Standard Operating Procedure (Sop) - Chillers 36 TR Ac Scroll - 3 CKT Switch "ON" Chiller
Standard Operating Procedure (Sop) - Chillers 36 TR Ac Scroll - 3 CKT Switch "ON" Chiller
Check the power supply in chiller panel, check all three indicator lamps ( R,Y,B) glow brightly
Check the supply voltage in volt meter . It should be 415 Volts AC +/- 10%
Switch ON the required No. of Primary/Condenser Pump(s) and cooling tower fan(s)
Switch on the chiller in auto mode by selecting the auto on display unit
Check the inlet & outlet water temperature & all electrical parameters
Check & note all the parameters in log sheet for future analysis
= END OF DOC =