Yau Lee Semi-precast Concrete MiC for High-rise Building

- Structural Submission

5. Durability
(Same as previous approval)

Generally concrete cover to all reinforcement including links shall fuifil the requirement stipulated in the Code of
Practice for Structural Use of Concrete 2013 and Code of Practice for Fire Safety in Buildings 2011 as tabulated
in the following:

Element types F.R.R. 1 HOURS

Exposure Condition 1 Exposure Condition 2(1)

Slabs 25 30

Beams 30 30

Posts 25 30

Walls 25 30

(1) Minimum concrete cover to all steel reinforcements of internal concrete surfaces exposed to high
humidity (exposure condition 2), e.g. bathrooms and kitchens should not be less than 30mm).

R360703.01 7