1 Scope
This Material Specification specifies the minimum technical requirements for design,
engineering, manufacture, inspection, testing, performance, and acceptance criteria of a
composite overhead optical fiber-ground wire (OPGW) that is installed as part of the
electrical transmission system. For the metallic part specifications and testing, it shall
be referred to Electrical Systems Division of CSD.
Any deviations, providing less than the mandatory requirements of this standard require
written waiver approval as per Saudi Aramco Engineering Procedure SAEP-302. For the
metallic part, any deviation shall be referred to Electrical Systems Division of CSD.
3 References
The selection of material and equipment, and the design, construction, maintenance, and
repair of equipment and facilities covered by this specification shall comply with the
latest edition of the references listed below, unless otherwise noted.
Page 2 of 8
Document Responsibility: Communications Standards Committee 18-SAMSS-005
Issue Date: 22 July 2012
Next Planned Update: 22 July 2015 Composite Overhead Fiber Optic Ground Wire (OPGW) Specifications
4 Specifications
4.1 The IEEE-1138 “IEEE Standard for Testing and Performance for Optical
Ground Wire (OPGW) for Use on Electric Utility Power Lines” and IEC 60794-
4-10 “Aerial optical cables along electrical power lines-Family specification for
OPGW (Optical Ground Wire)” are hereby adopted as Saudi Aramco Material
Specifications for OPGW. Deviations and exceptions are outlined below.
4.2 General
4.2.1 The composite OPGW shall be designed in which the integral optical
fibers are used for transmission of optical signals, and in which the
metallic materials are used for conduction of surge currents attributed to
lightning and electrical faults.
4.2.3 For the fiber optic specifications, refer to the Communications &
Computer Networks of P&CSD.
4.3.1 The fiber optical unit shall operate continuously up to ambient outdoor
temperature of +70°C without any degradation of cable guaranteed
performance.
Page 3 of 8
Document Responsibility: Communications Standards Committee 18-SAMSS-005
Issue Date: 22 July 2012
Next Planned Update: 22 July 2015 Composite Overhead Fiber Optic Ground Wire (OPGW) Specifications
4.3.2 The fiber optical unit shall be a metallic tube to house the fiber strands.
4.3.3 Filling compound shall be used to prohibit any moisture ingress from
outside or any water migration along the fiber optic unit. The filling
compound shall be able to withstand normal service conditions and shall
remain flexible (not to harden) throughout the entire expected life of the
fiber.
4.3.4.1 When buffer tubes or binders are used, the ANSI/TIA/EIA 598
shall be used.
Page 4 of 8
Document Responsibility: Communications Standards Committee 18-SAMSS-005
Issue Date: 22 July 2012
Next Planned Update: 22 July 2015 Composite Overhead Fiber Optic Ground Wire (OPGW) Specifications
4.3.5 Optical fibers shall comply with one of these standards based on the end
communication equipment:
(a) ITU-T G.652, Characteristics of a Single-Mode Optical Fiber and
Cable.
(b) ITU-T G.655, Non-zero Dispersion-shifted Single-Mode Optical
Fiber and Cable.
(c) ITU-T G.656, Characteristics of a fiber and cable with non-zero
dispersion for wideband optical transport.
5 Testing
5.1 The OPGW shall successfully pass the tests specified in the IEEE 1138 or
IEC 60794-4-10. The relevant tests are subdivided into three categories:
Type Tests, Routine Tests and Factory Acceptance Tests.
Type tests are usually conducted on new cable design. Manufacturer shall
provide Saudi Aramco with the results of these tests confirming that the cable
has passed successfully these tests according to Table (2).
Page 5 of 8
Document Responsibility: Communications Standards Committee 18-SAMSS-005
Issue Date: 22 July 2012
Next Planned Update: 22 July 2015 Composite Overhead Fiber Optic Ground Wire (OPGW) Specifications
FAT test shall be conducted on all cables. Witness tests on 10% of cables of
delivery lot as a minimum. Manufacturer shall demonstrate that the cable being
tested is exactly same as the one requested and tested during Qualification
(Type) and Routine tests. For each FAT and Type tests, individual Inspection &
test plan shall be prepared and agreed with Saudi Aramco prior to the test.
Page 6 of 8
Document Responsibility: Communications Standards Committee 18-SAMSS-005
Issue Date: 22 July 2012
Next Planned Update: 22 July 2015 Composite Overhead Fiber Optic Ground Wire (OPGW) Specifications
Test Note
Constructions Verify that the cable matches
the one tested under the
Qualification (Type) tests
5.5 The Optical Time Delay Reflectometer (OTDR) testing shall be conducted
(1) after manufacturing, (2) after receiving the cable at the site and (3) after
installation.
5.6 After “Lightning Arc” test and “Short-Circuit” tests, the remaining tensile
strength shall not be less than 75% RTS. The tensile strength can be calculated
by the tensile strength of the unbroken wires.
5.7 During the “Seepage of Flooding Compound Test”, the chamber shall be
preheated to at least 70°C. The filling compound shall not leak or drip at 70°C.
6 Markings
6.1 Composite OPGW reels shall be marked with a drum label in legible and
indelible letters providing the following particulars:
a) Manufacturer's name and country of origin
b) Year of manufacture
c) Type of cable, number of fiber strands and type
d) Serial number / supplier ID no.
e) Length and weight of composite OPGW on reel
f) Gross weight
g) Direction rolling of reel
h) BI Number/Contract Number
i) Purchase Order & Consignee Address
6.2 All markings shall appear on both sides of the reel. See Figure (1) for reel
marking location.
6.3 Composite OPGW reel identification shall include any additional information as
required by the SAUDI ARAMCO shipping instructions.
Page 7 of 8
Document Responsibility: Communications Standards Committee 18-SAMSS-005
Issue Date: 22 July 2012
Next Planned Update: 22 July 2015 Composite Overhead Fiber Optic Ground Wire (OPGW) Specifications
Revision Summary
22 July 2012 New Saudi Aramco Materials System Specification.