BENEFITS
HARDWARE
PACKAGED UNIT: all-in-one unit for fast installation and maintenance. Only electrical power and ducts for return/supply air
to the Data Hall are required.
READY TO USE: no extra components needed. Built in control system for ALL parts.
RUST FREE: totally recyclable: the whole unit is made of aluminium. 20-years warranty on the full CASING of the unit
against corrosion.
02/03
02/03
1,25
1,20 1,30
NT
T
Y EFFICIE
PARTIAL POWER USAGE EFFECTIVENESS
1,10 1,40
VER
1,05 1,45
The choice of the materials used to construct the units, the possibility to recycle them,
and the energy used to produce and recycle them are very important things to consider
when referring to global energy savings and CO2 emissions reductions.
WORKING PRINCIPLE
The machine is equipped with two cooling sections, each with filtering section, air/air heat exchangers
and supply fans with variable air-flow.
Each cooling section handle 50% of the total air flow of the system.
The cooling effect is obtained inside the cross-flow air to air heat exchangers where the ambient air flow
and Data Center airflow never come into direct contact ensuring treated air purity.
The ambient air flow is ensured by dedicated fans with variable flow.
A suction filter section guarantees the quality of ambient air flow.
Partialization damper
(optional)
Condensing coil Air suction
(optional) from
Ambient air fans
Data Center
50%
Ps2
Ambient air
T3
1°stadio
04/05
04/05
50%
T2
Ps1
Ambient air
T1 H1
2°stadio
50%
Air delivery to
Data Center
—
100%
50%
T4 T5
CLIMATE CONDITIONS
The operation of the SIVIS system is influenced by the climate and not all climates are suitable for the Adiabatic
Cooling System. An analysis of the climate profile at the place of installation is necessary to verify the operation
conditions of SIVIS system.
10 11
0 0
25
90
90%
24
80%
70%
80
22
60%
25
Weather Data Location United Kingdom: LONDON 70 20
50%
YA
Altitude: 62 meters
18
DR
60
OF
M
RA
16
OG
Barometric Pressure: 100.584 kPa
KIL
50 20
%
ER
40
JP
14
-K
Atmospheric Pressure: 14.588 psia
PY
AL
40
TH
12
EN
%
15
30
30 10
%
25
Each point represent one hour of the thermal profile 10
% IDIT
Y 8
20 20 UM
EH
TIV
of London for a total of 8760 hours 10 5 15%
RE
LA
6
0 0 4
10%
-10 8%
-5
Operation area of the SIVIS -15
-15
-10
6%
4%
2
90%
30 24
C°
80%
-W
0.94
ET
70%
80 BU
LB
22
60%
TE
MP
ER
AT
0.92
25 UR
70 E 20
50%
Thermal load 100% - Site LONDON Working example of SIVIS system. 60
25
18
0.90
Environmental conditions: LONDON 50 20
16
%
40
14
Thermal load: 100%
40
0.88
20 12
OF
M
RA
%
15
30
0.87
OG
KIL
30 10
VOLU
DRY OPERATION
ER
%
25
0.86
JP
ME -
-K
15
Free-Cooling Y 8
PY
10 IDIT
CUB
%
AL
20 20 UM
EH
TH
IC M
TIV
EN
0.84 LA
RE
ETER
10 6
10 5 15%
WET OPERATION
PER
0
0.82
0 4
KG D
Adiabatic cooling -10
5
10%
RY A
-5 0 8%
0.80
-15
6%
IR
-10 2
-5
4%
0.78
-15
WET OPERATION + COMPRESSOR -10
0.76
2%
0.74
INSTALLATION
100% 100%
100%
50% 50%
ROOF INSTALLATION
WITH HOT AISLE COMPARTMENT
Possibility of roof installation to reduce or eliminate
the footprint aroud Data Center building.
06/07
06/07
pPUE 1,025
20 YEARS
WARRANTY
on cabinet
EER up to 38,9 (London climatic profile)
DIMENSIONS (mm) c
SIZE a b c c
SIVIS 20 5200 2200 2400
SIVIS 30 6500 2350 2800
SIVIS 40 7200 2350 3300
SIVIS 80 7200 4700 3300 a
b
b a
THE COOLING CAPACITY DOES NOT CONSIDER THE SUPPLY FAN MOTOR THERMAL LOAD
1. Characteristics referred to supply air at 23°C-50%RH and return air at 35°C-25%RH.
2. Referred to London Climatic conditions.
3. Sound power level Lw according to ISO EN 9614 – 2.
RC SIVIS_05-18_ENG