7.3.2. Open areas including lobbies, waiting rooms and the like, may not be
obstructed by fences, barriers or doors that divide the area into rooms,
apartments or other uses.
If the egress path is blocked by furniture or other movable objects, the
barrier must be moved off the beaten path, or fences and other fixed
barriers must be installed to protect the egress route from encroachment.
7.3.3. Mirrors may not be installed at exit doors. Mirrors shall not be placed in or
adjacent to any exit in such a way as to confuse the direction of the exit.
7.3.4. Everyone must leave the facility or overcrowded occupancy when requested
by facility management or regulatory authorities. A facility is assessed as
overfilled when the occupancy load exceeds the exit capacity or the
installed or allowed occupancy load.
7.3.5. Inspection, testing and maintenance.
Inspection, testing and maintenance includes exits, access exits and
release exits, exit signs, emergency lighting and fire stair pressurization
fans.
254
Machine Translated by Google
7.3.5.1. Inspection.
Inspections should be carried out regularly on a monthly basis, or more
frequently depending on conditions, for the following:
(1) Exit doors
(a) May not be locked or padlocked.
(b) Damage to the automatic door closer. (c) There is a
chock or bond that keeps the door always open, on a door that must
always be in a closed state.
(d) Obstruction of objects and others in front of the exit door.
(2) Fire ladder
(a) There is a chock or tie holding the door open
ladder.
(b) Clean, and not used for resting/smoking areas
occupants/employees, and not used for warehouses.
(c) Not to be used to place equipment such as panels, AC units and
the like.
(d) Damage to floors, steps and banisters. (e) The lighting
lamp is on.
(3) Exit access and corridors used as exit routes
(a) Free from all kinds of obstacles. (b)
Not used for warehouse.
(4) Exit discharge on the ground floor leading to a public road or an open
place outside the building must not be locked.
(5) Exit sign
(a) Visibly unobstructed. (b) The
flashing light is on.
7.3.5.2. Maintenance.
Maintenance must be carried out as follows:
(1) Automatic door closers that are damaged must be repaired/replaced
immediately.
(2) Fire stair lighting lights or exit signs that are off
should be repaired/replaced immediately.
7.3.5.3. Testing.
Testing shall be carried out as follows:
255
Machine Translated by Google
(1) Emergency lighting at egress facilities must be tested for ½ hour every
year and for at least 10 seconds every month. The time for switching
to emergency lighting by a diesel generator shall not exceed 10
seconds.
(2) Operational and periodic testing of the pressurization fan system for
fire ladders must be carried out every 6 months and comply with SNI
03-6571-2001 or the latest edition of the fire smoke control system in
buildings.
7.3.5.4. A history of inspection, test run and maintenance records should be kept
as described in point 7.4.1.7.
256
Machine Translated by Google
7.4.1.5. While the aim of maintenance of the fire protection system is preventive maintenance and
corrective maintenance to maintain the optimum function of the equipment.
7.4.1.6. In the maintenance and care of the fire protection system, compliance with the applicable
provisions and standards must be guaranteed, including personnel certification requirements,
test and maintenance frequency, as well as documentation and reporting, including record
keeping .
(1) Records of the inspection/examination, testing and periodical maintenance of the system
and its components must be made available to the competent authority upon request,
and used as one of the considerations for determining the extension of the certificate
of proper functioning of the building.
(2) Records must show the procedure performed (eg inspection, testing or maintenance),
the organization/personnel who performed it, the results, and the date it was carried
out.
(5) Further records must be kept for a period of 1 (one) year after the inspection/examination,
testing and subsequent maintenance required.
7.4.1.8. It is important to realize that all of the fire protection systems mentioned above are not
separate and independent in their operations for fire prevention and control and rescue/
evacuation of building occupants.
There are interlocking influences, interlocks and interfaces between systems. Poor
maintenance and maintenance of one system can have a significant effect on the overall
fire safety of a building.
7.4.2. Fire Detection And Alarm Systems And Voice Communication Systems
Emergency.
7.4.2.1. This system includes a fire detection and alarm system, an emergency voice communication
system, or a sound system used in an emergency, and a fireman 's telephone system, if any.
257
Machine Translated by Google
7.4.2.3. The responsibility for a fire alarm system should lie with the building owner/
manager, but typically responsibility is shared between the owner/manager,
occupants, own staff and outside contractors. Consequently, personnel with
various skills, at several levels, and with different priorities are involved in
the maintenance of these systems. In many cases, an effective fire alarm
system maintenance program can be accomplished through the maximum
use of qualified own resources, while relying on skilled outside contractors
for activities beyond the capabilities of these own resources.
Speaker c. X X
Visible tools X X
2. Fire Alarm system battery:
a. Lead Acid Type X
b. Nickle-Cadmium type X
258
Machine Translated by Google
Hand
over to 1/
No Equipment Quarterly Monthly Annual
Semiannual
retest
d. Sealed Lead Acid Type
3. FA system control equipment
monitored for alarms,
supervision, error signals
(trouble) b. Melt guard
X X
c. Interface equipment X X
Primary/main
e. power supply X X
4. FA system control equipment
not monitored for
alarms, supervision, fault signals
b. Melting protection c. X X
Interface equipment X X
Primary/main
e. power supply X X
initiating equipment
9. devices:
detector Electromechanical X X
259
Machine Translated by Google
Hand
over to 1/
No Equipment Quarterly Monthly Annual
Semiannual
retest
h. Smoke detector X X
i. Supervision signaling X X
Speaker c. X X
Visible tools X X
2. Fire Alarm system battery:
a. Lead Acid Type
1. Charger Test X X
Specific Gravity b. X X
Nickle-Cadmium type
1. Charger Test X X
1. Charger Test X X
0
260
Machine Translated by Google
Hand
over to 1/
No Equipment Quarterly Monthly Annual
Semiannual
retest
3. Metallic conductor 4. X
Non-metallic conductor X
FA system control equipment
5. monitored for alarms,
supervision, fault
signals
a. X X
function b. Melting X X
c. protection Equipment interface X X
d. Lights and LEDs X X
Transponder
e. primary X X
f. power supply X X
Unmonitored FA system
6. control equipment
for alarms, supervision, fault
signals
a. X X
function b. Melting X X
c. protection Equipment interface X X
d. Lights and LEDs X X
Primary/main
e. power supply X X
f. Transponder X X
Control unit fault signal
7. (trouble) X X
Emergency voice/alarm
8. communication equipment X X
9. Power fiber optic cable X X
Security equipment / guard's
10. tour X X
equipment Initiating devices:
11.
Taking air samples /
a. water sampling X X
b. duct detector X X
Electromechanical
c. type removal tool X X
Fire extinguishing
d. system switch X X
261
Machine Translated by Google
Hand
over to 1/
No Equipment Quarterly Monthly Annual
Semiannual
retest
Fire alarm
box/manual call point
e. X X
f. Heat detector X X
Smoke detector X X
i. Supervision signal device X X
(6) The reading of the pressure gauge or indicator indicates the operable
position.
262
Machine Translated by Google
(7) For those using wheels, the condition of the wheels, carriage, hoses and nozzles.
(8) There is a maintenance label (tag) . Monthly inspection records,
containing the inspected small fire extinguisher, date and initials of
the personnel who performed it, must be contained in the
maintenance tag ( tag) attached to the said light fire extinguisher.
7.4.3.3.3 Corrective actions include the following:
(1) If during the inspection/examination there is a deficiency in point
7.4.3.3.2 mentioned above, corrective action must be taken
immediately.
(2) Light fire extinguisher that can be refilled: if during the inspection/
examination there is any shortage of conditions from point 7.4.3.3.2
(3), (4), (5), (6) and (7) mentioned above , then the applicable
maintenance procedures must be applied.
(3) Light fire extinguishers that cannot be refilled: if during the inspection
there are any deficiency conditions from item 7.4.3.3.2 (3), (4), (5),
(6). mentioned above, it must not be reused, used/sprayed, and must
be destroyed or returned to the supplier/manufacturer.
7.4.3.4. Maintenance.
7.4.3.4.1 Maintenance shall be carried out annually by the manufacturer, a light
fire extinguisher maintenance company, or by trained personnel.
263
Machine Translated by Google
264
Machine Translated by Google
Pump Operation :
*
Electric pump: operated for at least 10 minutes
Diesel pump: operated for at least 30 minutes
265
Machine Translated by Google
266
Machine Translated by Google
Hose Connection:
Piping :
Slang :
267
Machine Translated by Google
Hose nozzle
obstruction/obstruction Move
obstruction/obstruction Move
Hose box
Check general condition for damaged parts Repair or replace components; if necessary,
or rusted replace the entire hose box
If it's the break glass type , does the key work? Repair or replace
268
Machine Translated by Google
control valve :
alarm valve :
Check valve:
1 year /5
Interiors Inspection Year
269
Machine Translated by Google
control valve :
1 year
Control valve Maintenance
1 year
Pre-Action/Flood valve (Preaction/Deluge valve) Maintenance
1 year
Dry pipe valve (Dry pipe valve) Maintenance
0
270
Machine Translated by Google
Weekly/monthly
Control valve Inspection
(Table 7.4.5.3)
7.4.5.5. Inspection.
7.4.5.5.1 Table 7.4.5.2 (1) shall be used for inspection, testing and maintenance of all
classes of standpipe systems and hoses or yard hydrants.
7.4.5.5.2 The points of view and corrective action described in Table 7.4.5.2 (2) and
Table 7.4.5.2 (3) shall be followed to ensure that components are free from
rust, foreign matter, physical damage, or other conditions that adversely
affect on system operation.
271
Machine Translated by Google
7.4.5.5.3 Piping and fittings shall be inspected annually for good condition and
free from leaks, rust, mechanical damage and straightness of piping.
7.4.5.5.6 After each alteration or repair, a check shall be made to ensure that the
system is in standby and all control valves are in the normal position
and are electrically supervised locally (locked) or remote.
7.4.5.5.7 Inspection of control valves shall ensure that the valves are in condition
following:
272
Machine Translated by Google
7.4.5.6.2 Water flow tests shall be carried out every 5 years at the hydraulically
furthest hose connections, of each zone of the building's standpipe
system and hoses or hydrants, to verify that the water supply is still
providing the design pressure at the required flow.
7.4.5.6.3 The pressure gauge shall be replaced or tested every five years in
comparison with a calibrated pressure gauge.
7.4.5.6.6 Yard hydrants must be tested every year to guarantee their function by
means of each hydrant must be fully opened until all dirt and foreign
matter is removed for not less than 1 minute.
7.4.5.7. Maintenance.
7.4.5.7.1 Maintenance and repair shall be carried out in accordance with Table
7.4.5.2 (1), Table 7.4.5.2 (2) and Table 7.4.5.2 (3).
273
Machine Translated by Google
7.4.5.7.2 Hose connections: after each use, all hoses shall be cleaned, drained
of water and thoroughly dried before being reassembled.
7.4.5.7.3 The operating stem (stem) of the control valve type OS&Y (outside
screw & yoke) shall be lubricated annually, and then fully closed and
reopened to test operation and distribute the lubricant.
7.4.5.7.4 If the fire extinguisher (siamese) cap is not in place, the inside of the
fire extinguisher shall be inspected for obstruction or blockage.
7.4.5.7.5 Yard hydrants shall be lubricated annually to ensure that all rods, caps,
plugs and threads are in good operating condition.
7.4.5.7.6 Yard fire hydrant hose boxes shall be maintained annually to ensure
that all fire hoses and fittings are in usable condition.
274
Machine Translated by Google
20 Years and
Springkler Fast Response/ Sprinklers – Fast Test then every 10 years
Response
50 Years and
sprinkler Test then every 10 years
275
Machine Translated by Google
276
Machine Translated by Google
7.4.6.6.8 After each alteration or repair, a check shall be made to ensure that the
system is in standby and all control valves are in the normal position and
are electrically supervised locally (locked) or remote.
7.4.6.6.9 Inspection of control valves shall ensure that the valves are in condition
as referred to in the standpipe and hose system.
7.4.6.6.10 The pressure reducing valve in the sprinkler system is to be inspected every 3
month (quarterly) to ensure the following: (1)
The wheel/spin is not lost or broken.
(2) No leakage.
7.4.6.6.11 Fire connection (siamese) shall be inspected every 3
months (quarterly) as is done for standpipe and hose systems.
7.4.6.7. Testing.
7.4.6.7.1 The sprinkler head shall be tested as follows:
(1) If stipulated in other parts of this provision, sprinkler samples must
be submitted to a testing laboratory that is recognized and
accepted by the competent authority for testing.
(2) If the sprinkler has been used for 50 years, it must be replaced; or a
representative sample from one or more sites shall be piloted.
The trial procedure should be repeated at every 10 year interval.
(3) Fast response type sprinklers that have been used for 20 years must
be tested. The trial procedure should be repeated at every 10 year
interval.
(4) If the sprinkler has been used for 75 years, it must be replaced; or a
representative sample from one or more sites shall be piloted.
The trial procedure should be repeated at every 5 year interval.
(5) Dry sprinklers that have been used for 10 years must be tested or
replaced. If maintenance is carried out, it must be tested again at
every 10 year interval.
(6) A representative sample of sprinklers to be tested must consist of at
least 4 sprinklers or 1 percent of the number of sprinklers per
sample, whichever is greater. If one sprinkler in the representative
sample fails to meet the test requirements, all sprinklers
represented in the representative sample shall be replaced.
277
Machine Translated by Google
7.4.6.7.2 The pressure gauge shall be replaced or tested every five years in
comparison with a calibrated pressure gauge.
7.4.6.8.2 Sprinklers for painting room protection shall be protected against paint
spray residue, using plastic bags maximum thickness of 0.076 mm or
paper bags. The bag should be replaced when it becomes soiled with
residue.
278
Machine Translated by Google
7.4.6.8.3 Automatic sprinklers and nozzles used for the protection of commercial
cookware and their ventilation systems, shall be replaced annually. If
the annual inspection does not reveal any accumulation of grease or
other matter on the sprinklers and automatic nozzles, they do not need to be repl
7.4.6.8.4 The dry pipe type system shall be maintained as follows:
(1) The dry pipe type system shall be kept dry at all times.
(2) Air dryers and air compressors used in conjunction with dry pipe
type systems must be maintained in accordance with the
manufacturer's instructions.
7.4.6.8.5 The operating stem (stem) of the control valve type OS&Y (outside
screw & yoke) shall be lubricated/greased annually, and then fully
closed and reopened to test operation and distribute the lubricant.
7.4.6.8.6 If the fire extinguisher (siamese) cap is not in place, the inside of the
fire extinguisher shall be inspected for obstruction or blockage.
279
Machine Translated by Google
0 280
Machine Translated by Google
7.1. GENERAL.
7.1.1. The provisions in this chapter apply to existing buildings
as well as for new buildings.
7.1.2. Objective.
The goal to be achieved in this chapter is to prevent fires from occurring.
Many conditions exist in buildings or workspaces that can cause fires. In
fact a building can escape these conditions for long periods of time
without starting a fire. However, in the future these unsafe conditions
could cause fires or be a factor causing fires to spread out of control.
7.1.3. Function.
If these conditions can be identified and eliminated, the potential for fires
in buildings or workspaces will be substantially reduced. Fire prevention
can be carried out through a preventive maintenance program consisting
of inspection procedures and good housekeeping practices .
240
Machine Translated by Google
- CHAPTER VIII GENERAL PROVISIONS FOR MANAGEMENT OF FIRE PROTECTION SYSTEMS IN BUILDINGS -
CHAPTER VII I
8.1. GENERAL.
8.1.1. Every new or existing building or structure must be constructed, regulated,
installed, maintained and operated in accordance with these technical
requirements, such as providing an appropriate level of life safety,
property protection and public welfare from real and potential risks.
caused by fire, explosion and other risky conditions.
8.2.3. The owner, manager or occupant of the building, if the building is deemed
unsafe by OBS, must repair it by carrying out rehabilitation, demolition or
other corrective actions approved by OBS.
270
Machine Translated by Google
- CHAPTER VIII GENERAL PROVISIONS FOR MANAGEMENT OF FIRE PROTECTION SYSTEMS IN BUILDINGS -
8.2.4. The owner, manager or occupant of the building, must keep records of the maintenance,
inspection and testing of: fire protection systems, fire alarm systems, smoke control
systems, emergency evacuation and relocation drills, emergency planning, emergency
resources, lifts and other equipment as required by OBS .
8.2.5. All required records must be kept, guarded until the service life of the building has ended, as
required by law, or as required by these technical requirements.
8.3. RESIDENCE.
8.3.2. Buildings that already exist and are occupied before the enactment of these
technical requirements may continue to be used as long as the following conditions are me
(1) The occupancy classification remains the same.
(2) There are no conditions that are considered dangerous to life or property
object.
8.3.3. Buildings or parts of buildings, if the required means of egress are disturbed or the required
fire protection system is not functioning or during construction, repair or alteration, may
not be occupied without OBS approval, except for periodic maintenance or repairs,
8.3.4.1. In any building or structure, where a physical change is required or not required, a change
from one use or occupancy classification to another, must comply with the requirements
regarding building rehabilitation.
8.3.4.2. The occupancy classification and its sub-classification must be in accordance with
the building classification.
8.4.1. Any tools, equipment, systems, conditions, arrangements, levels of protection, fire-resistant
construction, or any other provisions required to comply with these technical requirements,
shall be continuously maintained in accordance with the application of these technical
requirements or as indicated by OBS.
271
Machine Translated by Google
- CHAPTER VIII GENERAL PROVISIONS FOR MANAGEMENT OF FIRE PROTECTION SYSTEMS IN BUILDINGS -
8.4.2. Existing provisions for life safety do not need to be eliminated or reduced if
these provisions meet the requirements for new construction.
8.4.3. Provisions for life safety that already exist and relate to the public, if not
required by these technical requirements, can be continued or deleted.
8.5.2. In crowded conditions when ordered by OBS to leave the building, no one
must fall.
Exercises for egress and for emergency relocation, which are required for
all occupancy classifications of buildings, must be carried out with
sufficient frequency to familiarize occupants with the drill procedures and
drills that are routine.
The exercise includes appropriate procedures to ensure that everyone
participates in the exercise.
272
Machine Translated by Google
- CHAPTER VIII GENERAL PROVISIONS FOR MANAGEMENT OF FIRE PROTECTION SYSTEMS IN BUILDINGS -
8.6.3. Competence.
Responsibility for planning and carrying out training is assigned only to
those who are competent to train.
8.6.4. Evacuation Order.
When conducting drills, attention should be paid to evacuation orders
rather than movement speed.
8.6.5. Condition Simulation.
Drills are conducted at specified or unspecified times and under various
conditions to simulate unusual conditions that could occur in a real
emergency.
8.6.6. Relocation Area.
The trainee must be relocated as previously determined and remain at
that location until a redial call or a release signal is given. .
8.6.7. Written records of each exercise required by this item are preferable
details such as, date, time, participants, location and results of the exercise.
8.7.1.3. This requirement is not intended to prohibit the owner, manager, or other
person in the building or place from making efforts to extinguish the fire
before the fire service arrives.
8.7.1.4. Anyone must not make, issue, place, or administer any regulations or
orders, written or oral, requiring people to take actions that may slow
down firefighting operations before reporting a fire to the fire department.
273
Machine Translated by Google
- CHAPTER VIII GENERAL PROVISIONS FOR MANAGEMENT OF FIRE PROTECTION SYSTEMS IN BUILDINGS -
8.7.2. Notice to release hazardous materials, must comply with the provisions on
hazardous materials.
8.7.3. No person should intentionally or maliciously set off a fire alarm when there is
in fact no fire.
8.7.4. It is a violation of these technical requirements for any person who intentionally
fabricates a lie, cheats, misleads, or fails to make a report or statement, or
intentionally misrepresents any facts with the intention of misleading officers
or disrupting the operations of the fire department.
8.8.1. No person shall alter any light or fixed fire extinguishing system or fire warning
device or system so that it is inoperative or inaccessible.
8.8.2. No one is allowed to change a system or tool so that it does not work during
an emergency unless directly by field operations officers.
8.8.3. No person, except those authorized by OBS, removes, opens, destroys, or
damages in a way to open gates, doors or barriers, chains, closures,
direction signs, labels, or seals that have been required by OBS according
to technical requirements This.
274
Machine Translated by Google
- CHAPTER VIII GENERAL PROVISIONS FOR MANAGEMENT OF FIRE PROTECTION SYSTEMS IN BUILDINGS -
8.9.2.2. Maintenance.
Emergency planning should be reviewed and updated annually.
Revised plans should be submitted if changes are made in the occupancy
or physical arrangement of the building or fire protection system or
provisions thereof.
8.9.3. The owner must provide floor plans for the fire department for OBS and fire
department approval.
8.10. SMOKE.
8.10.1. If smoking is considered a threat to fire hazard, OBS has the right to order
the owner to write and put a "NO SMOKING" sign in a conspicuous place,
the location where smoking is prohibited.
8.11. blackout.
OBS requires that every fire must be extinguished immediately if the fire
shows a dangerous condition.
275
Machine Translated by Google
- CHAPTER VIII GENERAL PROVISIONS FOR MANAGEMENT OF FIRE PROTECTION SYSTEMS IN BUILDINGS -
8.12.2.3. Such a warning sign shall be placed so that it can be readily seen from
the outside of the building.
8.12.3. Stair Path Marking.
8.12.3.1. One of the following two conditions for protected stairs must meet
8.12.3.1.1 to 8.12.3.1.8 : (1) New protected
stairs serving three floors or more.
(2) Existing sheltered stairs serving five or more floors.
8.12.3.1.1 Stairs shall be provided with special identification markings in protected
spaces at each floor landing.
8.12.3.1.2 The marking shall indicate the floor level.
8.12.3.1.3 The marking shall indicate the upper and lower ends of the protected
stairwell.
8.12.3.1.4 The marking shall show identification of the protected stairwell.
8.12.3.1.5 The markings shall show the floor level from, and the direction of the exit
release.
8.12.3.1.6 The markings shall in protected spaces be placed approximately 1.5 m
above the floor landing in a position which is easily visible when the
door is in the open or closed position.
8.12.3.1.7 The marking shall comply with these technical requirements.
276
Machine Translated by Google
- CHAPTER VIII GENERAL PROVISIONS FOR MANAGEMENT OF FIRE PROTECTION SYSTEMS IN BUILDINGS -
8.12.3.1.8 The floor level designation must also meet the standards and requirements
other applicable techniques.
8.12.3.2. Where protected stairs require passage in an upward direction to reach the
exit discharge level, special directional signs indicating the direction to
the exit discharge level shall be provided on each floor level landing from
the direction up the required passage, unless otherwise specified in
8.12.3.2. .1 and 8.12.3.2.2.
8.12.3.7. The floor level number must be placed in the middle of the marking with a
minimum figure height of 12.5 cm.
8.12.3.7.1 Mezzanine levels must have the letter "M" or other appropriate identification
letter in front of the floor number,
8.12.3.7.2 Basement levels must have the letter "B" or other appropriate identification
letters in front of the floor level numbers.
8.12.3.8. The bottom and top endings of stairways must be placed at the bottom of the
2.5 cm high directional signs in bold capital letters.
277
Machine Translated by Google
- CHAPTER VIII GENERAL PROVISIONS FOR MANAGEMENT OF FIRE PROTECTION SYSTEMS IN BUILDINGS -
The requirements of item 8.13.1 do not apply to buildings that are used
on a seasonal basis, or buildings that are temporarily vacated for tenant
changes or renovations.
8.13.2. All fire protection systems must be maintained in a ready condition
Use in vacant buildings.
8.13.2.1*With the approval of OBS, fire protection and fire alarm systems in vacant
buildings may be rendered inoperative.
0 278
Machine Translated by Google
- CHAPTER VIII GENERAL PROVISIONS FOR MANAGEMENT OF FIRE PROTECTION SYSTEMS IN BUILDINGS -
279
Machine Translated by Google
PIG X
SUPERVISION OF LIA N
9.1. GENERAL.
9.2.1. At this stage, inspections are carried out by authorized technical agencies
and planning consultants in order to comply with applicable standards and
regulations, through supervision and control of planning drawings.
9.2.3. The aspects examined in accordance with Article 9.2.1, in particular the
planning drawings which include: site plans, all passive and active fire
protection systems and facilities for safe exits.
9.2.4. The results of the examination at this stage will determine what is obtained
recommendations in order to obtain a building construction permit.
9.3.1. At this stage, inspections are carried out by authorized technical agencies
and supervisory consultants in the framework of supervision and control so
that the technical specifications and planning drawings of all fire protection
system installations, both passive and active as well as all facilities leading
to the exit, are in accordance with the results of the plan.
9.3.2. At this stage material inspection is carried out, inspection of the operation of
the entire fire installation system, approval tests, functional feasibility tests
and periodic reports.
280
Machine Translated by Google
281
Machine Translated by Google
9.4.1. Supervision and control at this stage are carried out apart from the building
owner as well as authorized technical agencies and consultants in the
field of building maintenance and the environment, so that the building is
always functional.
9.4.2. The aspects examined apart from checking all installations and construction,
as well as all supports that support the operation of the system.
9.4.3. Inspections are carried out periodically, including the entire operation test
existing equipment.
9.4.4. Required periodically to carry out "control exercises
fire"
9.4.5. Building managers/users are required to comply with all technical provisions
for urban fire management, particularly with regard to buildings and yards
in accordance with those provisions.
282
Machine Translated by Google
9.6.2. Test implementation, observation and assessment of test results are carried out
in accordance with applicable provisions and test method standards.
9.6.3. In the event that the test implementation cannot be carried out in Indonesia
due to standard procedures, human resources, and the condition of the
existing test equipment, the evaluation is carried out by referring to the
results of tests that have been carried out by accredited test institutions
both domestically and abroad.
283
Machine Translated by Google
- CHAPTER X CLOSING -
CHAPTER X
CLOSING
284
Machine Translated by Google
Machine Translated by Google
coach
Director Ir.
Agoes Widjanarko, MIP Ir. Budi Secretary General of the Ministry of Public Works
Yuwono P., Dipl., SE Director General of Cipta Karya
executor
Source person
Ir. Ismanto, MSc SAMPU for Socio-Cultural Affairs & Community Participation
Prof. Dr. Ir. Suprapto, MSc, FPE Ir, Settlement Research and Development Center
Daniel Mangindaan Association of Indonesian Electrical Experts Ir. Soekartono, IPM Association
of Indonesian Engineers Dr. Ir. Hari Nugraha Nurdjaman, MT HAPPI Ir. Soufyan
Sidik Umar, SH, MH Karya Legal Section of the Directorate General of Cipta Karya
And there are still other sources that cannot be mentioned one by one.
Machine Translated by Google
Working Group
Ir. Ismono Yahmo, MA
Ir. Adjar Prajudi, MCM, MSc.
Ir. RG Eko Djuli Sasongko, MM
Ir. Utuy History of Solomon,
MM Ir. Sumirat,
MM Ir. Sentot Harsono,
MT Ir.
Kartoko Budi Prastowo,
ST, MT Any
Virgyani, ST
Rogydesa, ST Wahyu
Imam Santoso, ST Mulyono, S.Sos
Final Alignment