You are on page 1of 1

30.04.

2023 ‫צרכנים כלליים חדרי המחשב‬

DESIGNE
D Nameplat Derating
PDU/STS/ BUSBAR REDUNDA Quantity
Quantity e rated factor(s)
NCY "over N" ‫זרם‬ ‫הספק‬
30.04.2023 (N; N+N; "N" = ?
=?
capacity on actual
N+1; N+2 per unit load
etc.)
ID / Name / Nr. --- pc pc A % A KW
Electrical Board UPS A N 1 2 630 90.0% 274 185
Electrical Board UPS B N 1 2 500 90.0% 176 122
Electrical Board UPS C N 1 2 400 90.0% 233 160
‫ לוח‬B ‫ישן באתר טאבולה‬ 160 15 9
Taboola - A3 1 2 250 90.0% 110 74
Taboola - B3 n+n 1 2 250 148.0% 144 99
Taboola - C3 N 1 2 250 116.0% 124 83
Taboola HVAC DX - B3 N+N 1 1 160 90.0% 59 35 0.86 ‫סאטק‬
Taboola HVAC DX - C3 N+N 1 1 160 90.0% 124 82 0.86 ‫סאטק‬
Menora - A5 N+N 1 1 250 90.0% 81 52 102+ 82 + 59
Menora - C5 N+N 1 1 250 90.0% 60 39 63+55+61
Paz - Opal - B1 N+N 1 1 160 90.0% 9 6 14+9+5
Paz - Opal - A1 N+N 1 1 160 90.0% 8 5 8+11+5

Post Bank / Hachshara 0.88 ‫סאטק תקול‬


N+N 1 1 160 90.0% 8 5 ‫קורא סיכום מודד‬
( Mekorot - Mehish) A2 ‫שמאלי בלבד‬ 5+14+4

Post Bank / Hachshara 0.43 ‫סאטק תקול‬


N+N 1 1 160 90.0% 6 4 ‫קורא סיכום מודד‬
( Mekorot - Mehish) C2 ‫שמאלי בלבד‬ 5+7+7

Chiller 4 Board - Data


N+1 1 1 630 90.0% 0 0
Center

Chiller 5 Board - Data


N+1 1 1 630 90.0% 135 202
Center

HVAC for CHW Cracks


N 1 1 400 90.0% 110 74
Board A

HVAC for CHW Cracks


N 1 1 250 90.0% 70 47
Board B

30.04.2023 - ‫הנתונים אמיתיים מהקריאה של‬

You might also like