RAMP & TRANSIT

BOEING 737-800

FUEL
OBJETIVO

• Detallar y describir el funcionamiento de


los componentes del sistema de
combustible.

2
B737-800 Ramp & Transit
CONTENIDO

 Introduction and General


Description
 Fuel Storage
 Pressure Fueling System
 Engine Fuel Feed
 APU Fuel Feed
 Defuel
 Fuel Indicating
 Fuel Temperature Indicating
System
 Fuel Measuring Stick –
Introduction

3
B737-800 Ramp & Transit
4
FUEL SYSTEM - INTRODUCTION

6
Ramp & Transit-Fuel Introduction & General Description
FUEL SYSTEM - GENERAL DESCRIPTION

10
Ramp & Transit-Fuel Introduction & General Description
11
FUEL STORAGE - GENERAL DESCRIPTION

13
Ramp & Transit-Fuel Storage
FUEL STORAGE - FUEL TANK ACCESS

15
Ramp & Transit-Fuel Storage
FUEL STORAGE - SUMP DRAIN VALVES

16
Ramp & Transit-Fuel Storage
FUEL STORAGE - FUEL VENT SYSTEM

17
Ramp & Transit-Fuel Storage
FUEL STORAGE - CENTER TANK SCAVENGE SYSTEM

The function of the Fuel Tank Sacavenge system is to remove water and fuel from the
lowest point of the tank to prevent corrosion. This system transfers fuel from the central tank to tank
# 1 when the left front pump is on and tank # 1 with less than 1990kg of fuel.

19
Ramp & Transit-Fuel Storage
FUEL STORAGE - CENTER TANK SCAVENGE SYSTEM

20
Ramp & Transit-Fuel Storage
FUEL STORAGE – WATER SCAVENGE SYSTEM

The function of this system is to remove water from the lowest point of the 03 tanks to prevent
corrosion. Jet Pump output discards fuel and water collected near Boost Pumps inlet. This
mechanism is coupled to each of the center tank pumps and rear wing pumps.

21
Ramp & Transit-Fuel Storage
22
PRESSURE FUELING SYSTEM - INTRODUCTION

Pressure fueling system:


a) Lets refuel all tanks.
b) Use to fuel transfer from tank to tank or
defueling

23
Ramp & Transit-Pressure Fueling System
PRESSURE FUELING SYSTEM - GENERAL DESCRIPTION

27
Ramp & Transit-Pressure Fueling System
PRESSURE FUELING SYSTEM - GENERAL DESCRIPTION

28
Ramp & Transit-Pressure Fueling System
PRESSURE FUELING SYSTEM - FUELING MANIFOLD

29
Ramp & Transit-Pressure Fueling System
PRESSURE FUELING SYSTEM - COMPONENT LOCATION

32
Ramp & Transit-Pressure Fueling System
PRESSURE FUELING SYSTEM - FUELING FLOAT SWITCHES

The fueling float switches prevent over-fueling the fuel tanks. The fueling float switches remove
power to the fueling valves when the fuel level in the tank is full. The fueling float switches have a
float that is in a cylindrical container. When the tank is less than full, the float switch lets power go
to the fueling valve solenoid. When the tank gets full, the fueling float switch removes power to
the fueling valve solenoid.

33
Ramp & Transit-Pressure Fueling System
PRESSURE FUELING SYSTEM - FUELING FLOAT SWITCHES

34
Ramp & Transit-Pressure Fueling System
PRESSURE FUELING SYSTEM - FUNCTIONAL DESCRIPTION -
POWER AND CONTROL

37
Ramp & Transit-Pressure Fueling System
PRESSURE FUELING SYSTEM - FUNCTIONAL DESCRIPTION -
POWER AND CONTROL

38
Ramp & Transit-Pressure Fueling System
PRESSURE FUELING SYSTEM - FUNCTIONAL DESCRIPTION -
POWER AND CONTROL

39
Ramp & Transit-Pressure Fueling System
PRESSURE FUELING SYSTEM - OPERATION

40
Ramp & Transit-Pressure Fueling System
PRESSURE FUELING SYSTEM - OPERATION

General
Fueling placards, with instructions for fueling, are on the fueling station door. Use these placards
when fueling the aircraft. The fueling station receives power when the fueling station door
opens.

41
Ramp & Transit-Pressure Fueling System
PARKING AND MOORING - STATIC GROUND

42
Ramp & Transit-Pressure Fueling System
44
ENGINE FUEL FEED - INTRODUCTION

48
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - INTRODUCTION

49
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED SYSTEM

Each tank has 02 electric fuel pumps, all powered by 115 V AC. The central tank pumps can supply
at least 23 PSI of pressure, with a minimum flow of 9,071 kg / h. The higher outlet pressure of the
center tank shoulders ensures that the engines first consume the entire contents of the center
tank. Main tank pumps can supply a minimum of 10 PSI of pressure, with a minimum flow of 9,071
kg / h.

50
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - GENERAL DESCRIPTION

52
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - FUNCTIONAL DESCRIPTION - CENTER TANK
BOOST PUMP

53
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - GENERAL DESCRIPTION

Crossfeed Valve is electrically controlled on the fuel system panel. Its function is to allow fuel
flow between both Fuel Manifolds. With the connection made between the Fuel Manifolds, it is
possible to feed an engine with fuel from the opposite tank.

54
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - COMPONENT LOCATION

The Emergency Fuel Shutoff Valve is a device used when the Hot Battery Bus voltage drops below
22v to close the Spar Valves or APU Fuel Shutoff Valve. This ensures that even if there is no more
electrical power available to the engines, there will be enough power to close the valves and cut
the engine fuel.
Center Tank Boost Pumps(2)
a) Installedon the rear spar.
b) Access  the wheel wells.

55
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - CENTER TANK BOOST PUMP
Center Tank Boost Pump Motor
The motor has the impeller and uses 3-phase, 115v ac power. It is inside the housing.

Pressure Switch
The low pressure switch sends a low center tank boost pump pressure signal to the LOW
PRESSURE light (P5).

57
Ramp & Transit-Engine Fuel Feed
GFI – GROUND FAULT INTERRUPTER

 In June 2001 the U.S. Federal Aviation Administration (FAA) issued


special federal aviation regulation SFAR-88, which requires
transport-category aircraft manufacturers to modify fuel systems to
eliminate the possibility of an ignition source developing within a
fuel tank.
 Our ground fault isolation solutions meet the SFAR-88 requirements,
and our products are compatible with the wiring interfaces,
footprints and form factors of the components that they replace.

58
Ramp & Transit-Engine Fuel Feed
GFI – GROUND FAULT INTERRUPTER

 Although no protection system is perfect, the ground fault detection


technology substantially reduces the chance of electrically induced
combustion within aircraft fuel tanks.

59
Ramp & Transit-Engine Fuel Feed
GFI – GROUND FAULT INTERRUPTER

 To aid in troubleshooting, all Leach brand FCD and GFI components


come with a built-in test feature to allow aircraft mechanics to verify
that fault sensing is functional. As well as a visual trip indicator on each
device that alerts mechanics that a ground fault has occurred.

60
Ramp & Transit-Engine Fuel Feed
62
Ramp & Transit-Engine Fuel Feed
GFI – GROUND FAULT INTERRUPTER

64
Ramp & Transit-Engine Fuel Feed
GFI RELAY - P91

65
Ramp & Transit-Engine Fuel Feed
GFI RELAY - P92

GFI

66
Ramp & Transit-Engine Fuel Feed
WARNING – LOW PRESSURE LIGHTS

• TRIPPED CB (FUEL PUMP) - SUPPLY THE 9072kgs CENTRAL TANK (CDCCL)


BEFORE RESET.
• TRIPPED GFI RELAY SUPPLY THE CENTRAL TANK WITH 6350kgs
(CDCCL) BEFORE RESET.

All fuel pumps have a GFI - Ground Fault Interrupter. Its function is to detect and protect the pumps
against short circuit or phase unbalance of the pump electrical supply. Both failures can cause
pumps to overheat and increase the risk of tank explosion.

CDCCL - Critical Design Configuration Control Limitations

67
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - FUNCTIONAL DESCRIPTION - CENTER TANK BOOST PUMP

70
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - MAIN TANK 1 FORWARD AND AFT BOOST
PUMPS

71
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - MAIN TANK NO. 2 FORWARD AND AFT
BOOST PUMPS

74
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - FUNCTIONAL DESCRIPTION - FORWARD
AND AFT BOOST PUMP

77
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - FUEL CROSSFEED VALVE

79
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - ENGINE FUEL SPAR VALVE

82
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - WATER SCAVENGE EJECTOR PUMP

85
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - OPERATION

The dimmed Spar Valve Closed indication indicates that the position of the Engine Start Lever
matches the current position of the valve. If there is a disagree between positions, the indication
will remain bright. The same concept applies to Crossfeed Valve Open and Engine Valve Closed
indication.

87
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - OPERATION

88
Ramp & Transit-Engine Fuel Feed
ENGINE FUEL FEED - OPERATION

91
Ramp & Transit-Engine Fuel Feed
92
APU FUEL FEED - INTRODUCTION

Purpose
The APU fuel feed system supplies fuel to the APU.

93
Ramp & Transit-APU Fuel Feed
APU FUEL FEED SYSTEM - GENERAL DESCRIPTION

94
Ramp & Transit-APU Fuel Feed
APU FUEL FEED SYSTEM - GENERAL DESCRIPTION

97
Ramp & Transit-APU Fuel Feed
APU FUEL FEED SYSTEM - COMPONENT LOCATION

99
Ramp & Transit-APU Fuel Feed
APU FUEL FEED SYSTEM - COMPONENT LOCATION

100
Ramp & Transit-APU Fuel Feed
APU FUEL FEED - APU FUEL SUPPLY LINE, SHROUD, AND DRAIN
LINE

101
Ramp & Transit-APU Fuel Feed
103
Ramp & Transit-APU Fuel Feed
APU FUEL FEED - APU FUEL SHUTOFF VALVE OPERATION

105
Ramp & Transit-APU Fuel Feed
107
DEFUEL - INTRODUCTION

General
The defuel system removes fuel from the fuel tanks to the refuel station. The defuel system
also permits fuel transfer from one fuel tank to another.

108
Ramp & Transit-Defuel
DEFUEL - GENERAL DESCRIPTION

109
Ramp & Transit-Defuel
DEFUEL - DEFUEL VALVE

112
Ramp & Transit-Defuel
DEFUEL - OPERATION

114
Ramp & Transit-Defuel
FUEL TRANSFER - OPERATION

115
Ramp & Transit-Defuel
117
FUEL INDICATING - INTRODUCTION

Fuel Quantity Indicating System (FQIS)


The FQIS measures fuel weight in the fuel tanks. The common display system (CDS) and the fueling
panel show fuel quantity.

118
Ramp & Transit-Fuel Indicating
FUEL INDICATING - GENERAL DESCRIPTION

119
Ramp & Transit-Fuel Indicating
FUEL INDICATING - TANK UNITS AND COMPENSATORS

120
Ramp & Transit-Fuel Indicating
FUEL INDICATING - WIRE HARNESSES

122
Ramp & Transit-Fuel Indicating
FUEL INDICATING - FUEL QUANTITY PROCESSOR UNIT

124
Ramp & Transit-Fuel Indicating
FUEL INDICATING - FUEL QUANTITY PROCESSOR UNIT

125
Ramp & Transit-Fuel Indicating
FUEL INDICATING - FUEL QUANTITY PROCESSOR UNIT - POWER

126
Ramp & Transit-Fuel Indicating
FUEL INDICATING - FUEL QUANTITY PROCESSOR UNIT - POWER

128
Ramp & Transit-Fuel Indicating
FUEL INDICATING - GENERAL DESCRIPTION

131
Ramp & Transit-Fuel Indicating
FUEL INDICATING - FUEL QUANTITY INDICATIONS

133
Ramp & Transit-Fuel Indicating
FUEL INDICATING - TRAINING INFORMATION POINTS - FQIS BITE
TEST MAIN MENU PAGES

136
Ramp & Transit-Fuel Indicating
FUEL INDICATING - TRAINING INFORMATION POINTS - FQIS BITE
TEST CURRENT STATUS PAGE

137
Ramp & Transit-Fuel Indicating
FUEL INDICATING - TRAINING INFORMATION POINTS - FQIS BITE
TEST INFLIGHT FAULT PAGES

138
Ramp & Transit-Fuel Indicating
FUEL INDICATING - TRAINING INFORMATION POINTS - FQIS BITE
TEST GROUND TEST PAGES

139
Ramp & Transit-Fuel Indicating
FUEL INDICATING - TRAINING INFORMATION POINTS - FQIS BITE
TEST IDENT/CONFIG PAGES

141
Ramp & Transit-Fuel Indicating
FUEL INDICATING - TRAINING INFORMATION POINTS - FQIS BITE
TEST INPUT MONITORING PAGES

143
Ramp & Transit-Fuel Indicating
FUEL INDICATING - TRAINING INFORMATION POINTS - FQIS BITE
TEST ERASE FAULT HISTORY PAGES

145
Ramp & Transit-Fuel Indicating
147
FUEL MEASURING STICK - INTRODUCTION

148
Ramp & Transit-Fuel Measuring