Gulf Cooperation Council Interconnection GCCIA Doc.

#: PCT-PRO-001
Authority GCCIA Issue #: 01
GCCIA Issue Date: 12-06-2018
Protection Maintenance Test Report
Omexom Doc. #: AUT-F-07 Rev.1

A. Relay Data
Date 27-01-22 Substation Ghunan DIA/Bay 1RB1

400KV REACTOR XL2


Relay BCU-XL1 - BAY C264M11I6650012301000061111R
Panel Designation GROUP-B Type/Model
Designation CONTROL UNIT 10
PROTECTION

Serial No. 131837 CMC No. LC282U Tested by Mahmoud Reda


Circuit
Firmware Version NA Aux: Voltage 110V DC BCU1+
Designation

B. Pre-Requisites
Equipment & Resources: Status
Competent personnel available for the test. OK
All competent persons are EHS certified to work in electrical environment. OK
AC & DC supply availability and security. OK
Test equipment calibrated and suitable for the test. OK
Safety:
Full understanding & electrical risk prevention instruction. OK
PPE safety available. OK
Awareness of electrical hazards precautions. OK
Isolation & Coordination:
Secondary Isolation of Tripping & Inter-tripping. OK
Primary Equipment isolation of Concerned equipment. OK
Coordination With Other Parties (GIS, Transformer, Etc.) OK

C. Record Test Sheet


1. Setting Verification
Settings Verification Items Assessment
All relay’s settings have been compared with GCCIA’s approved settings OK

2. Visual Inspection
Description Assessment
Relay Visual Inspection: OK
Clock set to GMT time: OK
Communication with PC & DCS: OK
Relay is synchronized by substation GPS: OK

3. CT/VT Data
Phase CT1 (A): 500 / 1 Main VT1 (V): 400000 / 110 LL

4. Measurement Value Test


Measurements
Value reference Value Injected Value displayed Assessment
IR CT1 500 A 500.460 A OK
IY CT1 500 A 500.310 A OK

GCCIA's Representative Omexom's Representative


Name: Hameed Name: Mahmoud Reda

Signature: Signature:

GCCIA_GHU_RB41_C264-BCU-XL1_2021_0 1/3
GCCIA - Protection Maintenance Test Report
IB CT1 500 A 500.430 A OK
IN CT1 500 A N.T. A OK

LED & Tripping Test


Description Assessment
Tripping initiated from the relay NA
All concerned tripping and Lockout relays operated correctly NA
CB tripped by Trip Relay NA
Trip LED operated correctly OK
Alarm LED operated correctly OK
Lockout Relay reset by DCS OK
Lockout Reset by ICC OK
CB close block interlock checked by DCS OK

Final Checks
Description Assessment
Events records extracted and checked NA
Fault Records Checked NA
Disturbances records extracted and checked NA
All Test equipment, leads, shorts and test blocks removed OK
Alarms rest LEDS reset OK
Trip and Lockout Relays reset OK
Disturbed customer wiring re-checked and normalized OK
CT /VT wiring tightness at terminal block checked OK
All relay setting re-checked and normalized OK

On Load Measurement after Energization


Note: Below mentioned relay measurements extracted from the Relay are attached with the report
Value displayed Assessment
IR CT1 184.660 A OK
IY CT1 184.600 A OK
IB CT1 184.700 A OK
IN CT1 NA A OK

D. Test equipment used


S.N0 Description Make Serial number Last calibration date Calibration due date
1 Injection Kit Omicron CMC356 LC282U 19-12-2019 19-12-2020
2 Multimeter FLUK 31210031 19-12-2019 19-12-2020
Type: EASRGY STUDIO
3 Relay Setting Software
Version : V.8

Remarks:

GCCIA's Representative Omexom's Representative


Name: Hameed Name: Mahmoud Reda

Signature: Signature:

GCCIA_GHU_RB41_C264-BCU-XL1_2021_0 2/3
GCCIA - Protection Maintenance Test Report

GCCIA's Representative Omexom's Representative


Name: Name:

Signature: Signature:

GCCIA's Representative Omexom's Representative


Name: Hameed Name: Mahmoud Reda

Signature: Signature:

GCCIA_GHU_RB41_C264-BCU-XL1_2021_0 3/3
OMICRON AUTOMATIC TESTS REPORT

GCCIA_GHU_RB41_C264-BCU-XL1_2021_0

Macro-Enabled
Worksheet

Test Object - Device Settings


Substation/Bay:
Substation: GHUNAN Substation address:
Bay: 1RB1 Bay address:
Device:

Name/description: Settings Manufacturer:


Device type: C264 Device address:
Serial/model number: 131837

Additional info 1: BCU-XL1 - BAY CONTROL UNIT

Additional info 2: C264M11I6650012301000061111


R10

Hardware Configuration
Test Equipment
Type Serial Number

CMC356 LC282U
Hardware Check
Performed At Result Details

1/27/2022 11:07:34 Passed


AM
Tested by:Mahmoud Reda - 27/01/2022 1/2 OMICRON

AUTOMATIC TESTS REPORT

GCCIA_GHU_RB41_C264-BCU-XL1_2021_0
Tested by:Mahmoud Reda - 27/01/2022 2/2