You are on page 1of 5

1

Modern Synchronous Condenser Performance


Considerations
Paul E. Marken, Senior Member, IEEE, Arthur C. Depoian, Member, IEEE, John Skliutas, Member,
IEEE, and Michael Verrier

There have also been many advances made in synchronous


Abstract—Many transmission entities around the world are machine technology in the past twenty-five years. Modern
considering the use of modern synchronous condensers as part of controls using microprocessors are much faster and more
their overall transmission solution. This paper explores the precise than control systems of yesterday. Modern field
performance characteristics of synchronous condensers and
exciters using power electronics are a far cry from the Ward-
provides reasons why this time-proven technology is now again
seen as offering many beneficial characteristics to the Leonard systems of 1911, resulting in synchronous condenser
transmission grid. Of particular interest are applications in performance that is much more in line with SVC response
small isolated systems with high penetrations of renewable power speeds. The dynamic response of a modern synchronous
sources. Such systems magnify the benefits provided by the condenser was reported in [6] and is not repeated here.
synchronous condenser. Another common application involves Although few synchronous condensers were produced in the
placement of synchronous condensers electrically near HVDC
last twenty-five years, generator technology continued to
installations to increase the system short circuit MVA. This
paper reports on observations from one particular system that advance. Using modern machine designs, as seen in Figure 1,
has been studied which involves all of the above situations. for a synchronous condenser allows for economic and reliable
production of machines that were not possible in the past.
Index Terms—Inertia, Power system dynamic stability, Source [7] from 1920 explains, for example, that condensers
Reactive power, Short circuit currents, Synchronous condenser. were made with multiple poles to slow the machine down, as
high-speed machines are too expensive.
I. INTRODUCTION AND HISTORY

S YNCHRONOUS condensers have been used to support


electric power systems almost as long as power systems
have existed. A General Electric publication from 1911
indicates that synchronous condensers were common at that
time. [1] As power electronics developed, static versions of
reactive power devices such as Static Var Compensators
(SVC) and STATCOM became more common. These devices
tended to require less up front capital costs and did not
involve a rotating machine and its associated maintenance
requirements. For the past twenty-five years, there has been
little interest in synchronous condensers and their application,
as SVCs have dominated this marketplace.
The winds of change have blown in an unprecedented
interest in renewable power. Many utilities have target Fig. 1. Modern synchronous machines applied as condensers
amounts of renewable generation that they are being
challenged or even required to meet. Wind power is With modern machine designs available today, and the
predominantly the solution of choice to meet these targets, modern electronics available for controls, it is appropriate to
though high levels of wind penetration can create again examine synchronous condensers as a dynamic reactive
challenges.[2, 3, 4, 5] Synchronous condensers offer some power solution. This paper examines modern synchronous
advantages over static devices when applied in support of condenser performance characteristics. Some study results
wind generation, including providing rotating inertia as well from a particularly interesting island power system are shared,
as increasing the short circuit strength of the grid. which demonstrate some of the unique benefits available using
a synchronous condenser solution. Figure 2 is a photo of an
historical synchronous condenser installation circa 1911.

Paul E. Marken is with GE Energy, Columbia City, IN USA (e-mail:


paul.marken@ieee.org).
Arthur C. Depoian is with GE Energy, Ft. Edward, NY. Michael Verrier is with Transend Networks Pty Ltd, Lenah Valley,
John Skliutas is with GE Energy, Schenectady, NY. Tasmania, Australia.

978-1-4577-1002-5/11/$26.00 ©2011 IEEE


2

Figure 3. SVC current output drops off with voltage.

Fig. 2. Historical Synchronous Condenser Installation [1]

II. PERFORMANCE CHARACTERISTICS


A synchronous condenser is a dynamic reactive power
device. As reported in [8], there are several comparative
differences with power electronic solutions. Depending on
the particular system being studied, these have varying degree
of significance. Included in the previously cited example
were harmonics, control interactions, low voltage ride
Figure 4. STATCOM and synchronous condenser current output can remain
through, overload capability, maintenance, and obsolescence. constant until voltage is very low.
Some of these characteristic differences are intuitive, such as
the lack of harmonics produced by a synchronous condenser,
and were covered in previous papers recently published, so are B. Overload capability
not discussed here. Modern synchronous machine designs not only allow
machines to be built reliably with fewer poles and faster
A. Low Voltage Output
speeds, but can also be built with significant overload
The output of a reactive power device at low voltage is of capability. The machines produced for Vermont Electric
particular importance. The function of the device after all, can Company were not necessarily typical, but are an example of
be summed up in the regulation of voltage at a particular point the overload capabilities possible with modern synchronous
in the power system. As a system event causes voltage to fall, condensers. As with most devices, the greater the amount of
the device must produce more reactive power to bring the overload current, the shorter the time the machines can
voltage back up. As a static, shunt device, an SVC’s current tolerate it. With a synchronous condenser, the values are quite
output drops off with the voltage. The reactive power output significant. Figure 5 shows the expected capability of these
capability of an SVC, therefore, drops off with the square of machines.
the voltage. A STATCOM is considered superior to an SVC
as its output current can remain constant at reduced voltage
levels. [9] A synchronous condenser is more similar to the
STATCOM in this regard as its output current can also be
maintained under low voltage conditions. Figures 3 and 4
illustrate this point graphically. Figure 3 shows how the
current output of an SVC can be expected to drop off with
voltage. Figure 4 shows the constant current nature of
STATCOM and synchronous condenser.

Fig. 5. Overload capability of the VELCO synchronous condenser at 2-hours,


10-minutes, and 5-seconds.
3

The figure shows that these machines could sustain


overload currents in the range of a few percent for 2 hours. D. Inertia
For a ten-minute scenario, currents up to 175% of nameplate
Rotating inertia is another interesting characteristic that is
are possible. For five seconds, up to three times rated current
unique to the synchronous condenser reactive power solution.
can be produced. As many power system events are measured
Renewable power sources are viewed very favorably,
in milliseconds, a ten-minute or even a five-second
however, they tend to provide less inertia to the power system
characteristic can actually be quite useful in applying a
than traditional thermal units. As thermal power sources are
synchronous condenser for dynamic support. [11]
effectively displaced by solar and/or wind power, the system
C. V-Q Curve Characteristic inertia tends to decrease. One manufacturer is offering wind
The reactive power output from any of these devices is turbines that can simulate higher inertia through clever use of
obviously the key reason for their being. The SVC, with its the controls. [2, 3] This incremental increase in inertia from
current decreasing with voltage, has a reactive power output the wind turbines, however, is not always enough.
that drops off with the square of the voltage. For applications The inertia problem can be especially acute in smaller and
where output under low voltage conditions is an important more isolated grids. One such power system exists on the
factor, the SVC performance is less impressive. The island state of Tasmania. The Tasmanian power system is
STATCOM performs better under low voltage conditions with supplied predominantly by hydro generators, which are
reactive power output decreasing in proportion to voltage. [9] subject to hydrological risks. The Basslink 630MW export
At first it would seem that the synchronous condenser 480MW import HVDC link, which at 290 km (181 miles) of
should perform similarly to the STATCOM. However, one undersea cable makes it the second longest of its type in the
must take into account the significant overload capability world [12], links Tasmania to the Australian mainland. This
mentioned above. For periods of a few seconds, it is possible link enables connection of the Tasmanian system into the
for a synchronous condenser’s reactive power output to National Electricty Market as depicted in Figure 7.
remain constant even as voltage decreases. Depending on The system inertia in Tasmania can be relatively low,
system needs, this could be a valuable characteristic. Figure 6 especially when power is being imported across the DC link at
shows possible V-I and V-Q curves of a synchronous time of low demand. The system also experiences shortages
condenser, when making use of the machine’s overload of fast acting frequency control ancillary services (FCAS)
capability. The reactive power output in the right half of because of the slow response of hydro generators to frequency
Figure 6 could be held constant as voltage decreases, up to a disturbances. There is presently one wind farm with 140MW
point. To achieve rated power output at low voltage would of installed capacity, with several others in committed or
require the current to increase. This increase in current can be publicly announced stages. As Transend, the Tasmanian
observed in the associated V-I curve of the left half of Figure transmission entity, considers future power system
6. The limit of the low voltage would depend on a number of possibilities, scenarios being studied include a second DC link
system design factors including the synchronous machine across the Bass Strait as well as additional wind power
itself, the control system, and even auxiliary components such sources. [10, 13]
as lubrication and cooling. Transend studies indicate that with the present 140MW of
wind generation capacity, the rate of change of frequency
approaches 3 hertz per second following a Basslink trip from
high import during a time of low system inertia. As more
wind generation is added to the system, it is expected that
local FCAS requirements will increase. As these services
become tight, Basslink is used to transfer FCAS from the
mainland, which reduces the energy transfer capability of the
DC link. In addition, because of the ‘no-go zone’ of this
thyristor based DC link, it is possible for Basslink to become
trapped on import and not be able to reverse flow. This in
Fig. 6. Magnetization as a function of applied field. turn causes the spot price of energy to collapse in their
simulations. Transend is recommending synchronous
As evidenced in the above figure, the overload capability of
condensers as part of the possible solution to the FCAS
the machine, combined with the speed and accuracy of
challenges as they increase system inertia. [15].
modern field exciters, can produce an effective combination.
Transend has also identified potential future voltage
The ability of a modern synchronous condenser to produce
stability issues due to the future load forecast increases in
rated reactive power, even at voltages below nominal, may
certain areas of Tasmania. Dynamic reactive support devices
allow smaller machines to suffice when compared to
such as SVC’s or STATCOM’s are known to be a suitable
nameplate ratings of SVCs. This unique characteristic may
solution to satisfy voltage stability issues but as these devices
prove valuable to system planners who must deal with low
only tackle one issue in the system Transend is closely
voltage contingencies.
researching the application of Synchronous Condensers as
4

they will not only provide voltage support for the voltage short circuit is also expected.
stability issues but also provide fault level and inertia support.
The fault level and inertia support is required for the increase I
of wind farm installations over and above that required to be jX”d jX t
provided by wind farm proponents. Transend is actively
looking to reduce capital equipment expenditure and O&M
costs and be pro-active to assist the increased penetration of
wind farms by installing modern synchronous condensers in
E Vt Vb
place of a combination of other forms of dynamic reactive
support, fault level and inertia support devices.
Fig. 8. One-Line diagram of simplified synchronous condenser short circuit.

One of the ways to maximize the effectiveness of the


synchronous condenser, from a short circuit perspective, is to
minimize the impedance of both the condenser and
transformer. Since the subtransient reactance is relatively
fixed in per unit on the condenser MVA base, reducing the
transformer leakage impedance is the only remaining option.
Australia To illustrate, consider the two following transformers, one
with Xt = 0.12 and one with Xt = 0.06 p.u. connected to a
condenser with X”d = 0.15 p.u., and an internal voltage of 1.0
p.u.: The short circuit current associated with the first
transformer is 3.70 p.u. compared to 4.76 p.u. with the lower
Basslink leakage transformer representing a 29% difference. In
HVDC general, it is more economical to reduce transformer leakage
undersea cable impedance than increase the condenser nameplate rating to
achieve a given short circuit current or short circuit MVA.
Fig. 7. Representation of HVDC connection of Tasmania to mainland The Basslink HVDC system was designed for a minimum
Australian and interconnection into eastern seaboard national electricity fault level of 1200MVA. Transend studies report that as
market [14]. future wind generation displaces the existing hydro
generation, that this minimum fault level may not always be
E. Short Circuit Strength met. Simulations involving a second, voltage source
Based on long-range system planning studies performed by converter based DC link help the FCAS situation, but
Transend, the steady state and dynamic performance of that interestingly increases the number of scenarios where an
system is improved with the addition of synchronous unacceptably low fault level occurs. As a possible mitigation
condensers. Enhanced system performance is related, in part, method for the low fault levels, Transend simulated adding
to the condenser’s ability to contribute to the short circuit synchronous condensers to their power system. These were
current in local faults in a manner similar to that of a modeled at three locations of four 25MVAR units each. This
conventional power plant. For a three-phase fault at the local was based on the installation reported in [6] and [8].
transmission bus, the first approximation of the symmetrical Rerunning the same cases with unacceptably low fault levels,
short circuit current, ignoring resistance, is determined by but now with synchronous condensers in the system, a
dividing the voltage behind subtransient reactance by the sum minimum fault level of 1440MVA was maintained [13].
of the subtransient reactance (X”d) and the transformer
III. CONCLUSIONS
leakage impedance (Xt). Figure 8 is a simplified one-line
Synchronous condensers can provide many benefits to a
diagram that corresponds to (1).
power system. They have useful characteristics with regard to
voltage support, especially when considering use of their
E short-term overload capability. They can provide rotating
I= (1)
jX "d + jX t inertia to a power system and can also increase system short
circuit strength. These traits can be helpful as systems adapt
In the event that the synchronous condenser is floating or to higher penetrations of renewable power sources, such as
operating with no net var output, the terminal voltage (Vt) and wind or solar. System challenges and the effectiveness of a
the internal voltage (E) will be the same, typically at or near synchronous condenser solution can be more pronounced in
1.0 per unit voltage. During maximum overexcited operation, smaller grids such as island power systems. In the island state
MVArs will be supplied to the system and the internal of Tasmania, simulations show that synchronous condensers
condenser voltage E will be higher than 1.0 p.u. A higher can not only help with system inertia and short circuit
5

strength, but also support the use of the existing and even VI. BIOGRAPHIES
possible future DC links. Although they have existed for many
Paul E. Marken (S’88, M’90, SM’08) graduated from Rose-Hulman Institute
years and were once considered obsolete, the value and of Technology in 1989 with a Bachelor of Science degree in Electrical
usefulness of the synchronous condenser is again resurfacing. Engineering. Paul has been with General Electric Company since 1990 and
has held a wide range of engineering positions. His roles have included Power
IV. ACKNOWLEDGMENT Systems Engineer, Project Engineer, Project Manager, and Application
Engineer. Paul is currently the FACTS Engineering Technical Leader for GE
The authors gratefully acknowledge the contributions from Digital Energy. Paul is a Registered Professional Engineer in the
Sead Pasalic, Manager Strategic Grid Planning, Transend Commonwealth of Pennsylvania and the State of Indiana. Paul is a Senior
Member of the IEEE Power and Energy Society.
Networks, and his work modeling the power system of
Tasmania. Arthur C. Depoian received a BSEE from Rensselaer Polytechnic Institute in
1976. He has been with GE since 1994 and is currently a Commercial
Manager in the Flexible AC Transmission (FACTS) business of GE. Art is
V. REFERENCES actively involved in both technical and commercial aspects of Series
[1] John Liston, "Typical Synchronous Condenser Installations," General Compensation, Variable Frequency Transformer, and Synchronous Condenser
Electric Company Review, vol. 14, pp. 234-241, Jan. 1911. projects. Prior to his career at GE, Art held a variety of Engineering and
Management positions in the textile, automotive, paper converting, and
[2] N. Miller and P. Marken, “Facts On Grid Friendly Wind Plants,” medical products industries. Art is a licensed Professional Engineer in the
presented at IEEE PES General Meeting, Minneapolis, MN, July 2010. State of New York, and a member of IEEE and NSPE.
[3] N. Miller, K. Clark, M. Cardinal, and R. Delmerico, "Grid Friendly John Skliutas (M ’89) received a BSEE degree from Worcester Polytechnic
Wind Plan Controls: GE WindCONTROL – Functionality and Field Institute and a MEE in Electric Power Engineering from Rensselaer
Tests,” European Wind Energy Conference & Exhibition, Brussels, Polytechnic Institute and has been with GE since 1980. He is currently a
Belgium, March/April 2008. Principal with GE Energy and conducts consulting and research work in the
area of insulation coordination, harmonics, and T&D equipment application.
[4] “Interconnection for Wind Energy”, U.S. Federal Regulatory
Commission, Order 661-A, December 12, 2005, Available Michael Verrier received an Associate Diploma of Engineering (Electrical)
http://www.ferc.gov. in 1990 from the Hobart technical college, Tasmania and a B.Tech (Power
Eng) degree in 2007 from the University of Southern Queensland. Michael has
[5] “Grid Code, High and Extra-High Voltage”, E.ON Netz GmbH, worked at Transend Networks for the last eight years and since August 2009
Bayreuth, Germany, April 1, 2006. in their Strategic Grid Planning department as the Senior Planning Engineer.
[6] P. Marken, D. LaForest, R. D’Aquila, D. Wallace, E. Kronbeck, and J. His work includes research and specification of the strategic direction of the
Skliutas, “Dynamic Performance of the Next Generation Synchronous Tasmanian transmission network as well as to investigate the need for and
Condenser at VELCO,” presented at IEEE PES Power Systems identify the requirements of dynamic reactive support devices for the
Conference and Exposition, Seattle, WA, March 2009. Tasmanian Transmission system.

[7] E. B. Plenge, "Synchronous Condensers," General Electric Company


Review, vol. 23, pp. 143-146, Jan. 1920.
[8] P. Marken, M. Henderson, D. LaForest, J. Skliutas, J. Roedel, and T.
Campbell, “Selection of Synchronous Condenser Technology for the
Granite Substation,” presented at IEEE PES Transmission and
Distribution Conference and Exposition, New Orleans, LA, April 2010.
[9] N. Hingorani and L. Gyugyi, Understanding FACTS, Concepts and
Technology of Flexible AC Transmission Systems, New York: Wiley,
2000, pp. 197-199.
[10] Wind power modelling and analysis of simulated output for regions in
Tasmania Executive summary. Transend Networks Pty Ltd. Tech. Rep.
TNM-GR-809-0874-001. [Online] Available:
http://www.transend.com.au/download/D10-34713

[11] P. Marken, “A Comparison of Reactive Power Devices: Synchronous


Condenser and FACTS, The VELCO case study,” presented at EPRI’s
High Voltage Direct Current & FACTS Conference, Palo Alto, CA,
October 2010.
[12] Basslink website: http://www.basslink.com.au/home/index.php?id=38
[13] “Simplified Market Simulations for 2nd Bass Strait DC Link,” Transend
Networks Pty Ltd Tech. Rep. D10/53821, Issue 0.1, July 2010.
[14] Transend website: http://www.transend.com.au/download/D07-40449
[15] M. Ringrose, B. March. (2009, May). Future wind generation in
Tasmania Executive Summary. Transend Networks Pty Ltd. Tech. Rep.
TNM-GR-809-0874-001. [Online] Available:
http://www.transend.com.au/download/D09-50930

You might also like