Acti9 iID B type EV and Acti9 iID B-SI type RCCB
O
sh
li
ub
re p
Contents hi befo
T
s pa
ge must be removed
Schneider Electric's range of residual current Variants
circuit breakers consists of different products
(A, B, C, D) to enable it to be the most Offers Pages
competitive range possible in each country, Offer A Catalog numbers 2
allowing for the special characteristics of each International except Belgium
market: Offer B Catalog numbers 3
- usual installation procedure Electric vehicle, international except Belgium
- price Offer C Catalog numbers 4
- accreditations by local bodies. Belgium
Offer D Catalog numbers 6
Electric vehicle, Belgium
Common pages 7
Onl
mar y the p
vali keted roduct
mandated bin your range
Fin ager, y the coun to be
sho al Distr in agre local p try and
be r uld be ibution ement roduct
emo reta ( w
ved ined FD) pa ith his
befo . Th rtne
re p e oth r
ubli
catiers will
on.
DB428451.eps
DB116619.eps
IEC/EN 61008-2-1
DB405571.eps
IEC/EN 62423
IEC 61543
DB122858.eps
DB406142.eps
DB405227.eps
DB123854.eps
VDE 0664
Country approval pictograms As per the above standards:
b The Acti9 iID B-SI type residual current circuit breakers provide:
v protection of persons against electric shock by direct contact (30 mA),
v protection of persons against electric shock by indirect contact (u 300 mA),
A9Z61225-40.eps
A
providing increased immunity from electrical interference and polluted environments.
Offe
e r
b The Acti9 iID B-SI type is compatible with Schneider Electric AC and A types wired
Off
in parallel or in series in the installation, following coordination tables (refer to earth
leakage protection guide CA908066E).
Catalog numbers
Acti9 iID B-SI type residual current circuit breakers g
Type l i shin Width in 9 mm mod.
b B-SI
2P fo r e puSensitivity 30 mA 300 mA 300 mA s 500 mA
This s ed be25 A
vRating
st be remo
A9Z61225 A9Z64225 - - 8
DB428453.eps
DB428451.eps
DB116619.eps
DB405571.eps
IEC/EN 61008-2-1
IEC/EN 62423
DB122858.eps IEC 61543
DB406142.eps
DB405227.eps
DB123854.eps
VDE 0664
Country approval pictograms
As per the above standards:
b The Acti9 iID B type EV residual current circuit breakers provide:
v protection of persons against electric shock by direct contact (30 mA),
A9Z51216-40.eps
B type
The Acti9 iID B type EV residual current circuit breakers provide:
b protection in the event of a continuous earth fault current on networks
generated by electric car charging station.
b The use of Acti9 iID B type EV residual current circuit breaker can be made
mandatory, according to standards applicable in country.
b The Acti9 iID B type EV is compatible with Schneider Electric AC and A types wired
in parallel or in series in the installation, following coordination tables (refer to earth
A9Z51440-40.eps
see page 1
s e lection
B
r
Offe
Offe r re pu b
Catalog numbers
Acti9 iID
l ish
Type
g B type EV residual current circuit breakers
in B Width in 9 mm
module
25 A A9Z51225
40 A A9Z51240
40 A A9Z51440
63 A A9Z51463
A9Z61225-40.eps
IEC/EN 61008-2-1
IEC/EN 62423
IEC 61543
VDE 0664
As per the above standards:
b The Acti9 iID B-SI type residual current circuit breakers provide:
v protection of persons against electric shock by direct contact (30 mA),
v protection of persons against electric shock by indirect contact (u 300 mA),
v protection of installations against the risk of fire (300 mA or 500 mA).
A9Z61425-40.eps
B-SI type
The Acti9 iID B-SI type residual current circuit breakers provide:
b protection in the event of a continuous earth fault current on networks
generated by:
v controllers and variable speed drives,
v battery chargers and inverters, such as used in photovoltaic application,
v backed-up power supplies.
b The use of Acti9 iID B-SI type residual current circuit breaker can be made
PB104488-14.eps
b The Acti9 iID B-SI type works optimally with the variable speed drives
manufactured by Schneider Electric, even with a long cable length between motor
and variable speed drive (up to 50 m).
b SI technology is embedded in Acti9 iID B-SI type residual current circuit breaker,
providing increased immunity from electrical interference and polluted environments.
b The Acti9 iID B-SI type is compatible with Schneider Electric AC and A types wired
in parallel or in series in the installation, following coordination tables (refer to earth
leakage protection guide CA908066E).
Accessories
b 4P sealable screw shield.
see page 1
s e lection
C
r
Offe
Offe r re p
u bl i shin g
efo
This s ed b
ticker must be remov
40 A A9Z61240 A9Z64240 - -
63 A A9Z61263 A9Z64263 - -
Accessory
Type Number of pole Ref. no.
Screw shield (set of 20) for upstream or downstream 4P A9A26981
see page 1
s e lection
C
r
Offe
Offe r re p
u bl i shin g
efo
This s ed b
ticker must be remov
B type
The Acti9 iID B type EV residual current circuit breakers provide:
b protection in the event of a continuous earth fault current on networks
generated by:
v electric car charging station.
b The use of Acti9 iID B type EV residual current circuit breaker can be made
mandatory, according to standards applicable in country.
b The Acti9 iID B type EV is compatible with Schneider Electric AC and A types wired
in parallel or in series in the installation, following coordination tables (refer to earth
leakage protection guide CA908066E).
Accessories
PB104488-14.eps
Catalog numbers
page 1
e lection see Acti9 iID B type EV residual current circuit breakers
rs
D
Offe
Type B Width in 9 mm
e r
module
Off
2P Sensitivity 30 mA
Rating 16 A A9Z51216 8
DB428453.eps
25 A A9Z51225
efore p
This s ed b
ticker must be remov
Voltage rating (Ue) 230 V
Operating frequency 50 Hz
4P Sensitivity 30 mA
Rating 25 A A9Z51425 (2) 8
DB428452.eps
40 A A9Z51440
63 A A9Z51463
Accessory
Type Number of pole Ref. no.
Screw shield (set of 20) for upstream or downstream 4P A9A26981
current (Inc/IDc)
Additional characteristics
Degree of protection Device only IP20
(IEC 60529) Device in modular IP40
enclosure Insulation class II
Endurance (O-C) Electrical y 63 A 15,000 cycles
> 63 A 10,000 cycles
Indifferent position of installation.
Mechanical 20,000 cycles
Range of test button 30 mA 2P 180...270 V AC
IP20 IP40 operating voltage 4P 300...450 V AC
300, 500 mA 2P 140...330 V AC
DB123314.eps
4P 220...450 V AC
Impulse withstand according to IEC 60068-2-27 15 g
Vibration withstand according to IEC 60068-2-6 3g
Electromagnetic compatibility According to IEC 61543
Operating temperature -25°C to +60°C
Storage temperature -40°C to +85°C
Dissipated power Module CA908009
Dielectric test
E63606.eps
DB428452.eps
73
Residual current circuit breakers
6 44 20
Type iID
2P 350
4P 415
91 88 45
DB122946.eps
DB122945.eps
DB122946.eps
DB122935.eps
DB118789.eps
DB118787.eps
All 1 to 25 mm² 1 to 16 mm² 1 to 35 mm² 1 to 25 mm² 50 mm2 Ø 5 mm 3 x 16 mm2 3 x 10 mm2
3.5 N.m
DB428595.eps
b Test button
DB428597.eps
DB429240.eps
VISI-TRIP window
b Large circuit labelling area
b Fault tripping is indicated by a red
mechanical indicator on the front face
VISI-SAFE window
Positive contact indication
b A green strip on the toggle indicates
full opening of all the poles
b Padlocking possible
l u t i o n s
Evo
ing
sh
li
ub
re p
hi befo
T
s pa
ge must be removed