#: PCT-PRO-001
Authority GCCIA Issue #: 01
GCCIA Issue Date: 12-06-2018
Protection Maintenance Test Report
Omexom Doc. #: AUT-F-07 Rev.1
A. Relay Data
Date 27-02-22 Substation Jasra DIA/Bay 1RA1
TEE2 - BUS
400KV FUTURE LINE
Relay FEEDER
Panel Designation GROUP-B Type/Model P6338491040NN03L00
Designation DIFFERENTIALRELA
PROTECTION
Y
B. Pre-Requisites
Equipment & Resources: Status
Competent personnel available for the test. OK
All competent persons are EHS certified to work in electrical environment. OK
AC & DC supply availability and security. OK
Test equipment calibrated and suitable for the test. OK
Safety:
Full understanding & electrical risk prevention instruction. OK
PPE safety available. OK
Awareness of electrical hazards precautions. OK
Isolation & Coordination:
Secondary Isolation of Tripping & Inter-tripping. OK
Primary Equipment isolation of Concerned equipment. OK
Coordination With Other Parties (GIS, Transformer, Etc.) OK
2. Visual Inspection
Description Assessment
Relay Visual Inspection: OK
Clock set to GMT time: OK
Communication with PC & DCS: OK
Relay is synchronized by substation GPS: OK
3. CT/VT Data
Phase CT1 (A): 2000 / 1 Main VT1 (V): 400000 / 110 LN
Phase CT2 (A): 2000 / 1 Main VT2 (V): 380000 / 110
Phase CT3 (A): 2000 / 1 Main VT3 (V): 380000 / 110
Signature: Signature:
GCCIA_JASRA_FUT_P633-TEE2_2022_0 1/4
GCCIA - Protection Maintenance Test Report
IR CT1 2000 A 1997.000 A OK
IY CT1 2000 A 1986.000 A OK
IB CT1 2000 A 1988.000 A OK
IN CT1 2000 A 1984.000 A OK
IR CT2 2000 A 2000.000 A OK
IY CT2 2000 A 1921.000 A OK
IB CT2 2000 A 1989.000 A OK
IN CT2 2000 A 1990.000 A OK
IR CT3 2000 A 1999.000 A OK
IY CT3 2000 A 1989.000 A OK
IB CT3 2000 A 1981.000 A OK
IN CT3 2000 A 1986.000 A OK
Functionalities Checks
Description Assessment
86 Lockout Relay Trip OK
DTT-B Send OK
Signature: Signature:
GCCIA_JASRA_FUT_P633-TEE2_2022_0 2/4
GCCIA - Protection Maintenance Test Report
1 DTT-B Send OK
1 3Phase Trip to 86CB OK
2 Alarm To BCU OK
Final Checks
Description Assessment
Events records extracted and checked OK
Fault Records Checked OK
Disturbances records extracted and checked OK
All Test equipment, leads, shorts and test blocks removed OK
Alarms rest LEDS reset OK
Trip and Lockout Relays reset OK
Disturbed customer wiring re-checked and normalized OK
CT /VT wiring tightness at terminal block checked OK
All relay setting re-checked and normalized OK
Signature: Signature:
GCCIA_JASRA_FUT_P633-TEE2_2022_0 3/4
GCCIA - Protection Maintenance Test Report
1 Injection Kit Omicron CMC356 GK705N 19-12-2019 19-12-2020
2 Multimeter FLUK 31210031 19-12-2019 19-12-2020
Type: EASRGY STUDIO
3 Relay Setting Software
Version : V.8
Remarks:
Signature: Signature:
GCCIA_JASRA_FUT_P633-TEE2_2022_0 4/4
OMICRON AUTOMATIC TESTS
REPORT
GCCIA_JASRA_FUT_P633-TEE2_2022_0
Macro-Enabled Worksheet
Hardware Configuration
Test Equipment
Type Serial Number
CMC356 GK705N
Hardware Check
Performed At Result Details
Group:Differential (87)
DIFF_Initial conditions S1
Instruction Text:
- IR-IY-IB Side 1 wired
- Omicron contact: Trip contact
- If only one accessible side , “Internal loopback” enabled for AREVA relays or keep optical fibers connected (TELECOM FAIL not
activited) without specific mode for Siemens relays
- If 87 Differential Current monitoring setting = ON, put OFF
User Input:
GCCIA_JASRA_FUT_P633-TEE2_2022_0
DIFF_IPickup_S1.rp:
Test Settings
General
No. of ramp states: 1
Total steps per test: 151
Total time per test: 30.200 s
No. of test executions: 1
Ramp States
Ramp Ramp 1
I L1 225.0 mA
0.00 °
50.000 Hz
I L2 225.0 mA
-120.00 °
50.000 Hz
I L3 225.0 mA
120.00 °
50.000 Hz
I(2)-1 0.00 A
0.00 °
50.000 Hz
I(2)-2 0.00 A
-120.00 °
50.000 Hz
I(2)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases Yes
Sig 1 From 225.0 mA
Sig 1 To 375.0 mA
Sig 1 Delta 1.000 mA
Sig 1 d/dt 5.000 mA/s
Bin. out 1 0
Bin. Out 2 0
Bin. Out 3 0
Bin. Out 4 0
dt per Step 200.0 ms
Ramp Steps 151
Ramp Time 30.200s
Trigger Bin
Trigger Logic OR
Trip 1
Step back No
GCCIA_JASRA_FUT_P633-TEE2_2022_0
IPickup_S1 Ramp 1 Trip 0->1 I L1, L2, 300.0 mA 293.0 mA 30.00 mA 30.00 mA -7.000 mA + 85.80 ms
L3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
DIFF_Initial conditions S2
Instruction Text:
- IR-IY-IB Side 2 wired
- Omicron contact: Trip contact
User Input:
DIFF_IPickup_S2.rp:
Test Settings
General
No. of ramp states: 1
Total steps per test: 151
Total time per test: 30.200 s
No. of test executions: 1
Ramped Quantities
I(2)-1, -2, -3 / Magnitude
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
GCCIA_JASRA_FUT_P633-TEE2_2022_0
I L3 0.00 A
120.00 °
50.000 Hz
I(2)-1 225.0 mA
0.00 °
50.000 Hz
I(2)-2 225.0 mA
-120.00 °
50.000 Hz
I(2)-3 225.0 mA
120.00 °
50.000 Hz
Force Yes
abs.
Phases
Sig 1 225.0 mA
From
Sig 1 To 375.0 mA
Sig 1 1.000 mA
Delta
Sig 1 d/dt 5.000
mA/s
Bin. out 1 0
Bin. Out 2 0
Bin. Out 3 0
Bin. Out 4 0
dt per 200.0 ms
Step
Ramp 151
Steps
Ramp 30.200s
Time
Trigger Bin
Trigger OR
Logic
Trip 1
Step back No
Delay 0.00 s
Time
Test
Module
Name: OMICRONVersion: 4.20
Ramping
Test 27-Feb- Test 27-Feb-
Start: 2022 End: 2022
11:31:23 11:31:39
User Manager:
Name:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
IPickup_S2 Ramp 1 Trip 0->1 I(2)-1, - 300.0 mA 295.0 mA 30.00 mA 30.00 mA -5.000 mA + 700.0 μs
2, -3
Assess: + .. Passed x .. Failed o .. Not assessed
GCCIA_JASRA_FUT_P633-TEE2_2022_0
Test State:
Test passed
With this relay type it might happen that the test points of the Characteristic Test vary around +/10%
the theoretical characteristic. This is a normal behavior of the relay. If it is necessary to check the
characteristic in a very exact manner one may set the trip time delay (Parameter Address: 010.162) to
20ms or 30ms and the hysteresis effective (Parameter Address: 072.006) to 'No' for the duration of the
test.
Attention! If the parameters are changed, they have to be set back after the test!
User Input:
DIFF_Char_S1_S2.df:
Test Module
Name: OMICRON Diff Operating Version: 4.20
Characteristic
Test Start: 27-Feb-2022 11:33:07 Test End: 27-Feb-2022 11:34:24
User Name: Manager:
Company:
Test State:
Test passed
4 out of 4 points tested.
4 points passed.
0 points failed.
DIFF_tDiff.sq:
Test Settings
State State 1 State 2
I L1 0.00 A 900.0 mA
0.00 ° 0.00 °
GCCIA_JASRA_FUT_P633-TEE2_2022_0
50.000 Hz 50.000 Hz
I L2 0.00 A 900.0 mA
-120.00 ° -120.00 °
50.000 Hz 50.000 Hz
I L3 0.00 A 900.0 mA
120.00 ° 120.00 °
50.000 Hz 50.000 Hz
50.000 Hz 50.000 Hz
50.000 Hz 50.000 Hz
50.000 Hz 50.000 Hz
Test Module
Name: OMICRON State Sequencer Version: 4.20
Test Start: 27-Feb-2022 11:34:48 Test End: 27-Feb-2022 11:34:51
User Name: Manager:
Company:
Test Results
Time Assessment
Ignore
Name before Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess
tDiff State 2 State 2 Trip 0>1 0.00 s 30.00 ms 30.00 ms 20.20 ms 20.20 ms +
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
GCCIA_JASRA_FUT_P633-TEE2_2022_0
User Input:
DIFF_IPickup_S3.rp:
Test Settings
General
No. of ramp states: 1
Total steps per test: 151
Total time per test: 30.200 s
No. of test executions: 1
Ramped Quantities
I(2)-1, -2, -3 / Magnitude
Ramp States
Ramp Ramp 1
I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(2)-1 225.0 mA
0.00 °
50.000 Hz
I(2)-2 225.0 mA
-120.00 °
50.000 Hz
I(2)-3 225.0 mA
120.00 °
50.000 Hz
Force Yes
abs.
Phases
Sig 1 225.0 mA
From
Sig 1 375.0 mA
To
Sig 1 1.000 mA
Delta
Sig 1 5.000
d/dt mA/s
Bin. out 0
1
Bin. 0
Out 2
GCCIA_JASRA_FUT_P633-TEE2_2022_0
Bin. 0
Out 3
Bin. 0
Out 4
dt per 200.0 ms
Step
Ramp 151
Steps
Ramp 30.200s
Time
Trigger Bin
Trigger OR
Logic
Trip 1
Step No
back
Delay 0.00 s
Time
Test
Module
Name: OMICRONVersion:4.20
Ramping
Test 27-Feb- Test 27-Feb-
Start: 2022 End: 2022
11:37:05 11:37:22
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact
IPickup_S3 Ramp 1 Trip 0->1 I(2)-1, - 300.0 mA 297.0 mA 30.00 mA 30.00 mA -3.000 mA + 21.40 ms
2, -3
Assess: + .. Passed x .. Failed o .. Not assessed
Test State:
Test passed
DIFF_Char_S1_S3.df:
Test Module
Name: OMICRON Diff Operating Version: 4.20
Characteristic
Test Start: 27-Feb-2022 11:38:35 Test End: 27-Feb-2022 11:39:51
User Name: Manager:
Company:
GCCIA_JASRA_FUT_P633-TEE2_2022_0
Test State:
Test passed
4 out of 4 points tested.
4 points passed.
0 points failed.
If the parameters (Trip time delay, Hysteresis effective) have been changed, Restore as original!
User Input:
DIFF_Restore conditions
Instruction Text:
- Restore settings as original (87 Differential Current monitoring setting if used)
User Input:
Test State: Continue
Group end:Differential
(87)