Voltage Drop Calculator for PDF Input Supply @25Degrees Celcius

Voltage Drop Calculator(Input)


Description QTY Units
Length of Wire Used 50 Meters Voltage Drop Calculator(Output)
Resistivity 1.72E-08 ᾩm Parameter
Crosssection of Wire Used 480 mm^2 Resistance of Wire
Load Current 1200 Amps Voltage Drop
Cross-Section of wire Used 0.00048 m^2
%Voltage Drop 4.479167 %

DC Busbar Volatge Drop for PDF @ 25 Degrees Celcius


Parameters for Bus bar Output Parameters of DC bu
Description QTY Units Description
Width 60 mm Max Current Carrying capacity
Thickness 10 mm Voltage Drop at Bus bar
cross-section Area 600 mm^2
Perimeter of the PDF bus bar 140 mm
5Degrees Celcius

rop Calculator(Output)
QTY Unit
0.001791667 ᾩ
2.15 Volts

ees Celcius
utput Parameters of DC bus bar
QTY Units
1300.903413 Ampere
0.001641 Volts at Max Current
Copper for Bus Bars a hanbook by Copper Association development page 62

https://www.scribd.com/doc/48087930/BUSBAR-CALCULATION-FOR-CURRENT-CARRYING-CAPACITY-1000-A-WITH-50-X-12-C
62

ACITY-1000-A-WITH-50-X-12-CU
Sr No. Rack Dimension (W*D*H) Equipment Watts

IBA-2
1 Rack-1 600*800*2200 X16A 6100
2 Rack-2 600*800*2200 X16A 6100
3 Rack-3 600*800*2200 X16A 6100
4 Rack-4 600*800*2200 X16A 6100
5 Rack-5 600*1000*2200 N9000-8/X3A/CE6870 7800
6 Rack-6 600*300*2200 3*M2F/CE6870 1600
7 Rack-7 600*1000*2200 4*NCE/1*Disk/2*S2350 2978(AC)
8 Rack 8 600*600*1200 PDF
9 Rack 9 600*800*1200 ODF
10 Rack 10 600*800*2200 ODF
11 Rack 11 600*800*2200 ODF
IBA-1
1 Rack-1 600*800*2200 X16A 6100
2 Rack-2 600*800*2200 X16A 6100
3 Rack-3 600*800*2200 X16A 6100
4 Rack-4 600*800*2200 X16A 6100
5 Rack-5 600*1000*2200 N9000-8/X3A/CE6870 7800
6 Rack-6 600*300*2200 5*M2F/CE6870 2400
7 Rack 7 600*600*1200 PDF
8 Rack 8 600*600*1200 PDF
9 Rack 9 600*800*2200 ODF
10 Rack 10 600*800*2200 ODF
LHR-GTN
1 Rack-1 600*800*2200 X16A 6100
2 Rack-2 600*800*2200 X16A 6100
3 Rack-3 600*800*2200 X16A 6100
4 Rack-4 600*800*2200 X16A 6100
5 Rack-5 600*1000*2200 N9000-8/X3A/CE6870 7800
6 Rack-6 600*300*2200 5*M2F/CE6870 2400
7 Rack 7 600*600*1200 PDF
8 Rack 8 600*600*1200 PDF
9 Rack 9 600*800*2200 ODF
10 Rack 10 600*800*2200 ODF
LHR-CTH
1 Rack-1 600*800*2200 X16A 6100
2 Rack-2 600*800*2200 X16A 6100
3 Rack-3 600*800*2200 X16A 6100
4 Rack-4 600*800*2200 X16A 6100
5 Rack-5 600*1000*2200 N9000-8/X3A/CE6870 7800
6 Rack-6 600*300*2200 5*M2F/CE6870 2400
7 Rack 7 600*600*1200 PDF
8 Rack 8 600*600*1200 PDF
9 Rack 9 600*800*2200 ODF
10 Rack 10 600*800*2200 ODF
KHI-PKCP
1 Rack-1 600*800*2200 X16A 6100
2 Rack-2 600*800*2200 X16A 6100
3 Rack-3 600*800*2200 X16A 6100
4 Rack-4 600*800*2200 X16A 6100
5 Rack-5 600*300*2200 6*M2F/1*CE6870 2800
6 Rack-6 600*1000*2200 N9000-8/X3A/CE6870 7800
7 Rack-7 600*1000*2200 N9000-8 6400
8 Rack-8 600*1000*2200 N9000-8 6400
9 Rack 9 600*600*1200 PDF
10 Rack 10 600*600*1200 PDF
11 Rack 11 600*800*2200 ODF
12 Rack 12 600*800*2200 ODF
13 Rack 13 600*800*2200 ODF
KHI-MRS
1 Rack-1 600*800*2200 X16A 6100
2 Rack-2 600*800*2200 X16A 6100
3 Rack-3 600*800*2200 X16A 6100
4 Rack-4 600*800*2200 X16A 6100
5 Rack-5 600*300*2200 5*M2F 2000
6 Rack 6 600*600*1200 PDF
7 Rack 7 600*600*1200 PDF
8 Rack 8 600*800*2200 ODF
9 Rack 9 600*800*2200 ODF
KHI-MSH
1 Rack-1 600*1000*2200 N9000-8 6400
2 Rack-2 600*1000*2200 N9000-8 6400
3 Rack-3 600*1000*2200 N9000-8 6400
4 Rack 4 600*800*2200 ODF
FSB-PCNY
1 Rack-1 600*800*2200 X16A 6100
2 Rack-2 600*300*2200 1*M2F/2*CE6870 800
3 Rack 3 600*600*1200 PDF
4 Rack 4 600*800*2200 ODF
FSD-CTX
1 Rack-1 600*800*2200 X16A 6100
2 Rack-2 600*300*2200 1*M2F/2*CE6870 1200
3 Rack 3 600*600*1200 PDF
4 Rack 4 600*800*2200 ODF
PSH-CITY
1 Rack-1 600*300*2200 2*CE6870 800
PSH-CANTT
1 Rack-1 600*300*2200 2*CE6870 800
GUJ MTWN
1 Rack-1 will be adjusted in existing CDN Rack 2*CE6870 800
GUJ CTX
1 Rack-1 will be adjusted in existing CDN Rack 2*CE6870 800
Amp Breakers
Customer
Qty
Breaker
Site Breakers
Rating
DC Module
Hw
AmpPDF/PDU
Rating End
(PM)NE-X16A
Remarks

Calculations
127.08333333 20 200A*2 63A
127.08333333 20 200A*2 63A
current configuration of Datacom2200W*3
only 3 PEM
Power
will ON
power
for up
Each
verified
X16A by Product lead …only for X16 Local PDF will procure
127.08333333 20 200A*2 63A
127.08333333 20 200A*2 63A
162.5 10 200A*2HW Own PDU
33.333333333 8 63A HW Own PDU
One CP and One
HW UPS
Own32A(AC
Power
PDB Breaker
Breaker)*2
Required rating depend on total consumption
For Power connectivity to X16A
For Power connectivity to X16A
For Fiber connectivity
For Fiber connectivity
Calculations
127.08333333 20 200A*2 63A
127.08333333 20 200A*2 63A
current configuration of Datacom2200W*3
only 3 PEM
Power
will ON
power
for up
Each
verified
X16A by Product lead …only for X16 Local PDF will procure
127.08333333 20 200A*2 63A
127.08333333 20 200A*2 63A
162.5 6 200A*2HW Own PDU
50 7 63A HW Own PDU
For Power connectivity to X16A
For Power connectivity to X16A
For Fiber connectivity
For Fiber connectivity
Calculations
127.08333333 20 200A*2 63A
127.08333333 20 200A*2 63A
current configuration of Datacom2200W*3
only 3 PEM
Power
will ON
power
for up
Each
verified
X16A by Product lead …only for X16 Local PDF will procure
127.08333333 20 200A*2 63A
127.08333333 20 200A*2 63A
162.5 6 200A*2HW Own PDU
50 7 63A HW Own PDU
For Power connectivity to X16A
For Power connectivity to X16A
For Fiber connectivity
For Fiber connectivity
Calculations
127.08333333 20 200A*2 63A
127.08333333 20 200A*2 63A
current configuration of Datacom2200W*3
only 3 PEM
Power
will ON
power
for up
Each
verified
X16A by Product lead …only for X16 Local PDF will procure
127.08333333 20 200A*2 63A
127.08333333 20 200A*2 63A
162.5 6 200A*2HW Own PDU
50 7 63A HW Own PDU
For Power connectivity to X16A
For Power connectivity to X16A
For Fiber connectivity
For Fiber connectivity
Calculations
127.08333333 20 200A*2 63A
127.08333333 20 200A*2 63A
current configuration of Datacom
2200W*3
only 3 PEM
Power
will ON
power
for up
Each
verified
X16A by Product lead …only for X16 Local PDF will procure
127.08333333 20 200A*2 63A
127.08333333 20 200A*2 63A
58.333333333 8 63A HW Own PDU
162.5 6 200A*2HW Own PDU
133.33333333 2 200A*2HW Own PDU
133.33333333 2 200A*2HW Own PDU
For Power connectivity to X16A
For Power connectivity to X16A
For Fiber connectivity
For Fiber connectivity
For Fiber connectivity
Calculations
127.08333333 20 200A*2 63A
127.08333333 20 200A*2 63A
current configuration of Datacom
2200W*3
only 3 PEM
Power
will ON
power
for up
Each
verified
X16A by Product lead …only for X16 Local PDF will procure
127.08333333 20 200A*2 63A
127.08333333 20 200A*2 63A
41.666666667 2 63A HW Own PDU
For Power connectivity to X16A
For Power connectivity to X16A
For Fiber connectivity
For Fiber connectivity
Calculations
133.33333333 2 200A*2HW Own PDU
133.33333333 2 200A*2HW Own PDU
133.33333333 2 200A*2HW Own PDU
For Fiber connectivity
Calculations
127.08333333 20 200A*2 200*2
16.666666667 4 HW Own PDU

For Fiber connectivity


Calculations
127.08333333 20 200A*2 200*2
25 6 HW Own PDU

For Fiber connectivity


Calculations
16.666666667 4 Powered from 1720 Rectifier
Calculations
16.666666667 4 Powered from 1720 Rectifier
Calculations
16.666666667 4 Powered from 1720 Rectifier
Calculations
16.666666667 4 Powered from 1720 Rectifier
Location Rectifier Module Attribute Per Module Capacity Total Modules
KHI-A 2*TP482000 1 Module 3 Phase 5800 20
Total Capacity Efficiency of rectBattery (Ah) Total Banks Load Per Phase Current
116000 0.95 3000 4 79674 176.243766384202
Breakers required to Power on the Rectifier Mains Breaker
2*3P*250Ampere or 2*3P*200 Ampere 400 Ampere
Cable crossection needs to Power on the rectifier Loading % Backup
50mm^2 Per Phase 118.33965517 5.783568
https://www.electricaltechnology.org/2013/04/three-phase-ac-circuits-mcqs.html
https://www.calculator.net/voltage-drop-calculator.html?material=copper&wiresize=0.2557&voltage=240&phase=
=0.2557&voltage=240&phase=ac&noofconductor=1&distance=100&distanceunit=meters&amperes=90&x=74&y=21

26.57778 8.859259
Site ID DC Cable Si DC Cable Size Ohm/Km
MUZP4019 12 3.31 5.21
MIRP3002 12 3.31 5.21
MIRP3014 12 3.31 5.21
MIRP4040 12 3.31 5.21
MIRP4042 12 3.31 5.21
MIRP4045 12 3.31 5.21
MIRP4050 12 3.31 5.21
MIRP4064 12 3.31 5.21
MIRP4071 12 3.31 5.21
MIRP4073 12 3.31 5.21
MUZP4023 12 3.31 5.21
MUZP4027 12 3.31 5.21
MUZP4029 12 3.31 5.21
MUZP4053 12 3.31 5.21
MIRP3006 12 3.31 5.21
MIRP4039 12 3.31 5.21
MIRP4029 12 3.31 5.21
Ohm/m Per RRU Load Distance(m) resistnace of Wire(Ohms)
0.00521 6.313333333 52 0.27092
0.00521 6.31333333333333 55 0.28655
0.00521 6.31333333333333 64 0.33344
0.00521 6.31333333333333 45 0.23445
0.00521 6.31333333333333 50 0.2605
0.00521 6.31333333333333 52 0.27092
0.00521 6.31333333333333 41 0.21361
0.00521 6.31333333333333 45 0.23445
0.00521 6.31333333333333 45 0.23445
0.00521 6.31333333333333 41 0.21361
0.00521 6.31333333333333 55.25 0.2878525
0.00521 6.31333333333333 45 0.23445
0.00521 6.31333333333333 35 0.18235
0.00521 6.31333333333333 50 0.2605
0.00521 6.31333333333333 50 0.2605
0.00521 6.31333333333333 48 0.25008
0.00521 6.31333333333333 45 0.23445
Voltage Drop Percent decreaseAllowable Limit Status
1.7104082666 3.4208 5 1
1.8090856667 3.6182 5 1
2.1051178667 4.2102 5 1
1.480161 2.9603 5 1
1.6446233333 3.2892 5 1
1.7104082667 3.4208 5 1
1.3485911333 2.6972 5 1
1.480161 2.9603 5 1
1.480161 2.9603 5 1
1.3485911333 2.6972 5 1
1.8173087833 3.6346 5 1
1.480161 2.9603 5 1
1.1512363333 2.3025 5 1
1.6446233333 3.2892 5 1
1.6446233333 3.2892 5 1
1.5788384 3.1577 5 1
1.480161 2.9603 5 1

2.7