work clothing and personal
protective equipment, etc.
14.4. Planned actions
The following actions have been envisioned in order to avoid above mentioned harms
and hazards:
The work area must be fire-protected.
Daily safety instructions will be given by the technical supervisor.
The execution of all sorts of tasks will be carried out in groups of at least two
installers.
CONSTRUCTION OF PHASE 1 OF NATIONAL DISPOSAL FACILITY
All switchgear units have safety shutters, doors, key, appropriate protection
against dust and water, and are made of metal or ABS non-combustion
materials.
The use of appropriate tools, work clothing, etc.
The responsible personnel will be trained how to fight fires.
14.5. Healthy and safe working conditions
The provision of healthy and safe working conditions is carried out in accordance with
the specific activities and the requirements of the technical, technological and social
development in order to protect the life, health and working capacity of the employees. The
work equipment shall be maintained and repaired promptly throughout its use and after its
decommissioning so as not to endanger the health and safety of the personnel.