Loads Calculations Manual-1
Loads Calculations Manual-1
Indoor loads
1- People loads
Sensible load (Qs)
𝑄𝑠=𝑁∗(𝑆𝐻𝐺)∗𝐶𝐿𝐹
Latent load (Ql)
𝑄𝐿=𝑁∗(𝐿𝐻𝐺)
2- Lightning loads
𝑸𝒍𝒊𝒈𝐡𝒕𝒊𝒏𝒈 = 𝑭𝒖 ∗ 𝑾 ∗ 𝑪𝑳𝑭
3- Equipment loads
𝑸𝒔 = 𝑺𝑯𝑮 ∗ 𝑪𝑳𝑭
𝑸𝑳 = 𝑳𝑯𝑮
From codes..
outdoor loads
1- Transmission loads
Walls &roofs:
External walls: walls that are directly exposed to solar radiation.
𝐐 = 𝐔 ∗ 𝐀 ∗ 𝐂𝐋𝐓𝐃𝐜𝐨𝐫𝐫
Internal walls (partitions): walls that are not exposed to direct solar
radiation.
𝐐 = 𝐔 ∗ 𝐀 ∗ (𝐓𝐨 − 𝐓𝐢 )
windows:
𝑄𝑔𝑙𝑎𝑠𝑠=𝐴∗(𝑆.𝐶) ∗ 𝑆𝐻𝐺𝐹𝑚𝑎𝑥∗𝐶𝐿𝐹
Abdalla Khairy
Ventilation loads:
Latent:
Ql = 3010*Q*(Wo-Wi) *Np
Sensible:
Qs = 1.23*Q*(T0-Ti) *Np
Total:
Qt =1.2*Q*(ho-hi)
We get Thermal Transmittance of walls, LM depending on the location and
direction of the wall, SHFG, CLF for the window from ASHRE tables.
Case study
(108.5 D.B.L.M)
Abdalla Khairy
Outdoor Loads: Room name 108.5 DBLM
R value = 1/U=1/0.121=8.26
CLTDcorrected= 44.1
So;
Indoor Loads:
1) People loads:
a) Sensible load (Qs):
𝑄𝑠=𝑁∗(𝑆𝐻𝐺)∗𝐶𝐿𝐹
𝑄𝑠=7∗80∗1=560 𝑊𝑎𝑡𝑡
Abdalla Khairy
b) Latent load (Ql):
𝑄𝐿=𝑁∗(𝐿𝐻𝐺)
𝑄𝐿=7∗140=980 𝑊𝑎𝑡𝑡
2) Lightning loads (Qlight):
𝑄𝑙𝑖𝑔ℎ𝑡𝑖𝑛𝑔= 𝐹𝑢∗𝑊 ∗ 𝐶𝐿𝐹∗𝑅𝑜𝑜𝑓 𝐴𝑟𝑒𝑎
𝑄𝑙𝑖𝑔ℎ𝑡𝑖𝑛𝑔=1 ∗702.3 ∗ 0.73=512.7 𝑊𝑎𝑡𝑡
Equipment loads:
𝑄𝑠 = 𝑆𝐻𝐺 ∗ 𝐶𝐿𝐹
Dry bench lab devices is only computers
Total equipment load =0.83∗ (7∗144) =836.64 𝑊𝑎𝑡𝑡
Ventilation Load:
a) Sensible load:
𝑄𝑠=1.23∗𝜐. ∗(𝑇𝑜−𝑇𝑖) ∗ 𝑁𝑃
𝑄𝑠=1.23∗ (25∗.47195) ∗ (40−24) ∗7=1625.4 𝑊𝑎𝑡𝑡.
b) Latent load:
𝑄𝐿=3010∗𝜐. ∗(𝑤𝑜−𝑤𝑖) ∗𝑁𝑃 𝑄𝐿
= 3010∗ (25∗0.47195) ∗ (0.0185−0.009) ∗7=2364.7 𝑊𝑎𝑡𝑡
Total loads
Qs Tot = ⅀Qs=4089.74 watt = 4.09 KW
Ql Tot = ⅀Ql = 3341.7 watt = 3.35 KW
Q Tot = ⅀ Q = 7.44 KW
Abdalla Khairy