• Switching on / off of the power supply to the teleprotection equipment.
• Switching on / off of the PLC/Fiber optic equipment at either end of
the line.
• Shorting the out put of the teleprotection transmitter or shorting of the
input to the teleprotection receiver.
• Operation of the HV line isolators in switchyards.
Each distance and directional earth fault protection shall have independent
permissive channel for teleprotection. A direct channel shall be provided for
breaker failure/busbar protection. Inter tripping facility for cable feeders shall
be via pilot wire or fiber optic cables.
C & PE 29