Shearail Design Manual to EC2 October 2010
Contents:
- Required information:
5. Punching Shear Resistance (vRd.cs) at the Control Perimeter (u1) with Reinforcement..
a. Punching Shear Resistance (vRd.cs)
b. Minimum punching shear reinforcement
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 1
Shearail Design Manual to EC2 October 2010
Required information.
x The mean ratio of tension reinforcement in both directions in a width of the column + 3d
each side (column under: top reinforcement, column over: bottom reinforcement).
- slab reinforcement drawing may be necessary, if this information isn’t given.
x Design value of the applied shear force VEd (Ultimate load: factored)
It is assumed that:
That any loads given by the Project Engineer have been factored using the EC load
factors (not from BS8110).
We should make sure that loads given are only the slab loads and do not include the
column above.
x The slab condition: i.e. Internal, edge or corner conditions, plus dimensions of the slab edge
from the face of the column.
Other consideration:
x Position and size of any hole/s in the slab within 6d from the edge of the supporting column,
pile, wall.
x Any changes in slab thickness, steps in level or movement joints local to the column/pile – a
general layout drawing may be necessary.
It is assumed that:
For internal columns 50% area of the top reinforcement should be provided placed in a equal
width to the sum of 0.125 times the panel each side of the column to resist the full negative
moment. 9.4.1.
For internal columns there will be a minimum of bottom two bars in each orthogonal direction
provided and this reinforcement should pass through the column. 9.4.1.
Similarly, the edge and corner columns conditions, the slab should be reinforcement to comply
with clause 9.4.2 (1)
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 2
Shearail Design Manual to EC2 October 2010
If the structure is unbraced or if adjacent spans differ by more than 25%, ȕ should be calculated,
refer to section 6.4.3 (3), (4) & (5).
(It is assumed that the Project Engineer will provide this information where applicable).
Cover
Top
T1
Overall Slab
T2
d
B2
B1
Bottom
Cover
Column/Pile below
Column above
Cover
Top
T1
Overall Slab
T2
d
B2
B1
Bottom
Cover
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 3
Shearail Design Manual to EC2 October 2010
C2
Internal column u0 = 2c1 + 2c2
C2
Edge column u0 = c2 + 3d or u0 = 2c1+ c2
(Smallest value of the two equations) 1.5d uo = perimeter of column face
C1
Corner column u0 = 3d or u0 = c1 + c2
1.5d
C2
(Smallest value of the two equations)
Note: holes within 6d of the face of the loaded area will reduce u0 accordingly. 6.4.2 (3) also see section 13
Holes/Penetrations in the slab
c. Design value of the applied shear stress (vEd 0) at the face of the column.
Where
Where
fcd the value of the design compressive strength of concrete.
NA to BS EN 1992-1-1-2004 3.1.2 (2)P Notes the limitation of C50/60, unless otherwise proven.
yc = 1.5 partial factor for material for ULS 2.4.2.4 table 2.1N
When vEd 0 is greater than vRd.max the slab depth(h) or the column size must be increased
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 4
Shearail Design Manual to EC2 October 2010
Internal column
by
2d C1 2d 2d C1 2d
u1 u1
2d
2d
C2
C1
bz
2d
2d
u1 = 2(c1 + c2) + 2ʌ(2d) u1 = 2ʌ(2d + (c1 / 2))
Edge column
C1 2d C1 2d
u1 u1
2d
2d
C2
C1
bz
2d
2d
u1 = 2c1 + c2 + ʌ(2d) u1 = ʌ(2d + (c1 / 2)) + 2e
Corner column
C1 2d C1 2d
e
f
C2
C1
2d
2d
u1 u1
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 5
Shearail Design Manual to EC2 October 2010
vRd.c = CRd.c k (100 l fck)1/3 + k1 scp > (vmin + k1 scp) (post-tensioned design) 6.4.4 (6.47)
where
k1 = 0.1 NA to BS EN 1992-1-1-2004 6.4.4 (1)
scp = (scy + scz) / 2 scy & scz are the normal concrete stress in the critical section
in y- and z- directions (MPa, positive if compression)
Ned.y & Ned.z Are the longitudinal forces across the full bay for internal columns
and the longitudinal force across the control section for edge columns,
The force may be from a load or pre-stressing action.
vRd.c = CRd.c k (100 l fck)1/3 > vmin (non-post or pre-tensioned design) 6.4.4 (6.47)
where
yc = 1.5 partial factor for material for ULS 2.4.2.4 table 2.1N
vRd.c = (0.18/ yc) k (100 l fck)1/3 > vmin & yc = 1.5 (Concise Eurocode 2, June 2006)
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 6
Shearail Design Manual to EC2 October 2010
5. Punching Shear Resistance (vRd.cs) at the Control Perimeter (u1) with Reinforcement.
vRd.cs = 0.75 vRd.c + 1.5 (d / sr) Asw fywd.ef (1 / (u1 d)) sin Į 6.4.5 (6.52)
Where
vRd.c < vEd 1 6.4.3 (3) 6.38
Į The angle between the shear reinforcement (studs at 90û = sin 90û = 1)
Transposed to:
vRd.cs = 0.75 vRd.c + 1.5 (d / sr) Asw fywd.ef (1 / (u1 d)) (vertical shear reinforcement)
vED 1 = vRd.cs
Asw = (vED 1 - 0.75 vRd.c) u1 sr / (1.5 fywd.ef) (per perimeter) (Concise Eurocode 2, June 2006)
or
Asw.min = (1.5 sin Į + cos Į) / (sr st) greater or equal to 0.08 ¥(fck) / fyk 9.4.3 (9.11)
Į The angle between the shear reinforcement (studs at sin 90û = 1 & cos 90û = 0)
Transposed to :
Asw.min x 1.5 / (sr st) > 0.08 ¥(fck) / fyk (IStuctE Manual Eurocode 2, Sept 2006)
Asw.min = 0.08 (sr st) ¥(fck) / 1.5 fyk
Asw.min / sr = 0.08 st ¥(fck) / (1.5 fyk) (as RCC Spreadsheet)
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 7
Shearail Design Manual to EC2 October 2010
The outermost perimeter of shear reinforcement should be placed at a distance not greater than kd
within Uout or Uout.ef 6.4.5 (4)
K=1.5 unless the perimeter Uout or Uout.ef is less than 3d from the face of loaded area
(column/pile). In this case the reinforcement should be placed in the zone 0.3d to
1.5d from the face of the column. NA to BS EN 1992-1-1-2004 6.4.5 (4)
The spacing of the reinforcement perimeters should not exceed 0.75d 9.4.3 (1)
The first stud is placed not less than 0.3d from the face of the support. 9.4.3 (1)
Similarly, the distance between the face of a support or circumference of a loaded area and the
nearest shear reinforcement taken into account in the design should not exceed d/2.
9.4.3 (4)
The spacing of reinforcement around a perimeter should not exceed 1.5d within the control
perimeter (2d from the loaded area), and should not exceed 2d for perimeters outside the
control perimeter, where that part of the perimeter is assumed to contribute to the shear
capacity. Reference 6.4.5 (4) figure 6.22
The shape of the perimeter Uout or Uout.ef will fluctuate in accordance to the arrangement of the
shear reinforcement and spacing limitations.
uout Control Perimeter uout Control Perimeter
u1 Control Perimeter at 2d
<2
from face of loaded area
d
<2
d
<1
.5
<1
d
<0 <0
.5
d
.7 5 .75
d d
.5d .5 d 1.5d
d-0 1.5d d- 0
0 .3 kd 0 .3 kd
d
kd
u1 Control Perimeter at 2d
from face of loaded area
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 8
Shearail Design Manual to EC2 October 2010
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 9
Shearail Design Manual to EC2 October 2010
d
5
1.
fixing on site. g1 g
x1
e
1.5d 2d
0.5d
2
u1
x
g 2*
This increase is ignored on the basis that the larger perimeter will have an increased load
capacity and is therefore a worst-case is being considered. d
e1 0.2
Aprrox. equal 0.053d
0.2d
1.5d
1 .5 d
e
2
0.75d Max.
5d
1.
0.75d Max.
u out
0.75d Max.
3d
68
1. Max 0.75d Max. g
Note: g2 = half the column g1
size, to a maximum of 0.75d 0.75d Max.
4d
e1
0.75d Max.
( k d)
.42 x
1 a
M 0.75d Max. 2d
1 .5 d
0.5d
u1
g 2*
0.5d g 2*
* Denotes: g = 0.75d maximum
*Denotes: The diagram indicates maximum spacing values in terms of ‘d’ (effective depth).
When the stud spacing is set to a maximum of 0.75d and g2 is also set at the
maximum of 0.75d, this allows for a site location tolerance between the studs around
the perimeter within the maximum stud spacing of 0.15d at 2d.
Provide intermediate corner rails when more than 4 perimeters of reinforcement are required
(more than four studs on a rail).
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 10
Shearail Design Manual to EC2 October 2010
1.553d
1.5d 1.5d e
e
Note: g2 = half the column size,
5d
to a maximum of 0.75d
1.
u out
3d
68 x
1. a
g1 g
M
1.
81
M 2d
4d ax
d)
42 x
e
1.
(k
a
M
1.5d
u1 0.5d 0.5d g 2*
c2
g 2*
(kd)
Assuming the slightly worst 2d case that all
1.5d
the sides are equal
e e
1.553d
1.5d 1.5d e
e
5d
1.
u out
3d
68 x
1. a
g1 g
M
1.
81
M 2d
4d ax
(kd)
42 x
e
e
1. a
M
1.5d
u1
g 2*
< 1.5d
0.5d g 2* g 2* 0.5d
e2
c2
g 2*
(kd)
2d
1.5d
e1 = c1 – 2g2
e2 = c2 – 2g2
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 11
Shearail Design Manual to EC2 October 2010
e
M 4d
ax
g 2* 0.5d u1 e2 c2
< 1.5d
g 2*
(kd)
2d
1.5d
< 0.75d < 1.5d
c1
e 1 = c 1 – g2 & e2 = c2 – g2 1.553d
1.5d e
M 4d
ax
(kd
)
g 2*
g 2* 0.5d u1 c2
< 1.5d
e2
g 2*
c1 2d
stud spacing = (g1 - 0.5d) / (number of stud on a rail – 1) (less than or equal to 0.75d)
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 12
Shearail Design Manual to EC2 October 2010
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 13
Shearail Design Manual to EC2 October 2010
e
around Uout for ‘e’, resulting 0.75d Max.
with a layout of 8 to 12 main
5d
0.75d Max.
1.
rails
u out
/2
0.75d Max.
st
The same pre-
la
g
st
fabricated rail can be 0.75d Max. g1
F°
used throughout the
0.75d Max.
layout.
3
0.75d Max.
e
st
(kd)
2d
E° 0.75d Max.
1.5d
u1 0.5d
g 2*
The number of rail spurs depends on the spacing rules inside 2d perimeter (less than or equal
to 1.5d) and on the last stud spacing (less than or equal to 2d).
As Uout is a polygon of equal sides: the number of sides = the number of main rail spurs.
.
e
1
Therefore try 8 spurs (as a standard layout)
u out increasing the number of spurs until e3 < 2d or e3 <
5d
/2
8
st
stud spacing = (g1 – 0.5d) / (number of stud on a rail -1) (less than or equal to 0.75d)
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 14
Shearail Design Manual to EC2 October 2010
9. Shearail Layout – Cruciform Pattern. (Note : Magenta coloured studs are not used in the design).
d
perimeters of studs.
>2
0.3d C 1 0.3d
b. General rules for a Cruciform Pattern
u out.ef
d
d
1.5d
kd
is 2
0.3d
Note: the value Uout.ef will not increase after more than three perimeters of reinforcement.
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 15
Shearail Design Manual to EC2 October 2010
u out.ef
d
uout. ef = (0.6d + c1) + (3dʌ) / 4 + 2d
(c1 column side)
= 2.6d + c1 + (3dʌ) / 4
5d
1.
similarly uout. ef for c2 column side = 2.6d + c2 + (3dʌ) / 4
d
= 5.2d + 2c1 + c2 + (3dʌ) / 2
kd
u out.ef
g1
C 2 0.3d
0.3d
< 0.75d
C1 0.3d
uout = 1.3d + c1 + (3dʌ) / 8 + 1.3d + c2 + (3dʌ) / 8
u out.ef
d
= 2.6d + c1 + c2 + (3dʌ) / 4
kd
u out.ef
g1
< 0.75d
0.3d
C
< 0.75d
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 16
Shearail Design Manual to EC2 October 2010
vRd.max = 0.3 fcd (1 – (fck / 250)) = 0.3 x 20 (1 - (30 / 250)) = 5.28 MPa
Consider reinforcement over 300 + 6 x 254 = 1.824m width in both directions from centre of
column.
Using H16 @ 150c/c both directions = 1340.41 mm2/m T1 & T2
ȡl = ¥((Asly / (b dy) x Aslz / (b dz)) = ¥(1340.41 / (1000 x 262) x 1340.41 / (1000 x 246)) =
= 0.00528 < 0.02
vRd.c = CRd.c k (100 l fck)1/3 = 0.12 x 1.887 (100 x 0.00528 x 30)1/3 = 0.569 MPa
check if vRd.c > vmin 0.569 > 0.497 Ok! (use largest value)
check if vED 1 < vRd.c 0.928 > 0.569 Shear reinforcement required
December 2009 check if vED 1 < 2vRd.c 0.928 < 1.138 Below 2vRd.c limitation
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 17
Shearail Design Manual to EC2 October 2010
Uout required = ȕ VEd / (vRd.c d) = 1.15 x 900 x1000 / (0.5688 x 254) = 7164mm
(note: any holes within 6d need to be allowed for)
0.75d = 190.5 mm
300 / 2 = 150 mm therefore: position rail central about column face in each direction
hence g 2 = 150 mm Uout required = 7164 mm
distance of 1st to last stud = 609 - 125 = 484 = 3 @165 mm < 0.75d = 190.5mm
Maximum stud distances on perimeter (st 1.5) = 1.5d = 381mm & (st last) = 2.0d = 508mm
fywd = (fy / 1.15) = 500 / 1.15 = 434.78 N/mm2 > 313.5 ok!
--- from earlier setting out: spacing rules are less then, 1.5d within 2d & 2d at the forth stud.
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 18
Shearail Design Manual to EC2 October 2010
Asw.min = 0.08 st sr ¥fck / (1.5 fyk) = 0.08 x 165 x 410.6 ¥30 / (1.5 x 500) = 39.6 mm2
598
405
5
32
598
5
16
8
62 5
16
16
5 u1
8
29
Rail Layout
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 19
Shearail Design Manual to EC2 October 2010
vRd.max = 0.3 fcd (1 – (fck / 250)) = 0.3 x 20 (1 - (30 / 250)) = 5.28 MPa or
Consider reinforcement over 300 + 6 x 254 = 1.824m width in both directions from centre of
column.
vRd.c = CRd.c k (100 l fck)1/3 = 0.12 x 1.887 (100 x 0.00528 x 30)1/3 = 0.569 MPa
check if vRd.c > vmin 0.569 > 0.497 Ok! (use largest value)
check if vED 1 < vRd.c 0.986 > 0.569 Shear reinforcement required
December 2009 check if vED 1 < 2vRd.c 0.928 < 1.138 Below 2vRd.c limitation
Uout required = ȕ VEd / (vRd.c d) = 1.15 x 900 x1000 / (0.569 x 254) = 7164mm
(note: any holes within 6d need to be allowed for)
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 20
Shearail Design Manual to EC2 October 2010
Try 10 spurs
e = 7164 / 10 = 716.4 mm
e2 = 1.5 x 254 x tan 18° = 123.8 mm F = 180°/ 10 = 18°
e3 = 716.4 – 123.8 x 2 = 468.8 mm 468.8 < 2d (508 mm)
therefore : use: 10 spurs without intermediate spacer rails
E = 360 / 10 = 36°
fywd = (fy / 1.15) = 500 / 1.15 = 434.78 N/mm2 > 313.5 ok!
Asw.min = 0.08 st sr ¥fck / (1.5 fyk) = 0.08 x 165 x 476 ¥30 / (1.5 x 500) = 45.9 mm2
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 21
Shearail Design Manual to EC2 October 2010
4 uout Perimeter
12
7234 mm long
°
18
401
1
6
38
47
Control Perimeter
117
4134mm long
74
1
3
723
605
36°
1171
Rail Layout
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 22
Shearail Design Manual to EC2 October 2010
Cruciform Pattern.
General rule: If more than 3 perimeters of studs are required then the Cruciform pattern
is normally unsuitable.
d
25
=
25
=
d
4
1
38
=
5d
7
53
1. Control Perimeter
4392mm long
9
26
1.5d = 381
Rail Layout
40 Studs total
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 23
Shearail Design Manual to EC2 October 2010
a. Spiral/Circular Pattern.
Edge column ȕ = 1.4 (unless advised otherwise by the Project Engineer).
d = 300 - 30 - 16/2- 16/2 = 254 mm
dy = 300 - 30 - 16/2 = 262 mm
dz = 300 - 30 – 16 - 16/2 = 246 mm
vRd.max = 0.3 fcd (1 – (fck / 250)) = 0.3 x 20 (1 - (30 / 250)) = 5.28 MPa
check if vED 0 < vRd.max 2.756 MPa < 5.28 MPa OK !
Consider reinforcement over 300 + 6 x 254 = 1.824m width in both directions from centre of
column.
Using H16 @ 150c/c both directions = 1340.41 mm2/m T1 & T2
ȡl = ¥((Asly / (b dy) x Aslz / (b dz)) = ¥(1340.41 / (1000 x 262) x 1340.41 / (1000 x 246)) =
= 0.00528 < 0.02
vRd.c = CRd.c k (100 l fck)1/3 = 0.12 x 1.887 (100 x 0.00528 x 30)1/3 = 0.569 MPa
check vRd.c > vmin 0.569 > 0.497 Ok! (use largest value)
check vED 1 < vRd.c 0.994 > 0.569 Shear reinforcement required
December 2009 check vED 1 < 2vRd.c 0.928 < 1.138 Below 2vRd.c limitation
Uout required = ȕ VEd / (vRd.c d) = 1.4 x 450 x1000 / (0.569 x 254) = 4362 mm
(note: any holes within 6d need to be allowed for)
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 24
Shearail Design Manual to EC2 October 2010
distance of 1st to last stud = 764 -125 = 639 say 4 @160 mm < .75d = 190.5mm
Maximum stud distances on perimeter (st 1.5) = 1.5d = 381mm & (st last) = 2.0d = 508mm
fywd = (fy / 1.15) = 500 / 1.15 = 434.78 N/mm2 > 313.5 ok!
--- from earlier setting out: spacing rules are less then, 1.5d within 2d & 2d at the forth stud.
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 25
Shearail Design Manual to EC2 October 2010
Asw.min = 0.08 st sr ¥fck / (1.5 fyk) = 0.08 x 165 x 410.6 ¥30 / (1.5 x 500) = 39.6 mm2
uout Perimeter
4416 mm long
480
6
48
315
0
32
Rail Layout
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 26
Shearail Design Manual to EC2 October 2010
a. Spiral/Circular Pattern.
Internal column ȕ = 1. 5 (unless advised otherwise by the Project Engineer).
d = 275 - 30 - 16/2- 16/2 = 229 mm
dy = 275 - 30 - 16/2 = 237 mm
dz = 275 - 30 – 16 - 16/2 = 221 mm
vRd.max = 0.3 fcd (1 – (fck / 250)) = 0.3 x 20 (1 - (30 / 250)) = 5.28 MPa or
check if vED 0 < vRd.max 2.347 MPa < 5.28 MPa OK !
vRd.c = CRd.c k (100 l fck)1/3 = 0.12 x 1.935 (100 x 0.00586 x 30)1/3 = 0.604 MPa
check if vRd.c > vmin 0.604 > 0.516 Ok! (use largest value)
check if vED 1 < vRd.c 1.067 > 0.604 Shear reinforcement required
December 2009 check vED 1 < 2vRd.c 1.067 < 1.208 Below 2vRd.c limitation
Uout required = ȕ VEd / (vRd.c d) = 1.5 x 215 x1000 / (0.604 x 229) = 2331.6 mm
(note: any holes within 6d need to be allowed for)
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 27
Shearail Design Manual to EC2 October 2010
fywd = (fy / 1.15) = 500 / 1.15 = 434.78 N/mm2 > 307.25 ok!
Check standard spacing less then 1.5d within 2d from column face.
Asw.min = 0.08 st sr ¥fck / (1.5 fyk) = 0.08 x 160 x 404 ¥30 / (1.5 x 500) = 37.8 mm2
uout Perimeter
2521.8 mm long
1
56
472
28
390
8
47
307
5
39
Control Perimeter
2
31
1320mm long
Rail Layout
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 29
Shearail Design Manual to EC2 October 2010
uout Perimeter
2542 mm long
1
43
369
Control Perimeter
1320 mm long
Rail Layout
30 Studs total
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 30
Shearail Design Manual to EC2 October 2010
uout Perimeter
Control Perimeter
at 2d
l2
Control Perimeter
at 2d
l2 ( l1 . l2 )
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 31
Shearail Design Manual to EC2 October 2010
When the hole is inside the stud arrangement the rails should be cut back and additional rails
added either side of the hole.
uout Perimeter
Control Perimeter
at 2d
l2
uout Perimeter
Control Perimeter Reduction
Reduction at 2d
Note: the studs shown in red cannot be used to calculate the steel area provided; this may
result in larger diameter studs being required, unless full length splitter rails are used.
The effected rail should be cut back to conform the spacing requirements.
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 32
Shearail Design Manual to EC2 October 2010
e1 0.2d
Rectangular / Square Columns. Aprrox. equal 0.053d
2
0.75d Max.
5d
studs outside of the 2d perimeter.
1.
0.75d Max.
u out 6d
.36 ax
3 M 0.75d Max.
0.75d Max. g
g1
0.75d Max.
4d
e1
0.75d Max.
(kd)
.42 x
1 a
1 .5 d M 0.75d Max. 2d
0.5d ** Max.
u1
g 2*
0.5d ** Max. g 2*
5d
1.
0.75d Max.
x 1.5d between studs inside
the 2d perimeter (U1) 0.75d Max.
u out
x 3.5d between studs 0.75d Max.
after the 2d
perimeter. 6d 0.75d Max. g1 g
. 36 ax
3 M 0.75d Max.
0.75d Max.
e1
4d 0.75d Max.
(kd)
.42 x
1 a
M 0.75d Max. 2d
1.5d
0.5d ** Max.
u1
g 2*
0.5d ** Max. g 2*
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 33
Shearail Design Manual to EC2 October 2010
e
As normal, the rails spiral around 0.75d Max. the
d5
column at an angle between 30o to
1.
45o giving equal lengths 0.75d Max.
st
la
around Uout for ‘e’, resulting uout
st
0.75d Max.
with a layout of 8 to 12 g
main rails. 0.75d Max. g1
F°
0.75d Max.
The same pre-
3
0.75d Max.
e
st
fabricated rail can be
(kd)
The number of rail spurs depends on the spacing rules inside 2d perimeter (less than or equal
to 1.5d) and on the last stud spacing (less than or equal to 3.5d).
As Uout is a polygon of equal sides: the number of sides = the number of main rail spurs.
.
e
1
Therefore try 8 spurs (as a standard layout)
u out increasing the number of spurs until e3 < 3.5d or e3 <
5d
/2
8
st
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 34
Shearail Design Manual to EC2 October 2010
g3
(kd)
1 .5d
0.75d Max.
e
0.75d Max.
5d
1.
0.75d Max.
u out 0.75d Max.
/2
.
ax
t
as
M
l
st
0.75d Max.
5d
g
3.
g1
F°
0.75d Max.
.
ax
0.75d Max.
M
5d
.
3.
ax
0.75d Max.
e
M
5d
3
0.75d Max.
st
1.
(kd)
2d
E° 0.75d Max.
1 .5 d
u1 0.5d ** Max.
g 2*
0.5d** Max. g 2*
* Denotes: g 2 = Column diameter / 2
** Denotes: 0.5d may be reduced to 0.3d
Max Frank Ltd Tel: +44 (0)1782 598041 . Fax: +44 (0)1782 315056 . e-mail: info@maxfrank.co.uk . web: www.maxfrank.co.uk Page 35