Professional Documents
Culture Documents
3-14
Users’ guide____Function illutration
OVER_LIMIT Force_Limit
ForceExc = 0 ForceExc = 1 @ELSE
@ELSE
OverExc = 1 OverExc = 0 IIT = IIT + IL*IL
CoollingTime -= 1 ForceCounter += 1
ILLimit = OverExcLimit Limit = ForceExcLimit
IlLimit -= 0.1
@ELSE
ILLimit -= 0.1
3-16
Users’ guide____Function illutration
Boe Deviation of the stator current limit curve Boe Regulator software setting
is the actual reactive power value, the difference between Quelim and Q integrates,
and then the output Qoegd overlaps to the voltage set value Ugd, the mode being the
decreasing excitation mode, limiting the amplification of reactive power.
The effective condition for stator current limit is: the circuit breaker at the exit of
the generator is closed and the present reactive power is more than 0. If the
conditions are not met, the stator current limit is invalid.
When the stator current limit is at work, the regulator sends “set A (B) stator current
limit ” alarm signal, locking the increasig of excitation.
3-18
Users’ guide____Function illutration
Freq
45.0
3. Fault detecting
3.1 Synchronization fault
The condictions for fault judgment:
(Utb+15%<Ug)&&R632&&(Utb>20%)
Ug Generator voltage
Utb Synchronization voltage
R632 >40%generator voltage
When the 3 following condictions are met, synchronization fault occurs:
Synchronization voltage is 15% lower than the generator voltage
Generator voltage >40%
Synchronization voltage >20%
If there are 3 consecutive fixed timing regulatory cycles of the above conditions,
3-19
Users’ guide____Function illutration
watchdog signal is sent out, so that the monitoring unit can detect fault in the
regulator and send out the channel shift command.
3.4 PT fault
The condictions for fault judgment:
Average 0.83Ug
Ug Generator voltage
Ua Generator A-phase voltage
Ub Generator B-phase voltage
Uc Generator C-phase voltage
Utb Synchronization voltage
IL Excitation current
3-20
Users’ guide____Function illutration
4. Fault prevention
4.1 Detection fault tolerance
Analogue quantity fault-tolerance and switch quantity fault-tolerance are included,
such as detection of PT disconnection, anti-conglutination of excitation increasing &
decreasing contacts, oil switch signal fault-tolerance etc.
5. Other functions
5.1 Signals R631
R631 is the rated value signal of the generator voltage >10%. However, in order to
lock the errors in abnormal condictions, the current judgment conditions are added.
3-21
Users’ guide____Function illutration
5.4 Reset
When the startup command disappears, reset operation occurs, including:
a. Automatic switch to automatic mode if PT fault causes the swich to
constant excitation current mode
b. Voltage setting value preset
c. Current set value preset as 0
3-22
Users’ guide____Function illutration
Anti-glutinous function:
Both the excitation increasing and decreasing has a 4-second anti-glutinous
function. If a command lasts for more than 4 seconds, the operation is not valid until
the operation is restored.
If both the excitation increasing and decreasing are at normal state, and two are
operating at the same time, the operation is invalid.
3-24
Users’ guide____Function illutration
3-25
Users’ guide____Function illutration
3-26
Users’ guide____Function illutration
3-27
Users’ guide____Function illutration
3-28
Users’ guide____Function illutration
3-29
Users’ guide____Human-machine interface
1. Regulator HMI...................................................................... 3
1.1 Brief introduction ............................................................. 3
1.2.Systemetic setup for the regulator HML .......................... 3
1.2.1 Communication setup .................................................. 3
4-2
Users’ guide____Human-machine Interface
1. Regulator HMI
1.1 Brief introduction
This system employs Profcae touching screen, which has the full screen touching
function, as the human-machine inteface. Its advantage is its funcction sufficiency,
which not only is used for operation, but also for testing and maintanece, with richful
frames, sound visual effect, easy operation and status display for data quantity,
analogue quantity, communicative status and system operation. The status of
equipment operation is shown clearly, so that the operators can master relative
operation in just several minutes.
4-3
Users’ guide____Human-machine Interface
4-4
Users’ guide____Human-machine Interface
Analogue display:
A) Generator voltage Ug, excitation current, generator active power P, generator
reactive power Q
The above analogue quantity is displayed in the form of percentage and its true value,
in which, the generator voltage Ug’s reference value is the rated generator voltage (V);
the excitation current’s reference value is the rated excitation current (A); the
reference value of generator active power P and generator reactive power Q is the
rated apparent capacity (KVA).
B) Control signal UKA in channel A, control signal UKB in channel B, control
signal UKC in channel C
Switch quantity display:
This shows partial information of the switch quantity in the excitation system.
A) Automatic/manual operation mode
B) Invertion
C) Interconnection
D) Limit
4-5
Users’ guide____Human-machine Interface
E) Force-excitation
Each switch quantity has an indicator light of status. When the lights are on, the
corresponding function is on. When the indicator “ automatic” is on, this means the
regulator is in the mode of automatic operation, or it is in the manual mode. When
any of the following is working, the “limit” light is on: “the excitation current limiter”,
“the under-excitation limiter”, “ V/F limit”, “the stator current limiter”.
Click the switch quantity display area, and enter the frame of switch quantity.
Fault alarm
When there’s any fault in the system, there’s a red flashing indicator light. Click the
fault report area, and enter the current fault display frame.
The current fault alarm is listed on a tavle as shown above, according to the
chronological order. The thing happen first is put in the front, and the ensuing put in
the end. Operators can search the old faults in the frame of old fault recording after
the fault is reset.
4-6
Users’ guide____Human-machine Interface
There are a lot of manus for frame selection, with each manu sorresponds to
different functional frames. Click the “key frame “ botton and you can return to the
key frame.
4-7
Users’ guide____Human-machine Interface
4-8
Users’ guide____Human-machine Interface
4-9
Users’ guide____Human-machine Interface
Attention please: this frame just shows the internal communication (the regulator,
recitifier and the de-excitator.)
4-10
Users’ guide____Human-machine Interface
On the left of the frame is the display of analogue quantity and the current
percentage, and the analogue quantity real-time curve on the right. The different
quantity is shown in different colors. The data on the left shown in color is the
corresponding amount to the real-time curve on the right. At the bottom of the frame,
one can also choose the data from channel A or channel B.
4-11
Users’ guide____Human-machine Interface
If there is the red flashing, that’s the current fault, while if there’s the static blue
light, that’s the historical fault.
Based on the FIFO priciple, the excitation system detailedly records the fault
content, the occurring time, and the resolved time, without being affected by the
power-fail.
4-12
Users’ guide____Human-machine Interface
4-13
Users’ guide____Human-machine Interface
There are 30 degrees for deviation regulaion rate. When you click the data block, a
data-input block appears, and you can set the regulation rate by selecting data on the
4-14
Users’ guide____Human-machine Interface
block. Click “confirm” botton, and see if the feedback value concurs with the set
value.
When powered on, the system defaulted the manual operation mode.
4-15
Users’ guide____Human-machine Interface
(2)After input of the code (default code 9000), press the key “enter”.
If the code is correct, you will enter the PSS operation frame. Click the PSS entry/PSS
withdrawal botton, the PSS will enter or withdraw.
If the code is incorrect, a warning message for the code error will appear, when the
user can only click the “OK” botton, to return to the parent manu to re-enter the code.
4-16
Users’ guide____Human-machine Interface
4-17
Users’ guide____Human-machine Interface
Users should select and enter correctly in this frame, or other errors may appear.
Eg.
If the rated capacity, rated terminal voltage and the rated excitation current is
wrongly entered, consequence is that the actual value of current active power, reactive
power, terminal voltage and excitation voltage will be incorrectly shown too.
(Percentage not affected).
The incorrect input of rated excitation current would affect the result of intelligent
current balancing.
The incorrect setup for quantity of power controller would lead to incorrectness of
power status shown on the HMI.
The incorrectness in entering of quantity for temperature-measures would affect the
temperature shown on the HIM.
Quantity for single cubicle fans , if wrongly entered, would affect the fan operation
4-18
Users’ guide____Human-machine Interface
on HIM.
Explanation 1: none of the setup is affected by power-fail.
Explanation2: none of the above setup affects the nomal operation of the system.
Explanation3: if the system is reset, registers are cleared, and the variables should
be reset too.
4-19
Users’ guide____Human-machine Interface
This function is used to test if the indicator light circuit on the intelligent IO board
is in normal state.
Click the botton of “operation for all relays”. If the functional indicator lights are
on, all the indicator lights on the intelligent IO board are on. Click it again. If the
functional indicator lights are off, the lights on the intelligent IO board are normal.
Click the botton of “ reset for all relays”. If the functional indicator lights are on, all
the indicator lights on the intelligent IO board are off. Click it again. If the functional
indicator lights are off, the lights on the intelligent IO board are normal.
4-20
Users’ guide____Human-machine Interface
4-21
Users’ guide____Human-machine Interface
4-22
Users’ guide____Human-machine Interface
Select “sysem” on the key frame, turn on the switch 1 on the power controller
intelligent board, and you will enter the system frame. On this frame, the following
testing items are to be chosen from.
4-23
Users’ guide____Human-machine Interface
4-24
Users’ guide____Human-machine Interface
Way of judgment 1: each Hall part has an “arrow” on the head. If the arrow
direction is the same as the actual current direction, this means “ positive “ installation,
otherwise it is “negative” installation.
Way of judgment 2: face the outlet terminal of Hall parts, if the actual current runs
in from behind of the outlet terminal and out from the outlet terminal, this is the
“positive “ installation.
4-25
Users’ guide____Human-machine Interface
4-26
Users’ guide____Human-machine Interface
You can set the alarm value when the wind temperature is too high (default value
50 degrees) and the return value (default value 45 degrees).
Explanation 1: if set value=reurn value=0, there’s no alarm signal.
Explaaiton 2: if set value<return value, the system employs the last set value and
return value as the default value.
4-27
Users’ guide____Human-machine Interface
On this frame, you can set the original value of current judgement (default=200A),
bidge arm current set value (default=5A) and the inbalanced current coefficient
(default=0).
Explanation 1: when the initiative condition is set as 0, there is no judgement on
bridge arm 0 flow and current inbalance.
Explanaton 2: when the current inbalance coefficient is 0,there’s no judgement of
current inbalance.
Explanation 3: when the contrller current >the initially set value, Ug>40%, and
bridge arm current <the set value of bridge arn 0 flow, there would be corresponding
signals for brige arm 0 flow.
Attention 4: when the contrller current >the initially set value, Ug>40%, and the
controller current/(3*maximum bridge arm value)<inbalanced current coefficient,
there would be judgement of current inbalance.
4-28
Users’ guide____Human-machine Interface
Possible faults testable are: fan A/B power fault, fast fuse, resistance-capacitance
fault, over-tempreture of wind, flow block in the 6 bidge arms, current inbalance and
pulse exit of this controller.
3. De-exciter HMI
3.1 Brief introduction
In de-exciter, a set of intelligent control system is installed, which comprises same
major hardware with that of power controller, such as intelligent detecting unit, LCD
display and corresponding input etc. Due to introduction of intelligent control system
4-29
Users’ guide____Human-machine Interface
4-30
Users’ guide____Human-machine Interface
F5 is to show flashing of fault. If there were anything wrong with the de-excitater,
this botton would flash, and at the same time click it to enter the fault display, so as to
check the problems. If everything is all right in thede-excitater, the botton would not
flash and the click of it leads to no operation.
Select “sysem” on the key frame, turn on the switch 1 on the de-excitater intelligent
board, and you will enter the system frame. On this frame, the following testing
items are to be chosen from.
4-31
Users’ guide____Human-machine Interface
4-32
Users’ guide____Human-machine Interface
4-33
Users’ guide____Human-machine Interface
The volt gauge has a range of 4 spans: 200V, 300V, 500V, and 750V. By the
keys of +/-, you can make the choice of the above, which would be shown on the
screen, too.
On this frame, you can set the alarm value (default value=0) and the returned value
(default value=0) when the temperature is too high for the rotor.
Explanation1: when the set value=returned value=0, the LCD just shows the
4-34