2 Piece(s) 1 3/4" X 11 7/8" 2.0E Microllam® LVL: Passed
2 Piece(s) 1 3/4" X 11 7/8" 2.0E Microllam® LVL: Passed
All locations are measured from the outside face of left support (or left cantilever end). All dimensions are horizontal.
Design Results Actual @ Location Allowed Result LDF Load: Combination (Pattern) System : Wall
Member Type : Header
Member Reaction (kN) 51.48 @ 4314mm 55.93 (76mm) Passed (92%) 1.15 1.25 D + 1.4 W + 0.5 S (Adj Spans)
Building Use : Residential
Shear (kN) 33.04 @ 3974mm 67.33 Passed (49%) 1.15 1.25 D + 1.4 W + 0.5 S (Adj Spans)
Building Code : NBCC 2015
Moment (kN-m) 36.32 @ 2426mm 40.14 Passed (90%) 1.15 1.25 D + 1.4 W + 0.5 S (Alt Spans) Provincial Code : OBC 2012
Live Load Defl. (mm) 10.415 @ 2426mm 10.489 Passed (L/363) -- 1.0 D + 1.0 S + 0.4 W (Alt Spans) Design Methodology : LSD
Total Load Defl. (mm) 14.807 @ 2426mm 15.733 Passed (L/255) -- 1.0 D + 1.0 S + 0.4 W (Alt Spans)
• Deflection criteria: LL (L/360) and TL (L/240).
• Overhang deflection criteria: LL (2L/360) and TL (2L/240).
• Upward deflection on left and right cantilevers exceeds overhang deflection criteria.
• A 13.3% decrease in the moment capacity has been added to account for lateral stability.
• A bearing length of 89mm has been used for Point Load Near Support Check.
• The importance category considered for this design is normal.
• The moment, shear, and member reaction values are based on factored loads (strength). Support reactions and deflections are based on unfactored loads (service).
Location Analysis Actual Allowed LDF Actual Allowed LDF Live Load Total Comments