Low-Voltage Busway Design Guide DG017003EN

Pow-R-Flex Effective February 2020


Fittings 24.2-9

Vapor–Fire Barriers End Closers


Vapor–fire barriers hold a two-hour fire rating and are used to End closers terminate a bus run and can be used to cap off either
seal the busway internally for penetrations through walls, floors, the left or right end of a section of busway. End closers enclose
and other fire-rated penetrations, preventing the passage of and prevent incidental contact with live conductors. An end
flame, noxious gas, smoke and moisture. See Figure 24.2-18 for closure adds 0.25 inches to the overall length of the busway run.
minimum dimensions. See Figure 24.2-20.

5.60 4.20
(142.2) (106.7)

8.50
Fire Barrier Material (215.9)

Figure 24.2-18. Vapor–Fire Barrier

1.25
Tees (Horizontal) (31.8)

Tee fittings allow for busway connection in three different


horizontal directions. Pow-R-Flex tee fittings consist of special
joint covers with instructions on how to place the bridge joint. 8.59
The through connections connect to the short sides of the bridge (218.2)
joint, and the change connections connect to the long side of the
bridge joint.
5.75
(146.1)

Figure 24.2-20. End Closer

Figure 24.2-19. Horizontal Tees