Professional Documents
Culture Documents
Transmission systems includes five overhead lines and the longest is between two substations B5 and
B2 around 600Km and all interconnected lines will be capable of carrying 1100 MW which is close to
SIL of the transmission lines.
In previous study it was shown in both ETAP and Simulink when the largest machines started up how
SVC can keep the voltage variations in an adjusted bandwidth with less overshoot to maintain the
stability of the system.
This model is purely focused on fault situations to observer how PSS with SVC helps to keep the
synchronism during fault and post fault condition.
1- Single phase fault at bus 5 at instant 5 and cleaning 5.1s no SVC with PSS
2- Single phase fault at bus 5 at instant 5 and cleaning 5.1s with SVC and PSS
3- Three phase fault at bus 5 at instant 5 and cleaning 5.1s no SVC with PSS
4- Three phase fault at bus 5 at instant 5 and cleaning 5.1s with SVC and PSS
Results:
Fig1: It shows that the system is unstable during the LG fault and post fault when SVC is not in
operation even with the presence of PSS
Fig2: It shows that the system is stable during the LG fault and post fault when SVC is in operation
with the presence of PSS
Fig3: It shows that the system is unstable during the 3LLL fault and post fault when SVC is not in
operation even with the presence of PSS
Fig4: It shows that the system is stable during the 3LLL fault and post fault when SVC is in operation
with the presence of PSS
Conclusion:
For both cases LG and 3LLL faults without SVC, system is unstable even when PSS is in operation on
the generators. It is obvious when a power system is large and long lines are interconnected, system
will get unstable even with a LG fault and rotor angles between three machines exceeds 90 degrees
and it results in losing their synchronism.
The graphs 2,4 respectively show that generator speeds and obviously generator G3 has a speed
increase during the fault since the electrical power is lower than its mechanical power and the speed
is oscillating at a low frequency 0.025Hz during the post fault until reaching to stability at 1p.u.
It is also obvious that when a SVC connected into the power system during the severe contingency, it
will inject the reactive power to the line to compensate the bus voltage variation compared with
reference voltage 1p.u. In addition, from plots 2 and 4, the voltage drop for a 3LLL is higher than the
LG fault.
Fig1: Single phase fault at bus 5 at instant 5 and cleaning 5.1s no SVC with PSS
Rotor angle variation
When LG happens
Fig2: Single phase fault at bus 5 at instant 5 and cleaning 5.1s with SVC and PSS
Fig3: Three phase fault at bus 5 at instant 5 and cleaning 5.1s no SVC and PSS
Rotor variations when
3LLL happens
Fig4: Three phase fault at bus 5 at instant 5 and cleaning 5.1s with SVC and PSS