Professional Documents
Culture Documents
Power Transformers
1
Objectives
Identify the diagnostic and condition
assessment methods
Oil Tests:
DGA
Oil quality tests (Dielectric, Power factor, …)
3
Contents
Advanced Condition Assessment Techniques:
4
Polarization Index
Propose:
Tests : Winding Insulation + Oil
Overall integrity of the winding insulation
Verify that the state of dryness of insulation
Definition:
Polarization Index : PI=R10-min /R1-min
Trend Measure of dielectric deterioration
Absorption ratio : AR=R60s /R15s
Test Method: H-LG, L-HG, HL-G
Utest=5 kV-DC
Time= 15 s, 60 s, 10 min
5
Insulation Resistance Model
iL iC
6
Test Arrangement
When to use Guard?
9
Test Arrangement
10
Test Case
Auxiliary Transformer 230kV/13.8kV
12
DC Resistance
Can detect:
Shorted-turns
Loose connection on bushing
Loose connections or high-contact resistance on tap changers
Broken winding strands
The above issues leads to hot-spots, generates gases DGA
13
Short circuit impedance
Applications:
14
Short circuit impedance
15
Short circuit impedance
If deviation exists it could be due to:
Type of excitation (1-phase versus 3-phase)
Different instrumentation
Winding deformation
17
Excitation Current Test
Factory tested at rated voltage (no-load)
If possible run three-phase if not ,can be
done single-phase.
Perform Excitation Test before any DC
test: DC test leaves residual magnetism in
the core.
Voltage is applied to HV :5kV or 10 kV
LTC set to: 1- Neutral , 2- 1 step up, 3- 1 step down
4- Full raise , 5- Full lower
18
Excitation Current Setup
19
Excitation Current Pattern
H1 H2 H3
Excitation
H1-H0
Similar to
Higher R
H3-H0 results higher
excitation
current
H2-H0
20
Excitation Current Results
Possible Characteristics of
patterns
H-L-H • 3 leg core-type (Most common)
• 5 leg core or shell type with a delta secondary
L-H-L • 3 leg core-type ,Y secondary, inaccessible
neutral
All equal • 5 leg with Y secondary
• 3 single phase connected as 3- phase
• Shell-type with Y-connected secondary
All • Can be due to magnetized core
different • Defects, Faults
Excitation current Criteria to detect defect
Iext<50 mA The difference between 2 higher 21
current >10%
Iext >50 mA The difference between 2 higher current >5%
Excitation Current with LTC
22
Power Factor Testing
Dissipation Factor or is
the ratio of the I=IC+IR
resistive current to
capacitive current I
Power Factor : P.F.= IR/I
IC IR
Dissipation factor : tan=IR/IC
2-Winding Transformer
1 phase of 3 phases shown
• CH: HV bushing + HV winding +Oil
• CL: LV bushing + LV winding + Oil
• CHL: Both windings+ barriers + Oil 24
Test Arrangement
3 test modes:
Grounded Specimen
with Guard (GST-g)
25
Test Arrangement
One of the most common source of measurement error: Neutral is
not properly connected.
27
Oil Test: DGA
• Rogers Ratio
• Doernenburg Ratio
Duval Triangle
IEC1 - (1st Edition 1978)
• IEC2 – (2nd Edition 1999)
• ANSI/IEEE (C57.104-1991)
•CIGRE Method
• Laborelec
• Japanese Method
• Russian Method
28
Key Gas Method
Key
Secondary Gas Fault Pattern Possible Root cause
Gas
Aging of insulation, possible
Low energy carbon particles in oil, poor
CH4 and minor C2H6
H2 Partial grounding of metal objects, loosed
and C2H4
Discharge lead, floating metal or
contamination
Paper insulation destroyed. Metal
C2H4 CH4 and minor H2 and
Oil overheating discoloration. Oil heavily
(ethylene) C2H6(ethane)
carbonized.
Poor contacts in leads, weakened
H2 and minor CH4 and High Energy
C2H2 insulation from aging, carbonized
C2H4 Arcing
oil.
If the fault involves Overloading or cooling problem,
CO, and oil-impregnated Conductor bad connection in leads, stray
CO2 structure CH4 and Overheating magnetic flux, discoloration of
paper. 29
C2H4
Duval Triangle
x = (C2H2); y = (C2H4); z = (CH4), in ppm
%C2H2=100x/(x+y+z);
%C2H4 = 100y/(x+y+z);
%CH4 = 100z/(x+y+z),
T1: Low-range thermal fault
(below 300 C)
T2 :Medium-range thermal
fault (300-700 C)
T3 :High-range thermal
fault (above 700 C)
D1: Low-energy electrical
discharge
D2 :High-energy electrical
discharge
DT: Indeterminate
30 - thermal
fault or electrical discharge.
IEEE Std C57.104
• Four-condition DGA guide to classify risks to transformers with
no previous problems.
the following
Thermal
Overloading
Y Y Case4
1<R2<3
Y
0.1<R1<1
Y
31
R >3
3
Y High energy
arcing
IEEE Std C57.104
Status H2 CH4 C2H2 C2H4 C2H6 CO CO2 TDCG
Condition 100 120 35 50 65 350 2500 720
1
Condition 101-700 121-400 36-50 51-100 66-100 351- 2500- 721-
2 570 4000 1920
Condition 701- 401-1000 51-80 101-200 101- 571- 4001- 1921-
3 1800 150 1400 10000 4630
Condition >1800 >1000 >80 >200 >150 >1400 >10000 >4630
4
• Not all techniques were applicable in all cases
• If most of Gas levels < 1 and one or two is high, the error of
regular methods might be high. Call your judgment,
32
do not
forget Key Gas Table.
Case 1:750 MVA,500kV
Date H2 CH4 C2H2 C2H4 C2H6 CO2 CO TCG
ppm/day
April 10 5 2 6 2 1398 277 47,800
2010
May 10 5 2 2 2 155 71 0.13
2009
35
Post Failure Test Interpretation
Suggested Problem Test Data
Category 1st priority 2nd priority 3rd priority
Turn-to-turn fault Out of tolerance Low winding Excitation increase
ratio resistance
Damage to major High power factor Low insulation Abnormal DGA
insulation resistance
Lead and terminal Abnormal DGA, DC resistance Excitation
issues trend inclines increases if load
increases
Through fault FRA shows Deviation of Change in impulse
mechanical different pattern exciting current
damage for faulty phase
Core heating Abnormal DGA Low core ground Excitation
resistance increases
Moisture High insulation Low dielectric oil Low insulation
power factor test 36
resistance
Selected Advanced Techniques
Partial Discharge
37
Partial Discharge
Wide-Band PD Narrow-band PD
measurement measurement
39
Partial Discharge Measurement
41
Partial Discharge Patterns
1 Cycle screenshot 1 Cycle screenshot
42
Case1 Case2
44
T-F Classification Map
45
Acoustic PD :Off-line/On-line
1. All-Acoustic (minimum 3 sensors)
2. Acoustic with Electrical PD trigger
Velocity of sound
46
in oil :1413 m/s at 20 °C
Acoustic PD
Vibration noises (core,fan,pump) <50kHZ
Band Pass filter: f1=50 kHz, f2=350 kHz
Propagation path: direct , indirect
47
Sensor locations when
phase of PD source is not known
Acoustic PD
Before placing the AE transducer, wipe the area (dirt, oil,
bugs,…).
Acoustic couplant needed for enhancing the mechanical and
acoustical coupling between the transducer and the tank
surface.
A sound transmitting epoxy to be used if the mounting
location is non-magnetic.
Magnetic tank shielding causes extra signal attenuation.
LTC operation contains a high electromechanical energy that
usually propagates through the entire transformer. To be
distinguished in post-analysis.
Initial place to start: one sensor in the bottom connection
of each bushing.
48
Application of Acoustic PD
When electrical PD is detected, for confirmation and source location
When DGA indicates the possible presence of PD
For PD detection during factory impulse testing
When static electrification is suspected
49
Acoustic PD
Electrical PD has a threshold 300 (500)pC. There is no similar
threshold for acoustic systems.
A strong signal buried deep within a winding may be very weak by
the time it reaches the acoustic sensor.
Sometimes longer monitoring period is necessary: weeks
Only high PD levels can be detected.
The correlation is weak between measured and real PD level due to
attenuation.
Direct signal
Wall propagation
50
Test Case:
Single phase autotransformer: 500/230/13.8
kV,146/194/243 MVA
After two years in operation started gassing.
Load is minimum
Voltage is maximum
51
Test Case:3-D Plot
52
Dielectric Frequency Response
53
How to Measure DFR
Measurement modes: UST, GST, GTS-g
54
Application
55
DFR to Estimate Moisture
56
Using DFR curve, the Wt% can be estimated.
How DFR Estimates Moisture?
X-Y Model of Insulation
1 1 1
Ccomb ( ) Cspacer ( ) Coil ( ) Cboard (
57 )
How DFR Estimates Moisture?
l Oil
– Non-polar liquid; er = 2.2
l Pressboard, oil impregnated cellulose
– More polar; er = 4.5
– Sensitive to moisture
58
Why moisture is important?
59
Conventional Moisture Estimation
MOISTURE EQUILIBRIUM BETWEEN OIL AND CELLULOSE
Uncertain area
60
Conventional Method Cons
62
Test Case :500 MVA 230kV GSU,1976
Conventional Power Factor :
Conclusion: Contamination,
no dry-out needed. Shipped
out to replace the windings.
66
Test techniques
Freq response analysis (FRA)
Impedance/admittance/transfer measurements
Typically 1kHz – 1MHz
Network analyzer or equivalent
Detects deformations/displacements
Compare against other phases , previous
measurement, or sister unit
The lead lengths need to be as short as possible,
and the test configuration must remain constant
for repeated tests.
67
Application
Detecting Faults which involves:
Winding deformations
Core movements
Faulty core grounds
Partial winding collapse
Hoop buckling
Broken clamping structures
Shorted turns and open windings
68
FRA
69
FRA
70
FRA
Repeatability is Key in FRA Measurement
Core NOT
grounded
Core
grounded
71
FRA-Typical Curves
72
FRA-Interpretation
Low frequencies
Core problems
shorted/open
windings
Medium frequencies
Winding deformations
High frequencies
Tap connections
Other winding
connection problems
73
FRA-Applied voltage
It is usually 10V.
2.8 V
Omicron
10 V
FRAX, Doble and others
74
FRA-Proper Grounding
Good Poor
grounding grounding
practice practice
75
FRA-Test Case -180 MVA off-shore
Acetylene up
Change in winding resistance
77