NOTES AND LEGEND


NOTES

1. THIS DRAWING IS TO BE READ IN CONJUNCTION WITH THE


MECHANICAL SPECIFICATION, AND ALL CONSULTANT'S
INFORMATION.

2. ALL PIPEWORK IS TO BE PRESSURE TESTED IN ACCORDANCE


WITH THE SPECIFICATION PRIOR TO OPERATION OF THE SYSTEM.

A 3. BRACKETS AND SUPPORTS ARE NOT SHOWN FOR CLARITY. ALL A


NECESSARY SUPPORTS/BRACKETING SHALL BE INCLUDED FOR AS
DESCRIBED IN THE SPECIFICATION.

4. THERMAL INSULATION AND PIPEWORK IDENTIFICATION IS NOT


To
SHOWN FOR CLARITY. ALL PIPEWORK SERVICES SHALL BE
Long
Wing INSULATED AND PROVIDED WITH RELEVANT IDENTIFICATION AS
DESCRIBED IN THE SPECIFICATION.
Ø50 Ø63 Ø75 Ø90 Ø110 Ø110 To
Ø40 Ø50 Ø63 Ø75 Ø90 Ø90 Central 5. DRAIN COCKS ARE TO BE INSTALLED AT SYSTEM LOW POINTS.
Ø50 Ø63 Ø75 Ø90 Ø90 Ø90 Wing
ROOF 6. PIPEWORK DIAMETERS INDICATED ARE EXTERNAL DIAMETERS.
PRV PRV PRV PRV PRV PRV PRV PRV PRV PRV PRV PRV
7. THERMOSTATIC MIXING VALVES SHALL BE FITTED, WHERE

Ø50
Ø40
Ø50

Ø50
Ø40
Ø50
Ø50
Ø40
Ø50

Ø50
Ø40
Ø50

Ø50
Ø40
Ø50

Ø50
Ø40
Ø50
ROOM 334 ROOM 332 ROOM 333 ROOM 331 ROOM 330 ROOM 328 ROOM 329 ROOM 327 ROOM 326 ROOM 324 ROOM 325 ROOM 323 REQUIRED, TO ALL WASH BASINS, BIDETS, SHOWERS AND BATHS
AND SHALL BE SUITABLE FOR USE WITH WATER HEATER
SELECTED TAKING INTO ACCOUNT EXPANSION REQUIREMENTS.
FLOW RESTRICTORS TO BE PROVIDED WHERE HOT WATER
B HEATERS FEED MIXING OUTLETS.
B
8. FINAL OUTLET CONNECTIONS ARE TO BE VERIFIED AGAINST
SANITARYWARE SCHEDULES AND ALLOWANCE MADE FOR ANY
CHANGE IN CONNECTION SIZES ETC.

LEVEL 03 9. ALL VALVES TO BE LOCATED TO ENSURE ACCESSIBILITY FOR

Ø50
Ø40
Ø40

Ø50
Ø40
Ø40
MAINTENANCE PURPOSES.
Ø50
Ø40
Ø50

Ø50
Ø40
Ø50

Ø50
Ø40
Ø50

Ø50
Ø40
Ø50
10. FINAL SETTING OUT OF OUTLETS TO BE IN LINE WITH INTERIOR
ROOM 234 ROOM 232 ROOM 233 ROOM 231 ROOM 230 ROOM 228 ROOM 229 ROOM 227 ROOM 226 ROOM 224 ROOM 225 ROOM 223 DESIGN/ARCHITECTURAL REQUIREMENTS.

11. HOT OUTLET TEMPERATURES SHALL BE AS FOLLOWS:

· SINKS 60°C (C/W WARNING LABEL INDICATING HIGH TEMPERATURE


OUTLET)

· WASH HAND BASINS 41°C

Ø110

Ø110

Ø110
C LEVEL 02 C

Ø90
Ø90

Ø75
Ø90

Ø90

Ø90
· BATHS 44°C
· BIDET 38°C

Ø32
Ø32
Ø32

Ø32
Ø32
Ø32
Ø40
Ø32
Ø40

Ø40
Ø32
Ø40

Ø40
Ø32
Ø40

Ø40
Ø32
Ø40
· SHOWER 41°C
ROOM 134 ROOM 132 ROOM 133 ROOM 131 ROOM 130 ROOM 128 ROOM 129 ROOM 127 ROOM 126 ROOM 124 ROOM 125 ROOM 123

15. ALLOWANCE SHALL BE MADE FOR EXPNASION/CONTRACTION OF


PIPEWORK.

16. WHERE PIPEWORK PASSES OVER MOVEMENT/SEISMIC JOINT,


RELEVANT EXPANSION PROTECTION DEVICES SHALL BE USED.

LEVEL 01 17. REFER TO SPECIFICATION FOR MATERIAL SPECIFICATIONS.

18. SHOULD THESE DRAWINGS IN ANY WAY CONFLICT WITH THE


INFORMATION PROVIDED IN THE SPECIFICATION, SCHEDULES OR
Ø32
Ø32
Ø32

Ø32
Ø32
Ø32

Ø32
Ø32
Ø32

Ø32
Ø32
Ø32
D ROOM 1034 ROOM 1032 ROOM 1033 ROOM 1031 ROOM 1030 ROOM 1028 ROOM 1029 ROOM 1027
ANY OTHER ISSUED INFORMATION, THE CONTRACTOR IS TO
REQUEST CLARIFICATION FROM THE ENGINEER DURING TENDER D
STAGE.
Offices/Meeting Offices/Meeting Offices/Meeting Offices/Meeting Offices/Meeting Offices/Meeting
rooms rooms rooms rooms rooms rooms 19. ALL PIPEWORK EQUIPMENT AND ACCESSORIES SHALL BE
INSTALLED IN A NEAT & TIDY FASHION TO THE SATISFACTION OF
Required Required Required Required Required Required
Plumbing to Plumbing to Plumbing to Plumbing to Plumbing to Plumbing to
THE ENGINEER & ARCHITECT.
be Confirmed be Confirmed be Confirmed be Confirmed be Confirmed be Confirmed
20. REFER TO MANUFACTURERS' LITERATURE FOR INFORMATION
LEVEL 00 REGARDING INSTALLATION REQUIREMENTS SUCH AS SUPPORT
STEELWORK, DRAINAGE, CLEARANCE REQUIREMENTS ETC.
MANUFACTURERS' REQUIREMENTS ARE DEEMED TO HAVE BEEN
INCLUDED IN THE CONTRACTORS' COST.

S-01 S-02 S-03 S-04 S-05 S-06


E To Short Wing Hot Water Pumps
E
To Calorifier
Connect to existing Water Softener
To Long Hot Water Pumps
To Calorifier
Connect to existing Water Softener
To Central Wing Hot Water Pumps
BASEMENT LEVEL THE CONTRACTOR IS OBLIGED TO INFORM THE CONSULTANT OF
DISCREPANCIES, IF ANY, BETWEEN THESE DRAWINGS AND THE WORKS. THE
CONTRACTOR SHALL NOT PROCEED WITH THE RELEVANT WORKS UNTIL
To Calorifier RECEIPT OF AN INSTRUCTION, IN WRITING, BY THE CONSULTANT.
Connect to existing Water Softener No part of this document may be reproduced, stored or transmitted in any form or by any means, without the
previous written permission of the author. Copyright ©

DRAWING ISSUE
PRELIMINARY (not for construction) FOR TENDER PURPOSES ONLY

South Wing FOR REVIEW & APPROVAL FOR INFORMATION PURPOSES ONLY

NOT TO SCALE PLANNING & PERMITTING FOR CONSTRUCTION

AS-BUILT

F Permission to proceed does not release contractor of the obligation to carry out works in accordance with
contract specifications; any variations are to be reported to the architect/engineer as soon as they are noted.
F
- - - -

REVISIONS
- - - -

NOTE: -
-
-
-
-
-
-
-
- - - -
- - - -
LEGEND · BOTH COLD AND HOT WATER 333
South
Wing
- - - -
Rev Description By Date
DOMESTIC COLD WATER SUPPLY . CONNECTION TO ROOMS ARE TO VALVE
331

334
S-02
S-01 329

PPR AQUATHERM SDR 11 332

HEADERS 330

S-03
S-04
327

Central
DOMESTIC HOT WATER SUPPLY .
325

328
Wing
323

PPR AQUATHERM SDR 9 326 S-06

G · ALL EXTERNAL PIPEWORK IS TO BE UV


S-05
324
335

S-07
337

S-08
339 341

S-10
343

G
DOMESTIC HOT WATER RETURN .
PPR AQUATHERM SDR 9
PROTECTED AND INSULATED S-13
302 S-09
336 338
S-11
340 342
DESIGN | ENGINEER | MANAGE
304 QPM Ltd., Triq Dun Karm, Birkirkara, BKR 9037, Malta
ISOLATION VALVE 306 S-12
301
T: +356 2551 3000 | F: +356 2551 3001 | E: info@qpml.com
S-15 303

· DDA ROOMS NEED TO BE PROVIDED WITH 310


308

S-14
305
Client Job No.

307
CPH 2411
PRESSURISATION VALVE BALANCING VALVE, TO BE COORDINATED 312

S-17 Design Drawn Checked Approved Sheet Size Scale Date

PRV
309

314 S-16
CS CS CS KF A2 N/A 02-06-2022
WITH APPROVED ROOM MATRIX ISSUED
311

316

S-19 313 Long Project Description


318 S-18 Wing
-Refurbishment of Corinthia Palace Hotel
BY ID
315

320

S-21 317

322 S-20
THERMOSTATIC BALANCING 319

S-23
H VALVE H
321

S-22 Sheet Title


· ALL SUITES HAVE A CONNECTION WITH -Plumbing Schematic for South Wing
NON-RETURN VALVE DOMESTIC HOT WATER AND RETURN TO Shaft Numbering
NOT TO SCALE
TOWEL WARMER. CONNECTION IS SHOWN Job No. Originator Zone Level Type Role & Code Doc. No. Rev

IN DETAIL IN PLAN LAYOUT DRAWINGS 2411 - QP - SW - XX - DR - BS53 - 00 00