Client BPCL

Consultant NA

Project Skid Revmoval for CO2 Capture

Doc. Title Data sheet for Control Valves

Doc. No

1 Tag No. Quantity FCV-101 / LCV 301


2 Service Aq.Monoethanolamin
GENERAL
3 Line No Pipe Size / Schedule S4
4 P&ID No Pipe Class / Material
5 Hazardous Area Classification General
6 Type of Body Globe
7 Body Size Port Size Trim Size 1/2"
8 Guiding No. of Ports Top
9 Valve Size Line Size In / Out 1/2"
BODY 10 End Connection & Rating Body Material 150# RF- SERR
11 Bonnet Type Required Seat Tightness Plain
12 Trim Form / Characteristic Trim Material ** / Equal %
13 Shaft Material Seat / Plug Material Packing Material SS 316 SST
14 Maximum Allowable Sound Level dBA Gasket Material 85 @ 1m from Sourc
15 Jacket / Tracing Requirement Not Required
16 Model No & Size **
17 Type of Actuator Spring Return Diaph
ACTUATOR
18 Spring Rate Stroke Time **
19 Flow Action to Fail Position **
20 Handwheel & Location
21 Manufacturer & Model No **
22 Type Technology Smart Electro - Pneu
23 Enclosure Class Electrical Connection IP 66
POSITIONER
24 Input Signal Output Signal (pneumatic) 4-20 mA
25 Filter Reg. Gauges By Pass Required
26 Electrical Protection General
27 Inlet Air Supply Pressure Min / Nor / Max Kg/cm g
2

28 Limit Switches Electrical Protection


OPTIONS
29 Solenoid Valve Electrical Protection **
30 Coil Voltage Electrical Connection **
31 Fluid / Phase
32 Max.
33 Flow Rate lpm 20.00
34 Inlet Pressure at Flow rate kg/cm2 A 5.00
35 Outlet Pressure at Flow rate kg/cm A 2
-
36 Delta p at Flow rate kg/cm2 **
37 Cv at Flow rate **
38 Predicted Sound Level dBA <85dBA * *
39 Valve CV Valve FL **
SERVICE
40 Max Shut off Delta P kg/cm2

41 Temperature Design °C Temperature Operating °C 100


42 Density Inlet/Outlet kg/m 3
Molecular Weight g/ mol 1050 - 1
43 Viscosity cP % Flash 5 to 1
44 Specific Heat Ratio Cp / Cv % Solid
45 Vapour Pressure Kg/cm2A Critical Pressure Kg/cm²g
46 Critical Temperature °C Design pressure Kg/cm²g
47 Compressibility Factor z
48 Toxic Corrosive Component NO
49 Manufacturer -
PURCHASE 50 Model **
51 Purchase Order Number ­
52 Serial number **
Notes:
1) ** To be confirmed by vendor/Manufacturer
2) Vendor To submit GA drawings

1) ** To be confirmed by vendor/Manufacturer
2) NA - Not Applicable, FV-Full Vacuum, VTA - Vendor To Advice, VTS - Vendor To Specify , *Client to confirm
3) Cable gland Entry shall be 1/2" NPT
4) Flow direction shall be engraved on body of instruments, control valve and on-off valve
5) Valves shall be designed, manufactured, assembled, tested and supplied in accordance with ANSI, ASME or
6) Vendor shall submit the completed (duly filled with all details) datasheets along with the bid.
7) Actuator must be designed to provide an output torque of atleast 1.5 times the designed torque defined by val
of 3.5 bar G and max shut off DP specified in the datasheet.
8) SS Tag plate required
Job Order
2201L
No.

Date 29.11.2022

Rev. 0

Sheet No. 1

FCV-101 / LCV 301 2 No


Aq.Monoethanolamine (MEA + Water)
S4 1/2" 40S
SS316
General
Globe
1/2" VTC 1/2" - VTC
Top 1
1/2" 1/2" 1/2"
150# RF- SERR SS 316
Plain ANSI Class IV **
** / Equal % SS 316
SS 316 SST 316SST/Stellited Double PTFE - Press/Vac
85 @ 1m from Source PTFE
Not Required
**
Spring Return Diaphragm
** **
** CLOSE (FC)
-
**
Smart Electro - Pneumatic Smart Hart
IP 66 1/2" NPT **
4-20 mA
Required Required **
General -
/4/

**

** **
** **
Liquid
Max. Norm. 50% Flow
20.00 10 15.00
5.00 3.00 3.00
- 2.50 2.50
** 0.50 0.50
** ** **
<85dBA * * <85dBA * * <85dBA * *
** **
5
100 50
1050 - 1150 31.0
5 to 15 Nil
Nil

5
1
NO Monoethanolamine
-
**
­
**

Specify , *Client to confirm

alve
dance with ANSI, ASME or manufacturer standard
h the bid.
igned torque defined by valve manufacturer with minimum air supply