Professional Documents
Culture Documents
com
11
Maintenance and Inspection
No.11Chapter Maintenance and Inspection IS550Series Servo Driver User Manual
Level 1 is "fault": the servo driver has a serious alarm and cannot work normally, and needs to be shut down for processing;doThe terminal output signal is /ALM.
Level 2 is "Warning": The servo driver issues a warning state, which will not damage the equipment temporarily, but if it is not handled in time,
it may evolve into a high-level fault output;doThe terminal output signal is /WARN.
in,NO.1,NO.2Indicates the failure stop mode,NO.1: Corresponding function codeH02-05,NO.2: Corresponding function codeH02-06.
Fault codes and their codesH/LThe relationship between them is shown in the table below. The fault code is displayed asEr.xxx.
Er.107 Product model selection failure Invalid motor model or drive model NO.1 no h h h
Er.108 Parameter storage failure Parameter storage device failure NO.1 no h h h
Frequency division pulse output The number of encoder frequency division pulses does not meet the setting conditions
Er.110 NO.1 no h h h
set failure /scope
11
Product component type (such as encoder, etc.)
Er.121 servoONcommand invalid fault inertia identification,JOGfunction, etc.), from the host NO.1 Can h h h
machine input servoONOrder
motor encoderEEPROM
Er.136 motor encoderEEPROMParameter exception NO.1 no h h h
Data validation error in
- 124 -
IS550Series Servo Driver User Manual No.11Chapter Maintenance and Inspection
The phase sequence of the servo motor power cable wiring is wrong,
Er.201 Driver overcurrent2 The hardware detects the overcurrent of the power transistor; NO.1 no L L h
The encoder wiring is wrong or the encoder is damaged;
Servo power-on self-test found output The servo power-on self-test found that the power circuit of the servo motor
Er.210 NO.1 no L L h
Short circuit fault to ground Cable to ground short circuit
Er.234 flying car failure When the given feedback forms positive feedback, the motor flies NO.1 no L L h
Er.400 Overvoltage The main circuitDCvoltage too high NO.1 Can L L h
Er.410 Undervoltage The main circuitDCvoltage undervoltage NO.2 Can h h L
Phase failure during operation,R\S\Tphase of a certain
Er.420 Power line phase loss NO.2 Can h h L
The state of low phase voltage continues1more than seconds
Er.500 excessive speed The motor speed exceeds the maximum speed NO.2 Can L h L
Exceeded the set encoder frequency division pulse number
Er.510 Frequency division pulse output overspeed NO.1 Can L L L
Motor speed upper limit
Er.600 Inertia identification failure fault Inertia ID run timed out NO.1 Can L L L
The return to origin time exceeds the set value and has not yet
Er.601 Return to origin timeout fault NO.1 Can L L L
If the origin is found, this fault will be reported
Er.602 Angle recognition failure fault Initial angle identification failed NO.1 Can L L L
Running with load exceeds the drive inverse time curve setting
Running with load exceeds motor inverse time limit curve setting
heat sink
Er.650 Servo drive radiator temperature exceeds the set value NO.2 Can L L L
overheat
Er.A34 Encoder loopback verification exception The communication content with the encoder is wrong NO.1 no L h L
- 125 -
No.11Chapter Maintenance and Inspection IS550Series Servo Driver User Manual
Fully closed loop encoder position and Position and motor encoding for external fully closed-loop monitoring
Er.b02 NO.1 no L L h
Motor position deviation is too large The sensor feedback position deviation is too large
Warning codes and their encodingsH/LThe relationship between them is shown in the table below. The warning code is displayed asEr.9xx.
Er.900 Position deviation is too large Accumulated position pulse deviation exceeds the set value h h h
Automatic release
Absolute encoder angle Encoder angle re-initialization deviates too much (greater than7.2
Er.960 L L L
initialization warning electrical degree) warning
11
The bus voltage is lower than the warning value, and it is about to reach the threshold of the undervoltage fault
Er.971 Undervoltage warning L L L
warning display
Er.981 Heatsink Overheating Warning Exceeded radiator warning setpoint, not reached fault setpoint h L L
Er.990 Input phase loss warning The driver with three-phase input must be connected to two-phase operation h L L
Er.991 Communication module self-test failure warning Communication module self-test failed h L L
Er.992 Communication module communication abnormal warning Communication module communication abnormal h L L
When the servo drive fails, the digital operator will display a fault display "Er.xxx". The fault display and its treatment measures are as follows. If the fault still
cannot be eliminated after treatment, please contact the service department of our company.
- 126 -
IS550Series Servo Driver User Manual No.11Chapter Maintenance and Inspection
1.Instantaneous drop in control supply voltage Measuring supply voltage Inside, restore the factory parameters (H02-
31).
2.cut off during parameter writing Restore factory parameters (H02-31)
Confirm the time of power outage
power supply After that, enter the parameters again.
5.due to gas, water droplets or cutting oil It is possible that the servo driver is faulty.
etc. lead to internal parts of the servo driver Confirm the setting environment. Repair or replace the servo driver. change
After turning on the power several times and restoring the factory
It is possible that the servo driver is faulty.
6.Servo drive failure If the fault is still reported after setting parameters, it is possible
Repair or replace the servo driver.
It is the servo drive that has failed
Er.102 Fault still reported after turning on the power several times
(programmable logic logic device failure , it may be that the servo drive sends Repair or replace the servo driver
often) 2.Servo drive failure , it may be that the servo drive sends Repair or replace the servo driver
Er.106
Two or more View the expansion card number, according to the number
(extension cards are mutually exclusive Choose the right expansion card
mutex expansion card on View Expansion Card Instructions
Fault)
Er.107
Products that do not exist (motors, etc.) Check the product brochure to see if this product is available
(product model selection Reselect the correct product number
Number Product number
select failure)
Er.108
After changing a parameter, power on again to see If the fault still occurs after multiple power-on
(parameter storage error An exception occurred in parameter storage
Whether the parameter value is saved failure, the drive needs to be replaced
barrier)
Er.110
(Frequency division pulse output
The stroke value cannot exceed the line of the encoder
The frequency division pulse number of the encoder does not meet the setting
number; absolute value code wheel: encoder frequency division
Change the encoder frequency division pulse value function
number1/4
(product match
A drive that is not supported by the selected drive is connected Check the user manual to confirm the selected driver
barrier)
Select the correct encoder type or more
Encoder type (such asP/Atype drive Types of encoders and supported encoders
Change to another type of drive
Absolute encoders, etc. are not supported) Does the type contain such encoders
- 127 -
No.11Chapter Maintenance and Inspection IS550Series Servo Driver User Manual
Er.130
(differentDIHeavy DIWhen assigning, the same CheckH03-02,H03-04… H03-20, do
change the duplicateDIvariable
Redistributed the same variable you have the same configuration
a function)
Er.131
(differentdoHeavy doWhen assigning, the same CheckH04-00,H04-02… H04-14, do
change the duplicatedovariable
Redistributed the same a variable you have the same configuration
a function)
After eliminating the above reasons, turn on the power several times
Motor memory failure Repair or replace the servo motor
Still reporting failureEr.136
- 128 -
IS550Series Servo Driver User Manual No.11Chapter Maintenance and Inspection
Main circuit cable or motor main circuit Make sure the wiring is correct, see "
modify wiring
The cable wiring is wrong, or the contact is bad Main circuit wiring"
Internal short circuit in the cable, or a ground UVWDoes a short occur between ground and Repair or replace cable
ground short circuit road. See "Main Circuit Wiring" for details
There is a short circuit inside the servo driver or UVWAlternate,UVWIs there a It is possible that the servo driver is faulty,
Er.200 short circuit to ground short circuit to ground. See "Main Repair or replace the servo drive
(over current1)
Circuit wiring"
Maybe the encoder wiring is aging and corroded; Confirm the reliability of the encoder wiring;
Re-solder or plug in the encoder cable
The encoder plug is loose; Confirm the reliability of the drive signal cable
and drive signal cables.
The drive signal cable is loose; sex;
function codeH0a-04set too small confirmH0a-04value ChangeH0a-04value to appropriate value
The external regenerative discharge resistor is too small or short Replace with a qualified regenerative bleeder
Measuring the resistance of the regenerative bleeder resistor
road resistance
(flying car failure) Initial phase monitoring error caused by interference UVWRun when the phase sequence is correct
Power off and restart
error Just report
around;
After turning on the power supply after the controller, it still sends out
The power supply is unstable, or is affected by
Measuring supply voltage When a fault occurs, it may be the servo drive
to the impact of lightning
Overvoltage
In the case of already high voltage, enter Confirm the power voltage and running speed
driver
WillACsupply voltage regulation to the product
11
Acceleration and deceleration degree, torque/thrust within specification
Servo drive failure - However, when an alarm occurs, it is possible that the
- 129 -
No.11Chapter Maintenance and Inspection IS550Series Servo Driver User Manual
Undervoltage around;
Power supply voltage drops during operation Measuring supply voltage Increase the power supply capacitance
momentary power failure Measuring supply voltage Adjust the power supply voltage to the normal range
Er.420
Bad connection of power cable Check wiring Check whether the power cable is badly connected
Power line phase loss
motor wiringUVWPhase sequence error Confirm the wiring of the servo motor Check if there is a problem with the motor wiring
The command input value exceeds the overspeed value Confirm input command Decrease the command value, or adjust the gain
Er.601 Confirm the zero return time (H0535)yes increase (H0535) during the search process
Search time set too short
(back to origin timeout No set too short between
Fault)
Increase the low-speed crawling process and reduce the high
Stop immediately after hitting the origin at high speed Check if it stops at the origin at high speed
Faster search speed, increase search addition and subtraction
without low speed reverse crawling process end
speed time
11
See if the motor rotates during identification Remove the load or increase the current loop gain
(angular recognition lost The encoder cable is not in good contact and cannot be found
Check if the motor rotates normally Replaced wire
failure) ZSignal
- 130 -
IS550Series Servo Driver User Manual No.11Chapter Maintenance and Inspection
Er.610 The motor (or drive) runs beyond the Confirm the overload characteristics of the motor or drive Rediscuss load conditions, operating conditions
(drive overload) Overload Protection Features sex and run commands parts, motor capacity
Reset the overload fault by turning off the power Check the fault record, whether it has been reported Change the fault reset method, considering the negative
bit, made multiple runs like this load failure operating conditions
Er.650
The installation direction of the servo drive, and
radiator overheating According to the installation standard of the servo drive
The interval of other servo drives is not suitable Confirm the setting status of the servo driver
to install
reason
Er.651 The ambient temperature is too high, or the frequency of the motor Sensor monitors motor temperature or manually
The environment is ventilated and shut down for a period of time
(motor overheating) Heavy acceleration and deceleration or serious overload near
Er.740 EncoderZdisturbed;
Take shielding measures for the encoder line;
(Encoder UVWThe wiring is not normal; Check encoder wiring
Tighten the encoder terminals;
zinterference) The encoder cable is loose;
Er.741 EncoderABdisturbed;
Take shielding measures for the encoder line;
(Encoder UVWThe wiring is not normal; Check encoder wiring
Tighten the encoder terminals;
ABinterference) The encoder cable is loose;
Er.831 ADUnit data exception; ADModule failure or servo drive Power on again, if power on multiple times still
(ADsampling Drive signal when replacing control board Fault; Problem Replace Drive or Seek Tech
Fault1) loose cable; Check the drive signal cable; support or reseat the cable;
Er.833 The data of the current sampling unit is abnormal; The current sampling module is faulty or the servo drive Power on again, if power on multiple times still
(Current sampling failure Drive signal when replacing control board Actuator failure; Problem Replace Drive or Seek Tech
barrier) loose cable; Check the drive signal cable; support or reseat the cable;
11
overvoltage) Change the input module,
(resolver communication Rotary encoder encoder communication failure Twist the motor shaft by hand Problem Replace Drive or Seek Tech
Fault) support or reseat the cable;
- 131 -
No.11Chapter Maintenance and Inspection IS550Series Servo Driver User Manual
The encoder is disconnected or not connected; Check if the encoder cable is incorrectly connected
(encoder loopback
The motor model may be selected incorrectly seek technical support seek technical support
parity exception)
Encoder type may be wrongly selected seek technical support seek technical support
Er.A35 Twist the motor shaft by hand to rotate a few times to see
EncoderZno signal Check whether the encoder wire is in good contact
(Zsignal loss) Is thereZsignal output
(Position follow error Add position command acceleration and deceleration time parameters
Acceleration of position command is too large Run after reducing the command acceleration
The difference is too large)
Numeral smoothing functions (H05-06)
Relative to operating conditions, position deviation Confirm the position deviation warning value (H0a-
set correctlyH0a-11value
Excessive warning value (H0a-11) 11)is it suitable
Servo drive failure - It may be the fault of the servo drive, repair
(external encoder
Er.b03
The electronic gear ratio setting exceeds Determine the function codeH05-11/H05-10 WillH05-11/H05-10Ratio setting
(Electronic gear set
[0.001,4000]Predetermined area ratio of within the appropriate range
fixed error)
When a warning occurs in the servo drive, a fault display "Er.9xx". The warning displays and their countermeasures are as follows.
If the warning still cannot be removed after handling, please contact the service department of our company.
error code
reason confirmation method Treatment measures
11
(alert content)
The first time to use our drive Re-initialize the angle This is normal, ignore this
Initialize the serial motor and the warning disappears warn
Er.960
The motor shaft is locked by external force or Check the motor and external machinery Let the motor run without load, re-
(absolute encoder angle initial
Too much load moment connect Start the initialization operation
warning)
Motor encoder or servo drive After eliminating the above reasons, again Contact the manufacturer to replace the servo motor
- 132 -
IS550Series Servo Driver User Manual No.11Chapter Maintenance and Inspection
Note: For the gray parts in the table below, please set the power supply of the servo drive toOFFAfter checking and processing
Check the connection between the main circuit power supply terminals
The main circuit power is not connected Calibrate the main circuit power supplyONcircuit
Voltage
Check input speed/position command letter Enter the speed/position command letter correctly
No speed/position command input
Number Number
Incorrectly set control mode (H02- Check the control mode (H02-00) Set the control mode correctly (H02-
During speed control: speed command input Confirm control mode (H02-00) Correctly set or input control parameters
During torque control: Torque command input Confirm control mode (H02-00) Correctly set or input control parameters
During position control: command pulse input examine(H05-15) command pulse Correctly set or input control parameters
Deviation count clear signal (CLR) examineCLR+ andCLR- WillCLR+ andCLR-input is set
KeepONstate enter(J9-14,15) toOFF
Servo drive failure Servo drive circuit board failure Replace the servo drive
Servo motor instant Motor wiring error Check motor wiring Correct motor wiring
stop after running
stand still
Encoder wiring error Check encoder wiring Correct encoder wiring 11
power line (u,V,Wphase) and the connection of
servo motor Retighten and handle terminals and connections
Poor contact of servo motor wiring the encoder connector is unstable
rotation instability Loosening of fastening parts
Certainly
- 133 -
No.11Chapter Maintenance and Inspection IS550Series Servo Driver User Manual
During speed control: speed command input Confirm control mode (H02-00) Correctly set or input control parameters
During torque control: Torque command input Confirm control mode (H02-00) Correctly set or input control parameters
Servo drive failure Servo drive circuit board failure Replace the servo drive
Servo motor mounting screws are loose Retighten the mounting screws
Poor mechanical installation Is the axis of the coupling misaligned? Align the shaft of the coupling
Check for sound, vibration near the bearing If there is any abnormality, please contact our company
Abnormal sound in the bearing
situation department contact
The input signal line specifications are different, subject to 0.12mm2above, and specification one
Make the input signal line specifications meet the requirements
interference Twisted pair shielded with tinned annealed copper
cable
The length of the input signal wire exceeds the use Confirm that the longest wiring length is3m.
Make the length of the input signal line meet the requirements
interfered with by range Impedance is100Ωthe following
Encoder signal wire specifications are different, subject to 0.12mm2above, and specification one Make the encoder signal line specifications meet the requirements
Servo motor generator to interfere Twisted pair shielded with tinned annealed copper beg
abnormal noise cable
The length of the encoder signal wire exceeds Make the length of the encoder signal line meet the requirement
Confirm that the longest wiring length is20m
interfered with using range beg
Encoder cable produces biting, outer sheath Replace the encoder cable and correct
Interference due to damaged encoder cable
damaged, the signal line is disturbed laying method
Servo motor ground terminal electricity Check the servo motor side, welding machine, etc.
Connect the device ground to avoid coding
Bit factor servo motor side equipment (electric welding grounding status (not grounded, not
tor signal line shunt
machines, etc.) fully grounded)
Servo drive pulse due to interference Implement anti-interference measures for encoder signal lines
Encoder signal line is disturbed
punch count error apply
11
Mechanical vibration or poor motor installation
Reduce mechanical vibration and standardize the installation of servo
The encoder is subjected to excessive vibration and impact (Mounting surface accuracy, fixation, deviation
clothing motor
Heart)
- 134 -
IS550Series Servo Driver User Manual No.11Chapter Maintenance and Inspection
Factory setting:400.0Hz
Velocity Loop Gain (H08-00)set up Correct speed loop gain (H08-
Please refer to the user manual for gain adjustment
set too high 00)set up
all
Factory setting:20.0Hz
Servo motor generator Position loop gain (H08-02)set up Correct position loop gain (H08-
Please refer to the user manual for gain adjustment
The frequency is200 set too high 02)set up
all
~400Hzof
Factory setting:20.00ms
vibration Velocity loop integration time (H08- Correct speed loop integral time
Please refer to the user manual for gain adjustment
01) is not set properly (H08-01)set up
all
Load moment of inertia ratio (H08- Check load moment of inertia ratio parameter Corrected load moment of inertia ratio (H08-
Factory setting:400.0Hz
Velocity Loop Gain (H08-00)set up Correct speed loop gain (H08-
Please refer to the user manual for gain adjustment
set too high 00)set up
all
Factory setting:20.0Hz
Position loop gain (H08-02)set up Correct position loop gain (H08-
Please refer to the user manual for gain adjustment
start and stop set too high 02)set up
all
when the speed exceeds
Factory setting:20.00ms
Adjust too big Velocity loop integration time (H08- Correct speed loop integral time
Please refer to the user manual for gain adjustment
01) is not set properly (H08-01)set up
all
Corrected load moment of inertia ratio (H08-
Load moment of inertia ratio (H08- Check load moment of inertia ratio parameter
17) setting, or use the mode switch
17) is not set properly (H08-17)
Function
11
- 135 -
No.11Chapter Maintenance and Inspection IS550Series Servo Driver User Manual
Inhibit forward/reverse drive input The action of the overtravel limit switch is unstable Stabilize the operation of the overtravel limit switch
Check the Inhibit Forward Drive input signal Calibration inhibits positive drive input signal
Prohibition of forward/reverse drive input signal
(P-OT)set up(H03) (P-OT)set up(H03)
number setting error (P-OTor
Check the inhibit backdrive input signal Calibration inhibits backdrive input signal
N-OT)
(N-OT)set up(H03) (N-OT)set up(H03)
check servoOFFemergency stop correction servoOFFemergency stop
Certainly(H02-05) Certainly(H02-05)
Motor stop mode selection error
Check emergency stop setting during torque control Emergency stop setting during correction torque control
Certainly(H07-15) Certainly(H07-15)
(over superior
Twisted pair shielded cable, core wire
specified by the device
Encoder signal wire specifications are different, subject to 0.12mm2above, and specification one Make the encoder signal line specifications meet the requirements
area) to interfere Twisted pair shielded with tinned annealed copper beg
cable
The length of the encoder signal wire exceeds Make the length of the encoder signal line meet the requirement
Confirm that the longest wiring length is20m
interfered with using range beg
Encoder cable produces biting, outer sheath Replace the encoder cable and correct
Interference due to damaged encoder cable
damaged, the signal line is disturbed laying method
Servo motor ground terminal electricity Check the servo motor side, welding machine, etc.
Connect the device ground to avoid coding
Bit factor servo motor side equipment (electric welding grounding status (not grounded, not
tor signal line shunt
machines, etc.) fully grounded)
Servo drive pulse due to interference Implement anti-interference measures for encoder signal lines
Encoder signal line is disturbed
punch count error apply
11 Mechanical and servo motor coupling difference Coupling part of machine and servo motor Correctly connect the machine and the servo motor
Encoder failure (pulse does not change) Encoder failure (pulse does not change) Replace Servo Motor
- 136 -
IS550Series Servo Driver User Manual No.11Chapter Maintenance and Inspection
Ambient temperature is too high Measure the ambient temperature of the servo motor Lower the ambient temperature to40below ℃
becauseACServo motors do not have brushes, so simple daily checks are all that is required. The inspection time in the table is an approximate standard. Please judge according to
the usage and usage environment to determine the most appropriate inspection time.
Notice
Check item check the time Inspection and maintenance essentials Remark
Confirmation with vibration and sound every day Judging by feeling and hearing no increase compared to usual
Visual inspection According to the state of pollution Wipe with a cloth or clean with an air gun -
Cut off the connection to the servo drive,
at least every5000Hour1 Remove the servo motor from the machine, then
Oil seal replacement Servo motors with oil seal only
Second-rate After replacing the oil seal
At least20000hours or
comprehensive inspection Please contact our service department Please do not disassemble the servo motor by yourself
By5Year1Second-rate
Although daily inspections are not necessary, please check annually1more than times.
Check item check the time Inspection and maintenance essentials Remark
Cleaning of main body and circuit board No litter, dust, oil stains, etc. Wipe with a cloth or clean up with an air gun.
11
Loosening of screws Tighten further.
at least once a year There must be no looseness.
The main body and parts on the circuit board There must be no discoloration due to heat,
Please contact our service department.
Exception Damaged and short-term etc.
Electrical and electronic components are subject to mechanical wear and aging. To ensure safety, please conduct regular inspections.
For the servo drive overhauled by our company, its user parameters have been transferred back to the factory settings. Be sure to reset to the user parameters
- 137 -
No.11Chapter Maintenance and Inspection IS550Series Servo Driver User Manual
Part Name Standard replacement period Replacement method, others Conditions of Use
Fan Service Life: Fan Life Estimates40000Hours (at rated voltage, ambient temperature of40℃, when the fan is running continuously at full
speed).
If the fan is covered with foreign matter, the performance of the fan will be reduced, and the air volume will be reduced. After the air duct is blocked, the wind resistance will increase, and the air volume
will also be reduced, which will affect the heat dissipation of the motor. When the temperature of the motor winding exceeds the motor protection temperature, the drive will reportERR45(IS300series drive)
error.
1, Remove the fixed air duct cover at the motor tail8screws (G1forM4inner hexagon,G2forM5Inner hexagon screws, cross recessed pan head screws were
2. After removing the cover plate, use a small flat-head screwdriver to clean the foreign matter on the surface of the fan. The foreign matter in the air duct should be cleaned as much as possible. No
foreign matter hinders the air path. After cleaning, blow it again with a high-pressure air gun;
3, After the cleaning is completed, cover the cover plate, tighten the original screws, and the cleaning is completed;
4, Determine the cleaning frequency of the fan according to the actual work site conditions.
11
- 138 -
12
appendix
No.12Chapter Appendix IS550Series Servo Driver User Manual
No.12Chapter Appendix
0-220V
H00 09 Rated voltage - - -
1-380V
H00 10 rated power 0.01kW~655.35kW 0.01kW - Effective immediately -
H00 11 rated current 0.001~655.35A 0.01A - Effective immediately -
H00 12 Rated torque 0.10Nm~655.35Nm 0.01Nm - Effective immediately -
H00 13 Maximum torque 0.10Nm~655.35Nm 0.01Nm - Effective immediately -
H00 14 Rated speed 1 rpm~9000rpm 1 rpm - Effective immediately -
H00 15 Maximum speed 1 rpm~9000rpm 1 rpm - Effective immediately -
0.01㎏c㎡〜655.35㎏ c 0.01
H00 16 Moment of inertiajm - -
㎏c㎡
Effective immediately
㎡
connect again
H00 17 2~360Opposite
Number of pole pairs of permanent magnet synchronous motor 1Opposite - -
after power
12
- 140 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
device (UVW-ABZ)
001-Wire-saving encoder
(ABZ(UVW))
002- Incremental encoder
(WithoutUVW)//None 001(HTie connect again
H00 30 Encoder selection (HEX) 1 -
010-Tamagawa absolute formula List:010) power supply
Encoder
amount, absolute)//none
020-SIN/COSEncoder
021-Resolver
connect again
H00 33 Initialize electrical angle 0.0°〜360.0° 0.1° 0.0° -
power supply
connect again
H00 34 uPhase electrical angle 0.0°〜360.0° 0.1° 0.0° -
power supply
connect again
H00 35 Resolver pole pairs 1—360 1 1 -
power supply
connect again
H01 10 Carrier period 4000Hz~8000Hz - 4000Hz -
after power
- 141 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
run
H01 20 Dead zone compensation - 500.0~500.0 0.1% 80.0 Effective immediately
set up
run
H01 27 Current loop proportional gainKp 1~65535 1 2000 Effective immediately -
set up
run
H01 28 Current Loop Integral Gain 0~65535 1 2000 Effective immediately -
set up
run
H01 30 Bus Voltage Gain Adjustment 50.0%~150.0% 0.001 100.0% Effective immediately -
set up
run
H01 31 Current correction factor 50.0%~150.0% 0.001 100.0% Effective immediately -
set up
shutdown
H01 33 AnalogAI1dead zone adjustment 0%~200% 0.01 2% Effective immediately -
set up
shutdown
H01 34 AnalogAI2dead zone adjustment 0%~200% 0.01 2% Effective immediately -
set up
shutdown
H01 35 AnalogAI3dead zone adjustment 0%~200% 0.01 2% Effective immediately -
set up
shutdown
H01 36 OffsetAI1Input voltage1 - 12000mV~1200mV 1mV 10000mV Effective immediately -
set up
shutdown
H01 37 OffsetAI1Sampling voltage1 - 12000mV~1200mV 1mV 10000mV Effective immediately -
set up
shutdown
H01 38 OffsetAI1Input voltage2 - 12000mV~1200mV 1mV - 10000mV Effective immediately -
set up
shutdown
H01 39 OffsetAI1Sampling voltage2 - 12000mV~1200mV 1mV - 10000mV Effective immediately -
set up
shutdown
H01 40 OffsetAI2Input voltage1 - 12000mV~1200mV 1mV 10000mV Effective immediately -
set up
shutdown
H01 41 OffsetA2Sampling voltage1 - 12000mV~1200mV 1mV 10000mV Effective immediately -
set up
shutdown
H01 42 OffsetAI2Input voltage2 - 12000mV~1200mV 1mV - 10000mV Effective immediately
set up
shutdown
H01 43 OffsetAI2Sampling voltage2 - 12000mV~1200mV 1mV - 10000mV Effective immediately -
set up
shutdown
H01 44 OffsetAI3Input voltage1 - 12000mV~1200mV 1mV 10000mV Effective immediately -
set up
set up
-
shutdown
H01 46 OffsetAI3Input voltage2 - 12000mV~1200mV 1mV - 10000mV Effective immediately -
set up
shutdown
H01 47 OffsetAI3Sampling voltage2 - 12000mV~1200mV 1mV - 10000mV Effective immediately -
set up
- 142 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
2-torque mode
3-speed mode↔torque mode 1 shutdown
H02 00 Control mode selection 1 Effective immediately -
4-location mode↔speed mode 1(P/H) set up
6-location mode↔speed↔
0-byCCWDirection is forward
direction(AadvancedB)
shutdown
H02 02 Rotation direction selection 1-byCWdirection is forward 1 0 Effective immediately PST
set up
to (reverse mode,Astagnant
backB)
0-byCCWDirection is forward
direction(AadvancedB)
Output pulse feedback direction connect again shutdown
H02 03 1-byCWdirection is forward 1 0 PST
choose after power set up
to (reverse mode,Astagnant
backB)
state
H02 10
Brake command--servoOFF
delay
1ms~500ms 1ms 100ms Effective immediately
shutdown
set up
PST 12
Brake command output speed shutdown
H02 11 0rpm~1000rpm 1 rpm 100rpm Effective immediately PST
limit value set up
- 143 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
shutdown
H02 20 Motor electrical angle offset 0-50.0 0.1Spend 0 Power on again -
set up
different models
Allowable power consumption of the drive
H02 twenty one 1~1000ohms read only 1ohm different silent Effective immediately show -
Minimum value of resistance
Default value
shutdown
H02 twenty four Momentary power failure holding time 20ms~1000ms 1ms 20 Effective immediately PST
set up
absorption by capacitance
different models
External energy consumption resistor power shutdown
H02 26 1W~65535W 1W different silent Effective immediately -
capacity set up
Default value
different models
User can set shutdown
H02 27 Resistance value of external energy consumption resistor 1ohm different silent Effective immediately -
1ohm~1000ohm set up
Default value
H02 28
H02 29
connect again shutdown
H02 30 user password 0~65535 1 0 -
after power set up
0-no action
1-Restore factory settings shutdown
H02 31 System parameter initialization 1 0 Effective immediately -
(removeH0/1group parameter) set up
run
H02 32 default display selection 0-50 1 50 Effective immediately
set up
Reserved parameters
Reserved parameters
H02 41 0~65535 - - - - -
(factory password)
12
H3Group Terminal Input Parameters
0~0xFFFF
Bit0-correspondFun IN.1;
Fun INLsignal not assigned connect again run
H03 00 Bit1-correspondFun IN.2 1 0 -
status(HEX) after power set up
;…
Bit15-correspondFun IN.16
- 144 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
0~0xFFFF
Bit0-correspondFun IN.17;
Fun INHsignal not assigned connect again run
H03 01 Bit1-correspondFun IN.18 1 0 -
status(HEX) after power set up
;…
Bit15-correspondFun IN.32
(refer toDIDObasic
function code list)
Input polarity:0-4
0-Indicates active low
1-Indicates active high
connect again run
H03 03 DI1Terminal logic selection 2-Indicates that the rising edge is valid 1 0 -
after power set up
3-Indicates that the falling edge is valid
efficient
(refer toDIDObasic
function code list)
Input polarity:0-4
0-Indicates active low
1-Indicates active high
connect again run
H03 05 DI2Terminal logic selection 2-Indicates that the rising edge is valid 1 0 -
after power set up
3-Indicates that the falling edge is valid
efficient
(refer toDIDObasic
function code list)
Input polarity:0-4
0-Indicates active low
1-Indicates active high
run
12
connect again
H03 07 DI3Terminal logic selection 2-Indicates that the rising edge is valid 1 0 -
after power set up
3-Indicates that the falling edge is valid
efficient
- 145 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
(refer toDIDObasic
function code list)
Input polarity:0-4
0-Indicates active low
1-Indicates active high
connect again run
H03 09 DI4Terminal logic selection 2-Indicates that the rising edge is valid 1 0 -
after power set up
3-Indicates that the falling edge is valid
efficient
(refer toDIDObasic
function code list)
Input polarity:0-4
0-Indicates active low
1-Indicates active high
connect again run
H03 11 DI5Terminal logic selection 2-Indicates that the rising edge is valid 1 0 -
after power set up
3-Indicates that the falling edge is valid
efficient
(refer toDIDObasic
function code list)
Input polarity:0-4
0-Indicates active low
1-Indicates active high
connect again run
H03 13 DI6Terminal logic selection 2-Indicates that the rising edge is valid 1 0 -
after power set up
3-Indicates that the falling edge is valid
efficient
12 1-32
0-no definition connect again run
H03 14 DI7Terminal function selection 1 8 -
1~32:Fun IN.1~ 32 after power set up
(refer toDIDObasic
function code list)
- 146 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
Input polarity:0-4
0-Indicates active low
1-Indicates active high
connect again run
H03 15 DI7Terminal logic selection 2-Indicates that the rising edge is valid 1 0 -
after power set up
3-Indicates that the falling edge is valid
efficient
(refer toDIDObasic
function code list)
Input polarity:0-4
0-Indicates active low
1-Indicates active high
connect again run
H03 17 DI8Terminal logic selection 2-Indicates that the rising edge is valid 1 0 -
after power set up
3-Indicates that the falling edge is valid
efficient
(refer toDIDObasic
function code list)
Input polarity:0-4
0-Indicates active low
1-Indicates active high
connect again run
H03 19 DI9Terminal logic selection 2-Indicates that the rising edge is valid 1 0 -
after power set up
3-Indicates that the falling edge is valid
efficient
(refer toDIDObasic
function code list)
Input polarity:0-4
0-Indicates active low
1-Indicates active high
12
connect again run
H03 twenty oneDI10Terminal logic selection 2-Indicates that the rising edge is valid 1 0 -
after power set up
3-Indicates that the falling edge is valid
efficient
- 147 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
shutdown
H03 50 AI1minimum input - 10.00V~10.00V 0.01V - 10.00V Effective immediately -
set up
shutdown
H03 52 AI1input - 10.00V~10.00V 0.01V 10.00V Effective immediately -
set up
run
H03 54 AI1Zero trim - 500.0mV~500.0mV 0.1mV 0mV Effective immediately -
set up
shutdown
H03 56 AI1input filter time 0.00ms~655.35ms 0.01ms 2.00ms Effective immediately -
set up
shutdown
H03 57 AI2minimum input - 10.00V~10.00V 0.01V - 10.00V Effective immediately -
set up
shutdown
H03 59 AI2input - 10.00V~10.00V 0.01V 10.00V Effective immediately -
set up
run
H03 61 AI2Zero trim - 500.0mV~500.0mV 0.1mV 0mV Effective immediately -
set up
shutdown
H03 63 AI2input filter time 0.00ms~655.35ms 0.01ms 2.00ms Effective immediately -
set up
shutdown
H03 64 AI3minimum input - 10.00V~10.00V 0.01V - 10.00V Effective immediately -
set up
shutdown
H03 66 AI3input - 10.00V~10.00V 0.01V 10.00V Effective immediately -
set up
run
H03 68 AI3Zero trim - 500.0mV~500.0mV 0.1mV 0mV Effective immediately -
set up
shutdown
H03 70 AI3input filter time 0.00ms~655.35ms 0.01ms 2.00ms Effective immediately -
set up
12 H03 80
Analog100%corresponding speed
degree value
0rpm-9000rpm 1 rpm 3000rpm Effective immediately
shutdown
set up
-
Analog100%Corresponding turn 1.00times ~8.00times rated 1.00Double the amount 1.00Double the amount shutdown
H03 81 Effective immediately -
Moment torque constant torque constant torque set up
- 148 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
Output encoding:1~16
0: no definition
shutdown
H04 00 DO1Terminal function selection 1~16: 1 1 Effective immediately -
set up
Fun OUT.1~16refer to DIDO
0-1
DO1Terminal logic level 0-output when validL shutdown
H04 01 1 0 Effective immediately -
choose Low level (optocoupler conduction) set up
Output encoding:1~16
0: no definition
shutdown
H04 02 DO2Terminal function selection 1~16: 1 4 Effective immediately -
set up
Fun OUT.1~16refer to DIDO
0-1
DO2Terminal logic level 0-output when validL shutdown
H04 03 1 0 Effective immediately -
choose Low level (optocoupler conduction) set up
Output encoding:1~16
0: no definition
shutdown
H04 04 DO3Terminal function selection 1~16: 1 3 Effective immediately -
set up
Fun OUT.1~16refer to DIDO
0-1
DO3Terminal logic level 0-output when validL shutdown
H04 05 1 0 Effective immediately -
choose Low level (optocoupler conduction) set up
Output encoding:1~16
0: no definition
shutdown
H04 06 DO4Terminal function selection 1~16: 1 10 Effective immediately -
set up
Fun OUT.1~16refer to DIDO
12
Output polarity inversion setting:
0-1
DO4Terminal logic level 0-output when validL shutdown
H04 07 1 0 Effective immediately -
choose low level set up
- 149 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
Output encoding:1~17
0: no definition
shutdown
H04 10 DO6Terminal function selection 1~17:Fun OUT.1~ 17refer 1 12 Effective immediately -
set up
toDIDOfunction selection
code selection definition
Output encoding:1~17
0: no definition
shutdown
H04 12 DO7Terminal function selection 1~17:Fun OUT.1~ 17refer 1 13 Effective immediately -
set up
toDIDOfunction selection
code selection definition
Output encoding:1~17
0: no definition
shutdown
H04 14 DO8Terminal function selection 1~17:Fun OUT.1~ 17refer 1 14 Effective immediately -
set up
toDIDOfunction selection
code selection definition
Bit0-DO1source
...
Bit7-DO8source
Bit8~Bit15reserved. shutdown
H04 twenty two dosource selection - 0 Effective immediately PST
set up
Bitx=0:DO(x+1)given
by the driver;
Bitx=1:DO(x+1)given by
communication
12
- 150 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
00-Motor speed
(1V/1000rpm)default
01-speed command
(1V/1000rpm)
02-Torque command
(1V/100%)
03-Position deviation
(0.05V/1command unit)
04-Position Amplifier Offset
run
H04 50 AO1signal selection Poor (after electronic gear) 1 0 Effective immediately -
set up
(0.05V/1Encoder pulse
unit)
05-Position command speed
(1V/1000rpm)
06-Positioning completion command (setting
Finish:0V)
07-speed feedforward
(1V/1000rpm)
run
H04 51 AO1Bias voltage 0-10000mV 1mV 5000mV Effective immediately -
set up
run
H04 52 AO1magnification - 99.99~99.99 0.01times 1.00 Effective immediately -
set up
0-Pulse command
H05 01
- 9999Command unit~ shutdown
H05 03 step amount 1command unit 50 Effective immediately P
9999command unit set up
H05 04 - - - - - - -
H05 05 - - - - - - -
Position instruction moving average shutdown
H05 06 0.0ms~128.0ms 0.1ms 0.0ms Effective immediately P
time set up
- 151 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
edit. (Defaults)
1-direction+pulse, negative logic
connect again shutdown
H05 15 Burst Morphology 2-APhase +BPhase Orthogonal Vein 1 0 P
after power set up
rush,4multiplier
3-CW+CCW(Pulse type
The drive does not have this function)
0-servoOFFand accident
clear position deviation pulse
shutdown
H05 16 clear action selection rush 1 0 Effective immediately P
set up
1-Clear bit on fault
offset pulse
out
1-The absolute value of the position deviation is small
for0time output
positioning complete approach signal 1Command unit~65535refer to 1order sheet 65535refer to shutdown
H05 twenty two Effective immediately P
amplitude order unit bit order unit set up
run
H05 27 0~1000
Interrupt fixed-length acceleration and deceleration time 1ms 100ms Effective immediately P
set up
12
Internal and external position deviation clear 0: clear run
H05 28 1 0 Effective immediately P
choose 1: do not clear set up
- 152 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
able;
1-passDIenter
ORGSETsignal to enable
Return to origin function;
2-passDIenter
ORGSETsignal enable run
H05 30 Return-to-origin enable control 1 0 Effective immediately P
Air return to origin function; set up
point return;
4-Return to origin immediately
make
6-Take the current position as the origin
machineZSignal
machineZSignal
shutdown
H05 35 Limit the time to find the origin 0-65535 ms 10000 Effective immediately P
set up
12
- 153 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
0-H05.36return to origin
After the coordinate value, the row encountered
1-H05.36return to origin
After the relative moving distance,
3-H05.36return to origin
After the relative moving distance,
origin
H05 41 Motor load deviation is too large - 2^31arrive2^31 1p 8192 Shutdown setting
run
H05 44 closed loop gain coefficient numerator 1-65535 1 1 Effective immediately P
set up
use
2-in reverse running direction
connect again shutdown
H05 45 Position closed-loop control mode use 1 0
after power set up
3-closed loopIOswitch and mark
run
H05 46 Closed-loop gain coefficient denominator 1-65535 1 1 Effective immediately P
set up
0-digital given
(H0603)
1-AI1 shutdown
H06 00 main speed commandAsource 1 0 Effective immediately S
2-AI2 set up
12 3-AI3
4-Jog speed command
- 154 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
0-digital given
(H0603)
1-AI1
2-AI2
shutdown
H06 01 Auxiliary speed commandBsource 3-AI3 1 3 Effective immediately S
set up
4-Jog speed command
6-reserve
7-reserve
4-Communication given
run
H06 04 Jog speed setpoint 0rpm~9000rpm 1 rpm 300rpm Effective immediately S
set up
shutdown
H06 07 Maximum speed limit 0rpm-9000rpm 1 rpm 9000rpm Effective immediately S
set up
shutdown
H06 08 forward speed limit 0rpm-9000rpm 1 rpm 9000rpm Effective immediately S
set up
shutdown
H06 09 speed reverse limit 0rpm-9000rpm 1 rpm 9000rpm Effective immediately S
set up
shutdown
H06 15 Zero fixed speed limit fixed value 0rpm~1000rpm 1 rpm 10rpm Effective immediately S
set up
shutdown
H06 17 Speed arrival signal width 0rpm~100rpm 1 rpm 10rpm Effective immediately PST
set up
12
H07Group torque control parameters
3-AI3
- 155 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
5-reserve
6-reserve
run
H07 03 Torque command keyboard setting value - 300.0%~300.0% 0.001 0 Effective immediately T
set up
shutdown
H07 05 Torque command filter time 0.00ms~655.35ms 0.01ms 0ms Effective immediately PST
set up
shutdown
H07 06 Torque command filter time2 0.00ms~655.35ms 0.01ms 0ms Effective immediately PST
set up
system (default)
(useP-CL,N-CL
choose)
shutdown
H07 07 Torque limit source 2-WillT-LMTused as external 1 0 Effective immediately PST
set up
Torque limit input
3-Take positive and negative external torque and
externalT-LMTminimum value of
P-CL,N-CLchoose)
1-AI1
shutdown
H07 08 T-LMTchoose 2-AI2 1 2 Effective immediately PST
set up
3-AI3
0.0%~300.0%
No.1Forward internal torque limit shutdown
H07 09 (100%Corresponding to double the rated 0.001 2.5 Effective immediately PST
system set up
Torque)
0.0%~300.0%
No.1Reverse internal torque limit shutdown
H07 10 (100%Corresponding to double the rated 0.001 2.5 Effective immediately PST
system set up
Torque)
0.0%~300.0%
12
shutdown
H07 11 Forward rotation side external torque limit (100%Corresponding to double the rated 0.001 2.5 Effective immediately PST
set up
Torque)
0.0%~300.0%
shutdown
H07 12 Reverse side external torque limit (100%Corresponding to double the rated 0.001 2.5 Effective immediately PST
set up
Torque)
- 156 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
0.0%~300.0%
shutdown
H07 15 Emergency stop torque (100%Corresponding to double the rated 0.001 1 Effective immediately PST
set up
Torque)
1-AI1
shutdown
H07 18 V-LMTchoose 2-AI2 1 3 Effective immediately T
set up
3-AI3
Internal speed under torque control shutdown
H07 19 0rpm-9000rpm 1 rpm 3000rpm Effective immediately T
degree limit set up
run
H08 00 speed loop gain 1.0Hz~2000.0Hz 0.1Hz 400.0Hz Effective immediately P.S.
set up
run
H08 02 Position loop gain 1.0Hz~2000.0Hz 0.1Hz 20.0Hz Effective immediately P
set up
run
H08 03 No.2speed loop gain 1.0Hz~2000.0Hz 0.1Hz 400.0Hz Effective immediately P.S.
set up
run
H08 05 No.2Position loop gain 1.0Hz~2000.0Hz 0.1Hz 20.0Hz Effective immediately P
set up
run
H08 06 Gain switching time1 0~65535 1ms 10 Effective immediately P
set up
run
H08 07 Gain switching time2 0~65535 1ms 10 Effective immediately P
set up
run
H08 08 Gain switching wait time1 0~65535 1ms 0 Effective immediately P.S.
set up
run
H08 09 Gain switching wait time2 0~65535 1ms 0 Effective immediately P.S.
set up
12
- 157 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
set to No.1gain
1-Manual Gain Switching
(H0811)
3-Take position pulse difference as bar
(H0812)
5-Conditional on torque command
(H0813)
Gain switching position deviation shutdown
H08 11 0~65535 P 30 Effective immediately P
Conditional magnitude (threshold) set up
H08 14
Load moment of inertia ratio flat run
H08 15 1.00~120.00 0.01 1.00 Effective immediately PST
average set up
H08 16 Moment of inertia identification current value 1.00~120.00 0.01 1.00 -- show
Speed feed-forward filter time run
H08 18 0.00ms~64.00ms 0.01ms 0.00ms Effective immediately P
parameter set up
run
H08 19 Velocity Feedforward Gain 0.0%~100.0% 0.1% 0.0% Effective immediately P
set up
run
12 H08 twenty one Torque Feedforward Gain 0.0%~200.0% 0.1% 0.0% Effective immediately
set up
P
shutdown
H08 twenty two Speed feedback filter time 0-64.00 0.01ms 0 Effective immediately P.S.
set up
0-PIcontrol
shutdown
H08 25 Speed loop control method 1-P-PIswitch control 1 0 Effective immediately P.S.
set up
2-IPcontrol
- 158 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
condition
condition
P-PIToggle condition location 0Command unit~10000refer to 1order sheet 0order sheet shutdown
H08 30 Effective immediately P
deviation order unit bit bit set up
0-prohibit shutdown
H0A 03 Power-down save enable option 1 0 Effective immediately
1-Enable set up
run
H0A 04 Motor overload protection gain 50%-3000% 0.01 1 Effective immediately -
set up
shutdown
H0A 05 Overload warning value 1%~100% 0.01 0.8 Effective immediately -
set up
pressure warning
When the main circuit is under voltage shutdown
H0A 08 1-Detect main circuit undervoltage 1 0 Effective immediately -
feature selection set up
warn
2-reserve
shutdown
H0A 09 Resolver Communication Fault Threshold 0-20 1 4 Effective immediately -
set up
- 159 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
run
H0A 25 Second encoder filter setting 0-200 20ns 20 Effective immediately -
set up
shutdown
H0A 29 Bus voltage filter time 0-3.000 0.001ms 3.000 Effective immediately -
set up
H0bgroup display
12
Feedback pulse counter
- 160 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
1-superior1fault
run
H0b 33 Display of fault records 2-superior2fault 1 0 Effective immediately
set up
...
9-superior9fault
first failure
H0b 34 error code - - -
code
H0b 35 Selected failure timestamp - 0.1s - show
H0b 37 The current speed at the time of the selected fault - 1 rpm - - show
current power at the time of the selected fault
H0b 38 - 0.01A - - show
flowu
shutdown
H0C 00 Servo axis address 1~247,0broadcast address 1 1 Effective immediately -
set up
0-2400
1-4800
bpserror shutdown
H0C 02 Serial port baud rate setting 2-9600 5 Effective immediately -
+ - 5% set up
3-19200 4-38400
5-57600
shutdown
H0C 11 communication virtualVDO 0-disabled1-Enable 1 0 Effective immediately PST
set up
- 161 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
Bit0-VDO1Defaults
VDOThe function is selected as0 shutdown
H0C 12 ...Bit15-VDO16silent 1 0 Effective immediately PST
default value set up
default value (HEX)
0x03/0x06/0x10
to the dataframe'sCRCcheck
code and data frame check code
not equal
mistake
0x0030
0x10Write16bit function code
running
MODBUScommand response run
H0C 25 0-5000ms 1 0 Effective immediately PST
time delay set up
0-high16first, lower16
after the (
MODBUS32bit function Use the background to modify the function code or run
H0C 26 1 0 Effective immediately -
code transmission sequence When reading the function code, it is set to0) set up
12
1-Low16first, high16 in
the back
- 162 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
0-no action
H0d 03 Encoder initial angle identification 1 0 - reserve -
1-start angular initialization
shutdown
H0d 11 JOGFunction 0~Rated speed 1 rpm 100 Effective immediately -
set up
select)
- 1073741824~ run
1order sheet 10000refer to
H11 12 No.1segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
- 163 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
run
No.1Segment displacement maximum operation
H11 14 0rpm~9000rpm rpm 200 Effective immediately When set P
speed
Certainly
run
No.1During segment displacement acceleration and deceleration
H11 15 0~1000 1ms 100ms Effective immediately When set P
between
Certainly
run
No.1After the segment displacement is completed, wait
H11 16 0~10000 1ms(1s) 10 Effective immediately When set P
waiting time
Certainly
- 1073741824~ run
1order sheet 10000refer to
H11 17 No.2segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
run
No.2Segment displacement maximum operation
H11 19 0rpm~9000rpm rpm 200 Effective immediately When set P
speed
Certainly
run
No.2During segment displacement acceleration and deceleration
H11 20 0~1000 1ms 100ms Effective immediately When set P
between
Certainly
run
No.2After the segment displacement is completed, wait
H11 twenty one 0~10000 1ms(1s) 10 Effective immediately When set P
waiting time
Certainly
- 1073741824~ run
1order sheet 10000refer to
H11 twenty two No.3segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
run
No.3Segment displacement maximum operation
H11 twenty four 0rpm~9000rpm rpm 200 Effective immediately When set P
speed
Certainly
run
No.3During segment displacement acceleration and deceleration
H11 25 0~1000 1ms 100ms Effective immediately When set P
between
Certainly
run
No.3After the segment displacement is completed, wait
H11 26 0~10000 1ms(1s) 10 Effective immediately When set P
waiting time
Certainly
- 1073741824~ run
1order sheet 10000refer to
H11 27 No.4segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
run
No.4Segment displacement maximum operation
H11 29 0rpm~9000rpm rpm 200 Effective immediately When set P
12
speed
Certainly
run
No.4During segment displacement acceleration and deceleration
H11 30 0~1000 1ms 100ms Effective immediately When set P
between
Certainly
- 164 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
run
No.4After the segment displacement is completed, wait
H11 31 0~10000 1ms(1s) 10 Effective immediately When set P
waiting time
Certainly
- 1073741824~ run
1order sheet 10000refer to
H11 32 No.5segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
run
No.5Segment displacement maximum operation
H11 34 0rpm~9000rpm rpm 200 Effective immediately When set P
speed
Certainly
run
No.5During segment displacement acceleration and deceleration
H11 35 0~1000 1ms 100ms Effective immediately When set P
between
Certainly
run
No.5After the segment displacement is completed, wait
H11 36 0~10000 1ms(1s) 10 Effective immediately When set P
waiting time
Certainly
- 1073741824~ run
1order sheet 10000refer to
H11 37 No.6segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
run
No.6Segment displacement maximum operation
H11 39 0rpm~9000rpm rpm 200 Effective immediately When set P
speed
Certainly
run
No.6During segment displacement acceleration and deceleration
H11 40 0~1000 1ms 100ms Effective immediately When set P
between
Certainly
run
No.6After the segment displacement is completed, wait
H11 41 0~10000 1ms(1s) 10 Effective immediately When set P
waiting time
Certainly
- 1073741824~ run
1order sheet 10000refer to
H11 42 No.7segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
run
No.7Segment displacement maximum operation
H11 44 0rpm~9000rpm rpm 200 Effective immediately When set P
speed
Certainly
run
No.7During segment displacement acceleration and deceleration
H11 45 0~1000 1ms 100ms Effective immediately When set P
between
Certainly
run
No.7After the segment displacement is completed, wait
H11 46 0~10000 1ms(1s) 10 Effective immediately When set P
12
waiting time
Certainly
- 1073741824~ run
1order sheet 10000refer to
H11 47 No.8segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
- 165 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
run
No.8Segment displacement maximum operation
H11 49 0rpm~9000rpm rpm 200 Effective immediately When set P
speed
Certainly
run
No.8During segment displacement acceleration and deceleration
H11 50 0~1000 1ms 100ms Effective immediately When set P
between
Certainly
run
No.8After the segment displacement is completed, wait
H11 51 0~10000 1ms(1s) 10 Effective immediately When set P
waiting time
Certainly
- 1073741824~ run
1order sheet 10000refer to
H11 52 No.9segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
run
No.9Segment displacement maximum operation
H11 54 0rpm~9000rpm rpm 200 Effective immediately When set P
speed
Certainly
run
No.9During segment displacement acceleration and deceleration
H11 55 0~1000 1ms 100ms Effective immediately When set P
between
Certainly
run
No.9After the segment displacement is completed, wait
H11 56 0~10000 1ms(1s) 10 Effective immediately When set P
waiting time
Certainly
- 1073741824~ run
1order sheet 10000refer to
H11 57 No.10segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
run
No.10Maximum segment displacement
H11 59 0rpm~9000rpm rpm 200 Effective immediately When set P
line speed
Certainly
run
No.10Segment displacement acceleration and deceleration
H11 60 0~1000 1ms 100ms Effective immediately When set P
time
Certainly
run
No.10After segment displacement is completed
H11 61 0~10000 1ms(1s) 10 Effective immediately When set P
waiting time
Certainly
- 1073741824~ run
1order sheet 10000refer to
H11 62 No.11segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
run
No.11Maximum segment displacement
H11 64 0rpm~9000rpm rpm 200 Effective immediately When set P
12
line speed
Certainly
run
No.11Segment displacement acceleration and deceleration
H11 65 0~1000 1ms 100ms Effective immediately When set P
time
Certainly
- 166 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
run
No.11After segment displacement is completed
H11 66 0~10000 1ms(1s) 10 Effective immediately When set P
waiting time
Certainly
- 1073741824~ run
1order sheet 10000refer to
H11 67 No.12segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
run
No.12Maximum segment displacement
H11 69 0rpm~9000rpm rpm 200 Effective immediately When set P
line speed
Certainly
run
No.12Segment displacement acceleration and deceleration
H11 70 0~1000 1ms 100ms Effective immediately When set P
time
Certainly
run
No.12After segment displacement is completed
H11 71 0~10000 1ms(1s) 10 Effective immediately When set P
waiting time
Certainly
- 1073741824~ run
1order sheet 10000refer to
H11 72 No.13segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
run
No.13Maximum segment displacement
H11 74 0rpm~9000rpm rpm 200 Effective immediately When set P
line speed
Certainly
run
No.13Segment displacement acceleration and deceleration
H11 75 0~1000 1ms 100ms Effective immediately When set P
time
Certainly
run
No.13After segment displacement is completed
H11 76 0~10000 1ms(1s) 10 Effective immediately When set P
waiting time
Certainly
- 1073741824~ run
1order sheet 10000refer to
H11 77 No.14segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
run
No.14Maximum segment displacement
H11 79 0rpm~9000rpm rpm 200 Effective immediately When set P
line speed
Certainly
run
No.14Segment displacement acceleration and deceleration
H11 80 0~1000 1ms 100ms Effective immediately When set P
time
Certainly
run
No.14After segment displacement is completed
H11 81 0~10000 1ms(1s) 10 Effective immediately When set P
12
waiting time
Certainly
- 1073741824~ run
1order sheet 10000refer to
H11 82 No.15segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
- 167 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
run
No.15Maximum segment displacement
H11 84 0rpm~9000rpm rpm 200 Effective immediately When set P
line speed
Certainly
run
No.15Segment displacement acceleration and deceleration
H11 85 0~1000 1ms 100ms Effective immediately When set P
time
Certainly
run
No.15After segment displacement is completed
H11 86 0~10000 1ms(1s) 10 Effective immediately When set P
waiting time
Certainly
- 1073741824~ run
1order sheet 10000refer to
H11 87 No.16segment shift 1073741824(order sheet Effective immediately When set P
bit order unit
bit) Certainly
run
No.16Maximum segment displacement
H11 89 0rpm~9000rpm rpm 200 Effective immediately When set P
line speed
Certainly
run
No.16Segment displacement acceleration and deceleration
H11 90 0~1000 1ms 100ms Effective immediately When set P
time
Certainly
run
No.16After segment displacement is completed
H11 91 0~10000 1ms(1s) 10 Effective immediately When set P
waiting time
Certainly
H12group multi-speed
select)
select)
2-through externalDIcut
Change
0-sec shutdown
H12 02 Run time unit selection 1 0 Effective immediately
1-min set up
shutdown
H12 03 acceleration time1 0ms~10000ms 1ms 10ms Effective immediately
set up
shutdown
H12 04 deceleration time1 0ms~10000ms 1ms 10ms Effective immediately
set up
set up
shutdown
H12 06 deceleration time2 0ms~10000ms 1ms 50ms Effective immediately
set up
shutdown
H12 07 acceleration time3 0ms~10000ms 1ms 100ms Effective immediately
set up
- 168 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
shutdown
H12 08 deceleration time3 0ms~10000ms 1ms 100ms Effective immediately
set up
shutdown
H12 09 acceleration time4 0ms~10000ms 1ms 150ms Effective immediately
set up
shutdown
H12 10 deceleration time4 0ms~10000ms 1ms 150ms Effective immediately
set up
shutdown
H12 20 No.1segment instruction - 9000~+9000rpm 1 rpm 0rpm Effective immediately
set up
shutdown
H12 twenty oneNo.1Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
set up
shutdown
H12 twenty three No.2segment instruction - 9000~+9000rpm 1 rpm 100rpm Effective immediately
set up
shutdown
H12 twenty fourNo.2Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
set up
shutdown
H12 26 No.3segment instruction - 9000~+9000rpm 1 rpm 300rpm Effective immediately
set up
shutdown
H12 27 No.3Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
set up
shutdown
H12 29 No.4segment instruction - 9000~+9000rpm 1 rpm 500rpm Effective immediately
set up
shutdown
H12 30 No.4Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
set up
12
0-Zero acceleration and deceleration time
shutdown
H12 32 No.5segment instruction - 9000~+9000rpm 1 rpm 700rpm Effective immediately
set up
- 169 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
shutdown
H12 33 No.5Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
set up
shutdown
H12 35 No.6segment instruction - 9000~+9000rpm 1 rpm 900rpm Effective immediately
set up
shutdown
H12 36 No.6Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
set up
shutdown
H12 38 No.7segment instruction - 9000~+9000rpm 1 rpm 600rpm Effective immediately
set up
shutdown
H12 39 No.7Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
set up
shutdown
H12 41 No.8segment instruction - 9000~+9000rpm 1 rpm 300rpm Effective immediately
set up
shutdown
H12 42 No.8Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
set up
shutdown
H12 44 No.9segment instruction - 9000~+9000rpm 1 rpm 100rpm Effective immediately
set up
shutdown
H12 45 No.9Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
set up
- 170 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
shutdown
H12 47 No.10segment instruction - 9000~+9000rpm 1 rpm - 100rpm Effective immediately
set up
shutdown
H12 48 No.10Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
set up
shutdown
H12 50 No.11segment instruction - 9000~+9000rpm 1 rpm - 300rpm Effective immediately
set up
shutdown
H12 51 No.11Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
set up
shutdown
H12 53 No.12segment instruction - 9000~+9000rpm 1 rpm - 500rpm Effective immediately
set up
shutdown
H12 54 No.12Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
set up
shutdown
H12 56 No.13segment instruction - 9000~+9000rpm 1 rpm - 700rpm Effective immediately
set up
shutdown
H12 57 No.13Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
set up
shutdown
H12 59 No.14segment instruction - 9000~+9000rpm 1 rpm - 900rpm Effective immediately
set up
H12 60 No.14Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
shutdown
set up
12
- 171 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
shutdown
H12 62 No.15segment instruction - 9000~+9000rpm 1 rpm - 600rpm Effective immediately
set up
shutdown
H12 63 No.15Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
set up
shutdown
H12 65 No.16segment instruction - 9000~+9000rpm 1 rpm - 300rpm Effective immediately
set up
shutdown
H12 66 No.16Segment instruction run time 0~6553.5 0.1s(m) 5.0s(m) Effective immediately
set up
H17group virtualDIDOset up
0: no definition
code list)
0-expressVDI1to write1
0: no definition
code list)
0-expressVDI2to write1
0: no definition
code list)
- 172 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
0-expressVDI3to write1
0: no definition
code list)
0-expressVDI4to write1
0: no definition
code list)
0-expressVDI5to write1
0: no definition
0: no definition
code list)
0-expressVDI7to write1
0: no definition
code list)
0-expressVDI8to write1
12
efficient connect again run
H17 15 VDI8Terminal logic selection 1 0
1-expressVDI8Write the value by after power set up
- 173 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
0: no definition
code list)
0-expressVDI9to write1
0: no definition
code list)
0-expressVDI10to write1
efficient connect again run
H17 19 VDI10Terminal logic selection 1 0
1-expressVDI10write value after power set up
0: no definition
code list)
0-expressVDI11to write1efficient
0: no definition
code list)
0-expressVDI12to write1
efficient connect again run
H17 VDI12Terminal
twenty three logic selection 1 0
1-expressVDI12write value after power set up
0: no definition
code list)
0-expressVD13to write1efficient
0: no definition
code list)
- 174 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
0-expressVDI14to write1
efficient connect again run
H17 27 VDI14Terminal logic selection 1 0
1-expressVDI14write value after power set up
0: no definition
code list)
0-expressVDI15to write1
efficient connect again run
H17 29 VDI15Terminal logic selection 1 0
1-expressVDI15write value after power set up
0: no definition
code list)
0-expressVDI16to write1
efficient connect again run
H17 31 VDI16Terminal logic selection 1 0
1-expressVDI16write value after power set up
Bit0:VDO1virtual level
slightly
H17 32 VDOvirtual level - - - - -
Bit15:VDO16virtual
level
0-no definition
0-no definition
0-no definition
- 175 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
0-no definition
0-no definition
0-no definition
0-no definition
0-no definition
0-no definition
0-no definition
- 176 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
0-no definition
0-no definition
0-no definition
0-no definition
0-no definition
0-no definition
12
- 177 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
Bit0 ~ 11reserve
Bit14 ~15reserve
Bit0-FunOUT1
H30 01 communication readFun Out ... 1 - - - PST
Bit15-FunOUT16
Bit0-FunOUT17
H30 02 communication readFun Out ... 1 - - - PST
Bit15-FunOUT32
Communication read input pulse
H30 03 - 1 - - - P
command sampled value
Bit0-VDI1virtual level
H31 00 VDIvirtual level ... - - - - PST
Bit15-VDI16virtual level
Bit0-DO1
Bit1-DO2
Bit2-DO3
Bit3-DO4
Bit4-null
Bit5-DO6
Communication givendooutput status run
H31 04 Bit6-DO7 - - Effective immediately PST
state set up
Bit7-DO8
Bit8~Bit15-reserved.
12 (optocoupler off)
run
H31 09 Communication given speed -9000000~9000000 0.001rpm 0 Effective immediately S
set up
- 178 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
run
H31 11 Torque command - 100000~100000 0.00001 0 Effective immediately T
set up
actual speed at
Note: Instructions for the use of communication given position increments: (newly added, this content has not been updated in the manual) In position mode, ifH05-00for3, the
position command comes from the communication given position incrementH31-07,H31-07The number of command pulses given by communication can be realized. The higher
the command pulse input frequency, the faster the motor speed, similar to this,H31-07The larger the written value, the faster the motor runs, but not exceedingH31-15set speed,
H31-15The set speed is equal to the electronic gear ratio of1:1When the actual speed of the motor, if the electronic gear ratio is not1:1, then the actual speed of the motor =(
H31-07only atH05-00set to3, and the current mode is the running state in the position mode, the written data will take effect, otherwise the written data will
Alarm reset signal The rear servo can continue to work. this
Fun IN.2 /ALM-RST (along effective work function is along the active level, when the terminal is set distribute
- 179 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
ZCLAMfunction for
Zero fix function Valid - enable the zero fix function, 0, for the speed control bar
Fun IN.12 /ZCLAMP distribute
enable signal Invalid - disable zero fix function , and the command source is
Analog
Forward rotation external torque Valid - the external torque limit is valid
Fun IN.16 /P-CL distribute
limitON Invalid - external torque limit is invalid
Position step input Valid - Execute the instruction of the instruction step amount;
Fun IN.20 /POSSTEP distribute External pop-up button
enterDIvariable Invalid - instruction is zero, bit state
HX1invalid,HX2efficient:X100
Fun IN.22 HX2 Handwheel override signal2
other:X1
distribute
12
set up
- 180 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
Interrupt fixed length state Invalid - does not respond to position commands; valid - solution The logic of the corresponding port needs to be
Fun IN.29 XINTFREE distribute
disarm signal In addition to position command lock state logic level is set to2or3
invalid - does not trigger The logic of the corresponding port needs to be
Fun IN.31 ORGNEAR Origin switch distribute
active-trigger logic level is set to2or3
The speed of the servo motor is higher than the speed threshold
Signal output when the servo motor stops rotating Instructions and feedback are both
Fun OUT.3 /ZERO+- Zero speed signal Effective motor speed is zero distribute Zero, not in torque mode
Invalid motor speed is not zero Consider the torque command
Fun OUT.4 /V-CMP+- Speed up The absolute value of the difference between degree instructions is less thanH0617
distribute
Fun OUT.6 /NEAR+- positioning approach signal Up to positioning proximity signal amplitudeH0522set up distribute
Fun OUT.7 /C-LT+- Torque limit signal Active - motor torque limited distribute
12
Confirmation signal of speed limitation during torque control
Fun OUT.8 /V-LT+- speed limit signal Active - motor speed limited distribute
Fun OUT.9 /BK+- brake output signal active - close, release brake distribute on, servoOFFOf
Inactive - Start Brake laterBKoutput
Fun OUT.10 /WARN+- Warning output signal Warning output signal is valid (conduction) distribute
- 181 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
Fun OUT.11 /ALM+- Fault output signal The status is valid when a fault is detected distribute
output3bit alarm
Fun OUT.12 ALMO1 output3bit alarm code distribute
the code
output3bit alarm
Fun OUT.14 ALMO3 output3bit alarm code distribute
the code
Fun OUT.16 ORGOK Origin return to zero output Valid - return to zero distribute
Er.107 Product model selection failure Invalid motor model or drive model NO.1 no h h h
Er.108 Parameter storage failure Parameter storage device failure NO.1 no h h h
The number of frequency division pulses of the encoder does not meet the setting conditions/
Er.110 Frequency division pulse output setting failure NO.1 no h h h
scope
Er.121 servoONcommand invalid fault inertia identification,JOGfunction, etc.), from the host NO.1 Can h h h
machine input servoONOrder
12 Er.130
Er.131
DIallocation failure
doallocation failure
manyDIassigned the same function
motor encoderEEPROM
Er.136 motor encoderEEPROMParameter exception NO.1 no h h h
Data validation error in
- 182 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
The phase sequence of the servo motor power cable wiring is wrong,
Er.201 Driver overcurrent2 The hardware detects the overcurrent of the power transistor; NO.1 no L L h
The encoder wiring is wrong or the encoder is damaged;
Servo power-on self-test found output The servo power-on self-test found that the power circuit of the servo motor
Er.210 NO.1 no L L h
Short circuit fault to ground Cable to ground short circuit
Er.234 flying car failure When the given feedback forms positive feedback, the motor flies NO.1 no L L h
Er.400 Overvoltage The main circuitDCvoltage too high NO.1 Can L L h
Er.410 Undervoltage The main circuitDCvoltage undervoltage NO.2 Can h h L
Phase failure during operation,R\S\Tphase of a certain
Er.420 Power line phase loss NO.2 Can h h L
The state of low phase voltage continues1more than seconds
Er.500 excessive speed The motor speed exceeds the maximum speed NO.2 Can L h L
Exceeded the set encoder frequency division pulse number
Er.510 Frequency division pulse output overspeed NO.1 Can L L L
Motor speed upper limit
Er.600 Inertia identification failure fault Inertia ID run timed out NO.1 Can L L L
The return to origin time exceeds the set value and has not yet
Er.601 Return to origin timeout fault NO.1 Can L L L
If the origin is found, this fault will be reported
Er.602 Angle recognition failure fault Initial angle identification failed NO.1 Can L L L
Running with load exceeds the drive inverse time curve setting
Running with load exceeds motor inverse time limit curve setting
heat sink
Er.650 Servo drive radiator temperature exceeds the set value NO.2 Can L L L
overheat
Er.651 motor overheat fault Motor over temperature fault point No.2 Can L L L
Er.740 Encoder interference fault1 incremental encoderZsignal interference NO.1 no h h h
Er.741 Encoder interference fault2 incremental encoderABsignal interference NO.1 no h h h
Er.831 NO.1 no h h h
12
ADsampling failure1 ADinitialization failure
Er.A34 Encoder loopback verification exception The communication content with the encoder is wrong NO.1 no L h L
- 183 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
Fully closed loop encoder position and Position and motor encoding for external fully closed-loop monitoring
Er.b02 NO.1 no L L h
Motor position deviation is too large The sensor feedback position deviation is too large
12.4Motor number
12
5300 5200 ISMG2-84C10CD-①131X 5330 5230 ISMG2-13D10CD-①131F
5301 5201 ISMG2-11D13CD-①131X 5331 5231 ISMG2-17D13CD-①131F
5302 5202 ISMG2-13D15CD-①131X 5332 5232 ISMG2-20D15CD-①131F
5303 5203 ISMG2-14D17CD-①131X 5333 5233 ISMG2-23D17CD-①131F
5304 5204 ISMG2-17D20CD-①131X 5334 5234 ISMG2-27D20CD-①131F
- 184 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
12.5.1wiring
1) Photoelectric encoderJ1wiring
12
a)Power on the drive, and when the servo is not enabled, face the motor shaft, turn the motor shaft counterclockwise, and observeH0B10Electrically from0degree to360The
degree increases continuously and changes cyclically, indicating that the wiring of the photoelectric encoder is correct.
b)likeH0B10The electrical angle is from360°change0°, descriptionA+,-andB+, - reversed, please exchangeAgroup andBgroup signal.
c)ifH0B10If there is no change in the electrical angle, it means that the encoder wiring is incorrect, please checkH00.00Whether the motor number setting
12.5.1.2Resolver wiring
- 185 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
1)MF38PG4Resolver wiring
PE
COS+
FAN-N
FAN-P
PTC-N
PT CP
QUR
KYP
W
COS -
EXT+
u
S IN-
SIN+
EXT-
PE
black/white
red/white
black
red
blue
yellow
Note: This color is Danaher resolver Note: KTY, PTC and FAN wiring do not need
Thread color definition. To distinguish positive/negative.
The definitions and colors of motor wire terminals are shown in the table below:
Danaher resolver wire colors red/white black/white red black yellow blue
signal definition EXC- EXC+ SIN+ SIN- COS+ COS-
"MF38PG4" PGCardDB9pin 1 2 3 4 5 9
◆ After the driver is powered on, when the servo is not enabled, face the motor shaft, turn the motor shaft counterclockwise, and observeH0B10Electrically from0degree to360The
degree increases continuously and changes cyclically, indicating that the resolver wiring is correct.
◆ IfH0B10The electrical angle is from360°change0°, descriptionSINgroup andCOSThe group signal is reversed, please exchangeSINgroup and
COSgroup signal;
◆ IfH0B10If there is no change in the electrical angle, it means that the resolver wiring is not correct, please checkH00.00Whether the motor number and
H00.00It is the function code for selecting the motor model. If the default motor model is inconsistent with the motor model you are using, please re-select the motor model, that is,
modifyH00.00function code. Please refer to the following table for the corresponding relationship of specific motor models:
- 186 -
IS550Series Servo Driver User Manual No.12Chapter Appendix
Note:
1)ISMG1The motor number corresponding to the photoelectric encoder feedback of the motor is51**, the motor number corresponding to the resolver feedback is50**;
- 187 -
No.12Chapter Appendix IS550Series Servo Driver User Manual
2)ISMG2The motor number corresponding to the photoelectric encoder feedback of the motor is52**, the motor number corresponding to the resolver feedback is53**;
3)ISMG1Rated speed1300rpm, there is no motor number temporarily, if you need to use it, please putH00.00Set the corresponding rated speed to be
4) or putH00.00Set as65535,BundleISMG1-47C13CD-U131XThe corresponding motor parameters are downloaded through the background software
12.5.3Initial angle identification (general resolvers need to perform this step, photoelectric motors do not need it)
Ensure that the motor is under no-load conditions,H0d03=1, which is the initial angle identification, at this time must be inrdystate, namelyservo_offstate, in the process of
performing angle identification, the motor will slowly rotate counterclockwise, and the maximum rotation1circle, approx.1minutes or so.
After completing the steps above, just to be on the safe side check firstH02.00Is it0, confirm that the servo is under the speed loop, then proceed SERVO_ON, to
see if the motor can rotate. If the motor does not turn, it will reportEr.610drive overload,ER.500, or for other alarms, execute12.5.4Initial angle identification,
otherwise, the motor can rotate, please execute12.5.5, speed gain adjustment.
in speed modeH02.00=0In the case of the situation, use the background software to observe the speed command and speed feedback, and adjust the speed ratio according to
Problem: The short-term process is too long, but it is more stable in continuous operation Problem: Excessive speed overshoot
Solution: increase the ratioH08.00, increasing the integration timeH08.01 Solution: increase the ratioH08.00, can increase the integration time
H08.01
12 Problem: Small sustained oscillations, noise, vibration during steady state operation Problem: The dynamic response is too slow, and the system has static deviations
- 188 -
Problem: The overshoot time is too long, and the dynamic speed reduction is large when the load changes Problem: Sustained Violent Vibration
Solution: reduce integration timeH08.01 Solution: increase the integration timeH08.01or reduce the ratioH08.00
12.6Version Change Notes
The warranty period of this product is eighteen months (subject to the barcode information on the fuselage). During the warranty period, under normal use according to the instruction manual, if the
During the warranty period, a certain maintenance fee will be charged for damage caused by the following reasons:
A, Machine damage caused by mistakes in use and unauthorized repair and modification;
B, Machine damage caused by fire, flood, abnormal voltage, other natural disasters and secondary disasters;
D., Machine damage caused by not following the user manual provided by our company;
E., Failure and damage caused by obstacles other than the machine (such as external equipment factors);
When the product fails or is damaged, please fill in the contents of the "Product Warranty Card" correctly and in detail.
The collection of maintenance fees shall be in accordance with the latest adjustment of our company's "Maintenance Price List".
This warranty card will not be reissued under normal circumstances, please be sure to keep this card and show it to the maintenance personnel during warranty.
If you have any questions during the service, please contact our agent or our company in time.
The right to interpret this agreement belongs to Shenzhen Inovance Technology Co., Ltd.
service department
Address: Baocheng, Baoan District, Shenzhen70Hongwei Industrial Park, Liuxian 2nd Road, DistrictE.Building
URL:www.inovance.cn
warranty card
Unit address:
information
Product number:
information
Agency name:
Fault
information
Repair man: