YCP (LANDMARK) PROJECT

2. Calculation Sheet of Pressure Loss in Duct ( FCU Nos - F-T1/B0-02)

Reference Dwg No. LMK-FC-LB1-B00-ICE-M-MEC-202-C Calculation Sheet of Pressure Loss in Duct (a) (b)

Description Duct Duct Airflow Duct Size (Rect.) Duct Size Air Velocity Duct Fitting Duct Duct Fitting
Pressure Pressure Pressure
Building / Room Name Type Tag No. Section Element Shape Rate width high (Equivalent Velocity Pressure Length Loss Remark
Loss, Loss, Loss,
L/S mm. mm. Round) m/s Pa m Coefficients Pa / m Pa Pa (ASHRAE Ref.) Roughness dh Re F F' Parameters

Driver Room FCU F-T1/B0-02 A RAG RA Grille 212.0 400 400 437 1.33 1.06 5.00 Appendix (C ) Page-C-07

Model FWC-06H B Chamber 212.0 1200 500 827 0.35 0.08 0.50 0.04 Appendix (B) Page-22-Table-SD1-2 L/D = 0.6 ꝋ  = 180'
Air Flow (L/S) 212 C Duct Canvas 212.0 800 300 520 0.88 0.47 0.15 0.04 0.0 Roughness in Table-1 (Page-12) 3 436.4 21179 0.0349 0.03486

Medium Speed FCU FCU

1 Duct Canvas 212.0 800 300 520 0.88 0.47 0.15 0.04 0.0 Roughness in Table-1 (Page-12) 3 436.4 21179 0.0349 0.03486

2 Contraction 212.0 300 300 328 2.36 3.34 0.11 0.37 Appendix (B) Page-B-22 Table-SD1-2 L/D = 0.6 ꝋ  = 45'
3 Flex. Duct 212.0 Dia. 300 300 3.00 5.41 1.5 0.80 1.2 Appendix (C ) Page-C-21

4 Chamber 212.0 350 350 383 1.73 1.80 0.84 1.51 Appendix (B) Page-B-37 Table-SR4-3 A0/A1 = 1.7 ꝋ  = 180'
5 4-Way Diffuser Diffuser 212.0 300 300 328 2.36 3.34 20.00 Appendix (C ) Page-C-05

Air 20 °C Total (a) + (b) 28.13

Viscosity 18.2 10^-6 m2/s Total External Static Pressure Loss with 20% margin 33.76

Density 1.204 kg/m3 #Selection of Supply Fan 212.0 L/S x 34.00 Pa 34.00

Proposed External FCU Static Pressure 50 Pa Appendix (E ) Page-E-02

Proposed Internal FCU Static Pressure 47 Pa Appendix (E ) Page-E-02

Proposed Total FCU Static Pressure 97 Pa Appendix (E ) Page-E-02

Damper VD ꝋ = 0' Appendix G - Example Static Calculation Sheet of ASHRAE Standard