This document provides calculations to select the proper vent valves for a tank containing n-hexane according to ISO28300/API2000 standards. It lists the tank data needed for the calculations including height, diameter, vapor pressure, flow rates, and temperature. It then outlines the steps to calculate the venting capacity for normal out-breathing and the vacuum capacity for in-breathing, and to determine the total venting capacity needed.
This document provides calculations to select the proper vent valves for a tank containing n-hexane according to ISO28300/API2000 standards. It lists the tank data needed for the calculations including height, diameter, vapor pressure, flow rates, and temperature. It then outlines the steps to calculate the venting capacity for normal out-breathing and the vacuum capacity for in-breathing, and to determine the total venting capacity needed.
This document provides calculations to select the proper vent valves for a tank containing n-hexane according to ISO28300/API2000 standards. It lists the tank data needed for the calculations including height, diameter, vapor pressure, flow rates, and temperature. It then outlines the steps to calculate the venting capacity for normal out-breathing and the vacuum capacity for in-breathing, and to determine the total venting capacity needed.
FLOW CALCULATION AND SELECTION OF VENT VALVES ACCORDING TO ISO28300/API2000 7 Ed.
PRODUCT: N HEXANE (HYDRICARBON STEAM)
Data: Valve type
Tank Height (H): Tank diameter (D): Vapor pressure: Input flow (Vpf): Outlet flow (Vpe): Average liquid temperature: Additional flow due to equipment failures or operating errors: Pressure set: Vacuum set: Vacuum over pressure:
Tank Capacity:
Latitude: below 42°
Venting capacity calculation (out-breathing)
Calculation of the thermal capacity of venting (out-breathing)
factor by latitude (table 1 API 2000)
insulation reduction factor, non-insulated equal to 1
Vacuum capacity calculation (inbreathing)
Calculation of vacuum thermal capacity (inbreathing)