Professional Documents
Culture Documents
V600R001C03
User Manual
Issue 05
Date 2020-06-15
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Website: https://e.huawei.com
Purpose
This document describes the energy control center 500 (ECC500 for short) in terms of its
overview, configurations, ports, installation, commissioning, user interfaces, maintenance, and
troubleshooting, providing guidelines for onsite installation personnel and technical support
engineers.
Manufacturing, assembly, and factory maintenance commands are not provided in this
document. Certain advance commands for project implementation and error locating may
cause device exceptions or service interruptions if they are misused. These commands are not
provided in this document. If you need these commands, contact Huawei technical support.
The screen snapshots in this document are for reference only. The actual screen prevails.
Intended Audience
This document is intended for:
Marketing engineers
Technical support engineers
System engineers
Hardware installation engineers
Commissioning engineers
Data configuration engineers
Maintenance engineers
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol Description
Indicates a hazard with a high level of risk which, if not
avoided, will result in death or serious injury.
Symbol Description
Indicates a hazard with a low level of risk which, if not
avoided, could result in minor or moderate injury.
Indicates a potentially hazardous situation which, if not
avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to
personal injury.
Supplements the important information in the main text.
NOTE is used to address information not related to
personal injury, equipment damage, and environment
deterioration.
Change History
Changes between document issues are cumulative. The latest document issue contains all the
changes made in earlier issues.
Issue 05 (2020-06-15)
Updated section "Commissioning Preparations".
Incorporated the content in ECC500 V600R001C03 Hardware Cable Connection and
Commissioning Guide into ECC500 V600R001C03 User Manual.
Issue 04 (2019-12-20)
Updated the safety information.
Issue 03 (2019-03-15)
Updated the air conditioner name to smart cooling product.
Updated some MDU screenshots.
Issue 02 (2018-05-20)
Updated section "How Can I Change the ECC500 IP Address on the WebUI?".
Updated section "How Should I Link an AI/DI Alarm to a DO Port".
Issue 01 (2017-10-28)
Added section "How Should I Link an AI/DI Alarm to a DO Port".
Contents
2 Overview ................................................................................................................................. 11
2.1 Positioning ........................................................................................................................................................... 11
2.2 Features................................................................................................................................................................ 11
2.3 Typical Application Scenarios ...............................................................................................................................12
5 UI Description ........................................................................................................................ 54
5.1 LCD .....................................................................................................................................................................54
5.1.1 LCD Menu Hierarchy ........................................................................................................................................54
5.1.2 LCD Operations ................................................................................................................................................55
5.2 WebUI ..................................................................................................................................................................56
5.2.1 Commissioning Preparations..............................................................................................................................57
5.2.2 Adding a T/H Sensor..........................................................................................................................................58
5.2.3 Adding Dry Contact Devices ..............................................................................................................................61
5.2.3.1 Adding a Smoke Sensor ..................................................................................................................................61
5.2.3.2 Adding an SPD ...............................................................................................................................................62
5.2.3.3 Adding a Door Status Sensor ...........................................................................................................................63
5.2.3.4 Adding a Water Sensor ....................................................................................................................................64
5.2.3.5 Adding a Device Connected to a DI Port on the GPRS Expansion Card ...........................................................65
5.2.4 Adding UPSs .....................................................................................................................................................68
1 Safety Information
General Requirements
Do not install, use, or operate outdoor equipment and cables (including but not limited to
moving equipment, operating equipment and cables, inserting connectors to or removing
connectors from signal ports connected to outdoor facilities, working at heights, and
performing outdoor installation) in harsh weather conditions such as lightning, rain,
snow, and level 6 or stronger wind.
All cable holes should be sealed. Seal the used cable holes with firestop putty. Seal the
unused cable holes with the caps delivered with the cabinet. The following figure shows
the criteria for correct sealing with firestop putty.
Personal Safety
If there is a probability of personal injury or equipment damage during operations on the
equipment, immediately stop the operations, report the case to the supervisor, and take
feasible protective measures.
To avoid electric shock, do not connect safety extra-low voltage (SELV) circuits to
telecommunication network voltage (TNV) circuits.
General Requirements
Use dedicated insulated tools when performing high-voltage operations.
AC and DC Power
Do not connect or disconnect power cables with power on. Transient contact between the core
of the power cable and the conductor will generate electric arcs or sparks, which may cause
fire or personal injury.
If a "high electricity leakage" tag is attached on the equipment, ground the protective
ground terminal on the equipment enclosure before connecting the AC power supply;
otherwise, electric shock as a result of electricity leakage may occur.
Before installing or removing a power cable, turn off the power switch.
Before connecting a power cable, check that the label on the power cable is correct.
If the equipment has multiple inputs, disconnect all the inputs before operating the
equipment.
A circuit breaker equipped with a residual current device (RCD) is not recommended.
A damaged power cable must be replaced by the manufacturer, service agent, or
professionals to avoid risks.
High voltage operations and installation of AC-powered facilities must be performed by
qualified personnel.
Cabling
When routing cables, ensure that a distance of at least 30 mm exists between the cables
and heat-generating components or areas. This prevents damage to the insulation layer of
the cables.
Do not route cables behind the air intake and exhaust vents of the equipment.
Ensure that cables meet the VW-1 flame spread rating requirements.
Bind cables of the same type together. When routing cables of different types, ensure that
they are at least 30 mm away from each other.
If an AC input power cable is connected to the cabinet from the top, bend the cable in a
U shape outside the cabinet and then route it into the cabinet.
When the temperature is low, violent impact or vibration may damage the plastic cable
sheathing. To ensure safety, comply with the following requirements:
Cables can be laid or installed only when the temperature is higher than 0°C. Handle
cables with caution, especially at a low temperature.
Cables stored at subzero temperatures must be stored at room temperature for at least 24
hours before they are laid out.
Do not perform any improper operations, for example, dropping cables directly from a
vehicle.
When selecting, connecting, and routing cables, follow local safety regulations and rules.
ESD
The static electricity generated by human bodies may damage the electrostatic-sensitive
components on boards, for example, the large-scale integrated (LSI) circuits.
Wear ESD gloves or a well-grounded ESD wrist strap when touching the device or
handling boards or application-specific integrated circuits (ASICs).
When holding a board, hold its edge without touching any components. Do not touch the
components with your bare hands.
Package boards with ESD packaging materials before storing or transporting them.
Neutral-Ground Voltage
It is recommended that the three-phase loads be equalized and the neutral-ground voltage be
kept at less than 2 V to meet power distribution requirements.
Installation at Heights
Working at heights refers to operations that are performed at least 2 meters above the
ground.
Do not work at heights if the steel pipes are wet or other potential danger exists. After the
preceding conditions no longer exist, the safety director and relevant technical personnel
need to check the involved equipment. Operators can begin working only after obtaining
consent.
When working at heights, comply with local relevant laws and regulations.
Only trained and qualified personnel are allowed to work at heights.
Before working at heights, check the climbing tools and safety gears such as safety
helmets, safety belts, ladders, springboards, scaffolding, and lifting equipment. If they do
not meet the requirements, take corrective measures or disallow working at heights.
Wear personal protective equipment such as the safety helmet and safety belt or waist
rope and fasten it to a solid structure. Do not mount it on an insecure moveable object or
metal object with sharp edges. Make sure that the hooks will not slide off.
Set a restricted area and eye-catching signs for working at heights to warn away
irrelevant personnel.
Carry the operation machinery and tools properly to prevent them from falling off and
causing injuries.
Personnel involving working at heights are not allowed to throw objects from the height
to the ground, or vice versa. Objects should be transported by tough slings, hanging
baskets, highline trolleys, or cranes.
Ensure that guard rails and warning signs are set at the edges and openings of the area
involving working at heights to prevent falls.
Do not pile up scaffolding, springboards, or other sundries on the ground under the area
involving working at heights. Do not allow people to stay or pass under the area
involving working at heights.
Inspect the scaffolding, springboards, and workbenches used for working at heights in
advance to ensure that their structures are solid and not overloaded.
Any violations must be promptly pointed out by the site manager or safety supervisor
and the involved personnel should be prompted for correction. Personnel who fail to stop
violations will be forbidden from working.
Do not drag steel ropes and hoisting tools or bump hoisted objects against hard objects
during hoisting.
Using Ladders
Use wooden or fiberglass ladders when you need to perform live working at heights.
When a step ladder is used, ensure that the pull ropes are secured and the ladder is held
firm.
Before using a ladder, check that it is intact and confirm its load bearing capacity. Do not
overload it.
Ensure that the ladder is securely positioned. The recommended angle for a ladder
against the floor is 75 degrees, as shown in the following figure. An angle rule can be
used to measure the angle. Ensure that the wider end of the ladder is at the bottom, or
protective measures have been taken at the bottom to prevent the ladder from sliding.
When climbing a ladder, take the following precautions to reduce risks and ensure
safety:
Keep your body steady.
Do not climb higher than the fourth rung of the ladder from the top.
Ensure that your body's center of gravity does not shift outside the legs of the ladder.
Drilling Holes
When drilling holes into a wall or floor, observe the following safety precautions:
Do not drill holes into the equipment. Doing so may affect the electromagnetic shielding of
the equipment and damage components or cables inside. Metal shavings from drilling may
short-circuit boards inside the equipment.
Obtain the consent from the customer, subcontractor, and Huawei before drilling.
Wear goggles and protective gloves when drilling holes.
When drilling holes, protect the equipment from shavings. After drilling, clean up any
shavings that have accumulated inside or outside the equipment.
When removing a heavy or unstable component from a cabinet, be aware of unstable or heavy
objects on the cabinet.
Be cautious to avoid injury when moving heavy objects.
When moving the equipment by hand, wear protective gloves to prevent injuries.
Move or lift the equipment by holding its handles or lower edges. Do not hold the
handles of modules (such as power supply units, fans, and boards) that are installed in
the equipment because they cannot support the weight of the equipment.
Avoid scratching the cabinet surface or damaging cabinet components and cables during
equipment transportation.
When transporting the equipment using a forklift truck, ensure that the forks are properly
positioned to ensure that the equipment does not topple. Before moving the equipment,
secure it to the forklift truck using ropes. When moving the equipment, assign dedicated
personnel to take care of it.
Choose railways, sea, or a road with good condition for transportation to ensure
equipment safety. Avoid tilt or jolt during transportation.
Move a cabinet with caution. Any bumping or falling may damage the equipment.
1.6 Others
Exercise caution when shutting down the smart cooling product. Doing so may cause
equipment and room overheating, which will damage the equipment.
Exercise caution when powering off the rPDU or PDU2000. Doing so may affect the
power supply to equipment, which will interrupt services.
Exercise caution when manually shutting down the UPS inverter for transferring to
bypass mode, or when adjusting the UPS output voltage level or frequency. Doing so
may affect the power supply to equipment.
Exercise caution when setting battery parameters. Incorrect settings will affect the power
supply and battery lifespan.
2 Overview
2.1 Positioning
The ECC500 collector is a cross-platform monitoring product, in which a main control
module works with several expansion cards to receive, collect, process, and report signals.
Figure 2-1 shows an ECC500.
In the infrastructure management system of data centers, the ECC500 receives signals from
monitoring devices, collects, processes, and reports the signals to the NMS. In the data centers,
the ECC500 provides a complete solution for working environment and security management.
It collects, manages, and analyzes operating information of power and environment
monitoring devices, and reports alarms for them.
2.2 Features
Hardware Functions
The ECC500 supports AC inputs of 100 V to 240 V, 50 Hz or 60 Hz, and can be used
worldwide.
RS485 Communication Card, AI/DI Expansion Card and independent deployment AI/DI
unit support only RJ45 terminals, minimizing cable types, simplifying delivery, and
enabling fast deployment.
The RS485 expansion card can be connected to southbound intelligent equipment such
as uninterruptible power systems (UPSs), smart cooling products, and power distribution
cabinets over the RS485 ports compatible with two-wire or four-wire cables.
The AI/DI input channel can detect signals from multiple types of sensors, including
4–20 mA sensors, negative temperature coefficient (NTC) resistor-based temperature
sensors, current-based sensors, and devices with dry contacts.
The ECC500 supports the automatic assess of sensors such as water sensors and NTC
resistor-based temperature sensors, simplifying delivery and deployment.
The ECC500 provides the 12 V DC power supply to devices such as sensors and audible
and visual alarms. Additional power supply to these devices is not needed.
All boards, cards, and sensors are hot-swappable.
The ECC500 supports fault isolation. If a port is short-circuited or damaged, it is isolated
to ensure that other ports and boards are not affected.
The ECC500 features flexible extensibility. Boards or modules can be added or removed
to meet requirements of different scenarios.
The ECC500 can be mounted on a rack or wall.
Software Functions
You can use a web browser to access the ECC500 for remote management.
You can upgrade the system, main control module, and other functional modules
remotely. The main control module rolls back to the source version if the upgrade fails.
You can re-upgrade functional modules if upgrades fail.
The ECC500 supports simple network management protocol (SNMP) northbound
interfaces that are compliant with SNMP v1, v2c, and v3.
The ECC500 allows you to download the management information base (MIB) files.
The ECC500 allows you to download or upload configuration files for system backup.
The ECC500 allows you to manage users and alarms. You can also download log files.
The ECC500 provides user-friendly interfaces, including the web user interface (WebUI)
and LCD user interface (LUI). You can remotely and locally maintain the ECC500 over
the WebUI and LUI respectively.
The ECC500 can automatically identify boards, cards, and sensor devices.
RS485 ports of the ECC500 support the transparent transmission mode, ensuring
real-time communication between the southbound equipment and the NMS.
The ECC500 locates abnormal sensor connections based on alarms, thereby facilitating
maintenance.
Northbound interface: connects to the upper-layer NMS or equipment for provisioning services and
reporting alarms and performance data.
Southbound interface: connects to the lower-layer NMS or equipment for provisioning services and
transmitting performance indicator data.
The ECC500 provides SNMP northbound interfaces for connecting to a third-party NMS to query
data and report alarms.
The ECC500 used for transparent data transmission can connect to diverse devices complying with
the Modbus protocol and providing dry contacts. For the devices that can be connected, see the
monitoring device list for the project.
Local Management
If the ECC500 is used for local management, there is no need to configure the NMS and the
ECC500 works as a data collector and manager. The ECC500 collects, analyzes, and
processes device data, while users manage the devices on the ECC500 WebUI.
Figure 2-3 shows the networking for local management.
For the devices that can be connected to and managed by the ECC500 used for local management, see B
Devices Managed by the ECC500.
3.1 Configurations
The ECC500 consists of a power module, a main control module, an RS485 expansion card,
and an AI/DI expansion card. The detailed configuration rules are as follows:
An ECC500 with standard configurations consists of a main control module, a power
module, an RS485 expansion card, and an AI/DI expansion card, as shown in Figure 3-1.
Depending on site requirements, a maximum of four RS485 expansion cards and AI/DI
expansion cards can be configured.
Independent deployment AI/DI units can only be connected to COM4 and COM5 ports
on RS485 expansion cards in slots 3 and 4. A maximum of two independent deployment
AI/DI units can be connected to each port, and the Independent Deployment AI/DI Unit
addresses can only be 1 or 2.
If two RS485 expansion cards are configured, a maximum of eight independent
deployment AI/DI units can be configured.
3.2 Port
3.2.1 Main Control Module
The main control module provides the LCD for querying, setting, and controlling local
parameters. Figure 3-2 shows ports on the front panel of the main control board.
Indicators
Table 3-2 describes indicators on the main control module.
LCD/Buttons
The LCD displays parameters that for you to configure and query in real time by pressing the
four buttons on the panel. Table 3-3 describes the buttons.
After a menu is displayed, the standby screen is displayed if no button is pressed within 1 minute.
After a menu is displayed, the LCD screen becomes dark if no button is pressed within 30 seconds.
Port Description
Table 3-4 describes ports on the front panel of the main control module.
Parameter Description
Operating 100–240 V AC
voltage range
Rated operating 110 V AC/220 V AC
voltage
Frequency 50 Hz/60 Hz
Rated output 53.5 V DC/15 V DC
voltage
Structure The subrack of the power module is less than 1 U high and occupies two
slots of the ECC500 subrack.
Table 3-6 describes indicators on the front panel of the RS485 communication card.
Table 3-6 Description of indicators on the front panel of the RS485 communication card
Table 3-7 describes ports on the front panel of the RS485 communication card.
Table 3-7 Description of ports on the front panel of the RS485 communication card
COM4/12V and COM5/12V ports: Pins 3 and 8 of these two ports provide 12 V DC power.
Therefore, before connecting equipment to the ports, check the equipment pin description
to ensure that pins of the equipment match those on the ports, preventing damage to ports
or the equipment.
If an RS232 port transfers to an RS485 port and connects to an RS485 communications
card, one COM port connects to only one RS232 device. The recommended COM port is
COM1, COM2, or COM3.
The internal circuit design of the RS485 communication card allows its COM port to support
two-wire RS485 and four-wire RS422, eliminating the need to cascade cables, as shown in
Figure 3-5.
Table 3-8 describes indicators on the front panel of the AI/DI expansion card.
Table 3-8 Description of indicators on the front panel of the AI/DI expansion card
Table 3-9 describes ports on the front panel of the AI/DI expansion card.
Table 3-9 Description of ports on the front panel of the AI/DI expansion card
Do not connect an active sensor to an AI/DI port. Otherwise, the port will be invalid.
Sensors including 4 mA to 20 mA sensors, door status sensors, water sensors, and smoke sensors
provide data for the ports.
The power supply of each AI/DI port can be separately controlled. Each port provides a maximum of
14.6 V, 54 mA output power.
Table 3-10 describes indicators on the front panel of the Independent Deployment AI/DI Unit.
Table 3-10 Description of indicators on the front panel of the Independent Deployment AI/DI
Unit
Table 3-11 describes ports on the front panel of the Independent Deployment AI/DI Unit.
Table 3-11 Description of ports on the front panel of the Independent Deployment AI/DI Unit
The Independent Deployment AI/DI Unit is configured with a 4-bit DIP switch. Set toggle
switches 1 to 3 to configure the address of the Independent Deployment AI/DI Unit, and set
toggle switch 4 to enable or disable the resistance for the RS485 port. Table 3-12 describes the
mapping between the Independent Deployment AI/DI Unit address and the DIP switch
settings.
Table 3-12 Mapping between the Independent Deployment AI/DI Unit address and the DIP
switch settings
If the signal quality is poor due to signal reflection caused by long communications cables (longer than
50 m), set toggle switch 4 to ON for the furthest independent deployment AI_DI unit. After the DIP
switch settings are modified, power off and restart the independent deployment AI_DI unit for the new
settings to take effect.
Context
A flat-head screwdriver can be used as a floating nut mounting bar.
Procedure
Step 1 Use a floating nut mounting bar to install floating nuts (one on each site) into the mounting
holes in the posts of the rack, as shown in Figure 4-2.
Ensure that the floating nuts on both sides are on the same horizontal line.
Step 2 Place the ECC500 on the correct guide rails in the cabinet.
Step 3 Secure the ECC500 in the cabinet by tightening the M6 screws clockwise on the right and left
mounting ears, as shown by (2) in Figure 4-3.
----End
Procedure
Step 1 Install mounting ears on the ECC500 in the position and direction shown in Figure 4-4.
Step 2 Place the ECC500 at the installation position on the wall and mark the mounting ear hole
positions using a marker.
Step 3 Drill holes at the marked installation position (hole spacing: 52 mm x 472 mm) on the wall
using a hammer drill, and install four M8 expansion bolts into the holes.
Step 4 Install the ECC500 at the expansion bolts on the wall and ensure that the rear panel of the
ECC500 is flush with the wall.
Step 5 Tighten the four expansion bolts for the ECC500 using a socket wrench, as shown in Figure
4-4.
----End
The following tools are available: Phillips screwdriver, flat-head screwdriver, and rubber
mallet.
Context
When installing a rack-mounted Independent Deployment AI/DI Unit, choose
appropriate long mounting ears delivered with the Independent Deployment AI/DI Unit.
A flat-head screwdriver can be used as a floating nut mounting bar.
Procedure
Step 1 Use a floating nut mounting bar to install floating nuts (one on each site) into the mounting
holes in the posts of the rack, as shown in Figure 4-5.
Ensure that the floating nuts on both sides are on the same horizontal line.
Step 2 Install long mounting ears on the Independent Deployment AI/DI Unit.
Step 3 Secure the Independent Deployment AI/DI Unit in the cabinet by tightening the M6 screws
clockwise on the right and left mounting ears, as shown in Figure 4-6.
----End
Procedure
Step 1 Install mounting ears on the Independent Deployment AI/DI Unit in the position and direction
shown in Figure 4-7.
Step 2 Place the Independent Deployment AI/DI Unit at the installation position on the wall and
mark the mounting ear hole positions using a marker.
Step 3 Drill holes at the marked installation position (hole spacing: 52 mm x 205 mm) on the wall
using a hammer drill, and install four M8 expansion bolts into the holes.
Step 4 Install the Independent Deployment AI/DI Unit at the expansion bolts on the wall and ensure
that the rear panel of the module is flush with the wall.
Step 5 Tighten the four expansion bolts for the Independent Deployment AI/DI Unit using a socket
wrench, as shown in Figure 4-7.
----End
Figure 4-8 shows the ground cable connections for the ECC500 and Independent Deployment
AI/DI Unit.
Connect an audible and visual alarm to the ECC500 using the delivered adapter.
Context
When connecting a T/H sensor to the ECC500, perform the following steps to prepare a
special monitoring cable.
The cable connection method described in the section applies to cable connections from
the ports of the RS485 expansion card in the ECC500 to devices.
Procedure
Step 1 Prepare an RJ45 connector on one end of a network cable, as shown in Figure 4-13.
Step 2 Prepare an RJ12 connector on the other end of the cable, as shown in Figure 4-14.
Step 3 Plug the RJ45 connector to an RS485 port with 12 V power supply in the ECC500 and the
RJ12 connector to the RS485 port in the T/H sensor.
----End
Context
The cable connection method described in the section applies to cable connections from the
ports of the RS485 expansion card in the ECC500 to devices.
Procedure
Step 1 Remove the rear cover from the T/H sensor to expose the interior panel.
Step 2 Prepare RJ45 connectors on both ends of a network cable, as shown in Figure 4-13.
Step 3 Route the network cable through the hole on the rear cover middle, then plug one RJ45
connector to an RS485 port with 12 V power supply in the ECC500 and the other one to the
RS485 port in the T/H sensor.
----End
Context
When connecting a UPS2000-G-B to the ECC500, perform the following steps to
prepare a special monitoring cable.
The cable connection method described in the section applies to cable connections from
the ports of the RS485 expansion card in the ECC500 to devices.
UPS2000-G-B V200R001 is used and equipped with an LCD screen, as shown in Figure
4-15.
Procedure
Step 1 Prepare an RJ45 connector on one end of a network cable, as shown in Figure 4-13.
Step 2 Prepare a special RJ45 connector (exchange No. 4 and 5 wires) on the other end of the cable,
as shown in Figure 4-16.
Step 3 Plug the common RJ45 connector to an RS485 port in the ECC500 and the special one to the
RS485 port in the UPS2000-G-B.
----End
Context
The cable connection method described in the section applies to cable connections from
the ports of the RS485 expansion card in the ECC500 to devices.
UPS2000-G-A V100R001 is used and equipped with an LCD screen, as shown in Figure
4-17.
Procedure
Step 1 Prepare RJ45 connectors on both ends of a network cable, as shown in Figure 4-13.
Step 2 Plug one RJ45 connector to an RS485 port in the ECC500 and the other one to the RS485 port
in the UPS2000-G-A.
----End
Context
The cable connection method described in the section applies to cable connections from the
ports of the RS485 expansion card in the ECC500 to devices.
Procedure
Step 1 Prepare RJ45 connectors on both ends of a network cable, as shown in Figure 4-13.
Step 2 Plug one RJ45 connector to an RS485 port in the ECC500 and the other one to the RS485 port
in the UPS5000-E.
----End
Prerequisites
You have obtained an adapter used for transferring an RS232 port to an RS485 port.
Context
The cable connection method described in the section applies to cable connections from the
ports of the RS485 expansion card in the ECC500 to devices.
Procedure
Step 1 Prepare RJ45 connectors on both ends of a network cable, as shown in Figure 4-13.
Step 2 Plug one RJ45 connector to an RS485 port in the ECC500 collector and the other one to the
RS485 port in the adapter.
Step 3 Connect the adapter to the monitoring port in the UL33 UPS.
----End
Context
The cable connection method described in the section applies to cable connections from the
ports of the RS485 expansion card in the ECC500 to devices.
Procedure
Step 1 Prepare RJ45 connectors on both ends of a network cable, as shown in Figure 4-13.
Step 2 Plug one RJ45 connector to an RS485 port in the ECC500 and the other one to the RS485 port
in the NetCol5000-A.
----End
Context
The cable connection method described in the section applies to cable connections from the
ports of the RS485 expansion card in the ECC500 to devices.
Procedure
Step 1 Prepare RJ45 connectors on both ends of a network cable, as shown in Figure 4-13.
Step 2 Plug one RJ45 connector to an RS485 port in the ECC500 and the other one to the RS485 port
in the NetCol8000-A.
----End
Context
The cable connection method described in the section applies to cable connections from the
ports of the RS485 expansion card in the ECC500 to devices.
Procedure
Step 1 Prepare RJ45 connectors on both ends of a network cable, as shown in Figure 4-13.
Step 2 Plug one RJ45 connector to an RS485 port in the ECC500 and the other one to the RS485 port
in the PDU8000.
----End
Context
Before the PDU8000 configured with an ABB OTM ATS is delivered, the wiring terminal
block in the PDU8000 is connected to the RS485 port on the rear of the ABB OTM ATS. You
only need to connect the monitoring cable to the wiring terminal block in the PDU8000.
Locate the RS485 port on the wiring terminal block by using either of the following methods:
Obtain the number of the RS485 port on the wiring terminal block from the delivered
conceptual diagram.
Locate the RS485 port on the rear of the ATS and the cable connected to the port. The
port to which the other end of the cable is connected is the RS485 port on the wiring
terminal block.
The cable connection method described in the section applies to cable connections from the
ports of the RS485 expansion card in the ECC500 to devices.
Procedure
Step 1 Prepare an RJ45 connector on one end of a network cable, as shown in Figure 4-13.
Step 2 Connect the orange-white wires on the other end of the cable to the RS485+ wiring terminal
in the PDU8000. Connect the orange wires to the RS485- wiring terminal in the PDU8000.
In the example shown in Figure 4-18, PDU8000 wiring terminal 1 is RS485+ and wiring
terminal 2 is RS485-.
Context
Before the power distribution cabinet (PDU8000) configured with the PD510 coulometer is
delivered, the wiring terminal block in the PDU8000 has connected to the RS485 port on the
rear of the PD510 coulometer. You only need to connect the monitoring cable to the wiring
terminal block in the PDU8000.
Locate the RS485 port on the wiring terminal block by using either of the following methods:
During onsite operations, obtain the number of the RS485 port on the wiring terminal
block from the conceptual diagram.
Locate the RS485 port on the rear of the coulometer and the other end of the cable. The
port to which the other end connects is the RS485 port.
The cable connection method described in the section applies to cable connections from the
ports of the RS485 expansion card in the ECC500 to devices.
Procedure
Step 1 Prepare an RJ45 connector on one end of a network cable, as shown in Figure 4-13.
Step 2 Connect the orange-white wires on the other end of the cable to the RS485+ wiring terminal
in the PDU8000. Connect the orange wires to the RS485- wiring terminal in the PDU8000.
In the example shown in Figure 4-19, PDU8000 wiring terminal 1 is RS485+ and wiring
terminal 2 is RS485-.
Context
The fan can be connected only to the COM1 port of the main control module in the ECC500.
Procedure
Step 1 Prepare RJ45 connectors on both ends of a network cable, as shown in Figure 4-13.
Step 2 Plug one RJ45 connector to the COM1 port on the main control module of the ECC500 and
the other one to the COM_OUT port on the fan.
----End
Parameter Description
IP address Set to 192.168.1.168 by default but can be adjusted according to the
network plan.
Subnet mask Set to 255.255.255.0 by default but can be adjusted according to the
network plan.
Gateway Set to 192.168.1.1 by default but can be adjusted according to the
network plan.
Figure 4-20 shows the procedure for setting these communications parameters.
Figure 4-24 shows how to restore ECC500 factory settings over the LCD.
Restoring factory settings will restore the ECC500 parameters to their factory settings.
Perform this operation with caution.
Toggles 1 to 6 of the DIP switch specify the device address in binary mode. ON indicates 1,
and OFF indicates 0. Table 4-3 shows an example of the switch settings.
Table 4-3 Mapping between T/H sensor device addresses and DIP switch settings
----End
Procedure
Step 1 Operate the DIP switch S2 on the optional Modbus card to set the UPS2000-G-A device
address.
Toggles 1 to 8 of DIP switch S2 specify the device address in binary mode. ON indicates 0,
and OFF indicates 1. Table 4-4 shows an example of the switch settings.
Table 4-4 Mapping between device addresses and Modbus card DIP switch settings
----End
Procedure
Step 1 Operate the DIP switch S1 on the optional Modbus card to set the UPS2000-G-B device
address.
Toggles 1 to 8 of DIP switch S1 specify the device address in binary mode. ON indicates 1,
and OFF indicates 0. Table 4-5 shows an example of the switch settings.
Table 4-5 Mapping between device addresses and Modbus card DIP switch settings
----End
Procedure
Step 1 Tap Settings on the UPS5000-E home screen.
Step 2 Enter the administrator user name and password and tap on the screen.
The preset user name and password for the UPS5000-E are respectively Admin and 000001. To ensure
access security, change the password upon first use.
Parameter Setting
RS485 address Indicates the device address assigned to the UPS5000-E. The
addresses of devices connected to a same port must be unique.
When creating a UPS5000-E on the ECC500 WebUI, enter this
value in Equipment Address.
RS485 baud rate Retain the default value 9600.
The DataBit, StopBit, and Parity for the UPS5000-E cannot be set on the WebUI. Their
default values are 8, 1, and None respectively.
----End
Procedure
Step 1 The default address of the UL33 UPS is 1 and does not need to be set. Fill the address in
Equipment Address when creating a UL33 UPS on the ECC500 collector.
----End
Procedure
Step 1 Tap Settings on the NetCol5000-A home screen.
Step 2 Enter the administrator user name and password and tap on the screen.
The preset user name and password for the NetCol5000-A are respectively Admin and 000001. To
ensure access security, change the password upon first use.
Parameter Setting
Com address Indicates the device address planned for the
NetCol5000-A. The addresses of devices
connected to the same collector port must be
unique. When creating a NetCol5000-A on
the ECC500 WebUI, enter the value in
Equipment Address.
Baud Rate Retain the default value 9600.
The DataBit, StopBit, and Parity for the NetCol5000-A cannot be set on the WebUI. Their
default values are 8, 1, and None respectively.
----End
Procedure
Step 1 Tap Settings on the NetCol8000-A home screen.
Step 2 Enter the administrator user name and password and tap on the screen.
The preset user name and password for the NetCol8000-A are respectively Admin and 000001. To
ensure access security, change the password upon first use.
Parameter Setting
Com address Indicates the device address planned for the
NetCol8000-A. The addresses of devices
connected to the same collector port must be
unique. When creating a NetCol8000-A on
the ECC500 WebUI, enter the value in
Device address.
Baud Rate Retain the default value 9600.
The DataBit, StopBit, and Parity for the NetCol8000-A cannot be set on the WebUI. Their
default values are 8, 1, and None respectively.
----End
Procedure
Step 1 Tap Settings on the PDU8000 home screen.
The preset user name and password for the PDU8000 are respectively admin and 000001. To ensure
access security, change the password upon first use.
Parameter Setting
Serial port baud rate Retain the default value 9600.
Serial port address Indicates the device address assigned to the PDU8000. The
addresses of devices connected to a same port must be unique.
When creating a PDU8000 on the ECC500 WebUI, enter this
value in Equipment Address.
The DataBit, StopBit, and Parity for the PDU8000 cannot be set on the WebUI. Their default
values are 8, 1, and None respectively.
----End
Procedure
Step 3 Press .
The preset password is 0001. To ensure access security, change the password upon first use.
Step 6 Press . On the Modbus parameter setting screen, set communications parameters.
Set the device address for the ABB OTM ATS. The addresses of devices connected to a same
port must be unique. When creating an ABB OTM ATS on the ECC500 WebUI, enter this
value in Equipment Address.
Step 7 Press ESC to return to the home screen.
----End
Procedure
Step 1 Hold down PROG/ESC for 3s on the display panel of the PD510 coulometer and enter the
correct password.
The preset password is 1000. To protect the access security, change the password after logging in to the
coulometer for the first time.
Parameter Description
Addr Indicates the device address planned for the
PD510 coulometer. The devices with the
same address cannot connect to the same
port. When creating a PD510 coulometer on
the ECC500 WebUI, enter this value in
Equipment Address.
DataBit, StopBit, and Parity for the PD510 coulometer cannot be set on the WebUI. Their
values are 8, 1, and None respectively.
Step 5 After the modification, hold down PROG/ESC for 3s to return to the home page so that the
configuration is completed.
----End
5 UI Description
5.1 LCD
The LCD of the ECC500 is located on the front panel of the main control module. It allows
you to:
View active alarms.
View the running status of the system.
Set system parameters, select a language, and set communications parameters.
Set basic parameters, such as the date, time, and LCD contrast.
Change the password.
Restore factory settings.
Selecting a Language
After powering on the ECC500, select English by pressing or , as shown in Figure 5-2,
After accessing the operating system, you can change the display language by performing the
steps shown in Figure 5-3.
Viewing Information
Figure 5-5 takes the equipment status as an example to show how to view information over
the LCD.
5.2 WebUI
To ensure secure data transmission, the ECC500 transmits encrypted data over the Secure
Sockets Layer (SSL) protocol to the WebUI, which allows you to:
View system status and current alarm information.
Set system parameters.
Add devices.
If the ECC northbound interface is connected by a NetEco, devices connected to the COM
port on the ECC500 do not need to be added on the ECC WebUI, such as the UPS,
temperature and humidity sensor, NetCol, PDU8000, and ATS.
Set the IP address.
If the SNMP network management system is deployed or the WebUI needs to be used in the
long term, deploy a firewall in front of the ECC500 collector.
You can log in to the ECC500 WebUI using Windows 7, Windows XP, Internet Explorer 8.0
or later, Firefox, or Chrome. It is recommended that you log in to the ECC500 WebUI using
Internet Explorer 8.0, FireFox32.0, and Chrome37.0.2062.103 m in Windows 7, and using
FireFox32.0 in Windows XP.
Set the TLS1.1 and TLS1.2 protocols for the browser. Use Internet Explorer 8 as an example.
Open the Internet Explorer, choose Tools > Internet Options, click the Advanced tab, and
select Use TLS1.1 and Use TLS1.2.
Context
After connecting a T/H sensor to the ECC500, add the T/H sensor on the ECC500 WebUI.
Procedure
Step 1 On a PC which is in the same IP address segment as the ECC500, enter
https://XX.XX.XX.XX in the address box, and press Enter.
Step 2 (Optional) Install a network security certificate if a certificate problem message is displayed.
For details, see 7.3 How Can I Install a Network Security Certificate?.
This operation is performed on Windows 7. If another operating system is used, perform this operation
based on actual conditions.
Step 3 Set User Name and Password, and click Log In. The WebUI login page is displayed, as
shown in Figure 5-7.
The setting example indicates that the T/H sensor is connected to the COM5 port of the
RS485 card in slot 3 of the ECC500. If the T/H sensor is connected to another port, set the
slot number for the connected port.
Parameter Setting
Communication Select 3 from the drop-down list box.
Board Slot
Communication Select 5 from the drop-down list box.
Board COM
Equipment Address In this example, set Equipment Address to 1. Set the actual
device address of the T/H sensor during operations.
Timeout The default timeout interval is 2s. Set the parameter to the required
value.
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.
Prerequisites
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Context
A smoke sensor should be connected to the AI/DI_1 port on the MUE05A4 of the
ECC500 by default. To connect the smoke sensor to another port, set the port parameters
using the following method.
A smoke sensor can be automatically identified. After it is connected to an AI/DI port on
the ECC500. The sensor type is automatically identified and displayed in AI/DI_1
Sensor Type on the ECC500 WebUI.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Monitoring > MUE05A Expansion Card > MUE05A4 > Running Parameter >
AI/DI_1 Port Settings.
Step 3 Set AI/DI_1 Sensor to Enable.
Step 4 Click Submit.
Step 5 Set AI/DI_1 Sensor Name, for example, to Smoke_sensor.
Step 6 Check whether Smoke Sensor is automatically displayed in AI/DI_1 Sensor Type.
Step 7 Set AI/DI_1 Power Supply to On.
Step 8 Click Submit. Figure 5-9 shows the configured page.
----End
Prerequisites
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Context
A surge protective device (SPD) should be connected to the AI/DI_2 port on the
MUE05A4 of the ECC500 by default. To connect the SPD to another port, set the port
parameters using the following method.
An SPD is a normally closed (NC) dry contact device. The normal signal status is NC,
and the alarm signal status is normally open (NO).
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Monitoring > MUE05A Expansion Card > MUE05A4 > Running Parameter >
AI/DI_2 Port Settings.
Step 3 Set AI/DI_2 Sensor to Enable.
Step 4 Click Submit.
Step 5 Set AI/DI_2 Sensor Name, for example, to SPD.
Step 6 Set AI/DI_2 Sensor Type to NC.
Step 7 Set AI/DI_2 Power Supply to On.
Step 8 Click Submit. Figure 5-10 shows the configured page.
----End
Prerequisites
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Context
A door status sensor should be connected to the AI/DI_3 port on the MUE05A4 of the
ECC500 by default. To connect the door status sensor to another port, set the port parameters
using the following method.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Monitoring > MUE05A Expansion Card > MUE05A4 > Running Parameter >
AI/DI_3 Port Settings.
Step 3 Set AI/DI_3 Sensor to Enable.
Step 4 Click Submit.
Step 5 Set AI/DI_3 Sensor Name, for example, to Door_Sensor.
Step 6 Set AI/DI_3 Sensor Type to Door Sensor.
Step 7 Set AI/DI_3 Power Supply to On.
Step 8 Click Submit. Figure 5-11 shows the configured page.
----End
Prerequisites
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Context
A water sensor should be connected to the AI/DI_4 port on the MUE05A4 of the
ECC500 by default. To connect the water sensor to another port, set the port parameters
using the following method.
A water sensor can be automatically identified. After it is connected to an AI/DI port on
the ECC500. The sensor type is automatically identified and displayed in AI/DI_4
Sensor Type on the ECC500 WebUI.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Monitoring > MUE05A Expansion Card > MUE05A4 > Running Parameter >
AI/DI_4 Port Settings.
Step 3 Set AI/DI_4 Sensor to Enable.
Step 4 Click Submit.
Step 5 Set AI/DI_4 Sensor Name, for example, to Water_Sensor.
Step 6 Check whether Leak Sensor(NC) is automatically displayed in AI/DI_4 Sensor Type.
Step 7 Set AI/DI_4 Power Supply to On.
Step 8 Click Submit. Figure 5-12 shows the configured page.
----End
Prerequisites
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Context
The following example describes how to add a diesel generator (DG) or mains status
monitoring device connected to a DI port on the GPRS expansion card.
After a DG or mains status monitoring cable is connected to the ECC500, set port
parameters on the ECC500 WebUI. After the setting, you can check whether the DG or
mains power supply is active on the ECC500 WebUI.
The DG and mains status monitoring cables are respectively connected to the DI_1 and
DI_2 ports on the MUC01A1 card (GPRS expansion card) in the ECC500 by default. If
they are connected to other ports, set the port parameters using the following method.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Monitoring > MUC01A1 > Running Parameter > DI_1 Port Settings.
Step 3 Set DI_1 Sensor to Enable.
Step 4 Click Submit.
Step 8 Choose Monitoring > MUC01A1 > Running Parameter > DI_2 Port Settings.
Step 9 Set DI_2 Sensor to Enable.
Step 10 Click Submit.
Step 11 Set DI_2 DI Level to NO.
Step 12 Set DI_2 Sensor Name, for example, to Mains_power_supply.
Step 13 Click Submit. Figure 5-14 shows the configured page.
----End
Follow-up Procedure
After setting the parameters, choose Monitoring > MUC01A1 > Running Parameter to
view the DG and mains status.
Prerequisites
A UPS2000-G is connected to the ECC500. The UPS2000-G and ECC500 have been
powered on.
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Context
After a UPS2000-G is connected to the ECC500, add the UPS2000-G on the ECC500 WebUI.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Home > Equipment Manage.
Step 3 Select UPS from the Equipment Type drop-down list box and set device parameters, as
shown in Figure 5-16. Table 5-3 describes the setting methods.
The setting example indicates that the UPS2000-G is connected to the COM2 port of the
RS485 card in slot 3 of the ECC500. If the UPS2000-G is connected to another port, set the
slot number for the connected port.
Parameter Setting
Communication Select 3 from the drop-down list box.
Board Slot
Communication Select 2 from the drop-down list box.
Board COM
Equipment Address In this example, set Equipment Address to 1. Set the actual
device address of the UPS2000-G during operations.
Timeout The default timeout interval is 2s. Set the parameter to the required
value.
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.
Prerequisites
A UPS5000-E is connected to the ECC500. The UPS5000-E and ECC500 have been
powered on.
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Context
After a UPS5000-E is connected to the ECC500, add the UPS5000-E on the ECC500 WebUI.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Home > Equipment Manage.
Step 3 Select UPS from the Equipment Type drop-down list box and set device parameters, as
shown in Figure 5-17. Table 5-4 describes the setting methods.
Parameter Setting
Communication Select 3 from the drop-down list box.
Board Slot NOTE
The setting example indicates that the UPS5000-E is connected to the
COM2 port of the RS485 card in slot 3 of the ECC500. If the UPS5000-E
is connected to another port, set the slot number for the connected port.
Equipment Address In this example, set Equipment Address to 1. Set the actual
device address of the UPS5000-E during operations.
Timeout The default timeout interval is 2s. Set the parameter to the required
value.
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.
Prerequisites
The EA800 UPS is connected to the ECC500. The EA800 UPS and ECC500 have been
powered on.
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Context
After the EA800 UPS is connected to the ECC500, add the EA800 UPS on the ECC500
WebUI.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Home > Equipment Manage.
Step 3 Select EA800UPS from the Equipment Type drop-down list box and set device parameters,
as shown in Figure 5-18. Table 5-5 describes the setting methods.
Parameter Setting
Communication Select 3 from the drop-down list box.
Board Slot NOTE
The setting example indicates that the EA800 UPS is connected to the
COM2 port of the RS485 card in slot 3 of the ECC500. If the EA800 UPS
is connected to another port, set the slot number for the connected port.
Parameter Setting
Board COM NOTE
The setting example indicates that the EA800 UPS is connected to the
COM2 port of the RS485 card in slot 3 of the ECC500. If the EA800 UPS
is connected to another port, set the number of the connected port.
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.
Prerequisites
A UL33 UPS is connected to the ECC500. The UL33 UPS and ECC500 have been
powered on.
You have obtained the ECC500 IP address as well as the user name and password for
WebUI login.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Context
After a UL33 UPS is connected to the ECC500, add the UL33 UPS on the ECC500 WebUI.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Home > Equipment Manage.
Step 3 Select UL33UPS from the Equipment Type drop-down list box and set device parameters,
as shown in Figure 5-19. Table 5-6 describes the setting methods.
Parameter Setting
Communication Select 3 from the drop-down list box.
Board Slot NOTE
The setting example indicates that the UL33 UPS is connected to the
COM2 port of the RS485 card in slot 3 of the ECC500. If the UL33 UPS is
connected to another port, set the slot number for the connected port.
Equipment Address In this example, set Equipment Address to 1. Set the actual
device address of the UL33 UPS during operations.
Timeout The default timeout interval is 2s. Set the parameter to the required
value.
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.
Context
After a NetCol5000-A is connected to the ECC500, add the NetCol5000-A on the ECC500
WebUI.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Home > Equipment Manage.
Step 3 Select NetCol from the Equipment Type drop-down list box and set device parameters, as
shown in Figure 5-20. Table 5-7 describes the setting methods.
Parameter Setting
Communication Select 3 from the drop-down list box.
Board Slot NOTE
The setting example indicates that the NetCol5000-A is connected to the
COM5 port of the RS485 card in slot 3 of the ECC500. If the
Parameter Setting
NetCol5000-A is connected to another port, set the slot number for the
connected port.
Equipment Address In this example, set Equipment Address to 1. Set the actual
device address of the NetCol5000-A during operations.
Timeout The default timeout interval is 2s. Set the parameter to the required
value.
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.
Context
After a NetCol8000-A is connected to the ECC500, add the NetCol8000-A on the ECC500
WebUI.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Home > Equipment Manage.
Step 3 Select NetCol from the Equipment Type drop-down list box and set device parameters, as
shown in Figure 5-21. Table 5-8 describes the setting methods.
Parameter Setting
Communication Select 3 from the drop-down list box.
Board Slot NOTE
The setting example indicates that the NetCol8000-A is connected to the
COM5 port of the RS485 card in slot 3 of the ECC500. If the
NetCol8000-A is connected to another port, set the slot number for the
connected port.
Equipment Address In this example, set Equipment Address to 1. Set the actual
device address of the NetCol8000-A during operations.
Timeout The default timeout interval is 2s. Set the parameter to the required
value.
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.
Context
After a PDU8000 is connected to the ECC500, add the PDU8000 on the ECC500 WebUI.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Home > Equipment Manage.
Step 3 Select PDU8000 from the Equipment Type drop-down list box and set device parameters, as
shown in Figure 5-22. Table 5-9 describes the setting methods.
Parameter Setting
Communication Select 3 from the drop-down list box.
Board Slot NOTE
The setting example indicates that the PDU8000 is connected to the COM5
port of the RS485 card in slot 3 of the ECC500. If the PDU8000 is
connected to another port, set the slot number for the connected port.
Parameter Setting
Communication Select 5 from the drop-down list box.
Board COM NOTE
The setting example indicates that the PDU8000 is connected to the COM5
port of the RS485 card in slot 3 of the ECC500. If the PDU8000 is
connected to another port, set the number of the connected port.
Equipment Address In this example, set Equipment Address to 1. Set the actual
device address of the PDU8000 during operations.
Timeout The default timeout interval is 2s. Set the parameter to the required
value.
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.
Context
After an ATS is connected to the ECC500, add the ATS on the ECC500 WebUI.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Home > Equipment Manage.
Step 3 Select ATS from the Equipment Type drop-down list box and set device parameters, as
shown in Figure 5-23. Table1 ATS parameters describes the setting methods.
Parameter Setting
Communication Select 3 from the drop-down list box.
Board Slot NOTE
The setting example indicates that the ATS is connected to the COM5 port
of the RS485 card in slot 3 of the ECC500. If the ATS is connected to
another port, set the slot number for the connected port.
Equipment Address In this example, set Equipment Address to 1. Set the actual
device address of the ATS during operations.
Timeout The default timeout interval is 2s. Set the parameter to the required
value.
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.
Context
After a PD510 coulometer is connected to the ECC500, add the PD510 coulometer on the
ECC500 WebUI.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Home > Equipment Manage.
Step 3 Select PD510 from the Equipment Type drop-down list box and set device parameters, as
shown in Figure 5-24. Table 5-11 describes the setting methods.
Parameter Setting
Communication Select 3 from the drop-down list box.
Board Slot NOTE
The setting example indicates that the PD510 coulometer is connected to
the COM2 port of the RS485 card in slot 3 of the ECC500. If the PD510
coulometer is connected to another port, set the slot number for the
connected port.
Parameter Setting
Communication Select 2 from the drop-down list box.
Board COM NOTE
The setting example indicates that the PD510 coulometer is connected to
the COM2 port of the RS485 card in slot 3 of the ECC500. If the PD510
coulometer is connected to another port, set the number of the connected
port.
Equipment Address In this example, set Equipment Address to 1. Set the actual
device address of the PD510 coulometer during operations.
Timeout The default timeout interval is 2s. Set the parameter to the required
value.
Follow-up Procedure
If the device addition fails, check whether the settings are consistent with the device
parameters.
Context
Networked devices, such as ATMs, are devices with the same IP attributes in an equipment
room or site. By adding a networked device, you connect the device to the ECC500 in the
same network so that the ECC500 monitors the device status. If the networked device is
offline, the ECC500 will report a disconnection alarm on its WebUI.
Procedure
Step 1 On a PC which is in the same IP address segment as the ECC500, enter
https://XX.XX.XX.XX in the address box, and press Enter.
Step 2 (Optional) Install a network security certificate if a certificate problem message is displayed.
For details, see 7.3 How Can I Install a Network Security Certificate?.
This operation is performed on Windows 7. If another operating system is used, perform this operation
based on actual conditions.
Step 3 Set User Name and Password, and click Log In. The WebUI login page is displayed, as
shown in Figure 5-26.
Context
After a video link is added, the camera IP address is recorded in the ECC500 WebUI and
you can open the linked camera page from the ECC500 WebUI.
A maximum of two video links can be added.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Maintenance > View Video.
----End
Follow-up Procedure
To delete a link from the list, select the target link in Video Info List, click Delete from list,
and click Submit.
Context
Set SNMPv3 parameters before connecting the ECC500 to the NMS. These parameters
are needed for setting up the ECC500 on the NMS.
The default values of SNMP Version and SNMP Port Number are SNMPv3 and 161
respectively. You change the SNMP version and port number using the following
method.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose System Settings > SNMP Settings.
Step 3 (Optional) Set SNMP Site Name as required, and click Submit.
Step 4 Set SNMP Version and SNMP Port Number to the required values, as shown in Figure
5-30.
Step 6 Set User Name. Select SHA or MD5 and AES or DES. Set MD5/SHA Password, Confirm
MD5/SHA Password, DES/AES Password, and Confirm DES/AES password. See Figure
5-32.
Set User Name, MD5/SHA Password, and DES/AES Password to any character strings that
meet the system requirements. Note that the MD5/SHA Password and DES/AES Password
must be different. Record the settings.
MD5 and DES are insecure. SHA and AES are recommended, and they are chosen in the
following example.
Step 7 After setting the parameters, click Confirm.
Step 9 Set Trap Target Address to the NetEco server IP address, Trap Port to the user-defined
port number, and SNMP Version to the required version.
Step 10 After setting the parameters, click Confirm.
----End
Context
If the ECC500 collector needs to communicate with an upstream network management
system, install the security authentication certificate by following instructions in this
section.
You need to apply to an organization authorized by the customer for a security certificate
and its key for the ECC500 collector to communicate with the network management
system. This section describes how to import the certificate and key.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose System Settings > Pass-through Settings.
----End
Follow-up Procedure
Import the NMS security certificate and key issued by an authorized party into the upper-level
NMS of the ECC500 collector. Then the ECC500 collector will be able to communicate with
the network management system.
Context
If the ECC500 collector needs to communicate with an upstream NMS, change the challenge
certification password by performing the following steps.
Procedure
Step 1 Log in to the WebUI of the ECC500 collector.
Step 2 Change the challenge certification password.
1. Choose System Settings > Pass-through Settings.
2. Set Enable security authentication to Enable and click Submit.
3. Set New Password and Confirm password, and then click Change Password.
Reset the challenge certification password only when necessary because the resetting will
disconnect the connection between the ECC500 collector and the NMS.
Step 3 (Optional) To restore the challenge certification password to the factory default, click Reset
password.
----End
Context
You can export parameter configurations for ECC500 A to a PC. If ECC500 B needs the same
parameter configurations, import the configuration file to ECC500 B.
The following parameters can be exported to a configuration file:
Device operating parameters in Monitoring
Before importing the operating parameters for a device, add the device on the ECC500 WebUI.
Device alarm parameters in System Settings > Alarm Parameters
System site name in System Settings > Site Settings
SNMP site name in System Settings > SNMP Settings
The number of connected devices for ECC500s A and B must be the same.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Maintenance > Configuration File, as shown in Figure 5-37.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Click Monitoring, select the device to be viewed, and select Running Information to view
the running parameters of the device.
Step 3 Choose Home > Active Alarms to view ECC500 to view active alarms of devices, boards,
and dry contacts connected to the ECC500 collector.
Step 4 Choose Query to view historical alarms and data, including performance data and operation
logs.
1. To view historical alarms, choose Query > Historical Alarms, and select Equipment,
Start Time, and End Time. Then click Query.
2. To view operation logs, choose Query > Operation Logs.
3. For details about how to view performance parameters and export data, see 7.18 How
Can I View Performance Data? and 7.21 How Can I Export Data?.
----End
All alarm IDs in this document are the alarm IDs allocated by the NetEco.
For details about the low voltage alarm for the COM5 port on the RS485 communication card and how
to clear the alarm, see the alarm description and troubleshooting instructions provided for the 6.2.1.2
MUS02A_COM4 Voltage Low Alarm.
Description
This alarm is generated when the board is not securely inserted or is faulty.
Attribute
Alarm ID Alarm Severity Alarm Type
22630 Set to Major by default. Equipment alarm
Possible Causes
The board is not securely inserted.
The board is removed.
The board is faulty.
Procedure
Step 1 Securely insert the board and tighten the screws.
Step 2 Replace the faulty board.
----End
Clearing
This alarm is cleared when the board is securely inserted into the subrack and the
communication between the board and the ECC500 resumes.
Description
This alarm is generated when the output voltage of the COM4 port is below the alarm
threshold.
Attribute
Alarm ID Alarm Severity Alarm Type
22631 Set to Major by default. Equipment alarm
Possible Causes
The power supply to the board is abnormal.
The power supply to the power module is abnormal.
RS485 equipment connected to the port is overloaded.
Loads connected to the port is short-circuited.
Procedure
Step 1 Replace the faulty board.
Step 2 Replace the faulty power module.
Step 3 Reduce the power consumption of the RS485 equipment or provide extra power supply to the
RS485 equipment.
Step 4 Check the cable connections between loads and the port.
----End
Clearing
This alarm is cleared when the output voltage of the COM4 port exceeds the alarm clearance
threshold.
For details about the alarms and troubleshooting for the four ports on the AI/DI expansion card, see the
alarm description and troubleshooting instructions provided for the AI/DI_1 port on the AI/DI expansion
card.
Description
This alarm is generated when the board is not securely inserted or is faulty.
Attribute
Alarm ID Alarm Severity Alarm Type
22634 Set to Major by default. Equipment alarm
Possible Causes
The board is not securely inserted.
The board is removed.
The board is faulty.
Procedure
Step 1 Securely insert the board and tighten the screws.
Step 2 Replace the faulty board.
----End
Clearing
This alarm is cleared when the board is securely inserted into the subrack and the
communication between the board and the ECC500 resumes.
Description
This alarm is generated when the normally open (NO) dry contacts are closed or the normally
closed (NC) dry contacts are open.
Attribute
Alarm ID Alarm Severity Alarm Type
22635 Set to Minor by default. Equipment alarm
Possible Causes
Alarms are generated.
Cables are not securely connected.
The sensors are faulty.
Procedure
Step 1 Query and clear alarms.
Step 2 Check that sensor cables are properly connected.
Step 3 Replace the faulty sensors.
----End
Clearing
This alarm is cleared when the NO dry contacts are open or the NC dry contacts are closed.
Description
This alarm is generated when the values reported by the sensors exceed the allowed ranges or
the sensors are not connected.
Attribute
Alarm ID Alarm Severity Alarm Type
22636 Set to Major by default. Equipment alarm
Possible Causes
Values reported by the sensors exceed the allowed ranges.
The sensors are not securely connected.
The sensors are faulty.
Procedure
Step 1 Check whether onsite signal volumes exceed the allowed ranges.
Step 2 Check that sensor cables are properly connected.
Step 3 Replace the faulty sensors.
----End
Clearing
This alarm is cleared after values reported by the sensors are within the allowed ranges or
sensors are properly connected.
Description
This alarm is generated when the values reported by the sensors exceed the upper alarm
thresholds.
Attribute
Alarm ID Alarm Severity Alarm Type
22637 Set to Minor by default. Equipment alarm
Possible Causes
Onsite signal volumes exceed the upper alarm thresholds.
The alarm thresholds are inappropriate.
The sensors are not securely connected.
The sensors are faulty.
Procedure
Step 1 Check whether the onsite signal volumes exceed the upper alarm thresholds.
Step 2 Check that the alarm thresholds are appropriate.
Step 3 Check that sensor cables are properly connected.
Step 4 Replace the faulty sensors.
----End
Clearing
This alarm is cleared when the values reported by the sensors are within the allowed ranges.
Description
This alarm is generated when the values reported by the sensors are below the lower alarm
thresholds.
Attribute
Alarm ID Alarm Severity Alarm Type
22638 Set to Minor by default. Equipment alarm
Possible Causes
Onsite signal volumes are below the lower alarm thresholds.
The alarm thresholds are inappropriate.
The sensors are not securely connected.
The sensors are faulty.
Procedure
Step 1 Check whether the onsite signal volumes are below the lower alarm thresholds.
Step 2 Check that the alarm thresholds are appropriate.
Step 3 Check that sensor cables are properly connected.
Step 4 Replace the faulty sensors.
----End
Clearing
This alarm is cleared when the values reported by the sensors are within the allowed ranges.
Description
This alarm is generated when the AIDI_1 output voltage is below the alarm threshold.
Attribute
Alarm ID Alarm Severity Alarm Type
22651 Set to Major by default. Equipment alarm
Possible Causes
The power supply to AIDI_1 is abnormal.
The power supply to the power module is abnormal.
Procedure
Step 1 Replace the faulty board.
Step 2 Replace the faulty power module.
----End
Clearing
This alarm is cleared when the AIDI_1 output voltage exceeds the alarm clearance threshold.
Description
This alarm is generated when the types of sensors detected by AIDI_1 do not match the
specified types or sensor cables are incorrectly connected.
Attribute
Alarm ID Alarm Severity Alarm Type
22698 Set to Major by default. Equipment alarm
Possible Causes
Sensor cables are incorrectly connected.
Types of the sensors do not match the specified types.
Procedure
Step 1 Check that sensor cables are properly connected.
Step 2 Check that the sensor types on the WebUI match the actual sensor types.
----End
Clearing
This alarm is cleared when the types of sensors detected by AIDI_1 match the specified types
and sensor cables are correctly connected.
For details about the alarms and troubleshooting for the eight ports on the Independent Deployment
AI/DI Unit, see the alarm description and troubleshooting instructions provided for the AI/DI_1 port on
the AI/DI expansion card.
Description
This alarm is generated when cables are not securely connected, the power supply is abnormal,
or the board is faulty.
Attribute
Alarm ID Alarm Severity Alarm Type
22656 Set to Major by default. Equipment alarm
Possible Causes
Cables are not securely connected.
The power supply is faulty.
The board is faulty.
Procedure
Step 1 Check that cables are properly connected.
Step 2 Rectify faults in the power supply.
Step 3 Replace the faulty board.
----End
Clearing
This alarm is cleared when the board is properly connected and the communication between
the board and the ECC500 resumes.
Description
This alarm is generated when the power voltage is below the alarm threshold.
Attribute
Alarm ID Alarm Severity Alarm Type
22697 Set to Major by default. Equipment alarm
Possible Causes
The power supply to the RS485 board is faulty.
Cables are not securely connected.
The power supply to the Independent Deployment AI/DI Unit is faulty.
Procedure
Step 1 Replace the faulty RS485 board or power module.
Step 2 Check that cables are properly connected.
Step 3 Replace the Independent Deployment AI/DI Unit.
----End
Clearing
This alarm is cleared when the power voltage exceeds the alarm clearance threshold.
Attribute
Alarm ID Alarm Severity Alarm Type
- Critical Alarm
Possible Causes
The communications cable is disconnected.
The ECC500 communications board is faulty.
The device is faulty.
Procedure
Step 1 Check whether the communications cable between the ECC500 and the device is
disconnected.
If yes, reconnect the communications cable.
If no, go to Step 2.
Step 2 Check whether the ECC500 communications board is faulty.
If yes, repair or replace the communications board.
If no, go to Step 3.
Step 3 Check whether the device is faulty.
If yes, repair the device.
If no, contact Huawei technical support.
----End
Attribute
Alarm ID Alarm Severity Alarm Type
- Warning Alarm
Possible Causes
The communications cable is disconnected.
Parameters are incorrectly set for the networked device.
The network is unstable.
Procedure
Step 1 Check whether the communications cable between the ECC500 and the networked device is
disconnected.
If yes, reconnect the communications cable.
If no, go to Step 2.
Step 2 Check whether the parameters are correctly set for the networked device. For details, see
5.2.10 Adding a Networked Device.
If yes, go to Step 3.
If no, reset the communications parameters.
Step 3 Check whether the network is proper.
If yes, go to Step 4.
If no, repair the network.
Step 4 Check whether the networked device is faulty.
If yes, repair the networked device.
If no, contact Huawei technical support.
----End
Attribute
Alarm ID Alarm Severity Alarm Type
- Warning Alarm
Possible Causes
The communications cable is disconnected.
The ECC500 is faulty.
Procedure
Step 1 Check whether the communications cable between the ECC500 and the switch is
disconnected.
If yes, reconnect the communications cable.
If no, go to Step 2.
Step 2 Check whether the ECC500 is faulty.
If yes, repair or replace the ECC500.
If no, contact Huawei technical support.
----End
6.3 Troubleshooting
Table 6-2 describes the common ECC500 faults and the troubleshooting measures.
For details about how to view alarm information, see 7.11 How Can I Handle Alarms?.
Before replacing parts, ensure that the power supply to the ECC500 has been disconnected
and power cable terminals have been removed.
Only trained and qualified personnel are allowed to perform the operations.
Operation personnel must wear electrostatic discharge (ESD) gloves.
The main control module, RS485 and AI/DI expansion cards can be replaced in the same way.
This section describes how to replace the main control module.
Replace the Independent Deployment AI/DI Unit if it is faulty. For the replacement method, see 4.2.3
(Optional) Installing a Rack-mounted Independent Deployment AI/DI Unit or 4.2.4 (Optional) Installing
a Wall-mounted Independent Deployment AI/DI Unit.
Procedure
Step 1 Remove cables from the old module, and insulate the cables and paste labels.
Step 2 Loosen the two captive screws on the panel of the old module counterclockwise by using an
M3 screwdriver.
Step 3 Hold the handle with both hands and pull out the module, as shown in Figure 6-1.
Step 4 Grasp the handle of the new module and put the module into the correct slot in the ECC500
subrack.
Step 5 Push the new module into the subrack until their front panels are aligned with each other.
Step 6 Close the handle.
Step 7 Push and tighten the captive screws using the M3 screwdriver, as shown in Figure 6-2.
Step 8 Connect the cables to the module based on the labels on the cables.
----End
7 FAQ
Context
Use Internet Explorer 8 as an example.
Procedure
Step 1 Open the Internet Explorer, choose Tools > Internet Options.
Step 2 Click Advanced, and select Use TLS1.1 and Use TLS1.2.
Step 3 Click Connections, and select LAN settings.
Step 4 Deselect Use a proxy server for your LAN in the Proxy server area.
Step 5 Click OK.
----End
Follow-up Procedure
If the ECC500 collector still cannot be logged in on the WebUI, contact Huawei technical
support.
Context
Install a network security certificate if a security certificate problem message is
displayed when you attempt to log in to the ECC500 WebUI.
You need to apply to an organization authorized by the customer for a network security
certificate and its key with the ECC500 IP address or domain name. This section
describes how to import the certificate and key.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose System Settings > Site Settings.
Step 3 Click Select a file behind Select network security certificate.
Step 4 Select the network security certificate to be imported from the PC and click Upload.
Step 5 Click Select a file behind Select the network security certificate key to be uploaded.
Step 6 Select the network security certificate key to be imported from the PC and click Upload.
Step 7 (Optional) If the network security certificate is encrypted, select If an encrypted private key
is imported, enter the password for decryption., and enter Key password and Confirm
key password.
----End
Context
A unified IP address (192.168.1.168) is configured for all ECC500s before delivery.
Reconfigure an IP address for the ECC500 as required to ensure normal communication with
a server.
Procedure
Step 3 Enter the password, press and to modify the value, and press .
Step 5 Press and to modify the value, and press to move the cursor to change IP
Address, Subnet Mask, and Default Gateway to the planned values.
----End
Context
A unified IP address (192.168.1.168) is configured for all ECC500s before delivery.
Reconfigure an IP address for the ECC500 as required to ensure normal communication with
a server.
Procedure
Step 1 On a PC which is in the same IP address segment as the ECC500, enter https://192.168.1.168
in the address box, and press Enter on the keyboard.
Step 2 (Optional) Install a network security certificate if a certificate problem message is displayed.
For details, see 7.3 How Can I Install a Network Security Certificate?.
This operation is performed on Windows 7. If another operating system is used, perform this operation
based on actual conditions.
Step 3 Set User Name and Password, and click Log In. The login page is displayed, as shown in
Figure 7-3.
Step 4 Choose System Settings > IP Address Settings. Change the IP address, subnet mask, and
default gateway for the ECC500 based on the planned parameters, as shown in Figure 7-4.
Procedure
Step 3 Enter the password, press and to modify the value, and press .
Remember the new password because it is necessary for ECC500 commissioning and
maintenance.
Step 5 Press and to change the value and press to confirm. Enter the old password
and then change the LUI password.
----End
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Maintenance > User Management.
Step 3 Select the user you want to modify, as shown in Figure 7-5.
Remember the new password because it is necessary for ECC500 commissioning and
maintenance.
Step 5 Select Change Password, set New Password and Confirm password for the ECC500, and
click Confirm, as shown in Figure 7-6.
Step 6 Enter the password that you have logged in to the system, and click Submit.
----End
Context
The Administrator, Engineer, and Operator user groups are optional on the user management
page, and they have different operation rights.
Administrator: Users in this group have all the rights, including user management as well
as browsing and modifying all parameters in the system.
Engineer: Users in this group have all the rights except system upgrade, and fault
information export.
Operator: Users in this group have all the rights except system upgrade, fault information
export, operation log viewing, data export, alarm parameter setting, monitoring module
IP setting, SNMP configuration, site configuration, and configuration file export.
The ECC500 allows a maximum of 16 users to be created and supports four concurrent online
users of the same level.
Procedure
Step 1 Log in to the ECC500 WebUI as an administrator.
Step 2 Choose Maintenance > User Management.
Step 3 Click Add, as shown in Figure 7-7.
Step 4 Set User Name, Password, and Confirm password, select an option from the Authority
drop-down list box, and click Confirm, as shown in Figure 7-8.
Step 5 Enter the password that you have logged in to the system, and click Submit.
----End
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose System Settings > Time Settings, as shown in Figure 7-9.
Context
Enable or disable an alarm and set the alarm severity depending on actual requirements.
If an alarm is set to Disable, the ECC500 will not report this alarm.
The setting methods for diverse alarms are the same. This section describes how to set
ECC500 network fault for System Equipment.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose System Settings > Alarm Parameters.
Step 3 Select System Equipment from the drop-down list box and click Confirm.
Step 4 Set ECC500 network fault to Enable or Disable and set Severity, as shown in Figure 7-10.
Figure 7-10 Enabling or disabling an alarm and setting the alarm severity
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Home > Active Alarms and view active alarms.
Step 3 Select an alarm to be acknowledged and click Confirm, as shown in Figure 7-11.
----End
Follow-up Procedure
Choose Query > Historical Alarm and view historical alarms.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Monitoring > MUE05A Expansion Card > MUE05A4 > Running Parameter >
AI/DI_1 Port Settings.
Step 3 Set AI/DI_1 Upper DI Alarm Association to the DO port to be associated, and then click
Submit.
SLOT1_DO (new page) or DO1 (old page) represents that the MUE05A expansion card where the
DO port is located is installed in slot 1 of the ECC500.
DO_1 represents the DO_1 port on the GPRS expansion card.
FAN1 represents fan 1 connecting to the ECC500.
Step 4 Choose Monitoring > MUE05A Expansion Card > MUE05A4 > Running Parameter >
DO Control.
Step 5 Click DO Settings, select Association, and click Submit.
----End
Context
Site network fault alarms are sent to the specified mobile phone numbers of maintenance
engineers through SMS. After the system site name is changed, the new site name will be
displayed in the short message content (for example, XXX site network fault) so that
maintenance engineers will know the site where the fault has occurred.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose System Settings > Site Settings.
Step 3 Modify System Site Name.
Step 4 Click Submit, as shown in Figure 7-14.
----End
Context
After the name of the device is changed, an alarm reported by the device will contain the
new device name. Using the device name, maintenance engineers can easily locate the
fault.
The names of the following devices can be changed: T/H sensor, UPS2000-G,
UPS5000-E, NetCol5000-A, NetCol8000-A, PDU8000, and ATS.
The device names can be changed in the same way. The following describes how to
change the names of the UPS2000-G and T/H sensor.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Change the UPS2000-G name.
1. Choose Monitoring > UPS2000 Group > UPS2000G-A31001 > Running
Parameter.
A31001 in UPS2000G-A31001 is variable and subject to change with the model, connected collector
port, and device address of the UPS2000-G. The displayed value prevails.
2. Set Name and click Submit, as shown in Figure 7-15.
34001 in Temp/Hum34001 is variable and subject to change with the model, connected collector port,
and device address of the T/H sensor. The displayed value prevails.
2. Set Name and click Submit, as shown in Figure 7-16.
----End
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Monitoring > Temp/Hum Group > Temp/Hum34001 > Running Parameter.
34001 in Temp/Hum34001 is variable and subject to change with the model, connected collector port,
and device address of the T/H sensor. The displayed value prevails.
Step 3 Set High Temperature Alarm Point, Low Temperature Alarm Point, High Humidity
Alarm Point, or Low Humidity Alarm Point, and click Submit, as shown in Figure 7-17.
----End
Context
A fan can be automatically identified. After the fan is connected to the ECC500, the fan
information is displayed on the ECC500 WebUI, as shown in Figure 7-18.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Monitoring > FAN Group > FAN1 > Running Parameter. Modify High
Temperature Alarm Thres and Low Temperature Alarm Thres.
Step 3 Choose Monitoring > FAN Group > FAN1 > Running Control. Set FAN Reset to Yes and
click Submit.
----End
Context
If there is no need to use or monitor a device, power off the device or disconnect the
device from the ECC500 and then delete the device failing in communication on the
ECC500. After the device is deleted, the device will not report any alarm to the ECC500.
Before deleting a device failing in communication, ensure that the device contains no other
devices that need to be monitored.
After a monitoring reset is performed, the ECC500 restarts.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Monitoring > System Equipment > Running Control.
Step 3 Select Monitor System Reset or Delete Communication Failed Equipment and click
Submit.
Step 4 (Optional) To reset the monitor, enter the password for the current user name and click
Submit.
----End
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Query > Performance Data.
Step 3 Set Equipment, Performance Data, Statistical Period, Start Time, and End Time, and
click Query. Figure 7-22 shows an example of querying temperature data collected by a T/H
sensor.
----End
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Query > Operation Logs and view ECC500 operation logs.
----End
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Click in the upper right corner of the home page and view the ECC500 version
information.
Step 3 Choose Maintenance > Version Information and view the ECC500 version information.
----End
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Query > Export Data.
You can export information of four types: Historical Alarms, Active Alarms, Performance
Data, and Operation Logs.
Step 3 Select the desired data type, for example, Historical Alarm and click Export Historical
Data, as shown in Figure 7-23.
You have prepared a PC which is in the same IP address segment as the ECC500 and
connected the PC to the ECC500 over a switch.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Maintenance > Fault Information and click Export Fault Information, as shown
in Figure 7-24.
Context
Restoring factory settings will restore parameters to their default factory values. Perform this
operation with caution.
Procedure
Step 1 Log in to the ECC500 WebUI.
Step 2 Choose Maintenance > Configuration File and click Restore Factory Settings, as shown in
Figure 7-25.
Step 3 Enter the password that you have logged in to the system, and click Submit.
----End
A Technical Specifications
Table A-2 describes the technical specifications of the Independent Deployment AI/DI Unit.
a: If the NetCol5000-A does not use ACC V100R001C30, contact Huawei technical support.
b: If the NetCol8000-A does not use ACC V100R001C20SPC500, contact Huawei technical support.
A
AI analog input
ATS Automatic Transfer Switch
D
DI digital input
DO digital output
E
ECC Energy Control Center
F
FE Fast Ethernet
I
IP Internet Protocol
L
LCD Liquid Crystal Display
LUI LCD user interface
M
MIB Management Information Base
P
PDU power distribution unit
S
SNMP Simple Network Management Protocol
U
UPS uninterruptible power system