You are on page 1of 34

DCAP-5051S

Back-up Protection Unit for Transformer


(V2.2.1.6-20160101)

湖 南 紫 光 测 控 有 限 公 司
HUNAN UNISPLENDOUR M&C CO .,LTD.
DCAP-5051S Back-up Protection Unit for Transformer

CONTENTS
1. Scope .................................................................................................................................................. 3
2. Main Functions ................................................................................................................................. 3
3. Inputs and Outputs .......................................................................................................................... 3
3.1 AC Voltage Inputs ....................................................................................................................... 3
3.2 AC Current Inputs ....................................................................................................................... 3
3.3 Auxiliary Power Supply and Control Circuit Voltage ................................................................. 3
3.4 Binary Input Signals .................................................................................................................... 4
3.5 Binary Output Signals.................................................................................................................. 4
3.6 DC Analog Input Circuit ............................................................................................................. 4
3.7 CB Control Circuit....................................................................................................................... 4
3.8 Communication Interfaces ........................................................................................................... 4
4. Human-Machine Interface .............................................................................................................. 4
5. Technical Data .................................................................................................................................. 5
5.1 Rating Data .................................................................................................................................. 5
5.2 Burden ......................................................................................................................................... 5
5.3 Thermal Withstand Capability ..................................................................................................... 5
5.4 Accuracy ...................................................................................................................................... 5
5.5 Environmental Conditions ........................................................................................................... 5
5.6 Insulation Property....................................................................................................................... 5
5.7 Output Contact Capacity.............................................................................................................. 5
5.8 Electromagnetic Compatibility (EMC) Tests .............................................................................. 5
5.9 Mechanical Tests ......................................................................................................................... 6
6. Protection Functions ........................................................................................................................ 6
6.1 Over-current Protection ............................................................................................................... 6
6.2 Inverse Time Over-current Protection ......................................................................................... 7
6.3 Zero-Sequence Over-voltage Protection ...................................................................................... 7
6.4 Zero-Sequence Over-current Protection ...................................................................................... 7
6.5 Under-voltage Protection ............................................................................................................. 8
6.6 Over-voltage Protection ............................................................................................................... 8
6.7 Gap Zero-Sequence Over-current Protection .............................................................................. 8
6.8 Overload Alarm ........................................................................................................................... 8
6.9 Breaker Fault Protection .............................................................................................................. 8
6.10 Impedance Protection ................................................................................................................ 9
6.11 Cooling Starting ....................................................................................................................... 10
6.12 TV Fault Alarm........................................................................................................................ 11
6.13 TA Fault Alarm........................................................................................................................ 11
6.14 Control Circuit Fault Alarm ..................................................................................................... 11
6.15 Four Programmable Logic Control Outputs ............................................................................ 11
6.16 Checking Synchronization and Checking No-voltage ............................................................. 12
6.17 Fault Recording ....................................................................................................................... 13
7. Normal Display ............................................................................................................................... 13
8. Menu Functions .............................................................................................................................. 14
8.1 Prot. values ................................................................................................................................ 14
8.2 Check synch. .............................................................................................................................. 15
8.3 Harmonics .................................................................................................................................. 16
8.4 Parameters ................................................................................................................................. 16
8.5 Check group............................................................................................................................... 16
8.6 Prot. sets..................................................................................................................................... 16
8.7 Prot. off/on ................................................................................................................................. 16
8.8 Trip table.................................................................................................................................... 16
8.9 DI status ..................................................................................................................................... 16
8.10 Fault record .............................................................................................................................. 17

1
DCAP-5051S Back-up Protection Unit for Transformer

8.11 Set para. ................................................................................................................................... 17


8.12 Set group .................................................................................................................................. 18
8.13 Set prot. .................................................................................................................................... 18
8.14 Set off /on ................................................................................................................................ 20
8.15 Set trip...................................................................................................................................... 21
8.16 AC adjust ................................................................................................................................. 22
8.17 DC adjust ................................................................................................................................. 22
8.18 Set PLC .................................................................................................................................... 22
8.19 Relay test ................................................................................................................................. 23
8.20 Initialize ................................................................................................................................... 23
8.21 Com. status .............................................................................................................................. 25
8.22 Fault test................................................................................................................................... 26
8.23 Time adjust .............................................................................................................................. 26
8.24 Coefficient ............................................................................................................................... 26
8.25 Version..................................................................................................................................... 26
9. Design Drawing .............................................................................................................................. 27
9.1 Screw Fixing Installation ........................................................................................................... 27
9.2 Bracket Fixing Installation......................................................................................................... 28
9.3 Connection Diagram .................................................................................................................. 31
9.4 Electrical Terminals ................................................................................................................... 32

2
DCAP-5051S Back-up Protection Unit for Transformer

1. Scope
DCAP-5051S protection unit, which is based on 32-bit DSP (Digital Signal Processor) and high-speed
Ethernet communication technology, is mainly used in, but not limited to three-winding transformer
which requires the complex voltage of all sides.
The unit contains 4 groups protection setting value in order to adapt different operation mode.

2. Main Functions
(1) Protective Functions
 Three-stage over-current protection (it is subject to the criterions of direction and complex
voltage)
 Inverse time over-current protection
 Zero-sequence over-voltage protection
 Zero-sequence over-current protection
 Under-voltage protection
 Over-voltage protection
 Gap zero-sequence over-current protection
 Overload alarm
 Cooling starting
 Breaker failure protection(CBF)
 Impedance protection
 TV fault alarm
 TA fault alarm
 Control circuit fault alarm
 Checking synchronization and checking no-voltage
 Four programmable logic control outputs (PLC1,PLC2,PLC3,PLC4)
(2) Power off alarm for the unit
(3) Faults wave recording (the largest recording duration is 20s)
(4) Time-adjust: software setting or GPS impulse setting
(5) The unit can save the latest 40 alarm records even after an auxiliary power supply fault.
(6) The unit has one RS-485 communication interface and one Ethernet communication interface
that are convenient to accomplish dual-network communication system.

3. Inputs and Outputs


3.1 AC Voltage Inputs
It contains 7 TVs(voltage transformer) which accept 7 AC voltages between 0V and 100V or between
0V and 400V, AC voltage definitions are marked on the unit.
 The first side voltage: Uab1, Ubc1, 3U0
 The second side voltage: Uab2, Ubc2
 The third side voltage: Uab3, Ubc3
3.2 AC Current Inputs
It contains 7 TAs(current transformer) which accept 7 AC currents with 5A or 1A selective ratings. AC
current definitions are marked on the unit.
 Measuring currents:MIa,MIc
 Protective currents on the first side :PIa,PIb,PIc,3I0
 Gap zero-sequence current: GI0
3.3 Auxiliary Power Supply and Control Circuit Voltage
The rated DC voltage of auxiliary power supply and control circuit voltage is DC220V or DC110V
marked on the unit, and the connecting terminals of auxiliary power supply and control circuit voltage
are P+,P- and L+,L-, respectively.

3
DCAP-5051S Back-up Protection Unit for Transformer

3.4 Binary Input Signals


It has 12 binary input signals. In a particular application, the user may reposition them, but the following
rules must be followed:
① SI1 should connect with the location signal of breaker.
② SI9 should connect the starting signal of circuit breaker failure protection.
③ SI2 to SI8 and SP1,SP2 are all general digital signal inputs.
④ SP1 and SP2 also used as input terminals of impulse signal (the order should be marked),
which could connect with active power impulse and reactive power impulse.
⑤ SGP, whose impulse signal is DC24V input, is GPS time setting impulse input to adjust time.
⑥ Signals from SI1 to SI9,SP1,SP2 are recognized as DC220V/DC110V input, SP1 and SP2
used as impulse input terminals are DC24V input.
3.5 Binary Output Signals
It contains 8 (TS1-TS8) output relays. Each of them can be repositioned as a certain protective function
(or the combination of several protective functions) tripping signal by setting up tripping logic table. We
can reposition the 8 output signals freely in tripping logic table (Note: 1 means On and 0 means Off).
The 9th lamp stands for normal working.
3.6 DC Analog Input Circuit
One DC analog input terminal in unit, whose input is 0-5V or 4-20mA standard DC signal, is used to
measure temperature or other DC analog signal.
3.7 CB Control Circuit
The circuit breaker (CB) control circuit has anti-tripping and tripping with holding functions.
3.8 Communication Interfaces
It has high-speed Ethernet and RS-485(or optical fiber)communication interfaces, various signals and
external remote signals could be uploaded to supervisory computer with complex automatic system by
communication network.

4. Human-Machine Interface
The front panel of the unit is made up of a 128X64 liquid crystal screen, 4 keys and the output
indication lamps. Most operations of the unit could be accomplished by operating the keys, and the
operating functions are defined as follows:
 Normal display:
It can enter into the main menu by pressing the key <SEL>.
 Key definitions when function selection:
<SEL> Return
<BIT> Cursor-up
<INC> Cursor-down
<ENT> Select
 Key definitions when setting values:
<SEL> Abandon
<BIT> Data bit select
<INC> Data increase
<ENT> Confirm
 Key definitions when setting on/off:
<SEL> Confirm/return
<BIT> Cursor-up
<INC> Cursor-down
<ENT> On/Off-select

4
DCAP-5051S Back-up Protection Unit for Transformer

5. Technical Data
5.1 Rating Data
 AC input voltage: 100V/400V
 AC input current: 5A/1A
 Auxiliary power supply and control circuit voltage: DC220V/110V
 AC Frequency: 50Hz or 60Hz
5.2 Burden
 Burden of each AC input quantity at rated voltage ≤0.5VA
 Burden of AC input quantity at rated current ≤0.5VA
 DC burden of auxiliary power supply under quiescent/operating condition ≤10W/ 15W
5.3 Thermal Withstand Capability
 Thermal withstand capability continuously: 2In, 1.5Un
 Thermal withstand capability for 1s: 20In
 Dynamic current withstand, half-wave value: 50In
5.4 Accuracy
Protecting accuracy:
 Operating values accuracy: 1%
 Operating time accuracy: 10ms
 Frequency deviation: 0.02Hz
Measuring accuracy:
 Current accuracy: 0.2%
 Voltage accuracy: 0.2%
 Active power and reactive power: 0.5%
 kWh and kVarh: 1%
5.5 Environmental Conditions
 Operating temperature range: -20℃~50℃,and daily mean temperature is not more than 35℃.
 Operating Altitude: below 4km above sea level.
 Monthly mean highest relative humidity in the moistest month is 90%, accordingly, monthly
mean of daily minimum temperature is 25ºC, the highest temperature is 40ºC, and the average
maximum relative humidity is not greater than 50% in this month.
5.6 Insulation Property
 The insulation resistance of each circuit to earth as well as between AC circuit and DC circuit
are not less than 100 MΩ.
 Each circuit to earth as well as between AC circuit and DC circuit should endure lasting 1 min
testing under alternating current 50Hz, 2kV (virtual value)(it should endure lasting 1 min
testing under alternating current 50Hz, 500V (virtual value )between the communication
terminals and earth ) and has no insulation breakdown or arcing phenomenon.
 Each circuit to earth as well as between AC circuit and DC circuit could endure the standard
lightning wave of which amplitude is 5kV (peak value).
5.7 Output Contact Capacity
 Continuous carry: 5A, 250V ac/dc.
5.8 Electromagnetic Compatibility (EMC) Tests
 It can endure the interference of group pulse which is made up of decaying oscillatory waves
whose frequency is 1MHz and 100kHz described in GB/T 14598.13(the common mode voltage
is 2.5kV and differential mode voltage is 1kV about the first half-wave voltage amplitude ).
 It can endure static discharge disturbance of which severity scale is class Ⅳ described in GB/T

5
DCAP-5051S Back-up Protection Unit for Transformer

14598.14.
 It can endure radiated electromagnetic disturbance of which severity scale is class Ⅳ described
in GB/T 14598.9.
 It can endure fast transient disturbance of which severity scale is Ⅳ described in GB/T
14598.10.
5.9 Mechanical Tests
 Operation conditions: It can tolerate the testing vibratory response and shock response of which
severity scale is class I.
 Transportation conditions: It can tolerate the testing vibration durability, shock durability and
collision of which severity scale is class I.

6. Protection Functions
6.1 Over-current Protection
The unit contains three-stage over-current protection which is subject to criterions of direction and
complex voltage. When any phase current is greater than its setting value, the relay will operate after
delay time.
Direction criterion:
U  1
The direction criterion for over-current protection is:  90  Arg  90
PI e  j 45


Where:

PI =protective current vector

U  1 =the first side line voltage vector


 = It could be assigned for a, b or c
 =bc,ca or ab
Complex voltage criterion:
The complex voltage criterion of over-current protection is :
U1  U1set or U 2  U 2 set
Where:
U1= positive-sequence voltage
U1set= the setting value of positive-sequence under voltage in complex voltage criterion
U2= negative-sequence voltage
U2set=the setting value of negative-sequence voltage in complex voltage criterion
The over-current protection block diagram is shown as below.

6
DCAP-5051S Back-up Protection Unit for Transformer

I>protection

CV criterion enable

TV1 fault Alarm enable


&
I>-->
≥1 Tripping and
& t
signaling
&
PIa^Ubc1 direction forward &
PIa>(I> start current)set

≥1
&
PIb^Uca1 direction forward & ≥1
PIb>(I> start current)set

≥1
&
PIc^Uab1 direction forward &
PIc>(I> start current)set

6.2 Inverse Time Over-current Protection


The extremely inverse time characteristic curve can be utilized in the protection.
The expression of the extreme inverse time characteristic curve is shown as below:


t  Fs / ( I / I p ) 2  1) 
Where:
 Fs=Inverse time constant
 I= measured value of the current
 Ip=pickup value of the current
 t=operating time

I>Inv protection
Tripping and
 
&
signaling
t  Fs / ( I / I p )  1)
2

6.3 Zero-Sequence Over-voltage Protection


When zero-sequence voltage is greater than its setting value, the relay will operate after delay time.

3U0> protection Tripping and


t1
signaling
&
3U0>[3U0> start voltage]set Tripping and
t2
signaling

6.4 Zero-Sequence Over-current Protection


When zero-sequence current is greater than its setting value, the relay will operate after delay time.

3I0> protection
Tripping and
& t
signaling
3I0>[3I0> start current]set

7
DCAP-5051S Back-up Protection Unit for Transformer

Tripping and
t1
3I0>> protection signaling
Tripping and
& t2
3I0>[3I0>> start current]set signaling
Tripping and
t3 signaling

6.5 Under-voltage Protection


When the line voltages Uab1,Ubc1 and Uca1 are all less than its setting value, the relay will operate after
delay time.
U< protection

CB closed
Tripping and
& t
Min(Uab1,Ubc1,Uca1)<[U< start voltage]set signaling

TV1 fault alarm enable

6.6 Over-voltage Protection


When any line voltage is greater than its setting value, the relay will operate after delay time.

U> protection
& Tripping and
t
Max(Uab1,Ubc1,Uca1)>[U> start voltage]set signaling

6.7 Gap Zero-Sequence Over-current Protection


When gap zero-sequence current is greater than its setting value, the relay will operate after delay time.

GI0> protection Tripping and


t1
signaling
&
GI0>[GI0>Gap start current]set Tripping and
t2
signaling

6.8 Overload Alarm


When any phase current is greater than its setting value, the relay will operate after delay time.
Overload alarm
Tripping and
& t
Max(PIa,PIb,PIc)>[Overload start current]set signaling

6.9 Breaker Fault Protection


The unit contains breaker failure protection.which accomplished by collecting the protective starting
signal and monitoring the current flowed through the breaker.

8
DCAP-5051S Back-up Protection Unit for Transformer

CBF protection

Max(PIa,PIb,PIc)>[CBF-I> start current]set


&
T=5s
SI9=1

CBF-I2>
Tripping and
& t1
I2>[CBF- I2> start current]set signaling
&
CBF-3I0> Tripping and
t2
& signaling
3I0>[CBF-3I0> start current]set

CBF blocked by HV

U11<[CBF-U1<(CV) start voltage]set &


≥1 ≥1
U22>[CBF-U2>(CV) start voltage]set

CBF blocked by MV

U12<[CBF-U1<(CV) start voltage]set &


≥1
U22>[CBF-U2>(CV) start voltage]set

CBF blocked by LV

U13<[CBF-U1<(CV) start voltage]set &


≥1
U23>[CBF-U2>(CV) start voltage]set

6.10 Impedance Protection


The unit contains two-stage low impedance protection which adopting homonym phase full-voltage and
full-current impedance relay
Computational formula:
 
Z   U  / I  , therein ,subscript  may be ab, bc or ca

Operating criterion:
PI   ZI set and Z   action region
The characteristic curve of impedance protection is shown as below:

9
DCAP-5051S Back-up Protection Unit for Transformer

jx jx
Z
0<(K=D'/D)<0.5 0.5<(K=D'/D)<1
Z'
A R
D Z0
Z0 D
Z' D'
A Z
R

D'

(1) (2)

jx jx jx

K=D'/D=0 Z A
R
Z' Z=Z'
D
D Z0 K=D'/D=1 A
Z0
Z'
D=D' Z0 R
Z D' K=D'/D=0.5
A
R

(3) (4) (5)

The characteristic curve of impedance protection


(1) The impedance characteristic curve in the positive direction drift
(2) The impedance characteristic curve in the reverse direction drift
(3) The impedance characteristic curve in the positive direction
(4) The impedance characteristic curve in the reverse direction
(5) Full impedance characteristic curve
Where:
D : diameter of impedance circle
D  : impedance deflection distance under the sensitive angle
K  D / D : drift coefficient
A : sensitive angle
Z 0 : the centre impedance
Z : measured impedance
Z   Z  Z0
The active region of impedance could be shown as follows:
Z  D/ 2
Z<(Z<<) protection

Max(PIa,PIb,PIc)>(Z-I> start current)set


& Tripping and
t
Zab∈ Z<(Z<<) active region signaling

Zbc∈ Z<(Z<<) active region ≥1

Zca∈ Z<(Z<<) active region

6.11 Cooling Starting


When any phase current is greater than its setting value in cooling starting, the unit will start output relay
after a certain time delay.

10
DCAP-5051S Back-up Protection Unit for Transformer

Cooling protection
Tripping and
& t
Max(PIa,PIb,PIc)>(Coolen start current)set signaling

6.12 TV Fault Alarm


Detecting one phase or two phases in fault: when negative-sequence voltage is greater than its setting
value,the unit will give the TV fault signal after 3s.
Detecting three phases in fault: when positive-sequence voltage is less than its setting value and any
phase has current, the unit will give the TV fault signal after 3s.

TV fault alarm on the first side:


TV1 fault alarm

Max(PIa,PIb,PIc)>[I>(TV fault) start current]set Tripping and


& t=3s
& signaling
U11<[U1<(TV fault) start voltage]set
≥1
U21>[U2>(TV fault) start voltage]set

TV fault alarm on the second side:


TV2 fault alarm

Max(PIa,PIb,PIc)>[I>(TV fault) start current]set Tripping and


& t=3s
& signaling
U12<[U1<(TV fault) start voltage]set
≥1
U22>[U2>(TV fault) start voltage]set

TV fault alarm on the third side:


TV3 fault alarm

Max(PIa,PIb,PIc)>[I>(TV fault) start current]set Tripping and


& t=3s
& signaling
U13<[U1<(TV fault) start voltage]set
≥1
U23>[U2>(TV fault) start voltage]set

6.13 TA Fault Alarm


TA fault criterion: one of the protective currents is greater than its setting value and one of the protective
currents is less than its setting value, the unit will give a TA fault signal after 3s.
TA fault alarm

Max(PIa,PIb,PIc)>[I>(TA fault) start current]set Tripping and


& t=3s
signaling
Min(PIa,PIb,PIc)<[I<(TA fault) start current]set

6.14 Control Circuit Fault Alarm


When the positive power or negative power signal in closing–tripping circuit is open, the unit will give
the control loop fault signal after 2s.
6.15 Four Programmable Logic Control Outputs
The 4 groups of inter-tripping have the programmable logic function at the scene and could be used in

11
DCAP-5051S Back-up Protection Unit for Transformer

various interlocks freely.


The inter-tripping that would actuate the output relay according to the change of state which the digital
input values inputted in the unit, locates in the submenu “Set PLC” and details are as follows.
①Input mask: select the effective binary input signals from No.1(SI1) to No.8(SI8) which will
participate the logic control function when its relevant bit is set to logic high (1);
② Level mask: define the effective logic level of the binary input signals. When the state of the binary
input signals coincides with the corresponding level mask, the inter-tripping functional element will
issue an output.
③ Output type: “0” stands for pulse mode, the output is an pulse output and the holding pulse width can
be set from 0s to 127s; “1”stands for level mode, the output is not a pulse and not holding.
④ Pulse width: the range of pulse width is between 0s and 127s.

PLC

PLC input signal closed Operating


& & t
and signaling
PLC level mask(closed effect)
≥1
PLC input signal opened
&
PLC level mask(opened effect)

6.16 Checking Synchronization and Checking No-voltage


The both could be modified independently, it could be performed by checking synchronization (checking
no-voltage) output contact being connected in series with CB closing circuit. During setting at factory,
the 8 outputs from TS1 to TS8 could be used as checking synchronization (checking no-voltage) output
contact which ought to be consistent with the normal closing relay on I/O board.
For example, suppose that TS8 is checking synchronization (checking no-voltage) output contact(the
relevant closing circuit references to the elementary drawing about checking synchronization and
checking no-voltage control circuit), when meeting closing condition of checking synchronization or
checking no-voltage permitted, the TS8 contact would be closed and allowed closing CB which means
that the TS8 is failure to actuate; otherwise, the output relay TS8 will actuate , so TS8 will be open to
forbid closing CB.
 Voltage difference: DU  U ab 3 - AC  U ab1

 Frequency difference: DF  FU ab 3 - FU ab1

 Angle difference: D  U ab 3  U ab1  C

 Angle compensation: C  U ab1  U ab 3


 Amplitude compensation: AC  U ab 3 / U ab1

12
DCAP-5051S Back-up Protection Unit for Transformer

Uab3>[U>(synch) start voltage]set

ACxUab1>[U>(synch) start voltage]set

DU<[DU>(synch) start voltage]set


&
DФ <[DФ (synch) start angle]set

DF<[DF(synch) start freq.]set

Close CB (synch)
Close CB (synch.,
≥1 ≥1 no-voltage) tripping
Close CB (no-voltage) and signaling

ACxUab1<[U<(synch) start voltage]set


&
Uab3>[U<(synch) start voltage]set
&
ACxUab1>[U<(synch) start voltage]set
& ≥1
Uab3<[U<(synch) start voltage]set

ACxUab1<[U<(synch) start voltage]set


&
Uab3<[U<(synch) start voltage]set

6.17 Fault Recording


Fault recording starts by the break-variable of protection current. when the break-variable is greater than
setting value, the unit will record all AC analog waveform.And the fault record duration can be set.
Maximum of break-variable : D  Max(PI a , PI b , PI c , 3I 0 , GI 0 )
Fault record object: Uab1,Ubc1,Uab2,Ubc2,Uab3,Ubc3,3U0,PIa,PIb,PIc,3I0,GI0
Start fault record
& Recording
D>[Fault record start current]set

7. Normal Display
After power-on, the unit will display the contents circularly which is shown as below.
Symbol Format Description Note
Voltage
Uab1 000.00 V/kV/MV Voltage Uab1
Multiply by TV ratio
Ubc1 000.00 V/kV/MV Voltage Ubc1
Uca1 000.00 V/kV/MV Voltage Uca1
Angle
ΦUab1 000.0° Phase angle of Uab1
Reference to Ua1
ΦUbc1 000.0° Phase angle of Ubc1
ΦUca1 000.0° Phase angle of Uca1
Current
MIa 000.00 A/kA Measuring MIa
Multiplied by TA ratio
MIb 000.00 A/kA Measuring MIb
MIc 000.00 A/kA Measuring MIc
Angle
Reference to Ua1
ΦMIa 000.0° Phase angle of MIa

13
DCAP-5051S Back-up Protection Unit for Transformer

ΦMIb 000.0° Phase angle of MIb


ΦMIc 000.0° Phase angle of MIc
Power
P 000.00 W/kW/MW Active power P Multiplied by TV ,TA ratio
Q 000.00 Var/kr/Mr Reactive power Q Multiplied by TV ,TA ratio
PF 0.00 Power factor
Measuring
PH 000000.00 Active energy kWh
QH 000000.00 Reactive energy kVarh
Measuring
Tm 000.0 Temperature
CRC 00000 CRC code

8. Menu Functions
After pressing the key [SEL] in normal display, we will go into the main menu.
Description Password Note
01. Prot.values Check protection analog data
02. Check synch. Check synchronizing values
03. Harmonics Check harmonics of voltage Huab and current MIa
04. Parameters Check measuring parameters
05. Check group Check protection setting group
06. Prot. sets Check protection setting values
07. Prot. off/on Check protection statues
08. Trip table Check tripping tables
09. DI status Check digital input statues
10. Fault record Check alarm records stored in the unit
11. Set para. 1111 Set measuring parameters
12. Set group 2222 Set protection group
13. Set prot. 2222 Set protection setting values
14. Set off/on 2222 Set protection statues
15. Set trip 2275 Set tripping tables
16. AC adjust 2266 Adjust AC inputs
17. DC adjust 1166 Adjust DC inputs
18. Set PLC 3333 Set 4 groups of inter-tripping
19. Relay test 1175 Test output relays
20. Initialize 1122 Load initializing parameters
21. Com. status Check communication interfaces
22. Fault test 2233 Simulate all fault and warning alarms
23. Time adjust 9999 Adjust real-time clock
24. Coefficient 2266 Check AC adjust coefficients
25. Version Check software version
8.1 Prot. values
Accessing the sub menu “Prot. values” from the main menu, the unit will show protection analogs
values.
Symbol Format Description Note
Voltage
Uab1 000.0 V Voltage Uab1
Ubc1 000.0 V Voltage Ubc1
Uca1 000.0 V Voltage Uca1
Angle Reference

14
DCAP-5051S Back-up Protection Unit for Transformer

ΦUab1 000.0° Phase angle of Uab1 to Ua1


ΦUbc1 000.0° Phase angle of Ubc1
ΦUca1 000.0° Phase angle of Uca1
Voltage
Uab2 000.0 V Voltage Uab2
Ubc2 000.0 V Voltage Ubc2
Uca2 000.0 V Voltage Uca2
Angle
ΦUab2 000.0° Phase angle of Uab2 Reference
ΦUbc2 000.0° Phase angle of Ubc2 to Ua1
ΦUca2 000.0° Phase angle of Uca2
Voltage
Uab3 000.0 V Voltage Uab3
Ubc3 000.0 V Voltage Ubc3
Uca3 000.0 V Voltage Uca3
Angle
ΦUab3 000.0° Phase angle of Uab3 Reference
ΦUbc3 000.0° Phase angle of Ubc3 to Ua1
ΦUca3 000.0° Phase angle of Uca3
Current
PIa 000.00 A Protective current PIa
PIb 000.00 A Protective current PIb
PIc 000.00 A Protective current PIc
Angle
ΦPIa 000.0° Phase angle of PIa Reference
ΦPIb 000.0° Phase angle of PIb to Ua1
ΦPIc 000.0° Phase angle of PIc
Current
3I0 000.00 A Zero-sequence current on the first side
I1 000.00 A Postive-sequence current on the first side
I2 000.00 A Negative-sequence current on the first side
Voltage
3U0 000.0 V Zero-sequence vlotage on the first side
U11 000.0 V Postive-sequence vlotage on the first side
U21 000.0 V Negative-sequence vlotage on the first side
Voltage
U12 000.0 V Postive-sequence vlotage on the second side
U22 000.0 V Negative-sequence vlotage on the second side
Voltage
U13 000.0 V Postive-sequence vlotage on the third side
U23 000.0 V Negative-sequence vlotage on the third side
Measuring
GI0 000.00 A Gap zero-sequence current
F Frequency
8.2 Check synch.
Accessing the sub menu “Check synch.” from the main menu, the unit will show synchronizing values.
Symbol Format Description Note
Uab1 000.0 V Uab on the first side
FUab1 00.00 Hz Frequency of Uab1
Uab3 000.0 V Uab on the third side

15
DCAP-5051S Back-up Protection Unit for Transformer

FUab3 00.00 Hz Frequency of Uab3


DU 000.0 V Voltage difference
DF 00.00 Hz Frequency difference
DΦ 000.0° Angle difference
8.3 Harmonics
Accessing the sub menu “Harmonics” from the main menu, the unit will show harmonics from
fundamental to 11th about HUab and MIa.
Symbol Format Description Note
Uab1 000.00 V Uab1 fundamental harmonic
Uab3 000.00 V Uab1 3th harmonics
Uab5 000.00 V Uab1 5th harmonics
Uab7 000.00 V Uab1 7th harmonics
Uab9 000.00 V Uab1 9th harmonics
Uab11 000.00 V Uab1 11th harmonics
MIa1 000.00 A MIa fundamental harmonic
MIa3 000.00 A MIa 3th harmonics
MIa5 000.00 A MIa 5th harmonics
MIa7 000.00 A MIa 7thd harmonics
MIa9 000.00 A MIa 9th harmonics
MIa11 000.00 A MIa 11th harmonics
8.4 Parameters
Accessing “Parameters” from the main menu, the unit will show supervisory parameters, and specifically
could refer to the direction for the submenu “Set para.”.
8.5 Check group
Accessing “Check group”from the main menu, the unit will show the device selected which group
protection setting.
8.6 Prot. sets
Accessing “Prot. sets” from the main menu, the unit will show the protection setting valuess, and
specifically could refer to the direction for the submenu “Set prot.”.
8.7 Prot. off/on
Accessing “Prot. off/on” from the main menu, the unit will show the protection statuses, and specifically
could refer to the direction for the submenu “Set off /on”.
8.8 Trip table
Accessing “Trip table” from the main menu, the unit will show settings in tripping table, and specifically
could refer to the direction for the submenu “Set trip”
8.9 DI status
Accessing “DI status” from the main menu, the unit will show digital input statuses.
Description Note
01. CB Open/Close
02. Digital 2 Open/Close
03. Digital 3 Open/Close
04. Digital 4 Open/Close
05. Digital 5 Open/Close
06. Digital 6 Open/Close
07. Digital 7 Open/Close
08. Digital 8 Open/Close

16
DCAP-5051S Back-up Protection Unit for Transformer

09. Start CBF Open/Close


10. GPS Open/Close
11. Digital 11 Open/Close
12. Digital 12 Open/Close
8.10 Fault record
Accessing “Fault record” from the main menu, the unit will show the latest 40 alarm records stored in the
unit which is made up of fault category, operating time and operating values.
Fault type table:
No. Fault category Note
01. I>
02. I>>
03. I>>>1
04. I>>>2
05. I>>>3
06. I>Inv
07. 3U0>1
08. 3U0>2
09. 3I0>
10. 3I0>>1
11. 3I0>>2
12. 3I0>>3
13. U< Fault signal
14. U>
15. GI0>1
16. GI0>2
17. PLC1
18. PLC2
19. PLC3
20. PLC4
21. Cooling
22. CBF 1
23. CBF 2
24. Z<
25. Z<<
26. Overload
27. TV1 fault alarm
28. TV2 fault alarm
29. TV3 fault alarm
Warning signal
30. TA fault alarm
31. Ctr loop fault alarm
32. Fault record
33. CPU error
8.11 Set para.
Accessing “Set para.” from the main menu by inputting password 1111, the supervisory parameters
could be edited.
Description Range Note
01. Addr. 2~99
02. IP[0]
Ethernet IP address
IP[1]

17
DCAP-5051S Back-up Protection Unit for Transformer

IP[2]
IP[3]
03. Submask[0]
Submask[1]
Ethernet Submask
Submask[2]
Submask[3]
04. MAC[0]
MAC[1]
MAC[2]
Ethernet physical address
MAC[3]
MAC[4]
MAC[5]
05. Port num. 0~9999
06. TV ratio 0.0~3000.0
07. TA ratio 0.0~3000.0
08. Pulse count per kWh 1~9999 The number of impulse per kilowatt hour
09. Pulse count per kVarh 1~9999 The number of impulse per kilowatt hour
10. Initial kWh 0.00~999999.99 Initial kWh value
11. Initial kVarh 0.00~999999.99 Initial kVarh value

8.12 Set group


Accessing “Set group.” from the main menu by inputting password 2222, the group 1~4 could be
selected.
Description Range Note
01. Set group 1~4

8.13 Set prot.


Accessing “Set prot.” from the main menu by inputting password 2222, the setting values of protections
could be modified.
Description Range Note
Rated parameter
01. Un 100.0~400.0V Rated voltage
02. In 0.10~20.00A Rated current
I>
03. I> start current 0.10~100.00A Return coefficient: 0.95
04. I> operate time 0.00~100.00s
05. I>> start current 0.10~100.00A Return coefficient: 0.95
06. I>> operate time 0.00~100.00s
07. I>>> start current 0.10~100.00A Return coefficient: 0.95
08. I>>>1 operate time 0.00~100.00s
09. I>>>2 operate time 0.00~100.00s
10. I>>>3 operate time 0.00~100.00s
11. U1<(CV) start voltage 10.0~300.0V Return coefficient: 1.05
12. U2>(CV) start voltage 1.0~200.0V Return coefficient: 0.95
I>Inv
13. IP 0.10~100.00A
14. Fs 0.10~300.00
3U0>
15. 3U0> start voltage 10.0~600.0V Return coefficient: 0.95

18
DCAP-5051S Back-up Protection Unit for Transformer

16. 3U0>1 operate time 0.00~100.00s


17. 3U0>2 operate time 0.00~100.00s
3I0>
18. 3I0> start current 0.10~100.00A Return coefficient: 0.95
19. 3I0> operate time 0.00~100.00s
20. 3I0>> start current 0.10~100.00A Return coefficient: 0.95
21. 3I0>>1 operate time 0.00~100.00s
22. 3I0>>2 operate time 0.00~100.00s
23. 3I0>>3 operate time 0.00~100.00s
U<
24. U< start voltage 10.0~400.0V Return coefficient: 1.05
25. U< operate time 0.00~100.00s
U>
26. U> start voltage 100.0~600.0V Return coefficient: 0.98
27. U> operate time 0.00~100.00s
Overload
28. Overload start current 0.10~100.00A Return coefficient: 0.95
29. Overload operate time 0.00~100.00s
PLC
30. PLC1 operate time 0.00~100.00s
31. PLC2 operate time 0.00~100.00s
32. PLC3 operate time 0.00~100.00s
33. PLC4 operate time 0.00~100.00s
GI0>
34. GI0> start current 0.10~100.00A Return coefficient: 0.95
35. GI0>1 operate time 0.00~100.00s
36. GI0>2 operate time 0.00~100.00s
Cooling
37. Cooling start current 0.10~100.00A Return coefficient: 0.95
38. Cooling operate time 0.00~100.00s
CBF
39. CBF-I> start current 0.10~100.00A Return coefficient: 0.95
40. CBF-U1<(CV) start voltage 10.0~300.0V Return coefficient: 1.05
41. CBF-U2>(CV) start voltage 1.0~200.0V Return coefficient: 0.95
42. CBF-I2> start current 0.10~100.00A Return coefficient: 0.95
43. CBF-3I0> start current 0.10~100.00A Return coefficient: 0.95
44. CBF 1 operate time 0.00~100.00s
45. CBF 2 operate time 0.00~100.00s
Z<
46. Z-I> start current 0.10~100.00A Return coefficient: 0.95
47. Z< diameter 0.10~100.00Ω Return coefficient: 1.05
48. Z< drift coefficient 0.00~1.00
49. Z< sensitive angle 0.0~90.00°
50. Z< operate time 0.00~100.00s
51. Z<< diameter 0.10~100.00Ω Return coefficient: 1.05
52. Z<< drift coefficient 0.00~1.00
53. Z<< sensitive angle 0.0~90.00°
54. Z<< operate time 0.00~100.00s

19
DCAP-5051S Back-up Protection Unit for Transformer

TV fault alarm
55. U1<(TV fault) voltage 10.0~300.0V Return coefficient: 1.05
56. U2>(TV fault) voltage 1.0~200.0V Return coefficient: 0.95
57. I>(TV fault) current 0.10~100.00A Return coefficient: 0.95
TA fault alarm
58. I<(TA fault) current 0.10~100.00A Return coefficient: 1.05
59. I>(TA fault) current 0.10~100.00A Return coefficient: 0.95
Close CB (synch.,no-voltage)
60. U>(synch) start voltage 10.0~400.0V Return coefficient: 0.95
61. U<(synch) start voltage 10.0~400.0V Return coefficient: 1.05
62. DU(synch) start voltage 1.0~200.0V Return zone:1V
63. DF(synch) start freq. 0.10~5.00Hz Return zone: 0.05 Hz
64. DФ(synch) start angle 1.0~50.0° Return zone:1.0°
65. CФ(synch) comp. angle 0.0~360.0°
66. AC(synch) comp. amp. 0.50~2.00
Fault record
67. Fault record start current 0.10~100.00A
68. Fault record duration 1~20s

8.14 Set off /on


Accessing the sub menu “Set off /on ” from the main menu by inputting password 2222, the protection
states could be set up.
Description Setting Note
01. I> Off/On
02. I>--> Off/On
03. I> blocked by CV1 Off/On
04. I> blocked by CV2 Off/On
05. I> blocked by CV3 Off/On
06. I>> Off/On
07. I>>--> Off/On
08. I>> blocked by CV1 Off/On
09. I>> blocked by CV2 Off/On
10. I>> blocked by CV3 Off/On
11. I>>> Off/On
12. I>>>--> Off/On
13. I>>> blocked by CV1 Off/On
14. I>>> blocked by CV2 Off/On
15. I>>> blocked by CV3 Off/On
16. I>Inv Off/On
17. 3U0> Off/On
18. 3I0> Off/On
19. 3I0>> Off/On
20. U< Off/On
21. U> Off/On
22. Overload Off/On
23. PLC1 Off/On
24. PLC2 Off/On
25. PLC3 Off/On
26. PLC4 Off/On
27. GI0> Off/On

20
DCAP-5051S Back-up Protection Unit for Transformer

28. Cooling Off/On


29. CBF Off/On
30. CBF blocked by CV1 Off/On
31. CBF blocked by CV2 Off/On
32. CBF blocked by CV3 Off/On
33. CBF-I2> Off/On
34. CBF-3I0> Off/On
35. Z< Off/On
36. Z<< Off/On
37. TV1 fault alarm Off/On
38. TV2 fault alarm Off/On
39. TV3 fault alarm Off/On
40. TA fault alarm Off/On
41. Ctr loop fault alarm Off/On
42. Close CB (synch) Off/On
43. Close CB (low -voltage) Off/On
44. Start fault record Off/On
8.15 Set trip
Accessing the sub menu “Set trip” from the main menu by inputting password 2275, the tripping table
could be modified. After modifying, we could regulate the 8 output relays.
Attention:
 1:on; 0:off
 Once the fault alarm and the warning alarm outputs have been set up, the output relay has no
return even though the alarm condition has vanished, except for pressing down the key [ENT].
 The tripping table could not be modified casually as soon as finished setting.
Tripping Table
Description TS8 TS7 7S6 TS5 TS4 TS3 TS2 TS1 Setting
Bit7 Bit6 Bit5 Bit4 Bit3 Bit2 Bit1 Bit0
01. I> 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
02. I>> 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
03. I>>>1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
04. I>>>2 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
05. I>>>3 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
06. I>Inv 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
07. 3U0>1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
08. 3U0>2 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
09. 3I0>1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
10. 3I0>>1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
11. 3I0>>2 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
12. 3I0>>3 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
13. U< 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
14. U> 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
15. Overload 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
16. PLC1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
17. PLC2 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
18. PLC3 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
19. PLC4 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
20. GI0>1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
21. GI0>2 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
22. Cooling 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000

21
DCAP-5051S Back-up Protection Unit for Transformer

23. CBF 1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
24. CBF 2 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
25. Z< 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
26. Z<< 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
27. TV1 fault alarm 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
28. TV2 fault alarm 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
29. TV3 fault alarm 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
30. TA fault alarm 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
31. Ctr loop fault alarm 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
32. Synch. 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
33. Fault signal 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
34. Warning signal 0/1 0/1 0/1 0/1 0/1 0/1 0/1 0/1 00000000
8.16 AC adjust
All current and voltage can be adjusted after accessing “AC adjust” from the main menu by inputting
password 2266.
Caution: the item has been regulated at factory, so it would be forbidden operation on the scene.
Symbol Description Default values
01. Uab1 Uab on the first side 100.00V
02. Ubc1 Ubc on the first side 100.00V
03. Uab2 Uab on the second side 100.00V
04. Ubc2 Ubc on the second side 100.00V
05. Uab3 Uab on the third side 100.00V
06. Ubc3 Ubc on the third side 100.00V
07. 3U0 Zero sequence voltage on the first side 200.00V
08. MIa Measuring MIa 5.00A
09. MIc Measuring MIc 5.00A
10. PIa Protective current PIa 15.00A
11. PIb Protective current PIb 15.00A
12. PIc Protective current PIc 15.00A
13. 3I0 Zero sequence current on the first side 15.00A
14. GI0 Gap zero-sequence current 15.00A
8.17 DC adjust
We could adjust DC analogs after accessing “DC adjust” from the main menu by inputting password
1166.
Caution: the item has been regulated at factory, so it would be forbidden operating on the scene.
Description Note
1. AN1
2. AN2
8.18 Set PLC
We could modify tripping table after accessing “Set PLC” from the main menu by inputting password
3333, and details could reference to the above relevant description.
Description Setting
01. PLC1 input mask 00000000
02. PLC1 level mask 00000000
03. PLC1 output type 0/1
04. PLC1 pulse width 0~127s
05. PLC2 input mask 00000000
06. PLC2 level mask 00000000

22
DCAP-5051S Back-up Protection Unit for Transformer

07. PLC2 output type 0/1


08. PLC2 pulse width 0~127s
09. PLC3 input mask 00000000
10. PLC3 level mask 00000000
11. PLC3 output type 0/1
12. PLC3 pulse width 0~127s
13. PLC4 input mask 00000000
14. PLC4 level mask 00000000
15. PLC4 output type 0/1
16. PLC4 pulse width 0~127s

8.19 Relay test


The 8 output relays can be tested after accessing “Relay test” from the main menu by inputting password
1175.
Caution: the test, which would be forbidden using in the unit normal running state, could be only
used to examine the relays, namely, the relays will operate during testing.
Description Note
01. Relay 1 Off/On
02. Relay 2 Off/On
03. Relay 3 Off/On
04. Relay 4 Off/On
05. Relay 5 Off/On
06. Relay 6 Off/On
07. Relay 7 Off/On
08. Relay 8 Off/On
8.20 Initialize
Accessing the sub menu “Initialize” from the main menu by inputting password 1122, we could finish
some initialization.
Description Setting Note
01. System frequency 50Hz/60Hz
02. Protocol type UNIS/ Standard
03. Protocol choose IEC-103/MODBUS
04. kWh/kVarh Pulse/Integral
05. Clean records Yes/No Cleaning all SOE records stored in the unit
06. Load factory sets Yes/No
07. Copy group Yes/No Copy group 1 to group 2~4.
System Frq:
Selecting “50Hz” means the unit could be used in 50Hz of the system frequency, or selecting “60Hz”
means the unit could be used in 60Hz of the system frequency.
Protocol:
Selecting “UNIS” means the unit could communicate with the monitoring computer through UNIS V2.0
protocol, while selecting “Standard” means through IEC-103 or MODBUS protocol.
kWh/kVarh:
When the item is set as “pulse”, it will calculate power by impulse (SP1 and SP2) external inputted,
otherwise, “integral”, it will calculate by integral to cumulative power.
Load factory sets:
When selecting “Yes” and then pressing the key [ENT], the submenus which contain “Set prot.”, “Set
off/on”, “Set trip” , “Set PLC” will be restored the default values.

23
DCAP-5051S Back-up Protection Unit for Transformer

Set prot. :
Description Factroy Setting
Rated parameter
01. Un 100.0V
02. In 5.00A
I>
03. I> start current 100.00A
04. I> operate time 100.00s
05. I>> start current 100.00A
06. I>> operate time 100.00s
07. I>>> start current 100.00A
08. I>>>1 operate time 100.00s
09. I>>>2 operate time 100.00s
10. I>>>3 operate time 100.00s
11. U1<(CV) start voltage 10.0V
12. U2>(CV) start voltage 200.0V
I>Inv
13. IP 100.00A
14. Fs 300.00
3U0>
15. 3U0> start voltage 600.0V
16. 3U0>1 operate time 100.00s
17. 3U0>2 operate time 100.00s
3I0>
18. 3I0> start current 100.00A
19. 3I0> operate time 100.00s
20. 3I0>> start current 100.00A
21. 3I0>>1 operate time 100.00s
22. 3I0>>2 operate time 100.00s
23. 3I0>>3 operate time 100.00s
U<
24. U< start voltage 10.0V
25. U< operate time 100.00s
U>
26. U> start voltage 600.0V
27. U> operate time 100.00s
Overload
28. Overload start current 100.00A
29. Overload operate time 100.00s
PLC
30. PLC1 operate time 100.00s
31. PLC2 operate time 100.00s
32. PLC3 operate time 100.00s
33. PLC4 operate time 100.00s
GI0>
34. GI0> start current 100.00A
35. GI0>1 operate time 100.00s
36. GI0>2 operate time 100.00s
Cooling
37. Cooling start current 100.00A
38. Cooling operate time 100.00s

24
DCAP-5051S Back-up Protection Unit for Transformer

CBF
39. CBF-I> start current 100.00A
40. CBF-U1<(CV) start voltage 10.0V
41. CBF-U2>(CV) start voltage 200.0V
42. CBF-I2> start current 100.00A
43. CBF-3I0> start current 100.00A
44. CBF 1 operate time 100.00s
45. CBF 2 operate time 100.00s
Z<
46. Z-I> start current 100.00A
47. Z< diameter 0.10Ω
48. Z< drift coefficient 0.00
49. Z< sensitive angle 0.00°
50. Z< operate time 100.00s
51. Z<< diameter 0.10Ω
52. Z<< drift coefficient 0.00
53. Z<< sensitive angle 0.00°
54. Z<< operate time 100.00s
TV fault alarm
55. U1<(TV fault) voltage 10.0V
56. U2>(TV fault) voltage 200.0V
57. I>(TV fault) current 100.00A
TA fault alarm
58. I<(TA fault) current 0.10A
59. I>(TA fault) current 100.00A
Close CB (synch.,no-voltage)
60. U>(synch) start voltage 400.0V
61. U<(synch) start voltage 10.0V
62. DU(synch) start voltage 1.0V
63. DF(synch) start freq. 0.10Hz
64. DФ(synch) start angle 1.0°
65. CФ(synch) comp. angle 0.0°
66. AC(synch) comp. amp. 1.00
Fault record
67. Fault record start current 100.00A
68. Fault record duration 1s
Set off/on:All the items are set as “Off ”.
Set trip:All are set as zero.
Set PLC:All are set as zero.
8.21 Com. status
Accessing the sub menu “Com. Status” from the main menu, the unit will show 2 communication
interface statues, when the data have changed, that is to say, the communication is in normal state.
Description Format
01. S-send 000
02. S-rec. 000
03. E-send 000
04. E-rec. 000
05. GPS 000000

25
DCAP-5051S Back-up Protection Unit for Transformer

8.22 Fault test


Accessing the sub menu “Fault test” from the main menu by inputting password 2233, the unit only
could actuate SOE reports which is upload to the computer and do not simulate faults’ tripping,
operating values are all zero to distinguish actual alarm records.
8.23 Time adjust
Accessing the sub menu “Time adjust” from the main menu by inputting password 9999, the internal
clock could be regulated in the unit.
Description Note
01. Year 0~99 years
02. Month 1~12 months
03. Day 1~31 days
04. Hour 0~23 hours
05. Minute 0~59 minutes
06. Second 0~59 seconds

8.24 Coefficient
Accessing the sub menu “Coefficient” from the main menu by inputting password 2266, each AC
coefficient can be checked and adjusted .
Symbol Format Note
01. Uab1 100V:xxx.xx/400V:xxx.xx Uab on the first side
02. Ubc1 100V:xxx.xx/400V:xxx.xx Ubc on the first side
03. Uab2 100V:xxx.xx/400V:xxx.xx Uab on the second side
04. Ubc2 100V:xxx.xx/400V:xxx.xx Ubc on the second side
05. Uab3 100V:xxx.xx/400V:xxx.xx Uab on the third side
06. Ubc3 100V:xxx.xx/400V:xxx.xx Ubc on the third side
07. 3U0 100V:xxx.xx/400V:xxx.xx Zero sequence voltage on the first side
08. MIa 5A:xxx.xx/1A:xxx.xx Measuring MIa
09. MIc 5A:xxx.xx/1A:xxx.xx Measuring MIc
10. PIa 5A:xxx.xx/1A:xxx.xx Protective current PIa
11. PIb 5A:xxx.xx/1A:xxx.xx Protective current PIb
12. PIc 5A:xxx.xx/1A:xxx.xx Protective current PIc
13. 3I0 5A:xxx.xx/1A:xxx.xx Zero sequence current on the first side
14. GI0 5A:xxx.xx/1A:xxx.xx Gap zero-sequence current

8.25 Version
Accessing the sub menu “Version” from the main menu, the unit will display the type of the unit,
version ,creating date and modifying data.
Description Note
01. Unit type 5051S -ENG
02. Version 2.2.1.6
03. Date 16.01.01
04. Modify 16.01.01

26
DCAP-5051S Back-up Protection Unit for Transformer

9. Design Drawing
9.1 Screw Fixing Installation

Outside View:

Outline and Installation Size:


Outline Size: 180.8(height)×213(width)×228(depth)mm

27
DCAP-5051S Back-up Protection Unit for Transformer

Installation Size: 179.0(height)×174.5(width)mm

9.2 Bracket Fixing Installation

Outside View:

28
DCAP-5051S Back-up Protection Unit for Transformer

Outline and Installation Size:

DCAP-5000 DIGITAL

HUNAN UNISPLENDOUR M&C CO.,LTD.

Front View

Plan View

29
DCAP-5051S Back-up Protection Unit for Transformer

Back View

Installation Drawing

30
DCAP-5051S Back-up Protection Unit for Transformer

9.3 Connection Diagram

CB
Control power -
Closing output
Closing input

Tripping output
Tripping input
Control power +

Measure

Output 1

Output 2
Protection
Output 3

Output 4

zero-sequence Output 5

Output 6

Output 7

Output 8
Gap zero-sequence

RS485 interface

Ethernet interface

CB(or digital 1) Power-off alarm


Digital 2
Digital 3
Digital 4 Power supply
Digital 5
Digital 6
Digital 7
Digital 8
CBF start(or digital 9)
DI common

GPS DC24V power

Digital 11(or KWh pulse) Tm


Digital 12(or KVarh pulse)
DI common

31
DCAP-5051S Back-up Protection Unit for Transformer

9.4 Electrical Terminals

32
行胜于言
ACTIONS SPEAK LOUDER THAN WORDS

HUNAN UNISPLENDOUR M&C CO., LTD.


Add: No. 456 of Lusong Road, Lu Valley in Hi-Tech Zoom, Changsha, Hunan, China
Tel: (86)731-88921111, 88800243, 88800343
Fax: (86)731-88809006
Service Tel: (86)731-88801099
Free Service Tel: 4000-348-006
Zip: 410205
Http://www.hn-unis.com
Email:hnunis@vip.sina.com

You might also like