11. Tolerances
It is recommended to use the dimensional tolerances as shown in below table 11.1. and figure 11.1.

Table 11.1. Tolerances to dimensional reference

Internal Diameter (mm) A B C D E F


25 – 200 ± 5mm ± 3mm ± 0.5° ± 3mm ± 1mm ± 0.5°
250 – 300 ± 5mm ± 3mm ± 0.3° ± 3mm ± 1mm ± 0.5°
350 – 400 ± 5mm ± 3mm ± 0.3° ± 3mm ± 2mm ± 0.5°
450 – 600 ± 10mm ± 5mm ± 0.3° ± 3mm ± 2mm ± 0.5°
700 – 900 ± 10mm ± 5mm ± 0.2° ± 4mm ± 3mm ± 0.5°
1000 – 1200 ± 10mm ± 5mm ± 0.15° ± 6mm ± 3mm ± 0.5°
The maximum gap shall be limited to 6 mm.

Dimension A
a. Face to Face dimensions.
b. Center to Face dimensions.
c. Location of attachments.
d. Center to Center dimensions.

Dimension B
Lateral transition of branches or connections.

Dimension C
Rotation of flanges, from the indicated position.

Dimension D
End preparations.

Dimension E
Cut of alignment of flanges from the indicated position,
measured across the full gasket face.

Dimension F
Angular deflection.

Fig. 11.1. Tolerances

32 Wavistrong Installation Guide for GRE Pipe Systems