You are on page 1of 13

Gulf Cooperation Council Interconnection GCCIA Doc.

#: PCT-PRO-001
Authority GCCIA Issue #: 01
GCCIA Issue Date: 12-06-2018
Protection Maintenance Test Report
Omexom Doc. #: AUT-F-07 Rev.1

A. Relay Data
Date 27-02-22 Substation Jasra DIA/Bay 1RA1

TEE2 - BUS
400KV FUTURE LINE
Relay FEEDER
Panel Designation GROUP-B Type/Model P6338491040NN03L00
Designation DIFFERENTIALRELA
PROTECTION
Y

Serial No. 2742227/08/07 CMC No. GK705N Tested by Mahmoud Reda


Circuit
Firmware Version 610.12 Aux: Voltage 110V DC 1RA1
Designation

B. Pre-Requisites
Equipment & Resources: Status
Competent personnel available for the test. OK
All competent persons are EHS certified to work in electrical environment. OK
AC & DC supply availability and security. OK
Test equipment calibrated and suitable for the test. OK
Safety:
Full understanding & electrical risk prevention instruction. OK
PPE safety available. OK
Awareness of electrical hazards precautions. OK
Isolation & Coordination:
Secondary Isolation of Tripping & Inter-tripping. OK
Primary Equipment isolation of Concerned equipment. OK
Coordination With Other Parties (GIS, Transformer, Etc.) OK

C. Record Test Sheet


1. Setting Verification
Settings Verification Items Assessment
All relay’s settings have been compared with GCCIA’s approved settings OK

2. Visual Inspection
Description Assessment
Relay Visual Inspection: OK
Clock set to GMT time: OK
Communication with PC & DCS: OK
Relay is synchronized by substation GPS: OK

3. CT/VT Data
Phase CT1 (A): 2000 / 1 Main VT1 (V): 400000 / 110 LN
Phase CT2 (A): 2000 / 1 Main VT2 (V): 380000 / 110
Phase CT3 (A): 2000 / 1 Main VT3 (V): 380000 / 110

4. Measurement Value Test


Measurements
Value reference Value Injected Value displayed Assessment

GCCIA's Representative Omexom's Representative


Name: Tushar Name: Mahmoud Reda

Signature: Signature:

GCCIA_JASRA_FUT_P633-TEE2_2022_0 1/4
GCCIA - Protection Maintenance Test Report
IR CT1 2000 A 1997.000 A OK
IY CT1 2000 A 1986.000 A OK
IB CT1 2000 A 1988.000 A OK
IN CT1 2000 A 1984.000 A OK
IR CT2 2000 A 2000.000 A OK
IY CT2 2000 A 1921.000 A OK
IB CT2 2000 A 1989.000 A OK
IN CT2 2000 A 1990.000 A OK
IR CT3 2000 A 1999.000 A OK
IY CT3 2000 A 1989.000 A OK
IB CT3 2000 A 1981.000 A OK
IN CT3 2000 A 1986.000 A OK

5. Protection Functionality Check


Differential [87]
(Note: Test equipment Auto Test Report is attached)
I Tolerance*: 0A 10 % T Tolerance*: 0.03 s 2%

Theoretical Measured Deviation Assessment


IPickup_Side1 0.30 A 0.29 A -0.01 A OK
TDiff 0.00 s 0.02 s 0.02 s OK
Characteristic Side 1 / Side 2 Mes 1 Mes 2 Mes 3 Mes 4
IBias 0.34 A 1.82 A 3.92 A 19.25 A
IDiff (Theoretical) 0.34 A 0.63 A 2.20 A 14.47 A
IDiff (Measured) 0.34 A 0.71 A 2.41 A 15.31 A
Deviation 0.78 % 12.30 % 9.20 % 5.79 %
Assessment OK OK OK OK
Theoretical Measured Deviation Assessment
K1 0.20 0.25 0.05 OK
K2 0.80 0.84 0.04 OK
IPickup_Side2 0.30 A 0.30 A -0.01 A OK

Characteristic Side 1 / Side 3 Mes 1 Mes 2 Mes 3 Mes 4


IBias 0.34 A 1.82 A 3.92 A 19.25 A
IDiff (Theoretical) 0.34 A 0.63 A 2.20 A 14.47 A
IDiff (Measured) 0.34 A 0.71 A 2.41 A 15.29 A
Deviation 0.78 % 12.30 % 9.20 % 5.71 %
Assessment OK OK OK OK
Theoretical Measured Deviation Assessment
K1 0.20 0.25 0.05 OK
K2 0.80 0.84 0.04 OK
IPickup_Side3 0.30 A 0.30 A 0.00 A OK
*as per OEM recommendations

Functionalities Checks
Description Assessment
86 Lockout Relay Trip OK
DTT-B Send OK

Binary Outputs Checks


Output No. Function Assigned Assessment

GCCIA's Representative Omexom's Representative


Name: Tushar Name: Mahmoud Reda

Signature: Signature:

GCCIA_JASRA_FUT_P633-TEE2_2022_0 2/4
GCCIA - Protection Maintenance Test Report
1 DTT-B Send OK
1 3Phase Trip to 86CB OK
2 Alarm To BCU OK

LED & Tripping Test


Description Assessment
Tripping initiated from the relay OK
All concerned tripping and Lockout relays operated correctly OK
CB tripped by Trip Relay OK
Trip LED operated correctly OK
Alarm LED operated correctly OK
Lockout Relay reset by DCS OK
Lockout Reset by ICC OK
CB close block interlock checked by DCS OK

Final Checks
Description Assessment
Events records extracted and checked OK
Fault Records Checked OK
Disturbances records extracted and checked OK
All Test equipment, leads, shorts and test blocks removed OK
Alarms rest LEDS reset OK
Trip and Lockout Relays reset OK
Disturbed customer wiring re-checked and normalized OK
CT /VT wiring tightness at terminal block checked OK
All relay setting re-checked and normalized OK

On Load Measurement after Energization


Note: Below mentioned relay measurements extracted from the Relay are attached with the report
Value displayed Assessment
IR CT1 A ?
IY CT1 A ?
IB CT1 A ?
IN CT1 A ?
IR CT2 A ?
IY CT2 A ?
IB CT2 A ?
IN CT2 A ?
IR CT3 A ?
IY CT3 A ?
IB CT3 A ?
IN CT3 A ?

D. Test equipment used


S.N0 Description Make Serial number Last calibration date Calibration due date

GCCIA's Representative Omexom's Representative


Name: Tushar Name: Mahmoud Reda

Signature: Signature:

GCCIA_JASRA_FUT_P633-TEE2_2022_0 3/4
GCCIA - Protection Maintenance Test Report
1 Injection Kit Omicron CMC356 GK705N 19-12-2019 19-12-2020
2 Multimeter FLUK 31210031 19-12-2019 19-12-2020
Type: EASRGY STUDIO
3 Relay Setting Software
Version : V.8

Remarks:

GCCIA's Representative Omexom's Representative


Name: Tushar Name: Mahmoud Reda

Signature: Signature:

GCCIA_JASRA_FUT_P633-TEE2_2022_0 4/4
OMICRON AUTOMATIC TESTS
REPORT

GCCIA_JASRA_FUT_P633-TEE2_2022_0

Macro-Enabled Worksheet

Test Object - Device Settings


Substation/Bay:
Substation: JASRA Substation address:
Bay: 1RA1 Bay address:
Device:

Name/description: Settings Manufacturer:


Device type: P633 Device address:
Serial/model number: 2742227/08/07

Additional info 1: TEE2 - BUS FEEDER


DIFFERENTIALRELAY
Additional info 2: P6338491040NN03L00

Hardware Configuration
Test Equipment
Type Serial Number

CMC356 GK705N
Hardware Check
Performed At Result Details

2/27/2022 11:18:05 Passed


AM

Group:Differential (87)

DIFF_Initial conditions S1
Instruction Text:
- IR-IY-IB Side 1 wired
- Omicron contact: Trip contact
- If only one accessible side , “Internal loopback” enabled for AREVA relays or keep optical fibers connected (TELECOM FAIL not
activited) without specific mode for Siemens relays
- If 87 Differential Current monitoring setting = ON, put OFF

User Input:

Test State: Continue

Tested by:Mahmoud Reda - 27/02/2022 1/9


OMICRON AUTOMATIC TESTS
REPORT

GCCIA_JASRA_FUT_P633-TEE2_2022_0

DIFF_IPickup_S1.rp:

Test Settings
General
No. of ramp states: 1
Total steps per test: 151
Total time per test: 30.200 s
No. of test executions: 1

Input Mode: Direct


Fault Type:
Ramped Quantities
I L1, L2, L3 / Magnitude

Ramp States
Ramp Ramp 1

I L1 225.0 mA
0.00 °
50.000 Hz
I L2 225.0 mA
-120.00 °
50.000 Hz
I L3 225.0 mA
120.00 °
50.000 Hz
I(2)-1 0.00 A
0.00 °
50.000 Hz

I(2)-2 0.00 A
-120.00 °
50.000 Hz
I(2)-3 0.00 A
120.00 °
50.000 Hz
Force abs. Phases Yes
Sig 1 From 225.0 mA
Sig 1 To 375.0 mA
Sig 1 Delta 1.000 mA
Sig 1 d/dt 5.000 mA/s
Bin. out 1 0
Bin. Out 2 0
Bin. Out 3 0
Bin. Out 4 0
dt per Step 200.0 ms
Ramp Steps 151
Ramp Time 30.200s
Trigger Bin
Trigger Logic OR
Trip 1
Step back No

Tested by:Mahmoud Reda - 27/02/2022 2/9


OMICRON AUTOMATIC TESTS
REPORT

GCCIA_JASRA_FUT_P633-TEE2_2022_0

Delay Time 0.00 s


Test Module
Name: OMICRON Ramping Version: 4.20
Test Start: 27-Feb-2022 11:30:39 Test End: 27-Feb-2022 11:30:55
User Name: Manager:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact

IPickup_S1 Ramp 1 Trip 0->1 I L1, L2, 300.0 mA 293.0 mA 30.00 mA 30.00 mA -7.000 mA + 85.80 ms
L3
Assess: + .. Passed x .. Failed o .. Not assessed

Test State:
Test passed

DIFF_Initial conditions S2
Instruction Text:
- IR-IY-IB Side 2 wired
- Omicron contact: Trip contact

User Input:

Test State: Continue

DIFF_IPickup_S2.rp:

Test Settings
General
No. of ramp states: 1
Total steps per test: 151
Total time per test: 30.200 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(2)-1, -2, -3 / Magnitude

Ramp States
Ramp Ramp 1

I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz

Tested by:Mahmoud Reda - 27/02/2022 3/9


OMICRON AUTOMATIC TESTS
REPORT

GCCIA_JASRA_FUT_P633-TEE2_2022_0

I L3 0.00 A
120.00 °
50.000 Hz
I(2)-1 225.0 mA
0.00 °
50.000 Hz
I(2)-2 225.0 mA
-120.00 °
50.000 Hz
I(2)-3 225.0 mA
120.00 °
50.000 Hz
Force Yes
abs.
Phases
Sig 1 225.0 mA
From
Sig 1 To 375.0 mA
Sig 1 1.000 mA
Delta
Sig 1 d/dt 5.000
mA/s
Bin. out 1 0
Bin. Out 2 0
Bin. Out 3 0
Bin. Out 4 0
dt per 200.0 ms
Step
Ramp 151
Steps
Ramp 30.200s
Time
Trigger Bin
Trigger OR
Logic
Trip 1
Step back No
Delay 0.00 s
Time
Test
Module
Name: OMICRONVersion: 4.20
Ramping
Test 27-Feb- Test 27-Feb-
Start: 2022 End: 2022
11:31:23 11:31:39
User Manager:
Name:
Company:
Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact

IPickup_S2 Ramp 1 Trip 0->1 I(2)-1, - 300.0 mA 295.0 mA 30.00 mA 30.00 mA -5.000 mA + 700.0 μs
2, -3
Assess: + .. Passed x .. Failed o .. Not assessed

Tested by:Mahmoud Reda - 27/02/2022 4/9


OMICRON AUTOMATIC TESTS
REPORT

GCCIA_JASRA_FUT_P633-TEE2_2022_0

Test State:
Test passed

DIFF_Initial conditions Char check


Instruction Text:
Note ONLY FOR AREVA P631/P632/P633/P611:

With this relay type it might happen that the test points of the Characteristic Test vary around +/10%
the theoretical characteristic. This is a normal behavior of the relay. If it is necessary to check the
characteristic in a very exact manner one may set the trip time delay (Parameter Address: 010.162) to
20ms or 30ms and the hysteresis effective (Parameter Address: 072.006) to 'No' for the duration of the
test.

Attention! If the parameters are changed, they have to be set back after the test!

User Input:

Test State: Continue

DIFF_Char_S1_S2.df:
Test Module
Name: OMICRON Diff Operating Version: 4.20
Characteristic
Test Start: 27-Feb-2022 11:33:07 Test End: 27-Feb-2022 11:34:24
User Name: Manager:
Company:

Test Results for Fault Location L1-L2-L3 at Reference Side Side 1


Idiff Idiff Check
Ibias Nominal Dev (rel) Dev (abs) Test State Result
Actual
0.34 In 0.337 In 0.340 In 0.78 % 0.0026 In Tested Passed

1.81 In 0.633 In 0.711 In 12.30 % 0.0779 In Tested Passed

3.92 In 2.203 In 2.406 In 9.20 % 0.2026 In Tested Passed

19.25 In 14.467 In 15.305 In 5.79 % 0.8383 In Tested Passed

Test State:
Test passed
4 out of 4 points tested.
4 points passed.
0 points failed.

DIFF_tDiff.sq:
Test Settings
State State 1 State 2

I L1 0.00 A 900.0 mA
0.00 ° 0.00 °

Tested by:Mahmoud Reda - 27/02/2022 5/9


OMICRON AUTOMATIC TESTS
REPORT

GCCIA_JASRA_FUT_P633-TEE2_2022_0

50.000 Hz 50.000 Hz

I L2 0.00 A 900.0 mA
-120.00 ° -120.00 °

50.000 Hz 50.000 Hz

I L3 0.00 A 900.0 mA
120.00 ° 120.00 °

50.000 Hz 50.000 Hz

I(2)-1 0.00 A 0.00 A


0.00 ° 0.00 °

50.000 Hz 50.000 Hz

I(2)-2 0.00 A 0.00 A


-120.00 ° -120.00 °

50.000 Hz 50.000 Hz

I(2)-3 0.00 A 0.00 A


120.00 ° 120.00 °

50.000 Hz 50.000 Hz

Test Module
Name: OMICRON State Sequencer Version: 4.20
Test Start: 27-Feb-2022 11:34:48 Test End: 27-Feb-2022 11:34:51
User Name: Manager:
Company:

Test Results
Time Assessment
Ignore
Name before Start Stop Tnom Tdev- Tdev+ Tact Tdev Assess

tDiff State 2 State 2 Trip 0>1 0.00 s 30.00 ms 30.00 ms 20.20 ms 20.20 ms +
Assess: + .. Passed x .. Failed o .. Not assessed

Test State:
Test passed

DIFF_Initial conditions S1_S3


Instruction Text:
- IR-IY-IB Side 1 wired
- IR-IY-IB Side 3 wired
- Omicron contact: Trip contact

Tested by:Mahmoud Reda - 27/02/2022 6/9


OMICRON AUTOMATIC TESTS
REPORT

GCCIA_JASRA_FUT_P633-TEE2_2022_0

User Input:

Test State: Continue

DIFF_IPickup_S3.rp:
Test Settings
General
No. of ramp states: 1
Total steps per test: 151
Total time per test: 30.200 s
No. of test executions: 1

Input Mode: Direct


Fault Type:

Ramped Quantities
I(2)-1, -2, -3 / Magnitude

Ramp States
Ramp Ramp 1

I L1 0.00 A
0.00 °
50.000 Hz
I L2 0.00 A
-120.00 °
50.000 Hz
I L3 0.00 A
120.00 °
50.000 Hz
I(2)-1 225.0 mA
0.00 °
50.000 Hz
I(2)-2 225.0 mA
-120.00 °
50.000 Hz
I(2)-3 225.0 mA
120.00 °
50.000 Hz
Force Yes
abs.
Phases
Sig 1 225.0 mA
From
Sig 1 375.0 mA
To
Sig 1 1.000 mA
Delta
Sig 1 5.000
d/dt mA/s
Bin. out 0
1
Bin. 0
Out 2

Tested by:Mahmoud Reda - 27/02/2022 7/9


OMICRON AUTOMATIC TESTS
REPORT

GCCIA_JASRA_FUT_P633-TEE2_2022_0

Bin. 0
Out 3
Bin. 0
Out 4
dt per 200.0 ms
Step
Ramp 151
Steps
Ramp 30.200s
Time
Trigger Bin
Trigger OR
Logic
Trip 1
Step No
back
Delay 0.00 s
Time
Test
Module
Name: OMICRONVersion:4.20
Ramping
Test 27-Feb- Test 27-Feb-
Start: 2022 End: 2022
11:37:05 11:37:22
User Name: Manager:
Company:

Assessment Results
Name/ Exec. Ramp Condition Sig Nom. Act. Tol.- Tol.+ Dev. Assess Tact

IPickup_S3 Ramp 1 Trip 0->1 I(2)-1, - 300.0 mA 297.0 mA 30.00 mA 30.00 mA -3.000 mA + 21.40 ms
2, -3
Assess: + .. Passed x .. Failed o .. Not assessed

Test State:
Test passed

DIFF_Char_S1_S3.df:
Test Module
Name: OMICRON Diff Operating Version: 4.20
Characteristic
Test Start: 27-Feb-2022 11:38:35 Test End: 27-Feb-2022 11:39:51
User Name: Manager:
Company:

Test Results for Fault Location L1-L2-L3 at Reference Side Side 1


Idiff Idiff Check
Ibias Nominal Dev (rel) Dev (abs) Test State Result
Actual
0.34 In 0.337 In 0.340 In 0.78 % 0.0026 In Tested Passed

1.81 In 0.633 In 0.711 In 12.30 % 0.0779 In Tested Passed

Tested by:Mahmoud Reda - 27/02/2022 8/9


OMICRON AUTOMATIC TESTS
REPORT

GCCIA_JASRA_FUT_P633-TEE2_2022_0

3.92 In 2.203 In 2.406 In 9.20 % 0.2026 In Tested Passed

19.25 In 14.467 In 15.293 In 5.71 % 0.8261 In Tested Passed

Test State:
Test passed
4 out of 4 points tested.
4 points passed.
0 points failed.

DIFF_Restore Initial conditions Char check


Instruction Text:
Note ONLY FOR AREVA P631/P632/P633/P611:

If the parameters (Trip time delay, Hysteresis effective) have been changed, Restore as original!

User Input:

Test State: Continue

DIFF_Restore conditions
Instruction Text:
- Restore settings as original (87 Differential Current monitoring setting if used)

User Input:
Test State: Continue

Group end:Differential
(87)

Tested by:Mahmoud Reda - 27/02/2022 9/9