Professional Documents
Culture Documents
IGEM/UP/1C
Communication 1751
Founded 1863
Royal Charter 1929
Patron: Her Majesty the Queen
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
IGEM/UP/1C
Communication 1751
All content in this publication is, unless stated otherwise, the property of IGEM. Copyright laws
protect this publication. Reproduction or retransmission in whole or in part, in any manner,
without the prior written consent of the copyright holder, is a violation of copyright law.
For information on other IGEM Standards please visit our website, www.igem.org.uk
IGEM/UP/1C
CONTENTS
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
SECTION PAGE
1 Introduction 1
2 Scope 4
4 Strength testing 7
4.1 Decision whether to strength test 7
4.2 Strength test methodology 8
4.3 Determination of MOP and MIP 8
4.4 Method, pressure, duration and test criteria for strength testing 12
4.5 Procedures 12
5 Tightness testing 16
5.1 Decision whether to tightness test 16
5.2 General 16
5.3 Determination of TTP 17
5.4 Tightness test duration (TTD) 19
5.5 Procedures – tightness testing 21
5.5.1 By-passing components 21
5.5.2 Ambient conditions 21
5.5.3 Section and valve isolation 21
5.5.4 Testing 21
5.6 Completion 22
6 Direct purging 25
6.1 General 25
6.2 Planning and supervision 25
6.3 Site precautions 26
6.3.1 Warning notices and labels 26
6.3.2 Electrical and fire 26
6.4 Designing and positioning purge points, hoses and vent stacks 27
6.5 Verification of purge velocity 28
6.6 Identification of purge gas cylinders 28
6.7 Gas detectors, oxygen measuring devices and other
electronic equipment 28
6.8 Determination of the purge volume, minimum purge flow rate
and purge time 29
6.9 Vent gas testing 30
6.10 Purging procedures 30
6.10.1 Direct purging from air to gas i.e. commissioning 30
6.10.2 Direct purging from gas to air i.e. de-commissioning 33
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
APPENDIX
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
2 References 38
FIGURES
TABLES
1 Example 1. A low pressure outlet fed from a low pressure network (NG) 11
3 Example 3. A low pressure outlet fed from a low pressure network (LPG) 11
4 Selection of the pressure, duration, and the test criteria for strength testing 12
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
12 Flammability limits and safe purge end points for inert purge 41
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
SECTION 1 : INTRODUCTION
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
1.1 This Standard has been drafted by an Institution of Gas Engineers and Managers
(IGEM) Panel, appointed by IGEM’s Gas Utilization Committee, and has been
approved by IGEM’s Technical Co-Ordinating Committee on behalf of the Council
of IGEM.
1.2 It is necessary to check the scope of referenced standards given below. Figure 1
shows the most suitable Standard for a particular situation.
IGEM/UP/1C deals with strength testing, tightness testing and direct purging of
meter installations (as defined in IGEM/G/1), containing either Natural Gas (NG)
or liquefied petroleum gas (LPG), of volume not exceeding 1 m3 and MOP not
exceeding 7 bar.
IGE/UP/1 Edition 2 deals with all aspects of strength testing, tightness testing
and direct purging of selected 1st, 2nd and 3rd family gases. For example, for NG,
it covers pipework downstream of the emergency control valve (ECV) of
maximum operating pressure (MOP) not exceeding 16 bar.
IGE/UP/1A Edition 2 deals with strength testing, tightness testing and direct
purging of NG installations of volume not exceeding 1 m3 and diameter not
exceeding 150 mm, of MOP (and operating pressure (OP)) not exceeding 40
mbar and supply MOP not exceeding 75 mbar.
1
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
1.3 “MOP” and other new terms such as “maximum incidental pressure” (MIP) and
OP have been introduced to reflect gas pressure terminology used in European
standards. IGEM/G/4 defines these terms and IGE/GM/8 Part 1 explains them in
greater detail.
Referring to Figure 2, note how OP is shown to oscillate about the set point
(SP). Note also that MOP can be declared at any value from OP upwards to a
limit below MIP. The strength test pressure (STP) has to be at least 110% MIP
and in many cases (see Table 4) will be greater.
2
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
1.4 This Standard makes use of the terms “must”, “shall” and “should” when
prescribing particular requirement. Notwithstanding Sub-Section 1.7:
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
the term “must” identifies a requirement by law in Great Britain (GB) at the
time of publication
the term “shall” prescribes a requirement which, it is intended, will be
complied with in full and without deviation
the term “should” prescribes a requirement which, it is intended, will be
complied with unless, after prior consideration, deviation is considered to be
acceptable.
Such terms may have different meanings when used in legislation, or Health and
Safety and Executive (HSE) Approved Code of Practice (ACoPs) or guidance, and
reference needs to be made to such statutory legislation or official guidance for
information on legal obligations.
1.5 The primary responsibility for compliance with legal duties rests with the
employer. The fact that certain employees, for example “responsible engineers”,
are allowed to exercise their professional judgement does not allow employers
to abrogate their primary responsibilities. Employers must:
have done everything to ensure, so far as it is reasonably practicable, that
“responsible engineers” have the skills, training, experience and personal
qualities necessary for the proper exercise of professional judgement
have systems and procedures in place to ensure that the exercise of
professional judgement by “responsible engineers” is subject to appropriate
monitoring and review
not require “responsible engineers” to undertake tasks which would
necessitate the exercise of professional judgement that is not within their
competence. There should be written procedures defining the extent to
which “responsible engineers” can exercise their professional judgement.
When “responsible engineers” are asked to undertake tasks which deviate
from this they should refer the matter for higher review.
1.6 It is now widely accepted that the majority of accidents in industry generally are
in some measure attributable to human as well as technical factors in the sense
that actions by people initiated or contributed to the accidents, or people might
have acted in a more appropriate manner to avert them.
1.7 Notwithstanding Sub-Section 1.4, this Standard does not attempt to make the
use of any method or specification obligatory against the judgement of the
responsible engineer. Where new and better techniques are developed and
proved, they should be adopted without waiting for modification to this
Standard. Amendments to this Standard will be issued when necessary, and
their publication will be announced in the Journal of the Institution and other
publications as appropriate.
1.8 Requests for interpretation of this Standard in relation to matters within its
scope, but not precisely covered by the current text, should be addressed in
writing to Technical Services, IGEM, IGEM House, High Street, Kegworth
Derbyshire, DE74 2DA and will be submitted to the relevant Committee for
consideration and advice, but in the context that the final responsibility is that of
the engineer concerned. If any advice is given by or on behalf of IGEM, this
does not relieve the responsible engineer of any of his or her obligations.
3
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
SECTION 2 : SCOPE
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
2.1 This Standard applies for any meter installation (or part thereof):
Note: Meter installation is defined in IGEM/G/1 and IGEM/G/4.
supplying Natural Gas or LPG
MOP 7 bar
with a volume not exceeding 1 m3
having a method of temporarily sealing the outlet of the installation/section,
for example a valve, blanking device, etc.
not including polyethylene (PE) pipe or fittings
which is not within scope of IGE/UP/1B (see Figure 1).
Note 1: The diversity of meter installations is such that it is inappropriate to provide detailed
guidelines for all types of meter installation covered by the scope of this Standard. It is
recognised that special circumstances may occur, on a meter installation, for which some of
the requirements in this Standard cannot be applied. In such a case, IGE/UP/1 applies and
the procedure needs to be developed by personnel with the relevant competency and
experience.
Certain “legacy” meter installations do not comply with the Standard arrangements given in
IGEM/G/1. The principles of this Standard may be applied to the majority of such legacy
installations.
Note 2: “Meter installation (or part thereof)” is hereafter referred to as “meter installation”.
2.2 This Standard covers pneumatic strength testing and tightness testing, and
direct purging. It does not address hydrostatic testing.
2.3 This Standard covers strength testing and/or tightness testing in the following
circumstances:
prior to a new installation being commissioned with gas
where a leak is suspected to exist on an existing installation
where a new section has been added into an existing installation
where there has been a complete loss of pressure, for any reason, for
example component replacement, section replacement, etc.
2.5 All pressures quoted are gauge pressures unless otherwise stated.
2.6 Italicised text is informative and does not represent formal requirements.
2.7 Appendices are informative and do not represent formal requirements unless
specifically referenced in the main sections via the prescriptive terms “must”,
“shall” or “should”.
4
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
2.8 IGEM/UP/1C adopts the concept of “Gauge readable movement” (GRM). When
using a water gauge, it may be possible to reduce the duration of tests by
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
M
Downstream system kept
pressurised
Note: The section on which work is being carried out is indicated in red.
5
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
3.1 This Standard is set out against a background of legislation in force in GB at the
time of publication. Similar considerations are likely to apply in other countries
where reference to appropriate national legislation is necessary.
All relevant legislation must be applied and relevant ACoPs, official Guidance
notes and referenced codes, standard, etc. shall be taken into account.
3.2 Any person engaged in strength testing, tightness testing or purging of pipework
must be a competent person.
Note: Any person carrying out the installation of gas pipework and associated fittings must be
competent to do so. Where gas installation work is carried out in properties covered by the
current Gas Safety (Installation and Use) Regulations (GS(I&U)R), the persons carrying out
that work must be a “member of a class of persons” as specified by those Regulations.
Persons who are deemed competent to carry out gas work under GS(I&U)R are those who
hold a current certificate of competence in the type of activity to be conducted issued under
aligned S/NVQ arrangements, or by a certification body accredited by the United Kingdom
Accreditation Service (UKAS) for the Nationally Accredited Certification Scheme (ACS).
3.3 Consideration shall be given to the environmental impact of methane and other
hydrocarbons in the atmosphere.
3.4 In the following situations, any electronic equipment used shall be certified for
use in a hazardous area:
when seeking the source of a known or suspected gas leak, using a gas
detector
when a hazardous area is imposed by another installation, for example an oil
supply, and the equipment is to be used within that area
when a risk assessment indicates that use of uncertified equipment is not
acceptable (see below)
when it is anticipated that the area in which the equipment will be located
will be left unattended at any time during the test/purge.
The decision on whether electronic equipment, for example pressure gauges and
gas detectors, can be of a type not certified for use in a hazardous area, may be
complex and is not an issue that can be developed in IGEM/UP/1C. However,
unless the pipework being tested or purged is known to contain only air and/or
inert gases (in which case equipment that is not certified may be used) any use
of such uncertified equipment shall be subject to a suitable risk assessment
prior to use. Equipment manufacturers’ instructions may assist in this risk
assessment.
Note 1: For lower pressures, water gauges can always be used if there is any doubt about the use
of uncertified gauges.
Note 2: For MOP 75 mbar, use of uncertified gauges placed in the open air and located at least
150 mm from any potential gas source (a greater clearance may be required) may be
acceptable although it is still possible for a hazardous area to apply, particularly as imposed
by another installation.
6
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
Only proprietary leak detection fluids (LDFs) shall be used. LDFs containing more than 30
parts per million of halogens shall not be used on stainless steel components. LDFs containing
ammonia shall not be used on copper or brass components.
Note 2: Detergents and soap solutions such as “washing-up” liquids are not suitable.
Note 3: Care is necessary to ensure that LDF is wiped off pipe and fittings after use.
If necessary, for example when joints are to be broken, temporary continuity bonds shall be
installed before the separation of the components and testing commences.
Where an installation contains fuel gas, it shall be purged to nitrogen (N2) or air before
strength testing.
4.1.1 A strength test shall be carried out on any new or replacement meter installation
(or part thereof) except for components that have been pre-tested or have been
removed to avoid over pressurisation, for example regulators and meters.
4.1.2 There is no need to carry out a strength test on the assembly when the meter
installation is:
pre-assembled and fully tested by the manufacturer, and
comes complete with documentation, and
has not been modified or altered in any way.
4.1.4 A strength test should not normally be carried out on an existing meter
installation unless it has been subjected to repairs involving forming pipes,
welding, or new components that have not been pre-tested separately, or OP is
to be increased to a level not previously covered by strength testing.
7
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
The procedures outlined in this Standard assume a separate test for each.
4.3.1 The majority of meter installations will incorporate a pressure regulator and, as
such will normally incorporate a pressure break. The pressure break is a point in
the installation defined by the designer, either side of which a different strength
test pressure is applied.
The location of the pressure break will vary depending on the provision of valves
and the characteristics of the upstream Network and downstream installation.
Typically, the pressure break will be the outlet of the first valve downstream of
the pressure regulator, (see Figures 4(a) and 4(b)). However, where the
downstream installation has the ability to subject the meter installation to a
higher reverse pressure under fault conditions (MIPc), the pressure break will be
on the inlet to the first safety device (see Figures 4(c) and 4(d)).
Where the information available on site indicates that the pressure break is not
located as shown in Figure 4, this shall be taken into account.
The values of STP shall be determined for the different sections of pipework to
be tested.
4.3.2 Where different parts of a meter installation have different DPs, MIPs, etc., the
strength testing requirements of each part of the meter installation shall be
determined separately and tested accordingly.
Figures 4(e) to 4(g) describe the strength testing requirements (of IGE/GM/8)
either side of the pressure break for different situations.
4.3.3 For consistency with IGE/UP/1, IGE/UP/1A and IGE/UP/1B, the procedures
incorporated in this Standard base STP on a multiple of MOP or MIP. This is
based on the assumption that MOP will always equal DP, but this will not always
be the case. When calculating STP, the following shall be applied:
if DP > MOP, the DP shall be used instead of MOP, and
where available DMIP shall be used instead of MIP.
8
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
9
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
10
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
4.3.4 STP shall be determined using a multiple of either MIP or MOP (see Table 4)
Normally, the values of MIP and MOP shall be obtained from the MAM. However,
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
11
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
The method, pressure (STP), duration (STD) and criteria for pneumatic strength
testing shall be as given in Table 4.
Where STP is calculated to exceed 3.5 bar for pipework of diameter exceeding
150 mm, or 10.5 bar for diameter exceeding 25 mm, a hydrostatic strength test
shall be carried out in accordance with IGE/UP/1. Pneumatic testing shall not be
carried out in such circumstances.
* Where surrounding conditions are stable, the responsible engineer may judge
the installation to have stabilised before the time periods given.
4.5.1 A thorough survey of the meter installation, to detect any major integrity defect,
shall be carried out before testing, including inspection of certificates, non-
destructive testing (NDT), etc.
4.5.2 It shall be ensured that all components are inspected prior to testing and have
been designed, installed and anchored to withstand STP.
12
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
4.5.6 Gauges and recorders shall be certificated for calibration and, if appropriate,
zeroed before use.
4.5.7 An exclusion zone, in accordance with Table 5, shall be set up around the area
of any meter installation for which STP exceeds 1 bar. Personnel shall not be
within this distance while pressurising or during the stabilisation and test
periods.
Note: In general, this will mean that the pressurisation equipment and test instruments are also
outside this area, the latter being piped into the area in small bore pipework. The distances
detailed in Table 5 are based on the centre-line of fittings and components and extend both
sides.
For STP exceeding 7 bar, a suitable risk assessment shall be carried out to
determine the distance required.
STP DISTANCE
(bar) (m)
>12 1
>25 2
>57 3
4.5.8 A final inspection of the meter installation shall be carried out to ensure that it is
ready for the test (it shall be ensured that any exclusion zone is clear of all
personnel - see Table 5).
13
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
4.5.9 If STP exceeds 2 bar, a check for general integrity, for example for open ends,
shall be carried out at a pressure of 350 mbar. The meter installation shall be
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
pressurised slowly. For STP exceeding 2 bar, after reaching 2 bar, the pressure
shall be increased in 10% stages up to STP leaving a short period between each
increase.
4.5.10 The pressure in the meter installation should be maintained at STP over the
stabilisation period.
4.5.11 At the end of the stabilisation period, the pressure source shall be disconnected
from the meter installation and the strength test duration (STD) (see Table 4)
shall start. The gauge shall be monitored for the full test period.
4.5.12 If the meter installation fails the strength test (see Table 4 – permitted drop),
the pressure shall be reduced to no greater than 1 bar prior to allowing
personnel into the exclusion zone to test joints, glands, etc. for leakage, using
LDF.
Before work commences to remedy any leakage, the test pressure within the
meter installation should be reduced to zero, by safely venting to atmosphere.
Once any repairs are complete, a further strength test shall be carried out which
shall be in accordance with the above procedures.
4.5.13 Following a satisfactory test (see Table 4 – permitted drop), the pressure in the
meter installation should be reduced to OP if a tightness test is to be carried out
immediately. If not, the pressure shall be vented and the meter installation left
in a safe condition until the tightness test is to be carried out. Any exclusion
zone then can be re-opened for all site personnel.
4.5.14 The strength test shall be documented and included in any site Health and
Safety File. Results should be recorded on a formal certificate, a copy of which
should be given to the MAM of the installation.
STP and MOP shall be recorded clearly and be available for reference by any
party subsequently working on the installation.
14
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
START
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
NO YES
DO COMPONENTS
REMOVE AND YES
OR SUB
REPLACE/SEAL
ASSEMBLIES
NEED TO BE
REMOVED?
(4.5.3)
NO
APPLY
PRECAUTIONS
AND TEST
(4.5)
YES
DOCUMENT AND
GO TO
TIGHTNESS
TEST (5)
Note: This algorithm does not show all necessary steps and the full procedures in Section 4 apply.
15
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
Even if a tightness test result is satisfactory, any smell of gas or a gas detector reading
indicating the presence of gas is not acceptable. For simplicity this Standard treats new and
existing meter installations as the same. When testing a section of an existing meter
installation, the test may be against an isolation valve(s) which could be relatively old and
worn, this may result in the section failing the test. Under such circumstances, IGE/UP/1
defines a maximum level of leakage for existing installations and may be therefore a more
appropriate test.
Some LDFs have an adverse effect on certain installation materials. Consequently, any
residual fluid shall be washed off thoroughly and subsequently be dried. LDFs containing more
than 30 parts per million of halogens shall not be used on stainless steel components.
If necessary, for example when joints are to be broken, temporary continuity bonds shall be
installed before the separation of the components and testing commences.
5.1.2 Where the downstream installation pipework is being kept live the pressure
should be maintained and monitored to be at a positive pressure (normally OP).
It should be ensured that there are no major leaks on the temporary pipework
supplying the gas, by using LDF or a gas detector, as appropriate.
5.1.3 Where a temporary supply is being used to maintain a positive pressure in the
downstream installation pipework, all aspects shall be agreed with the
responsible person on site.
5.1.4 Where it is intended to reduce the pressure in the downstream installation this
shall not be undertaken until a let-by test of the section isolation valves (for
example, ECV, meter outlet valve (MOV), stream isolation valve) has been
completed.
5.2 GENERAL
5.2.1 A thorough survey of the meter installation shall be carried out before testing,
to detect and correct any major integrity defect.
5.2.2 For any meter installation of tightness test pressure (TTP) exceeding 1 bar,
either the safety distances given in Table 5 shall be applied or the test carried
out when the premises are unoccupied.
16
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
5.2.3 If the meter installation contains fuel gas, it should be tested with fuel gas
unless a complete purge to air/N2 is carried out (see Section 6) before testing
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
with air/N2.
5.2.4 Where a meter installation containing air is pressurised with fuel gas, and
following a satisfactory tightness test, it shall immediately be purged to fuel gas.
If the tightness test should fail, the leak shall be traced and repaired. If it is
necessary to open the gasways to do this, the installation shall be depressurised
and purged to air (see Section 6).
Any section on the inlet side of the pressure regulator(s) that can be tested as a
separate section at OPu, shall be tested with a TTP equal to OPu.
The section incorporating the pressure regulators and safety devices is more
problematic. The pressure regulators will have to be by-passed and the whole
section tested at either OPu or OPmi:
where all components within the section to be tested can withstand OPu, the
whole section should be tested at OPu
where components may be damaged by pressurising the downstream side of
the pressure regulators to OPu, the whole section shall be tested with a TTP
equal to OPmi, and all the joints upstream of the pressure regulators
subsequently tested with LDF at OPu.
17
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
18
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
5.4.1 A pressure gauge with a GRM of 0.5 (see Table 15) should be used and the
actions outlined in A4.3.2 undertaken.
Note 1: If adopting the concept of NPM, TTD can be calculated by dividing the durations given
above by 2 and rounding up to the nearest minute, with a minimum test time of 2 minutes.
Note 3: Further TTDs for larger installations are shown in Tables 7 and 8.
19
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
LENGTH
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
(m) 1 2 3 4 5 6 7 8 9 10
DIAMETER
(mm)
40 2 2 2 2 2 2 2 2 2 2
50 2 2 2 2 2 2 2 2 2 2
80 2 2 2 2 2 2 2 2 2 2
100 2 2 2 2 2 3 3 3 3 4
150 2 2 3 3 4 5 5 6 7 7
200 2 3 4 5 6 8 9 10 11 12
250 2 4 6 8 9 11 13 15 16 18
300 3 5 8 10 13 15 18 20 23 25
Note: If adopting the concept of NPM, TTD can be calculated by dividing the durations given
above by 2 and rounding up to the nearest minute, with a minimum test time of 2 minutes.
LENGTH
(m) 1 2 3 4 5 6 7 8 9 10
DIAMETER
(mm)
40 2 2 2 2 2 2 2 2 2 2
50 2 2 2 2 2 2 2 3 3 3
80 2 2 2 3 3 4 5 5 6 6
100 2 2 3 4 5 6 7 8 9 10
150 3 5 7 9 12 14 16 18 20 23
Note 1: If adopting the concept of NPM, TTD can be calculated by dividing the durations given
above by 2 and rounding up to the nearest minute, with a minimum test time of 2 minutes.
20
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
5.5.1.1 If there is any component in the meter installation that could trap pressure, for
example a regulator, a non-return valve (NRV), etc., the component concerned
shall be by-passed temporarily to equalize the pressure either side of the
component. All valves shall be open, or by-passed.
5.5.2.1 Where a meter installation includes exposed pipework, the test shall be carried
out taking account of ambient conditions i.e. when ambient conditions are
stable. Testing shall not be carried out if any part of the meter installation would
be exposed to direct sunlight during the test period.
5.5.2.2 For a meter installation in a building, testing should take place when the
temperature will not change over the test period.
All valves in the meter installation shall be spaded off, plugged or capped and
left in the open position, in order that the test will include the valves and will be
made against sealed ends. The ECV shall be spaded off on the downstream side.
A let-by test shall be carried out on the section inlet and outlet valves.
5.5.4 Testing
(a) If testing a meter installation with fuel gas, a let-by test of the section
isolation valve(s) shall be carried out, ensuring the valve(s) is/are closed,
by adjusting the pressure to approximately 50% OP.
If, over the same test period as calculated for the tightness test (TTD), a
rise in pressure of more than GRM is observed, the isolation valve may
be letting-by. Any defective isolation valve shall be repaired/replaced
before proceeding to the tightness test. If let-by is confirmed on an ECV,
the Gas Emergency Contact Centre (for LPG, the gas supplier) shall be
notified and the installation made safe, suspending the test until a repair
has been made.
(b) If TTP exceeds 2 bar, a check for general integrity, for example for open
ends, shall be carried out at a pressure of 350 mbar. The meter
21
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
(c) The temperature should be allowed to stabilise for TTD or for 6 mins,
whichever is the longer.
Note: Where surrounding conditions are stable, the responsible engineer may judge the
installation to have stabilised before the time periods given.
(d) The gauge shall be monitored as necessary for the duration of the test.
Any movement of the gauge shall be less than GRM (Table 15). If greater
movement is detected, the test has failed and the leak(s) shall be located
and rectified and the test repeated.
Note: For the scope of this Standard, correction for atmospheric pressure and
temperature variations is not needed.
(e) If spades, etc. are fitted, the meter installation shall be de-pressurised,
the spades, etc. removed and any disturbed joints checked with LDF.
5.6 COMPLETION
5.6.1 If testing on air/N2 the pressure shall be released in a safe and controlled
manner, and the meter installation may be purged to fuel gas immediately
following a successful tightness test. If purging is not carried out immediately, a
further tightness check must be carried out immediately prior to purging.
5.6.2 Where a meter installation containing air has been tested with fuel gas,
following completion of a satisfactory tightness test, the meter installation shall
be immediately purged to fuel gas. If the test should fail, the leak shall be
traced and repaired. If it is necessary to open the gas ways, the meter
installation shall be de-pressurised and purged to air/N2 prior to undertaking
repairs.
5.6.3 After proving tightness, any purging shall be carried out as detailed in Section 6.
5.6.4 The tightness test shall be documented and included in any site Health and
Safety File. Results should be recorded on a formal certificate, a copy of which
should be given to the MAM of the pipework tested.
22
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
START
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
YES
STRENGTH TEST CARRIED
OUT OR PRE-TESTED AND/ NO NO DO NOT TIGHTNESS TEST,
STRENGTH TEST, PASS?
OR ALL EXISTING RECONSTRUCT
EQUIPMENT CERTIFICATED?
YES
YES
ALLOW TO STABILISE
YES
YES YES
COMPLETE
DOCUMENTATION (5.6) AND
PURGE (SECTION 6)
Note: This algorithm does not show all necessary steps and the full procedures in Section 5 apply.
23
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
START
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
YES
STRENGTH TEST CARRIED
OUT OR PRE-TESTED AND/ NO NO DO NOT TIGHTNESS TEST,
STRENGTH TEST, PASS?
OR ALL EXISTING RECONSTRUCT
EQUIPMENT CERTIFICATED?
YES
YES
YES
ALLOW TO STABILISE
YES
YES YES
COMPLETE
DOCUMENTATION (5.6) AND
PURGE (SECTION 6)
Note: This algorithm does not show all necessary steps and the full procedures in Section 5 apply.
24
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
This section deals with direct purging with air or fuel gas. If, for any reason, the purge is not
complete, it will be necessary to carry out an indirect purge using N2, guidance on which is
provided in Appendix 3 (see also clause 6.1.2 and Sub-Section 6.8).
This Standard assumes that the installation will be pressurised during purging.
6.1 GENERAL
6.1.1 The environmental impact of releasing methane into the atmosphere shall be
considered and the volume of any vented gas should be minimised, for example
by minimising the section to be purged through the use of appropriate isolation
valves, only purging the section being worked on and not significantly exceeding
the calculated purge volume.
6.1.2 For LPG, reference should be made to the advice contained in Appendix 5 when
assessing safety.
If the assessment indicates that safety would be compromised, the LPG gas
shall be purged indirectly seeking specialist advice if necessary.
6.1.3 A tightness test must be carried out immediately prior to any purge admitting
gas. Vent points shall be leakage tested.
Note: This equally applies when admitting N2 to be followed by NG/LPG (see Appendix 3).
6.1.4 The pressure created during purging shall not exceed MOP of any component
being purged.
6.1.5 If compressed air from a cylinder is used for purging, the air shall be supplied
through high capacity regulators, appropriate precautions being taken for
example pressure gauges, safety devices and multi stage regulation.
Note: This is to prevent icing of regulators and excess pressure being applied.
6.1.7 Where a meter installation is to be taken temporarily out of service for repairs
or alterations, a let-by test shall be carried out on any valve(s) to be used to
isolate the meter installation (see clause 5.5.4.1(a)). Where an installation is
left unattended, it shall be isolated physically, for example by spading or, where
not practicable, by reliably locking off to prevent unauthorised operation.
6.2.1 The meter installation shall be checked to ensure that it has all necessary valves
and sufficient access points to allow the purging operation to take place safely.
6.2.2 Purging of a meter installation shall be carried out only with the agreement of its
owner prior to the purge.
25
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
6.2.3 Purging shall be planned carefully and the following procedures shall be
undertaken as appropriate:
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
6.2.4 During the purging operation, all other work on the meter installation being
purged shall be prohibited.
6.2.5 The complete purge procedure shall be continuous and the minimum purge flow
rate, and hence the minimum velocity, given in Table 9 shall be achieved.
Note 1: This is to prevent stratification and, hence, low or zero flow of one of the contained gases.
Note 2: It is not a requirement to purge at OP. In general, if purge points are sized adequately, the
minimum required velocity will be achieved more easily at lower pressures (see Table 9,
column 5).
If it becomes immediately apparent that a direct purge will not achieve the
required flow rate, the restriction may be removed and the purge re-started.
Otherwise, an indirect purge using N2 shall be carried out (see Appendix 3).
Consequently, planning shall take into account the need for sufficient quantities
of N2 to be available.
6.2.6 Purge points shall be located at the remote ends of the section to be tested.
6.2.7 Purge points shall be located as close as possible to the extremities of the
installation to enable a complete purge.
6.2.8 When purging with air, it must be ensured that air will not enter the GT’s or any
other distribution network.
6.2.9 The direct purge shall be a complete displacement purge and consideration shall
be given to any dead-legs.
6.3.1.1 Appropriate “No smoking” and/or “No naked lights” signage shall be displayed
prominently around any vent and the overall area where purging will take place.
6.3.1.2 Any valve to or from the meter installation to be purged shall be labelled clearly,
for example “Do not operate – purging in progress”.
6.3.2.1 Where appropriate, due regard shall be paid to the intrinsic safety of any
electrical equipment used in the vicinity of the vent points.
6.3.2.2 Any fitted electrical continuity bonds shall be maintained throughout the purging
operation.
26
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
6.3.2.3 Sufficient and appropriate fire extinguishers should be situated near the vent
point(s).
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
6.4.1 Precautions shall be taken to reduce, as far as possible, the hazards associated
with venting, for example by avoiding venting close to property air intakes, or to
any potential sources of ignition such as street lamps and electrical plant. If
there is any doubt about the minimum clearance to ignition sources, reference
should be made to IGE/SR/23. Any electrical switch or isolator in the vicinity of
the vent outlet shall not be operated during purging.
6.4.2 Purge points, associated vents, hoses and vent/flare stacks shall be sized to
permit sufficient flow in order to maintain the required purge rate/velocity,
Table 9, columns 4 and 5 should be used.
Note: Where the minimum required flow rate cannot be achieved, multiple vents may be used.
These may be operated simultaneously, provided each point is supervised and
communications are adequate to enable a safe purge.
Any valve used in the purge process should be full bore, where possible.
6.4.3 Any vent stack should terminate with a suitable flame arrestor.
Note: Where the purge velocity can be guaranteed, it may not be necessary to fit an arrestor.
6.4.4 Any vent stack shall incorporate a full bore control valve and sample point.
Hose materials that may generate static electricity, for example PE, shall not be
used.
Note: The possibility of generating static electricity increases as the purge velocity increases.
6.4.7 Any vent outlet should be located in open air, terminate at least 2.5 m above
ground and be located at least 5 m downwind of any potential ignition source.
6.4.8 Precautions shall be taken to prevent vented gas drifting into buildings.
6.4.9 When purging small volumes of Natural Gas, purging may be carried out directly
into a well ventilated internal area without the use of a purge hose, vent stack
or flame arrestor, but only if all the following criteria are satisfied:
OP of the meter installation being purged shall not exceed 21 mbar
the total volume of the pipework to be purged shall not exceed 0.02 m3
27
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
with the exception of an external purpose built meter house, the volume of
the internal area shall not be less than 30 m3
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
Note: The exception for purpose built meter houses is only applicable where there is no
means of gas entering the building from the housing.
the internal area shall be well ventilated, for example with windows and
doors open and any mechanical ventilation in operation
the purge point(s) shall be located in a well ventilated section of the internal
area and shall not exceed 25 mm
there shall be no potential ignition sources within 3 m of any purge point
the valve used to control the purge shall be in the same internal area as the
purge point(s)
the gas concentration in the area shall be monitored and, as far as is
possible, it shall not be permitted to exceed 10% lower flammability limit
(LFL). If it does, the purge shall be stopped immediately and the system
purged to outside.
6.5.1 A method of verifying that the required purge velocity (Table 9) is achievable
shall be available and shall be one of the following:
a suitably sized “volume” meter (used in conjunction with a timer to enable
the flow rate to be calculated) already fitted in the section of pipework to be
purged
a suitably sized “rate of flow” meter, i.e. capable of passing well in excess of
the purge flow rate without sustaining damage
a suitable flow measuring device fitted downstream of the purge point(s),
such as an independent positive displacement or turbine meter.
Note 1: Usually, the meter being purged will fulfil this function. However, for short purge times, the
purge gas passed may not register.
Note 2: Provided there is confidence (see also clause 6.2.5) that the required purge velocity
(Table 9) will be achieved, a timed passage of purge gas (see clause 6.8.4) may be used at
the discretion of a responsible, competent person.
6.5.2 A test of the vent gas shall always be carried out (see Sub-Section 6.10).
When the purge gas for example, air is supplied from a cylinder, special care
shall be taken to ensure that the cylinder does not contain the wrong gas, for
example oxygen. Cylinders shall be checked in this respect, before use.
Note: This can be achieved, for example by using an oxygen detector or by confirmation of the
contents of the cylinder by the supplier, etc.
Any gas detector, oxygen measuring device or other electronic equipment shall:
comply with Sub-Section 3.4
be operated in accordance with the manufacturer’s instructions and by a
trained competent person capable of interpreting the results obtained
have its batteries tested prior to use
be zeroed at the commencement of each test and have its zero checked at
the finish of each test
be tested, overhauled and calibrated in accordance with the manufacturer’s
instructions.
28
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
6.8.1 The purge volume (PV) of the installation and purge hose/vent pipe shall be
calculated as follows:
Note: The volume of the purge hose may be significant in relation to small volumes of installation
and this needs to be taken into consideration.
PV of a diaphragm meter
= 5 x cyclic volume (Table 13)
Note: The cyclic volume (capacity per revolution) is shown either on the index plate of
modern meters or, on older tin case meters, on the badge plate.
PV of a RD, turbine or ultrasonic meter
= 1.5 x volume of an equivalent length of pipe (see Table 13)
PV of the remainder of pipework and components within the installation
= 1.5 x (IVp + IVf) (see Appendix 4)
PV of a purge hose/vent pipe
= 1.5 x volume of hose/pipe (Table 14).
6.8.2 It should be confirmed that the velocity of the purging medium through the pipe
is above a minimum level, to ensure that the effect of stratification does not
impair the purging.
Note: Although velocity is not easily measured in such a situation, it can be related to purge flow
rate which can be monitored with a flow meter or a timing method.
6.8.3 The minimum purge flowrate (Q) shall be determined from Table 9. For a meter
installation including significant volumes of pipe, the largest diameter pipe shall
be used to determine Q.
Note: If Q is not achieved, the purge time and volume of purge gas required will be excessive
and, even then, a satisfactory purge may not be achieved as the minimum velocity
required, the key factor, will also not be achieved.
6.8.4 Where necessary (see clause 6.5.1), the maximum purge time (PTmax) shall be
calculated as follows:
PV(m3 ) x 3600
PTmax (secs) =
Q (m3 h1)
Note: This is the maximum time (purge time) it will take before a vent gas test should indicate a
sufficient quantity of fuel gas or air as appropriate to indicate completion of the purge.
Example:
A single filter and regulator within a section of 80 mm pipe of total length 0.8 m.
An RD meter with no by-pass, fitted in a section of 100 mm pipe of total length 1.2 m.
10 m long purge hose of 40 mm diameter.
Minimum purge flow rate from Table 9 for 100 mm pipe is 0.33 m3/min
PTmax is therefore 0.0452/0.33 = 0.137 mins = 9 secs.
29
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
1 2 3 4 5
NOMINAL MINIMUM MINIMUM PURGE PURGE HOSE/ FLAME
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
Note: While the dimensions of nominal bore given will achieve the necessary flow rates, other
sizes may be used. In any event, the minimum required purge velocity has to be achieved.
The criteria given in Table 10 shall be used when testing the vent gas.
Note: Table 10 is intended to ensure safe conditions, but not necessarily efficient combustion
performance.
Note 2: It is recommended that these gases be purged using N2 rather than air due to their low
LFLs or high specific gravity. Refer to Appendix 3 for N2 purging.
Note 3: Gas detectors used for differing gases need to be calibrated for the particular gas being tested.
The procedure assumes that, prior to purging, any purge point and any valve on
any connected vent/flare stack is closed, that the section isolation valve(s)
is/are closed and that any other valve within the meter installation is open.
Throughout the purge operation, steps should be taken to ensure that the
pressure in any upstream pipework or at an appliance will not be affected by the
purging operation.
30
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
Note: On larger meter installations at higher pressures, for example exceeding 2 bar, it may be
necessary to use a valved rider to bypass the section isolation valve, in order to enable a
satisfactory level of control of pressurisation. It also may be necessary to introduce a
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
pressure regulator into the rider to control the supply pressure to prevent
overpressurisation of attached purge hoses and vents.
(a) Ensure that a satisfactory tightness test (Section 5) has been carried out,
immediately before starting the purge.
(b) Open all purge points and open valves on connected vent/flare stacks
and the section isolation valve to admit gas. Simultaneously, start the
chosen method of measuring the flow of purge gas (see clause 6.5.1),
i.e.;
start a timer and
read the in-line meter or read the flow meter rate.
Note: If using a flow meter, it will be immediately apparent if the minimum required
purge volume rate is not being achieved. In this case, it may be possible to stop
the purge, rectify the reason for the incomplete purge and re-start the purge (from
the beginning) without resorting to an indirect (N2) purge (see (d) below).
(c) After half the estimated purge time (see clause 6.9.3) has elapsed (or
earlier if desired – which may limit the wastage of gas), start testing the
concentration of fuel gas in the vent gas using a suitable gas detector.
Note: For an RD meter the purge could be very short, in which case testing of the vent
gas may need to be started immediately.
(d) Stop the purge by closing the vent/flare stack valve(s) (and record the
in-line meter reading, if applicable) when a level of fuel gas, as indicated
in Table 10 for safe purge end point, is achieved, or the metered purge
volume has passed.
Note: Any method has to be verified by a satisfactory vent gas sample.
If Table 10 concentrations are not achieved within the purge time (or by
the time the purge volume has passed) an incomplete purge is indicated.
In this case, close the section isolation valve(s) and immediately purge
the meter installation with N2 in accordance with Appendix 3. Before
repeating steps (a) to (d), identify and rectify the reason for the
incomplete purge.
Note 1: For any "partially complete" purge, the meter installation will contain a mixture of
gas and air that is potentially hazardous. If it is possible to rectify the problem
without opening the gasway, then it may be acceptable to so rectify and re-start
the purge from the beginning. In the intervening period, it is imperative that the
gasway is not opened, that any section isolation valve is not opened, that the
meter installation is not left unattended and that site precautions (see Sub-Section
6.3) remain in place. An overall risk assessment is required which, if sufficient
assurance of safety is not indicated, will lead to an indirect purge using N2 (see
Appendix 3).
Note 2: The reason for an incomplete purge is likely to be insufficient velocity of the NG.
Check the purge time recorded against any meter reading/ flow rate recorded. Any
metered reading less than PV is suspect (see clause 6.9.1). Any flow rate less than
PV expressed as a flow rate is also suspect (see clause 6.9.2). If both are
satisfactory, re-check the calculations (see Sub-Section 6.9). If no problem is
found, it is likely that the actual design of the meter installation is not as assumed
when calculating PV.
Note 3: In conjunction with a stopwatch for metered flow, all the above methods will serve
to confirm that the purge velocity is the minimum required (see Table 9).
(e) Close all purge points, disconnect vent/flare stacks, remove all purge
equipment and plug or cap the open ends with an appropriate fitting.
Test any disturbed joints with LDF or a gas detector.
31
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
Note 1: A gas detector is not permitted to move from zero or 0% LFL on the 0% to 10%
LFL scale.
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
Note 2: Disconnected purge equipment (hoses, meters, etc.) will need to be purged of NG.
(g) Seal with an appropriate fitting the outlet of the meter installation and
label to indicate that gas is turned on and purged up to that point.
32
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
The following procedure assumes that, prior to purging, any purge point and
any valve on any connected vent/flare stack is closed, that the section isolation
valve is closed and that any other valve within the installation is open.
Throughout the purge operation, steps should be taken to ensure that the
pressure in any upstream pipework or at an appliance will not be affected by the
purging operation.
(a) Carry out a let-by test on the section isolation valve(s), to prove its/their
integrity (see clause 5.5.4.1 (a)). The let-by test period should be as
calculated or 4 minutes, whichever is lesser.
(d) Open all purge points and valves on connected vent/flare stacks and
admit air. Simultaneously, start the chosen method of “measuring” the
flow of air (see clause 6.5.1) i.e.
start a timer and
read the in-line meter, or read the flow meter rate.
Note: If using a flow meter, it will be immediately apparent if the minimum required
purge volume rate is not being achieved. In this case, it may be possible to stop
the purge, rectify the reason for the incomplete purge and re-start the purge (from
the beginning) without resorting to an indirect (N2) purge (see (f) below).
(e) After half the estimated purge time (see clause 6.9.3) has elapsed (or
earlier if desired) start testing the concentration of air in the vent gas
using an appropriate instrument.
Note: For an RD meter, the purge time could be very short and it may not be practical to
start testing so early in the purge.
(f) Stop the purge by isolating the air supply (and record the in-line meter
reading, if applicable) when a level of air, as indicated in Table 10 for
safe purge end point, is achieved or the metered purge volume has
passed, whichever occurs first.
Note: Any method has to be verified by a satisfactory vent gas sample.
If Table 10 concentrations are not achieved within the purge time (or by
the time the purge volume has passed) an incomplete purge is indicated.
In this case, close the section isolation valve(s) and immediately purge
the meter installation with N2 in accordance with Appendix 3. Before
repeating steps (a) to (d), identify and rectify the reason for the
incomplete purge.
Note 1: For any "partially complete" purge, the meter installation will contain a mixture of
fuel gas and air that is potentially hazardous. If it is possible to rectify the problem
without opening the gasway, then it may be acceptable to so rectify and re-start
the purge from the beginning. In the intervening period, it is imperative that the
gasway is not opened, that any section isolation valve is not opened, that the
meter installation is not left unattended and that site precautions (see
33
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
Note 2: The reason for an incomplete purge is likely to be insufficient velocity of NG. Check
the purge time recorded against any meter reading/flow rate recorded. Any
metered reading less than PV is suspect (see clause 6.9.1). Any flow rate less than
PV expressed as a flow rate is also suspect (see clause 6.9.2). If both are
satisfactory, re-check the calculations (see Sub-Section 6.9). If no problem is
found, it is likely that the actual design of the meter installation is not as assumed
when calculating PV.
Note 3: Provided there is confidence (see also clause 6.2.5) that the required purge
velocity (Table 9) will be achieved, a timed passage of purge gas (see
clause 6.9.4) may be used at the discretion of a responsible, competent person.
(g) Close all purge points, disconnect vent/flare stacks, remove all purge
equipment and plug or cap the open ends with an appropriate fitting.
Test any disturbed joints with LDF. Seal or disconnect pipework from the
gas supply, sealing all ends with an appropriate fitting.
34
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
GAS TO AIR
De-commissioning
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
Carry out all preparation work Vent stacks and hoses correctly
(6.2, 6.3, 6.4, 6.6, 6.7) located. Purge gas (air) supply
available. Notices, barriers, fire
extinguishers available and checked.
Test meters and detectors checked.
Calculate: purge volume
purge flow rate
purge time
(6.9)
35
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
GLOSSARY
Recommended and legacy gas metering arrangements are given in IGEM/G/1 which is freely
available:
with the purchase of any IGEM Standard, upon request
by downloading a printable version from IGEM’s website.
36
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
UNITS
in inch
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
m metre
mbar millibar
min minute
mm millimetre
m3 cubic metre
m3 h-1 cubic metre per hour
SYMBOLS
Q flow rate
> greater than
less than or equal to
ø nominal diameter
V volume
valve (open)
valve (closed)
regulator
safety device
A appliance
`M meter
filter
blanking device
d diameter
L length
N2 nitrogen
SUBSCRIPTS
c consumer
f fittings, etc
m meter
mi meter installation
p pipe
t total
u upstream
37
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
APPENDIX 2 : REFERENCES
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.
This Appendix lists legislation and standards that are referred in the Standard. In addition,
legislation and Standards are listed which are not referenced within this Standard, but which
may be of use to the reader.
A2.1 LEGISLATION
Gas Act 1986 (as amended by the Gas Act (1995)
Health and Safety at Work etc. Act 1974
Note: This applies to all work activities. It places general duties on employers to ensure, so far
is reasonably practicable, the health safety and welfare of their employees and the
health and safety of members of the public who may be affected by the activity.
Petroleum Act 1962
Confined Spaces Regulations 1997
Construction (Design and Management) Regulations 2007
Control of Substances and Hazardous to Health Regulations 2002
Dangerous Substances and Explosive Atmospheres Regulations 2002
Electricity at Work Regulations 1989
Gas Safety (Installation and Use) Regulations 1998
Note: These apply to domestic and commercial premises. For industrial premises, the
requirements of these Regulations could be considered relevant in any investigation
under the Health and Safety at Work etc. Act. The Regulations set out detailed
requirements for gas installation work. In particular, they require that anyone carrying
out such work must be competent to do so. They also prescribe circumstances in which
a tightness test and purge must be carried out.
Management of Health and Safety at Work Regulations 1999
Manual Handling Operations Regulations 1995
Personal Protective Equipment at Work Regulations 1992
Pressure Equipment Regulations 1998
Pressure Systems Safety Regulations 2000
Note: For cylinders etc., Carriage of Dangerous Goods (Classification, Packaging and
Labelling) and Use of Transportable Pressure Receptacles Regulations 1996 (as
amended), the Transportable Pressure Vessel Regulations 2001 may also be relevant.
Provision and Use of Work Equipment Regulations 1998.
38
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
39
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
A3.1 If a direct purge has been unsuccessful, make the installation and the
surroundings safe, before implementing fallback plans.
If the cause is identified and can be rectified, (for example following calculation
error, blocked hose, closed valve, restrictive purge points etc.), the direct purge
can be repeated.
Note: Take additional care at purge gas vent point as a flammable mixture may occur at a
different stage in the operation.
A3.2 Ensure the indirect purge is a complete displacement purge using volume based
measurement of inert gas and vent gas testing. Pay particular attention to any
dead-legs.
Take precautions to prevent the purge gas entering the GT’s or any other
distribution network.
A3.3 Start with the largest diameter pipe and progress to the smallest.
A3.4 As a guide, a standard 1.5 m long N2 cylinder usually has a capacity of 6.5 m3.
The maximum flow rate through a high capacity single-stage regulator is,
typically, 60 m3 h-1.
A3.5 The criteria given in Table 12 apply when testing the vent gas.
A3.6 Following the indirect purge, if hot work is to be undertaken, take care in case
small pockets of gas remain in the pipe due to the effects of stratification or due
to the effect of dead-legs.
A3.7 When undertaking any work following an indirect purge, take suitable
precautions to account for the presence of N2.
40
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
Note: For de-commissioning purges, purging to lower levels may be advisable where gasways
could be exposed to potential sources of ignition following the purge.
A3.8 Once the purge to N2 is complete, it is advisable to then purge to air and ensure
the oxygen level is at least 20%.
41
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
A4.1.1 General
A4.1.2 Calculations
A4.1.2.1 The following formula can be used to calculate the total installation volume (IVt)
(m3) of the meter installation:
Note: The IVt (m3) needs to be calculated to two significant figures with “rounding” being upwards
only.
It is not advisable to round the calculations of IV of individual parts of a section as this may
cause the test to be more onerous than necessary.
Use Table 13 or consult the meter manufacturer for any other meter.
42
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
For a 1 m length of pipe, obtain the volume of the particular pipe from
Table 14. Multiply the value given by the length of the pipe in the
section.
Note: For sizes not shown, go to the next larger size given.
In the event that IVf cannot be calculated, add an additional 10% of the
pipe volume (IVp).
The gauges listed in Table 15 are typical of the instruments used for tightness
testing and have to be used (for the gauges listed) to determine GRM. The list
does not preclude the use of other types or ranges of gauge but the gauge used
needs its GRM specified.
Note: If an inferential gauge is used then, to ensure accuracy, care needs to be taken regarding
rounding errors caused by using the last decimal place.
Note: Longer tightness test durations (TTD) are possible if an absolute gauge is used.
43
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
A4.4.1 To calculate TTD, use the formula as given in A4.4.3. GRM and the factor F1 can
be obtained from Table 15 and Table 16 respectively.
A4.4.2 TTD needs to be rounded up to the next full minute and not less than 2 mins.
A4.4.3 Table 15 specifies the maximum TTD for particular gauge types, which minimise
the effect of normal variations in barometric pressure and ambient temperature.
TTD = GRM x IV x F1
F1 = as derived from Table 16
FACTOR F1
44
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
IGEM/UP/1C
Differing fuel gases have very different flammable ranges and, when working
with these various gases, it is essential that the range is understood as well as
having gas detection equipment suitable for the gas being monitored.
The most common of the heavier than air gases in use are known as Liquefied
Petroleum Gas, or LPG, (3rd family gases). BS 4250 covers the specification for
commercial LPG, but gases outside this specification are often used for special
purposes.
It is stored in the liquefied state under pressure. The actual pressure in the
storage container, known as the vapour pressure, is dependent upon the
specification of the actual LPG and the temperature of the stored liquid.
These procedures apply only to the pipework downstream of the first stage
pressure regulator in a vapour system. They do not apply to the storage vessel,
the high pressure pipework feeding the first stage regulator, or to any part of a
system containing LPG in the liquid phase.
LPG vapour is, normally, used for gas supplies to gas fired equipment. This
vapour may be generated by natural vaporisation of the liquefied LPG, or for
large industrial offtakes by the use of an in line vaporiser where the latent heat
required is provided from an external source.
Some LPG may contain small quantities of heavy hydrocarbons that do not
readily vaporise, often described as "heavy ends". Where they are present,
these heavy ends will concentrate in the bottom of storage vessels used for
natural vaporisation systems, or in the base of external vaporisers. In abnormal
situations, or where the plant operators fail to drain the system regularly, they
may be carried over into the gas supply pipework.
45
IGEM, IGEM House, High Street, Kegworth, Derbyshire, DE74 2DA. Website igem.org.uk
Copyright © 2015, IGEM. Licensed Copy: IGEM Online Standards. Not to be reproduced.