You are on page 1of 9

22/11/2022

Course Structure
Power system Planning and operation

EE 467
Planning Operational planning Operation
Power System Planning & Operation
• Long-term load • Automatic generation
forecasting • Short-term load control
Automatic Generation Control • Generation expansion
forecasting
• Optimal power flow
• Unit commitment
• Transmission expansion • System security
Prof. Mohamed Abido • Economic dispatch
• Maintenance scheduling • State estimation
1
2

1 2

Load-Frequency Control Stimulating Questions


• 50/60 Hz frequency! Which one? Why?

• Why do we need constant frequency?


What are the consequences?

• What causes frequency change? What is


the solution?

• What are the methods of regulating the


3
system frequency 4

3 4

Objectives Load-Frequency Control


• Basic Functions of AGC
• Power System Modeling
• Generator
• Load
• Turbine
• Governor
• Governor Droop Characteristics
• Load Reference Set Point
• Tie-Line Model
• Model of Interconnected Control Areas
• Frequency Response to Load Change
• Supplementary Control
• Area Control Error 5
Frequency is a global variable 6

5 6

1
22/11/2022

Load-Frequency Control Load-Frequency Control


• Frequency control was not a critical issue before because there • Consequences of a significant drop in frequency:
used to be a large enough fleet of traditional synchronous ̶ stalling of generators and motors,
machines.
̶ high magnetizing currents in induction motors and
• Frequency becomes a critical issue due to possible shortfall of transformers,
inertia associated with inverter-based generation (renewables). ̶ loss of auxiliary motor drives in power stations,
• PV and Wind generations are not contributing much to the ̶ development of errors in equipment that utilize electric
system inertia. timers (“electric clocks go slow”),
• Some solutions are based on virtual inertia using grid-forming ̶ reduction in the values of the reactances of circuit elements,
converters.
̶ loss of blocks of demand through underfrequency load
shedding (frequency dependent load-tripping relays).
7 8

7 8

Load-Frequency Control Load-Frequency Control


• Consequences of a significant rise in frequency: • Methods of regulating the system frequency:
̶ tripping on overspeed of synchronous generators and ̶ Speed governor system that regulates the frequency
motors by adjusting the power output of the generator
̶ errors developing in equipment utilizing electric timers through the prime-mover (turbine) control.
(“electric clocks go fast”) ̶ In wind turbines and solar PV systems, regulation of
̶ increase in the reactances of circuit elements which the local frequency is achieved by purely electronic
leads to change in voltage drop and real system and means which has now been made technologically
reactive losses. possible
̶ loss of blocks of demand through over-frequency. ̶ large batteries and high voltage direct current (HVDC)
links
9 10

9 10

Generation Control System Generation Control System

11 12

11 12

2
22/11/2022

Automatic Generation Control (AGC) Basic Turbine-Generator


Objectives:
• Restore system frequency when it deviates from
the nominal value 50 or 60 Hz.
• Frequency directly related to speed of rotation
• Reallocate generation to keep it at economic – Constant frequency = constant speed of rotation
dispatch
• If mechanical energy in = electrical energy out
• Keep interchange with other control areas at the – Mechanical torque = Electrical torque
scheduled MW – Speed remains constant
• Monitor and control generators as they ramp up and • Electrical load changes are uncontrolled, so we must
down control mechanical energy input to match
13 14

13 14

Mathematical analysis of generation control Automatic Generation Control


𝑑𝜔 𝑑2 𝛿
𝑃𝑛𝑒𝑡 = 𝑃𝑚𝑒𝑐ℎ − 𝑃𝑒𝑙𝑒𝑐 = 𝑀𝛼 = 𝑀 =𝑀 2
𝑑𝑡 𝑑𝑡
 = rotational speed (rad/sec)
 = rotational acceleration Generator Model
 = phase angle of a rotating machine
Pnet = net accelerating power
Pmech = mechanical power input
Pelec = electrical power output
M = angular momentum (inertia) of the machine 15
16

15 16

Generator Model Automatic Generation Control

Load Model

17 18

17 18

3
22/11/2022

Load Model Automatic Generation Control

Prime Mover Model

19 20

19 20

Turbine-Generator System Prime Mover Model


The simplest prime-mover model, the non-reheat turbine, is

TCH = “Charging time” time constant


∆Pvalve = per unit change in valve position from nominal
Combined prime-mover and generator model

21 22

21 22

Automatic Generation Control Governor Model with Speed Droop

Governor Model with


Speed Droop

23 24

23 24

4
22/11/2022

Governor Model with Speed Droop Governor Model with Speed Droop

25 26

25 26

Governor Droop Characteristics Governor Droop Characteristics


• R is the speed regulation that determines the change on the unit output Common practice is to set R on each generating unit so that a
for a given change in frequency (i.e., the slope of the characteristic). change from 0 to 100% (i.e., rated) output will result in the same
∆𝜔 frequency change for each unit. As a result, a change in electrical
𝑅= 𝑝𝑢
∆𝑃 load on a system will be compensated by generator unit output
• For instance, 3% regulation for a unit indicates that a 100% (1.0 pu)
change in unit output requires a 3% change in frequency. changes proportional to each unit rated output.

R
3%

27 28

27 28

Governor Droop Characteristics Automatic Generation Control


Example:
The two units start at a nominal frequency of f0. When a load increases,
PL, it causes the units to slow down, the governors increase output until
the units seek a new, common operating frequency, f ′. The amount of load
pickup on each unit is proportional to the slope of its droop characteristic.
Load Reference Set
Point

29 30

29 30

5
22/11/2022

Load Reference Set Point Load Reference Set Point


• By changing the load reference, the droop characteristic can be set to give reference
frequency at any desired unit output.
• By adjusting this set point on each unit, a desired unit dispatch can be maintained while
holding system frequency close to the desired nominal value.
• This is the boundary between response capability and economic allocation by economic
dispatch.

31

31 32

31 32

Automatic Generation Control Model of Governor, Turbine, and Generator

Integrated Model

34
33

33 34

Model of governor, turbine, and generator Model of governor, turbine, and generator
Example: The steady-
Using the block diagram, find the frequency change, ω, state value
for a step increase in load, PL. of ω can
Solution: be found as
The transfer function relating ω and PL is given by
Note that if D were 0, the change in speed would simply be
If several generators were connected to the system, the frequency
change would be
and ,

35 36

35 36

6
22/11/2022

Automatic Generation Control Tie-Line Model


The power flowing across a transmission line can be
modeled using the DC load flow method as

Tie-Line Model Then;

Alternatively;

where T = 377 × 1/Xtie (for a 60-Hz system)


T is tie-line stiffness coefficient
37 38

37 38

Automatic Generation Control Model of interconnected control areas

Two-area System Model

39 40

39 40

Model of Interconnected Control Areas Model of Interconnected Control Areas


For a load change PL1 in area 1, the steady state frequency, after all Substituting
oscillations have damped out, will be constant and equal to the same
value on both areas and can be calculated as follows.

Solving

and

41 42

41 42

7
22/11/2022

Model of Interconnected Control Areas Model of Interconnected Control Areas


For a load change PL1 in area 1, the steady state frequency Substituting
without governor action can be calculated as follows.

Solving

Without governor action


Pmech1 = 0 Pmech2 = 0
43 44

43 44

Model of Interconnected Control Areas Model of Interconnected Control Areas


Example: Solution:
You are given two system areas connected by a tie line with
the Characteristics shown in the table below. A load change
of 100 MW (0.2 pu) occurs in area 1. What is the new
steady-state frequency and what is the change in tie flow?
Assume both areas were at nominal frequency (60 Hz) to
begin.

45 46

45 46

Model of Interconnected Control Areas Frequency Response to Load Change


The change in prime-mover power would be
Observations:
• The figure shows the average
frequency (omitting high
freq. oscillations)
The total changes in generation is 98.814 MW, which is 1.186 MW short of • A step change in load would
the 100 MW load change. always result in a steady
The change in total area load due to frequency drop would be state freq. error
• A supplementary control is
Therefore, the total load change = 1.186 MW, which accounts for the
needed to eliminate the
difference in total generation change and total load change. steady state error in freq.
47 48

47 48

8
22/11/2022

Power System Planning & Operation Automatic Generation Control (AGC)


Objectives:
1. To hold system frequency at a specified nominal
Automatic Generation value (e.g., 50 or 60 Hz).
2. To maintain the correct value of interchange
Control (AGC) power between control areas.
3. To maintain each unit’s generation at the most
economic value.

50
49

49 50

Supplementary Control Rules of tie line control

Supplementary integral or PID control is necessary to force


the frequency error to 0 by adjustment of the load
reference set point. 51
52

51 52

Area Control Error

54
53

53 54

You might also like