SMU02X V100R021C10 Site Monitoring Unit

User Manual

Issue 03
Date 2021-08-28

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2021. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees
or representations of any kind, either express or implied.

The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: https://www.huawei.com
Email: support@huawei.com

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. i


SMU02X V100R021C10 Site Monitoring Unit
User Manual Preface

Preface

Purpose
This document describes the site monitoring unit SMU in terms of its hardware,
liquid crystal display (LCD), web user interface (WebUI), common operations,
remote management, and replacement.

This document describes all the functions of the SMU. Some functions are
implemented by hardware (such as the DC meter and battery cell detector). If the
corresponding hardware is not connected to the SMU, the function is not
available.

Figures in this manual are for reference only.

Intended Audience
This document is intended for:

● Sales engineers
● Technical support personnel
● Maintenance personnel

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description

Indicates a hazard with a high level of risk which, if not


avoided, will result in death or serious injury.

Indicates a hazard with a medium level of risk which, if not


avoided, could result in death or serious injury.

Indicates a hazard with a low level of risk which, if not


avoided, could result in minor or moderate injury.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. ii


SMU02X V100R021C10 Site Monitoring Unit
User Manual Preface

Symbol Description

Indicates a potentially hazardous situation which, if not


avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to personal
injury.

Supplements the important information in the main text.


NOTE is used to address information not related to personal
injury, equipment damage, and environment deterioration.

Change History
Changes between document issues are cumulative. The latest document issue
contains all the changes made in earlier issues.

Issue 03 (2021-08-28)
Updated A LCD Menu Hierarchy.

Issue 02 (2021-03-15)
Updated A LCD Menu Hierarchy.

Issue 01 (2021-02-10)
This is the first official release.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. iii


SMU02X V100R021C10 Site Monitoring Unit
User Manual Contents

Contents

Preface........................................................................................................................................... ii
1 Product Overview.................................................................................................................... 1
2 Component Description......................................................................................................... 3
2.1 SMU02C...................................................................................................................................................................................... 3
2.2 MDU Display Screen...............................................................................................................................................................7
2.3 WIM01C1................................................................................................................................................................................. 10
2.4 UIM02C..................................................................................................................................................................................... 12
2.5 UIM02D.................................................................................................................................................................................... 16
2.6 UIM03D.................................................................................................................................................................................... 19
2.7 UIM05B1.................................................................................................................................................................................. 23
2.8 NIM02D.................................................................................................................................................................................... 27
2.9 NIM01C3.................................................................................................................................................................................. 28
2.10 CIM02C................................................................................................................................................................................... 32
2.11 GIM01C.................................................................................................................................................................................. 34

3 User Interfaces....................................................................................................................... 36
3.1 LCD............................................................................................................................................................................................. 36
3.1.1 Setup Wizard....................................................................................................................................................................... 36
3.1.2 Modifying the display language...................................................................................................................................37
3.1.3 Restart Button.....................................................................................................................................................................38
3.1.4 Password............................................................................................................................................................................... 38
3.1.5 Standby Screen................................................................................................................................................................... 38
3.2 MDU.......................................................................................................................................................................................... 39
3.2.1 Modifying the display language...................................................................................................................................39
3.2.2 Password............................................................................................................................................................................... 39
3.2.3 Standby Screen................................................................................................................................................................... 40
3.3 WebUI....................................................................................................................................................................................... 41
3.3.1 Connecting a Communications Cable........................................................................................................................ 41
3.3.2 Setting Parameters............................................................................................................................................................41
3.3.3 Logging In to the WebUI................................................................................................................................................ 42

4 NMS Management................................................................................................................ 44
4.1 U2000-SPM Management................................................................................................................................................. 44
4.1.1 Connecting a Communications Cable........................................................................................................................ 44

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. iv


SMU02X V100R021C10 Site Monitoring Unit
User Manual Contents

4.1.2 Setting Parameters............................................................................................................................................................44


4.2 NetEco Management........................................................................................................................................................... 45
4.2.1 IP Networking..................................................................................................................................................................... 45
4.2.2 Wireless Networking........................................................................................................................................................ 47
4.2.3 BBU In-band Networking............................................................................................................................................... 51
4.2.4 Logging In to the NetEco................................................................................................................................................52
4.3 NMS Management over SNMP........................................................................................................................................ 52
4.3.1 Site Configuration............................................................................................................................................................. 52
4.3.1.1 Connecting a Communications Cable..................................................................................................................... 52
4.3.1.2 Setting Parameters........................................................................................................................................................ 53
4.3.2 Setting SNMP Parameters.............................................................................................................................................. 53
4.3.3 NMS Commissioning........................................................................................................................................................ 57
4.4 NMS Management over YDN1363 Protocol................................................................................................................57
4.4.1 Connecting a Communications Cable........................................................................................................................ 58
4.4.2 Setting Parameters............................................................................................................................................................58
4.5 NMS Management over Modbus.................................................................................................................................... 59
4.5.1 Connecting a Communications Cable........................................................................................................................ 59
4.5.2 Setting Parameters............................................................................................................................................................59
4.6 NMS Management over TCP-Modbus........................................................................................................................... 60
4.6.1 Connecting a Communications Cable........................................................................................................................ 60
4.6.2 Setting Parameters............................................................................................................................................................60

5 Common Tasks....................................................................................................................... 62
5.1 Common Installation Tasks............................................................................................................................................... 62
5.1.1 Using a USB Flash Drive for Site Deployment.........................................................................................................62
5.1.2 Setting the Time Zone and Time................................................................................................................................. 63
5.1.3 Setting Basic Battery Parameters................................................................................................................................. 63
5.1.4 Setting the Alarm Enable Option, Alarm Severity, and Associated Relays....................................................66
5.1.5 Setting Alarm Parameters for Dry Contacts.............................................................................................................66
5.1.6 Setting Rectifier Addresses............................................................................................................................................. 67
5.1.7 Setting Basic DG Parameters......................................................................................................................................... 69
5.1.8 Starting a Genset Self-Check.........................................................................................................................................71
5.1.9 Setting WiFi Parameters..................................................................................................................................................72
5.2 Common Maintenance Tasks............................................................................................................................................74
5.2.1 Backing Up the Current Settings.................................................................................................................................. 74
5.2.2 Importing a Configuration File..................................................................................................................................... 74
5.2.3 Restoring Factory Defaults............................................................................................................................................. 75
5.2.4 Upgrading Software..........................................................................................................................................................75
5.2.5 Changing a User Password.............................................................................................................................................76
5.2.6 Viewing Dry Contact Association Information........................................................................................................ 78
5.2.7 Viewing Active Alarms..................................................................................................................................................... 79
5.2.8 Viewing Historical Alarms.............................................................................................................................................. 79
5.2.9 Viewing Version Information......................................................................................................................................... 80

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. v


SMU02X V100R021C10 Site Monitoring Unit
User Manual Contents

5.2.10 Exporting Maintenance Information........................................................................................................................ 80


5.2.11 Setting Battery Test Parameters................................................................................................................................ 82
5.2.12 Deleting Devices Devices Failing in Communication.......................................................................................... 83
5.3 Common Installation Tasks (MDU)................................................................................................................................ 84
5.3.1 Common Functions........................................................................................................................................................... 84
5.3.2 Setting Common Parameters........................................................................................................................................ 84
5.3.3 Setting Basic Battery Parameters................................................................................................................................. 85
5.3.4 Setting Rectifier Parameters.......................................................................................................................................... 90
5.3.5 Setting Mains Parameters.............................................................................................................................................. 91
5.3.6 Setting Overvoltage and Undervoltage Alarm Thresholds for the DC Cabinet...........................................92
5.3.7 Setting Overvoltage and Undervoltage Alarm Thresholds for the Rectifier Cabinet................................ 92
5.3.8 Setting Combined Cabinet Parameters...................................................................................................................... 93
5.3.9 Setting Communications Parameters......................................................................................................................... 93
5.3.10 Quick Settings.................................................................................................................................................................. 94
5.3.11 Setting Sensor Parameters........................................................................................................................................... 94
5.3.12 Setting WAN Port............................................................................................................................................................ 95
5.4 Common Maintenance Tasks (MDU)............................................................................................................................ 95
5.4.1 Viewing Version Information......................................................................................................................................... 95
5.4.2 Viewing Active Alarms..................................................................................................................................................... 96

6 Hardware Replacement....................................................................................................... 97
6.1 Replacing an SMU02C......................................................................................................................................................... 97
6.2 Replacing a WIM01C1......................................................................................................................................................... 99
6.3 Replacing a UIM02C Board............................................................................................................................................. 100
6.4 Replacing a UIM02D Board.............................................................................................................................................102
6.5 Replacing an UIM03D Board.......................................................................................................................................... 104
6.6 Replacing an UIM05B1..................................................................................................................................................... 105
6.7 Replacing an NIM02D Board.......................................................................................................................................... 106
6.8 Replacing an NIM01C3..................................................................................................................................................... 108
6.9 Replacing a CIM02C.......................................................................................................................................................... 110
6.10 Replacing a GIM01C........................................................................................................................................................111

A LCD Menu Hierarchy.......................................................................................................... 112


A.1 Running Information.........................................................................................................................................................113
A.2 Setting Wizard..................................................................................................................................................................... 130
A.3 Parameters Settings.......................................................................................................................................................... 134
A.4 Running Control................................................................................................................................................................. 225
A.5 Site Maintain....................................................................................................................................................................... 232
A.6 User Management............................................................................................................................................................. 233

B MDU Menu Hierarchy........................................................................................................ 234


B.1 Running..................................................................................................................................................................................234
B.2 Alarm...................................................................................................................................................................................... 239
B.3 Settings.................................................................................................................................................................................. 240

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. vi


SMU02X V100R021C10 Site Monitoring Unit
User Manual Contents

B.4 Maintenance........................................................................................................................................................................ 255


B.5 About...................................................................................................................................................................................... 255

C Technical Specifications.....................................................................................................256
D FAQ.........................................................................................................................................257
D.1 How Do I Prepare the WebUI Operating Environment?...................................................................................... 257
D.2 What Should I Do If I Forgot the Password?............................................................................................................ 261

E Acronyms and Abbreviations............................................................................................263

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. vii


SMU02X V100R021C10 Site Monitoring Unit
User Manual 1 Product Overview

1 Product Overview

Figure 1-1 Monitoring unit panel

(1) Slots for the (2) SMU02C (3) The user interface module
communications expansion (compatible with the NIM02D)
module and DG expansion
module

NOTICE

The NIM01C3 can be installed only in the upper slot. The CIM02C can be installed
either in the upper or lower slot.

Table 1-1 Monitoring unit configure

Monitoring Unit Function Introduction

SMU02C The SMU02C (SMU for short) is a compact high-end


monitoring module that monitors and manages box-type
and cabinet-type power systems.
The SMU can manage a site power system through the
liquid crystal display (LCD), web user interface (WebUI) and
NetEco.

UIM02C, It provides sensor ports, RS485 ports, and dry contact input
UIM02D, and output ports to manage the interior environment of the
UIM03D, and power system and to report alarms.
UIM05B1

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 1


SMU02X V100R021C10 Site Monitoring Unit
User Manual 1 Product Overview

Monitoring Unit Function Introduction

NIM02D It provides sensor ports, and FE ports to connect the NMS or


smart device such as an IP camera.

NIM01C3 It is mainly used for 4G communication. It can also extend


the RS485/CAN port of the main control board or extend
the southbound communication equipment.

CIM02C It is used to extend the RS485/CAN port of the main control


board and provides 12 V power supply for the southbound
equipment.

GIM01C It provides dry contact ports to interact with the AMF


controller or generator management unit (GMU) for
implementing functions such as DG startup, shutdown, and
reset.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 2


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

2 Component Description

2.1 SMU02C
Figure 2-1 SMU02C appearance

(1) SD card slot (2) Run indicator (3) Minor alarm indicator

(4) Major alarm indicator (5) Buttons (6) USB ports (protected by a
security mechanism)

(7) RS485/RS232 port (8) Fast Ethernet (FE) port (9) CAN communications port

(10) LCD

Indicators

Table 2-1 Indicator description

Name Color Status Description

Run Green Off The SMU is faulty or has no DC


indicator input.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 3


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Name Color Status Description

Blinking The SMU is running properly and


slowly (0.5 communicating with the host
Hz) properly.

Blinking fast The SMU is running properly but fails


(4 Hz) to communicate with the host
properly.

Minor alarm Yellow Off No minor or warning alarm is


indicator generated.

Steady on A minor or warning alarm is


generated.

Major alarm Red Off No critical or major alarm is


indicator generated.

Steady on A critical or major alarm is


generated.

Buttons

Table 2-2 Button description

Button Name Description

Up
Press and to scroll through the menus or to
change the value of a parameter.
Down

Cancel Returns to the previous menu without saving the


settings.

Enter ● Enters the main menu from the standby screen.


● Enters a submenu from the main menu.
● Saves menu settings on a submenu.
NOTE
● The LCD screen becomes dark if no button is pressed within 30 seconds.
● You need to log in again if no button is pressed within 1 minute.

● To increase or decrease a parameter value quickly, hold down or .

● To restart the SMU, hold down and for 10 seconds.

● To increase (or decrease) the LCD backlight, hold down and (or ) for 2
seconds.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 4


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

SD Card Slot
SD card is used for storing the camera capture images, maximum support 32 G
capacity.

USB Ports
You can quickly deploy a site, import and export configuration files, export running
logs, and upgrade software by inserting the USB flash drive that is specially used
for site deployment into the USB port.
After installing the specific WiFi module using the USB port, you can access the
WebUI locally, which facilitates operations.

Communications Ports

Table 2-3 Communications port description


Communications Communications Communications Function
Port Parameter Protocol

FE 10/100M SNMP protocol Connects to a


autonegotiation third-party NMS.

BIN protocol Connects to a


NMS.

HTTPS protocol Connects to a PC


and manages
SMU over the
WebUI.

TCP-Modbus Adapts to TCP-


protocol Modbus protocol
and connects to a
third-party NMS.

RS485/RS232 Baud rate: 1200 M/S protocol Connects to a


bit/s, 2400 bit/s, NMS.
4800 bit/s, 9600
bit/s, 14400 bit/s, YDN protocol Connects to a
19200 bit/s, third-party NMS.
115200 bit/s Modbus protocol Connects to a
southbound
device and
connects to a
third-party NMS.

CAN Baud rate: 125 CAN protocol Connects to a


kbit/s southbound
device.
NOTE
All these ports are protected by a security mechanism.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 5


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Figure 2-2 Communication port pins

Table 2-4 Pin definitions for the FE port


Pin Signal Description

1 TX+ Transmits data over FE

2 TX-

3 RX+ Receives data over FE

6 RX-

4/5/7/8 NA -

Table 2-5 Pin definitions for the RS485/RS232 port


Pin Signal Description

1 TX+ Transmits data over RS485

2 TX-

4 RX+ Receives data over RS485

5 RX-

3 RX232 Receives data over RS232

7 TX232 Transmits data over RS232

6 PGND Connects to the ground

8 NA –

Table 2-6 Description for the CAN port pins


Pin Signal Description

1 RX+ Receives data over RS485

2 RX-

3 NA -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 6


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Pin Signal Description

4 TX+ Transmits data over RS485

5 TX-

6 NA -

7 CANH CAN high level signal

8 CANL CAN low level signal

2.2 MDU Display Screen


Figure 2-3 MDU

(1) Status indicator (2) LCD touchscreen

Indicators

Table 2-7 Indicator description


Status Indicator Color Description

On Red A critical or major alarm is generated, and the


buzzer buzzes.

Yellow minor alarm or warning is generated.

Green The SMU is running properly and


communicating with the host properly.

Off - The MDU is powered off.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 7


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Figure 2-4 MDU ports

Table 2-8 Description of MDU ports


No. Port Name Description

1 MUS05A Connects to the MDU and monitoring interface card.

2 GE Supports 10 M/100 M autosensing, the HTTPS, NetEco


Bin, SNMP, and TCP-Modbus protocols

3 CAN Supports the CAN protocol and 12 V power port.

4 RS485_1 Supports the master/slave protocol, YDN protocol, and


Modbus protocol

5 FE_1 Cascading port, connects to the monitoring device.

6 FE_2 Reserved

7 DIP switch Implements specific functions by using the DIP switch and
specific buttons; controls the CAN communication resistor
in a parallel system.

8 SD Reserved

9 USB host Connects to a USB flash drive to import and export the
configuration file, export run logs, and upgrade software.

Figure 2-5 GE/FE/RS485_1 pins

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 8


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Table 2-9 Definitions for FE port pins

Pin Signal Description

1 TX+ Transmits data over FE.

2 TX-

3 RX+ Receives data over FE.

6 RX-

4, 5, 7, and 8 N/A -

Table 2-10 Definitions for RS485_1 port pins

Pin Signal Description

1 RS485+ RS485 data+

2 RS485– RS485 data–

4 RS485+ RS485 data+

5 RS485– RS485 data–

6 GND Signal ground

3, 7 and 8 - -

Figure 2-6 CAN pins

Table 2-11

Pin Signal Description

1 12V_IN 12 V power input

3 CAN_H CAN high level signal

4 CAN_L CAN low level signal

6 GND Signal ground

2 and 5 - -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 9


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

2.3 WIM01C1
The wireless interface module 01C1 (WIM01C1) is used to transfer signals and
supports WiFi access.

Figure 2-7 WIM01C1 panel

(1) WiFi indicator (2) RF indicator (3) Button

(4) GE cascading port (5) WiFi antenna port (6) RF_B antenna port

(7) RF_A antenna port (8) GE ports (9) Power port

Indicators and Buttons

Table 2-12 RF indicator description


Status Description

Off There is no power input or the module is


faulty.

Steady on The module does not properly communicate


with the host or is not networked.

Blinking at intervals of 2s (on The module properly communicates with the


for 1s and then off for 1s) host.

Blinking at intervals of 0.25s (on Networking is in progress.


for 0.125s and then off for
0.125s)

Blinking at intervals of 0.125s Network parameters are being cleared.


(on for 0.0625s and then off for
0.0625s)

On for 0.25s and off for 0.25s The module is blinking.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 10


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Table 2-13 Button description


Action Function Description

Hold down Allow or When the WIM01C1 is in Disallow Node


for 3s disallow node Networking state, if you hold down the button for
networking 3s, the WIM01C1 switches to the Allow Node
Networking state and the indicator blinks at short
intervals.

When the WIM01C1 is in Allow Node Networking


state, if you hold down the button for 3s, the
WIM01C1 switches to the Disallow Node
Networking state. You can determine the current
status of the WIM01C1 according to the indicator
description.

Hold down Erase the After you press the button, the indicator blinks for
for 8s network several seconds (blinks for 1s each time). After the
indicator blinks for eight times, it will blink at
super short intervals for 3s, indicating that
network erasing is successful.

Ports

Table 2-14 Pin definitions for the GE_CASCADE/GE1/GE2 ports


Pin Signal Description

1 TRX0+ Communications port, 100M/


1000M autonegotiation
2 TRX0-

3 TRX1+

4 TRX2+

5 TRX2-

6 TRX1-

7 TRX3+

8 TRX3-

Table 2-15 48 V power input port description


Port Type Silk Screen No. Description

48 V power input 48V + 48 V power input, positive


port

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 11


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Port Type Silk Screen No. Description

- 48 V power input,
negative

WiFi Function
You can locally access the WebUI using WiFi.

NOTICE

● You are advised to periodically change the WiFi password to improve account
security and prevent unauthorized network attacks, such as data tampering.
● We will not be liable for any losses incurred if you do not change the account
password in time or forget the new password. (Lost passwords cannot be
retrieved.)
● The WiFi function is disabled by default. Enable the WiFi function before using
it and disable it after using it to ensure network security.

Enable or disable the WiFi function: choose System Settings > Network Config >
WIFI.
Change the WiFi account password: choose System Settings > Network Config >
WIFI.

2.4 UIM02C
Panel

Figure 2-8 Panel

(1) Communications (2) Dry contact output (3) Dry contact input (4) Sensor ports
port ports ports

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 12


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Port Description

Table 2-16 Port description


Port Type Silk Screen Remarks

Sensor ports TEM-HUM Ambient temperature and humidity


sensor

WATER Water sensor

TEMP1 Temperature sensor 1

TEMP2 Temperature sensor 2

GATE Door status sensor

SMOKE Smoke sensor

BTEMP Battery temperature sensor

Dry contact input DIN1 Dry contact input 1


ports
DIN2 Dry contact input 2

DIN3 Dry contact input 3

DIN4 Dry contact input 4

DIN5 Dry contact input 5

DIN6 Dry contact input 6

Dry contact output ALM1 Dry contact output 1


ports
ALM2 Dry contact output 2

ALM3 Dry contact output 3

ALM4 Dry contact output 4

ALM5 Dry contact output 5

ALM6 Dry contact output 6

ALM7 Dry contact output 7

ALM8 Dry contact output 8

Communications port COM RS485

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 13


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Communications Port

Table 2-17 COM port description


Communications Communications Communications Purpose
Port Parameter Protocol

COM Baud rate: 1200 Master/slave, Connects to a


bit/s, 2400 bit/s, Modbus and downstream
4800 bit/s, 9600 YDN1363 device, such as
bit/s, 14400 bit/s, protocols the intelligent
19200 bit/s, battery detector
115200 bit/s or intelligent air
conditioner.
NOTE
The COM port is protected by a security mechanism.

Figure 2-9 Pins in the COM port

Table 2-18 COM port pin definitions


Pin Signal Remarks

1 RX+ Receives data over RS485.

2 RX-

4 TX+ Transmits data over RS485.

5 TX-

6 PGND Connects to the ground.

3, 7, 8 NA -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 14


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Sensor Ports

Figure 2-10 Pins in sensor ports

Table 2-19 UIM02C pin definitions


Silk Screen No. Pins

TEM-HUM 1 12 V

2 ENV_TEMP

3 12 V

4 ENV_HUM

WATER 1 12 V

2 WATER

3 GND

4 -

TEMP1 1 GND

2 TEMP1

TEMP2 1 GND

2 TEMP2

GATE 1 GATE+

2 GATE-

SMOKE 1 SMOKE

2 12 V

BTEMP 1 GND

2 BTEMP

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 15


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

2.5 UIM02D
Panel
Figure 2-11 shows a UIM02D panel, and Table 2-20 lists the ports on it.

Figure 2-11 UIM02D panel

Ports

Table 2-20 UIM02D port description

Port Type Silk Screen Description

Sensor port TEM-HUM Ambient temperature and


humidity sensor

WATER Water sensor

TEMP1 Temperature sensor 1

TEMP2 Temperature sensor 2

GATE Door sensor

SMOKE Smoke sensor

BTEMP Battery temperature sensor

Dry contact input DIN1 Dry contact input 1


NOTE
For details about the DIN2 Dry contact input 2
alarms associated with dry
contact inputs, see the DIN3 Dry contact input 3
power system user manual.
DIN4 Dry contact input 4

DIN5 Dry contact input 5

DIN6 Dry contact input 6

Dry contact output ALM1 Dry contact output 1


NOTE
For details about the ALM2 Dry contact output 2
alarms associated with dry
contact outputs, see the ALM3 Dry contact output 3
power system user manual.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 16


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Port Type Silk Screen Description

ALM4 Dry contact output 4

ALM5 Dry contact output 5

ALM6 Dry contact output 6

ALM7 Dry contact output 7

ALM8 Dry contact output 8

ALM9 Dry contact output 9

ALM10 Dry contact output 10

ALM11 Dry contact output 11

ALM12 Dry contact output 12

Communications port COM RS485 port

Communication Port

Table 2-21 COM communication port description


Communication Communications Communications Function
Port Parameter Protocol

COM port Baud rate: 1200 bit/s, M/S and Modbus Connects
2400 bit/s, 4800 bit/s, protocol to lower-
9600 bit/s, 14400 level
bit/s, 19200 bit/s, devices
115200 bit/s such as
the
battery
inspection
unit, DC
air
condition
er
NOTE
The COM port supports the security mechanism.

Figure 2-12 Pins in the COM port

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 17


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Table 2-22 Pin definitions for the COM port

Pin Signal Description

1 RX+ Receives data over RS485.

2 RX-

4 TX+ Transmits data over RS485.

5 TX-

6 PGND Connects to the ground.

3, 7, 8 NA -

Pins
Figure 2-13 shows the numbers of pins in sensor ports. Table 2-23 describes the
pin definitions.

Figure 2-13 UIM02D pin numbers

Table 2-23 UIM02D pin definitions

Silk Screen No. Pin Definition

TEM-HUM 1 12 V

2 ENV_TEMP

3 12 V

4 ENV_HUM

WATER 1 12 V

2 WATER

3 GND

4 -

TEMP1 1 GND

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 18


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Silk Screen No. Pin Definition

2 TEMP1

TEMP2 1 GND

2 TEMP2

GATE 1 GATE+

2 GATE-

SMOKE 1 SMOKE

2 12V

BTEMP 1 GND

2 BTEMP

2.6 UIM03D
Panel

Figure 2-14 UIM03D panel

(1) Communications ports (2) Dry contact outputs (3) Dry contact inputs

(4) Sensor ports

Ports

Table 2-24 UIM03D port description

Port Type Silk Screen Description

Sensor ports TEM-HUM Ambient T/H sensor

WATER Water sensor, normally


open (NO)
Supports 12 V power
supply.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 19


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Port Type Silk Screen Description

TEMP1 Ambient temperature


sensor 1

TEMP2 Ambient temperature


sensor 2

GATE Door status sensor,


normally closed (NC)

SMOKE Smoke sensor, normally


open (NO)

BTEMP Battery temperature


sensor

Dry contact input ports DIN1 Dry contact input 1


(Default setting:
DIN2 Dry contact input 2
normally closed for
DIN1, normally open for DIN3 Dry contact input 3
DIN2–6)
DIN4 Dry contact input 4

DIN5 Dry contact input 5

DIN6 Dry contact input 6

Dry contact output ports ALM1 Dry contact output 1


The default setting (normally open by
(closed: alarm; open: default)
normal) can be modified. ALM2 Dry contact output 2
(normally open by
default)

ALM3 Dry contact output 3


(normally open by
default)

ALM4 Reserved

ALM5 Reserved

ALM6 Reserved

ALM8 Dry contact output 8


(normally closed by
default)

Communications ports COM 4-wire RS485

ALM7 2-wire RS485

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 20


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Communications Ports

Table 2-25 Communications port description


Communications Port Communications Function
Parameter

COM Baud rate: Connects to a


Default value: 9600 bit/s downstream device, such
as a third-party power
Options: 300 bit/s, 600 supply.
bit/s, 1200 bit/s, 2400
bit/s, 4800 bit/s, 9600
bit/s, 14400 bit/s, 19200
bit/s, 38400 bit/s, 56000
bit/s, 57600 bit/s, 115200
bit/s

ALM7 Baud rate: Connects to a


Default value: 9600 bit/s downstream device, such
as a smart device.
Options: 9600 bit/s,
19200 bit/s, 115200 bit/s
NOTE
The COM port is protected by a security mechanism.

Figure 2-15 Pins in the COM port

Table 2-26 COM port pin definitions


Pin Signal Description

1 RX+ Receives data over


RS485.
2 RX-

3 12V Supplies power.

4 TX+ Transmits data over


RS485.
5 TX-

6, 8 PGND Connects to the ground.

7 Reserved -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 21


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Table 2-27 ALM7 port pin definitions

Pin Signal Description

+ RS485+ RS485 data +

- RS485- RS485 data –

Pin Definitions

Figure 2-16 UIM03D pin numbers

Table 2-28 Pin definitions for UIM03D sensor ports

Silk Screen No. Pin Definition

TEM-HUM 1 12V

2 ENV_TEMP

3 12V

4 ENV_HUM

WATER 1 12V

2 WATER

3 GND

4 -

TEMP1 1 TEMP1

2 GND

TEMP2 3 TEMP2

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 22


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Silk Screen No. Pin Definition

4 GND

GATE 1 GATE+

2 GATE-

SMOKE 3 12V

4 SMOKE

BTEMP 1 BTEMP

2 GND

2.7 UIM05B1
Figure 2-17 Mian Panel

(1) Dry contact ports and (2) COM communications port (3) Battery temperature sensor
sensor ports port

(4) Door status sensor port (5) Battery switch (6) Cable hole

(7) Handle

NOTE

The battery switch is used only when the mains supply is unavailable.

Ports

Figure 2-18 Dry contacts and sensor ports

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 23


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Table 2-29 Port description


Port Type Silk Screen Description

Sensor port TEMP Temperature sensor

WATER Water sensor

SMOKE Smoke sensor

BTEMP Battery temperature


sensor

GATE Door status sensor

Dry contact input DIN1 (Multiplexed with Dry contact input 1


dry contact output 1)

DIN2 (Multiplexed with Dry contact input 2


dry contact output 2)

DIN3 (Multiplexed with Dry contact input 3


dry contact output 3)

DIN4 Dry contact input 4

Dry contact output ALM1 (Multiplexed with Dry contact output 1


dry contact input 1)

ALM2 (Multiplexed with Dry contact output 2


dry contact input 2)

ALM3 (Multiplexed with Dry contact output 3


dry contact input 3)

ALM4 Dry contact output 4

ALM5 Dry contact output 5

ALM6 Dry contact output 6

ALM7 Dry contact output 7

ALM8 Dry contact output 8

Communications port COM RS485

Communications Port

Figure 2-19 Pins in the COM port

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 24


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Table 2-30 COM port pin definitions


Pin Signal Description

1 RX+ Receives data over


RS485
2 RX-

3 12V Power supply

4 TX+ Transmits data over


RS485
5 TX-

6 GND Connects to the ground.

7 Reserved –

8 GND Connects to the ground.

Table 2-31 RS485/CAN port pin definitions


Pin Signal Description

1 CANH CAN high level signal

2 CANL CAN low level signal

3 RS485+ RS485 data +

4 RS485- RS485 data -

Table 2-32 CAN port pin definitions


Pin Signal Description

1 CANH CAN high level signal

2 CANL CAN low level signal

3 NA -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 25


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Sensor Ports

Figure 2-20 Pins in sensor ports

Table 2-33 UIM05B1 pin definitions


Sensor Port No. Pin Definition

TEMP 1 TEMP1+

2 TEMP1-

WATER 1 WATER

2 GND

SMOKE 1 12V

2 SMOKE

BTEMP 1 BTEMP1+

2 BTEMP1-

GATE 1 GATE+

2 GATE-

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 26


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

2.8 NIM02D
Panel

Figure 2-21 Panel

(1) FE cascade port (2) Signal Input ports/12 V (3) FE ports


power port

Ports

Table 2-34 Port Description


Port Function Communications
Parameter

FE_CASCADE Connects to the FE port on the 10/100M


SMU. autonegotiation

FE1/2 Connects to an NMS or a


smart device such as an IP
camera.

CH1/2/3/4/5/6 Signal Input ports. -

12 V 12 V power output. -

Remarks:
● The FE ports are protected by a security mechanism.
● CH1/2/3/4 supports AI (4–20 mA), AI (0–10 V DC), or DI detection. The
function can be used by hardware jumper or software parameter
configuration.
● CH5/6 supports only AI (4–20 mA) detection by default.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 27


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Figure 2-22 Pins in an FE communications port

Table 2-35 Pin definitions for FE communications ports

Pin Signal Description

1 TX+ Transmits data over FE.

2 TX-

3 RX+ Receives data over FE.

6 RX-

4, 5, 7 and 8 NA -

2.9 NIM01C3
Panel

Figure 2-23 NIM01C3 panel

(1) SIM card slots (2 PCS) (2) 4G indicator (3) Alarm indicator

(4) Run indicator (5) ANT communications port (6) COM1 port

(7) COM2 port (8) COM3/CAN port (9) COM4 port

(10) Handle

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 28


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Indicators

Table 2-36 Indicator description


Indicator Color Status Description

4G indicator Green Steady on The dial-up connection is in


the data service state.

Blinking at a period of 2s (on for 0.1s and The network has been
then off for 1.9s) registered.

Blinking at a period of 2s (on for 0.1s, off A network is in search, or


for 0.1s, on for 0.1s and then off for 1.7s) no network is connected.

Blinking at a period of 2s (on for 0.3s and A network is in search, or


then off for 1.7s) no network is connected.

Alarm Red Off No alarm is generated.


indicator
Steady on An alarm is generated.

Run indicator Green Off The NIM01C3 is not


running because it is faulty
or has no DC input.

Blinking at a period of 2s (on for 2s and The NIM01C3 is running


then off for 1s) and communicating with
the host properly.

Blinking at a period of 0.25s (on for The NIM01C3 is running


0.125s and then off for 0.125s) properly, but fails to
communicate with the host.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 29


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Communications Ports

Table 2-37 Communications port description

Communications Communications Parameter Description


Port

COM1 port Baud rate: 1200 bit/s, 2400 Supports master/slave


bit/s, 4800 bit/s, 9600 bit/s, protocols and Modbus
14400 bit/s, 19200 bit/s, protocols.
115200 bit/s Supplies 12 V power.

COM2 port Baud rate: 1200 bit/s, 2400 Supports master/slave


bit/s, 4800 bit/s, 9600 bit/s, protocols and Modbus
14400 bit/s, 19200 bit/s, protocols.
115200 bit/s Supplies 12 V power.

COM3/CAN port Baud rate: 1200 bit/s, 2400 COM3: Supports master/
bit/s, 4800 bit/s, 9600 bit/s, slave protocols and
14400 bit/s, 19200 bit/s, Modbus protocols.
115200 bit/s CAN: Supports CAN
protocol.

COM4 port Baud rate: 1200 bit/s, 2400 Supports Modbus


bit/s, 4800 bit/s, 9600 bit/s, protocols.
14400 bit/s, 19200 bit/s,
115200 bit/s

Figure 2-24 Pins in the COM1, COM2, and COM3 ports

Table 2-38 Description for the pins in the COM1 and COM2 ports

Pin Signal Description

1 RS485+ RS485 data +

2 RS485- RS485 data -

3 12 V Supply power

4 RS485+ RS485 data +

5 RS485- RS485 data -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 30


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Pin Signal Description

6 NA -

7 NA -

8 GND Connects to the ground.

Table 2-39 Description for the COM3/CAN port pins


Pin Signal Description

1 RX+ Receives data over


RS485.
2 RX-

3 NA -

4 TX+ Transmits data over


RS485.
5 TX-

6 GND Connects to the ground.

7 CANH CAN high level signal.

8 CANL CAN low level signal.

Table 2-40 Description for the COM4 port pins


Silk Screen Signal Description

R+ RS485+ RS485 data +

R- RS485- RS485 data -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 31


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

2.10 CIM02C
Panel

Figure 2-25 CIM02C panel

(1) COM1 port (2) COM2 port (3) COM3/COM4 port

(4) 12 V power port (5) COM5 port (6) Handle

Communications Ports

Table 2-41 Communications port description

Communications Description Communications


Port Parameter

COM1 port Supports RS485. Baud rate


12 V power supply, maximum Default value: 9600
output 1.5 A. bit/s
Connects to a smart device. Options: 1200 bit/s,
2400 bit/s, 4800 bit/s,
COM2 port Supports RS485. 9600 bit/s, 14400 bit/s,
12 V power supply, maximum 19200 bit/s, 115200
output 1.5 A. bit/s
Connects to a smart device.

COM3/COM4 port COM3 supports RS485.


COM4 supports RS232 and CAN.
RS232 is used by default, which
can be changed to CAN by using
a jumper.
Connects to a third-party power
supply.

COM5 port Supports RS232 and RS485.


RS485 is used by default, which
can be changed to RS232 by
using a jumper.
Connects to an air conditioner.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 32


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Figure 2-26 Pins in the COM1, COM2, or COM3/COM4 port

Table 2-42 Pin definitions for the COM1 and COM2 ports
Pin Single Description

1 RS485+ RS485 data +

2 RS485- RS485 data -

3 12 V Power supply

4 RS485+ RS485 data +

5 RS485- RS485 data -

6 NA –

7 NA –

8 GND Connects to the ground.

Table 2-43 Pin definitions for the COM3/4 port


Pin Single Description

1 RS485_RX+ Receives data over RS485.

2 RS485_RX-

3 RS232_RXD Receives data over RS232.

4 RS485_TX+ Transmits data over RS485.

5 RS485_TX-

6 GND Connects to the ground.

7 CANH/RS232_TXD CAN high level signal/Transmits


data over RS232.

8 CANL CAN low level signal.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 33


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Table 2-44 Pin definitions for the COM5 port

Silk Screen Signal Description

R+/TX RS485+/RS232_TXD RS485 data + or transmits data


over RS232.

R-/RX RS485-/RS232_RXD RS485 data - or receives data


over RS232.

GND GND Connects to the ground.

2.11 GIM01C
Panel

Figure 2-27 GIM01C panel

(1) Run indicator (2) DG 1 control ports (3) DG 2 control ports

(4) DG 1 reset ports (5) DG 2 reset ports (6) Fuel level 1 detection ports

(7) Fuel level 2 detection ports (8) COM communications (9) CAN communications port
ports

(10) Alarm indicator

Indicators

Table 2-45 Indicator description

Name Color Status Remarks

RUN Green Off The module is faulty or has no DC


indicator input.

Blinking slowly The module is running and


(0.5 Hz) communicating with the host
properly.

Blinking fast (4 The module is running properly but


Hz) does not communicate with the
host properly.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 34


SMU02X V100R021C10 Site Monitoring Unit
User Manual 2 Component Description

Name Color Status Remarks

ALM Red Reserve


indicator

Ports

Table 2-46 Port description


Port Type Silk Screen Description Remarks

DG control port DG1_C NC DO normally closed port Controls DG


TL startup and
M Common port shutdown.
NO DO normally open port

DG2_C NC DO normally closed port


TL
M Common port

NO DO normally open port

DG reset port RST1 M Common port The DG resets if


the port is
NO DO normally open port closed.
RST2 M Common port

NO DO normally open port

Fuel level AI1 + +12 V power supply Detect the fuel


detection port level.
- Analog signal

AI2 + +12 V power supply

- Analog signal

Communications COM R+ RS485 data + Used for RS485


port communication.
R- RS485 data –

CAN + CAN data + Used for CAN


communication.
- CAN data –

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 35


SMU02X V100R021C10 Site Monitoring Unit
User Manual 3 User Interfaces

3 User Interfaces

3.1 LCD

3.1.1 Setup Wizard


After the SMU is powered on for the first time, the Setup Wizard page is
displayed, as shown in the following figure.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 36


SMU02X V100R021C10 Site Monitoring Unit
User Manual 3 User Interfaces

Figure 3-1 Setup wizard

3.1.2 Modifying the display language


The monitoring unit supports English, Chinese, French, Spanish, Portuguese,
Russian, Italian, German, Turkish, and Japanese.
When the monitoring unit is running properly, choose the following menus to
select a language.

Table 3-1 Modifying the display language

Main Menu Second-Level Menu Third-Level Menu Setting

Parameters Settings Local Parameters Language Select a desired


language.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 37


SMU02X V100R021C10 Site Monitoring Unit
User Manual 3 User Interfaces

3.1.3 Restart Button

To restart the monitoring unit, hold down and for 10s.

3.1.4 Password
Two-level password management supported by the LCD, two user levels are
available.

Table 3-2 Two-level password management

Level Operation Permission Password

engineer All permissions except for 000001


changing the administrator
password and resetting the
web password.

admin Has all operation permissions. 012589


NOTE
The admin password can only be
used by the administrator. It must
not be provided for third-party
maintenance personnel.

3.1.5 Standby Screen


The following figure shows the monitoring unit standby screen, which displays
basic power system information, including the DC output voltage, total load
current, and total battery current.

NOTE

The parameter values in the figures are for reference only.

Figure 3-2 Standby screen

The standby screen is displayed if no button is pressed within 1 minute on any


screen.

On the standby screen, you can press , , and to enter the version
information screen, basic information screen, and main menu screen respectively,
as shown in the following figure.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 38


SMU02X V100R021C10 Site Monitoring Unit
User Manual 3 User Interfaces

Figure 3-3 Standby screen operations

Main menu include active alarm, running information, setting wizard, parameters
settings, running control, site maintain and user management.

3.2 MDU

3.2.1 Modifying the display language


The monitoring unit supports English, Chinese, French, Spanish, Portuguese,
Russian, Italian, German, Turkish, and Japanese.

When the monitoring unit is running properly, choose the following menus to
select a language.

Table 3-3 Modifying the display language

Main Menu Second-Level Menu Third-Level Menu Setting

System Information Settings Common Select a desired


language.

3.2.2 Password
Two-level password management supported by the LCD, two user levels are
available.

Table 3-4 Two-level password management

Level Operation Permission Password

engineer All permissions except for changing the 000001


administrator password and resetting the
web password.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 39


SMU02X V100R021C10 Site Monitoring Unit
User Manual 3 User Interfaces

Level Operation Permission Password

admin Has all operation permissions. 012589


NOTE
The admin password can only be
used by the administrator. It must
not be provided for third-party
maintenance personnel.

3.2.3 Standby Screen


The following figure shows the monitoring unit standby screen, which displays
basic power system information, including the DC output voltage, total load
current, and total battery current.

NOTE

The parameter values in the figures are for reference only.

Figure 3-4 Standby screen

Table 3-5 Main screen description

Number Area Function

1 Alarm bar Displays active alarms in a scrolling list and the


number of active alarms based on severity. Tap the
alarm icon area to open the active alarm page.

2 Informatio Displays the power flow as well as key information


n area such as load and battery information.

The following table lists the functions of the buttons on the main screen.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 40


SMU02X V100R021C10 Site Monitoring Unit
User Manual 3 User Interfaces

Table 3-6 Functions of common buttons

Button Function

Returns to the main screen.

Scrolls the page down.

Scrolls the page up.

Returns to the upper-level menu.

Logs a user out.

3.3 WebUI

3.3.1 Connecting a Communications Cable

Procedure
Step 1 Preparing the Operating Environment.

Step 2 Connect the FE port on the SMU by using a network cable.

Figure 3-5 Connecting a communications cable

(1) FE

----End

3.3.2 Setting Parameters

Procedure
Step 1 Apply to the site or equipment room network administrator for a fixed IP address.

Step 2 Set the IP type, IP address, subnet mask, and gateway address on the LCD.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 41


SMU02X V100R021C10 Site Monitoring Unit
User Manual 3 User Interfaces

Table 3-7 IP parameters


Main Second-Level Third-Level Default Setting Value
Menu Menu Menu Value

Setting Network IP Type IPv4 Set as required.


Wizard Parameters
IP Address 192.168.0.10 Set this parameter according to the
address provided by the network
administrator.

Subnet Mask 255.255.255.0 Set this parameter according to the


subnet mask provided by the
network administrator.

Default 192.168.0.1 Set this parameter according to the


Gateway gateway address provided by the
network administrator.

----End

3.3.3 Logging In to the WebUI


Procedure
Step 1 Set the PC IP address in the same network segment as the SMU IP address.
For example, if the SMU has an IP address of 192.168.0.10, a subnet mask of
255.255.255.0, and a default gateway of 192.168.0.1, set the IP address to
192.168.0.11, subnet mask to 255.255.255.0, and default gateway to 192.168.0.1
on the PC.
Step 2 Enter https://monitoring unit local IP address (for example, https://
192.168.0.10) in the address box of the browser, and then press Enter to access
the WebUI login page.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 42


SMU02X V100R021C10 Site Monitoring Unit
User Manual 3 User Interfaces

Figure 3-6 WebUI login page

NOTE

The preset user names include admin, engineer, and operator, and the preset password is
Changeme. The user names are intended for administrators, engineers, and operators
respectively.
Change the preset password when you first log in to ensure system security. The method
about how to change the password, see 5.2.5 Changing a User Password.

----End

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 43


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

4 NMS Management

4.1 U2000-SPM Management

4.1.1 Connecting a Communications Cable


Procedure
Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU.
Step 2 Connect the other end to the MON0 or MON1 port on the BBU.

Figure 4-1 Connecting a communications cable

(1) RS485/RS232 port (2) MON1 port

----End

4.1.2 Setting Parameters


Step 1 On the LCD, set the port mode, communications protocol type, baud rate, and
communications address on the LCD, as shown in the following table.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 44


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

Table 4-1 Communications parameters

Main Menu Second-Level Third-Level Fourth-Level Fifth-Level Setting


Menu Menu Menu Menu Value

Parameters Comm. Serial Port Northbound Port Mode Manual


Settings Parameters
Protocol Type M/S
Protocol

M/S Protocol Baud Rate - 9600

Comm. Address - 3

----End

4.2 NetEco Management

4.2.1 IP Networking
Step 1 Connect a network cable to the FE port on the SMU.

Figure 4-2 Connecting a communications cable

(1) FE Port

Step 2 Apply to the site or equipment room network administrator for a fixed IP address.

Step 3 Set the IP type, IP address, subnet mask, and gateway address on the LCD.

Table 4-2 IP parameters

Main Second-Level Third-Level Menu Default Value Setting


Menu Menu

Setting Network IP Type IPv4 Set as required.


Wizard Parameters
IP Address 192.168.0.10 Set this parameter based
on the address assigned by
the network administrator.

Subnet Mask 255.255.255.0 Set this parameter based


on the address assigned by
the network administrator.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 45


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

Main Second-Level Third-Level Menu Default Value Setting


Menu Menu

Default Gateway 192.168.0.1 Set this parameter based


on the address assigned by
the network administrator.

Step 4 Set IP addresses and port numbers for the active and standby NetEco servers and
backup NetEco servers on the LCD.

Table 4-3 NetEco parameters


Main Second-Level Third-Level Fourth-Level Default Setting
Menu Menu Menu Menu Value

Parameters Comm. Network NetEco Primary 192.168.0.10 Set this parameter


Settings Parameters Parameters IP to the IP address
of the active
NetEco server.
NOTE
● If the NetEco is
deployed in a
single-server
system, set
NetEco Primary
IP to the IP
address of the
NetEco server.
You do not need
to set NetEco
Backup IP.
● If the NetEco is
a local HA
system, set
NetEco Primary
IP to the
floating IP
address of the
NetEco.
● If the NetEco is
a remote cold
backup system,
set NetEco
Primary IP and
NetEco Backup
IP to the IP
addresses of the
active and
standby NetEco
servers
respectively.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 46


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

Main Second-Level Third-Level Fourth-Level Default Setting


Menu Menu Menu Menu Value

NetEco Backup 192.168.0.10 Set this parameter


IP to the IP address
of the standby
NetEco server.

NetEco Port 31220 31220


Number NOTE
Please contact
technical support if
you need change
the port number.

----End

4.2.2 Wireless Networking


Installing a Wireless Antenna
Step 1 Insert the SIM card into the SIM card slot in the communications expansion board.
The SIM card inserted into the communications expansion module (NIM01C3)
should support GSM, WCDMA, TD-SCDMA, TDD, and FDD standards, and have the
SMS and data service functions enabled.
Step 2 Connect the GPRS antenna to the ANT port on the NIM01C3.

Figure 4-3 Connection between a GPRS antenna and an NIM01C3

----End

Setting Communications Parameters


Step 1 Check whether the default wireless communications parameters on the LCD are
consistent with the communication configurations of the carrier network that the

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 47


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

SIM card belongs to. If they are inconsistent, modify the parameters according to
the actual configurations of the carrier network.

Table 4-4 Checking wireless communication parameters


Main Menu Second- Third-Level Fourth-Level Menu Default Value
Level Menu Menu Value Range

Parameters Comm. Mobile Carrier Operator Automatic Automatic,


Settings Parameters Data Others

SIMn Acc Point Name - A maximum


NOTE of 28
This parameter is characters,
displayed only when including
Carrier Operator is set lowercase
to Others.
English
SIMn Access Point No - letters (a-z),
uppercase
NOTE
This parameter is English
displayed only when letters (A-Z),
Carrier Operator is set digits (0-9),
to Others. and special
characters
SIMn User Name - (@_#*-.).
NOTE
This parameter is
displayed only when
Carrier Operator is set
to Others.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 48


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

Main Menu Second- Third-Level Fourth-Level Menu Default Value


Level Menu Menu Value Range

SIMn User Password - A maximum


NOTE of 27
This parameter is characters,
displayed only when including
Carrier Operator is set lowercase
to Others.
English
letters (a-z),
uppercase
English
letters (A-Z),
digits (0-9),
and special
characters
(@_#-.).
It is
recommend
ed that the
password
contain at
least two
types of
characters
and the
length
exceed six
characters.

Step 2 Set IP addresses and port numbers for the active and standby NetEco servers and
backup NetEco servers on the LCD.

Table 4-5 Setting NetEco parameters


Main Second-Level Third-Level Fourth-Level Default Setting
Menu Menu Menu Menu Value

Parameters Comm. Network NetEco 192.168.0.10 Set this parameter


Settings Parameters Parameters Primary IP to the IP address of
the active NetEco
server.

NetEco 192.168.0.10 Set this parameter


Backup IP to the IP address of
the standby NetEco
server.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 49


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

Main Second-Level Third-Level Fourth-Level Default Setting


Menu Menu Menu Menu Value

NetEco Port 31220 31220


Number NOTE
Please contact
technical support if
you need change
the port number.

----End

Verifying Network Connection Status


After the SIM card and wireless antenna are installed, the SIM card automatically
accesses the wireless network in dial-up mode. You can view the network
connection status on the LCD.

Table 4-6 Verifying the network connection status

Main Menu Second-Level Menu Third-Level Menu Remarks

Running Mobile Data Info Connection Status Connected indicates successful


Information dial-up and normal network
connection.

NOTE

The following table shows general requirements of GPRS Network performance. If the
network performance is worse than the requirements, communication interruption may
happen.

Table 4-7 GPRS main performance index

Index Description Reference

Received signal strength If the probability of received signal P (RSCP > –89 dBm)
indicator (RSSI) code power (RSCP) greater than –89 95%
dBm is less than 95%, the cell
coverage of wireless signals is poor.

Packet Data Protocol (PDP) PDP activation success rate = 95%


activation success rate Successful number of PDP activation/
Total number of PDP activation

Attach attachment success rate Attach attachment success rate = 95%


Successful number of PDP
attachment/Total number of PDP
attachment

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 50


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

Index Description Reference

Handover success rate Handover success rate = Successful 98%


number of GPRS handover/Total
number of GPRS handover

4.2.3 BBU In-band Networking


Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU.

Step 2 Connect the other end to the MON0 or MON1 port on the BBU.

Figure 4-4 Connecting a communications cable

(1) RS485/RS232 Port (2) MON1 Port

Step 3 Set the port mode, communications protocol type, baud rate, and communications
address on the LCD.

Table 4-8 Setting communications parameters

Main Menu Second-Level Third-Level Fourth-Level Fifth-Level Setting


Menu Menu Menu Menu

Parameters Comm. Serial Port Northbound Port Mode Manual


Settings Parameters
Protocol Type M/S Protocol

M/S Protocol Baud Rate - 9600

Comm. - 3
Address

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 51


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

----End

4.2.4 Logging In to the NetEco

Procedure
Step 1 Enter https://NetEco IP address: port number for NetEco login (for example,
https://10.10.10.1:31943) in the address box of the browser and press Enter. The
NetEco login page is displayed.

Step 2 Enter the correct user name and password and click Log In.

NOTICE

To obtain the NetEco user name and password, contact the site or equipment
room network administrator.

----End

4.3 NMS Management over SNMP

4.3.1 Site Configuration

4.3.1.1 Connecting a Communications Cable

Procedure
Step 1 Connect the FE port on the SMU by using a network cable, as shown in Figure
4-5.

Figure 4-5 Connecting a communications cable

(1) FE port

----End

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 52


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

4.3.1.2 Setting Parameters

Procedure
Step 1 Apply to the site or equipment room network administrator for a fixed IP address.

Step 2 Set the IP type, IP address, subnet mask, and gateway on the LCD, as shown in
Table 4-9

Table 4-9 IP parameters

Main Menu Second-Level Third-Level Default Value Setting Value


Menu Menu

Setting Wizard Network IP Type IPv4 Set as required.


Parameters
IP Address 192.168.0.10 Set this
parameter
according to the
address provided
by the network
administrator.

Subnet Mask 255.255.255.0 Set this


parameter
according to the
subnet mask
provided by the
network
administrator.

Default Gateway 192.168.0.1 Set this


parameter
according to the
gateway address
provided by the
network
administrator.

----End

4.3.2 Setting SNMP Parameters

Prerequisites
NOTE

You can set SNMP parameters remotely or locally on the WebUI.

Before setting SNMP parameters, obtain the information listed in Table 4-10 from
the SNMP NMS.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 53


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

Table 4-10 Information obtained from the NMS

Item Description

SNMP version SNMP version and port number used for


communication between the SMU and NMS.
SNMP Port Number The SNMP version can be SNMPv1, SNMPv2c,
SNMPv3.

Read Community Name If you use SNMPv1 or SNMPv2c, enter the read
and write community names that comply with
Write Community Name the NMS. Otherwise, the SMU will not connect
to the NMS.
The read community name must be different
from the write community name.

User Name To enhance the security, you need a user name


and password for authentication if you use
MD5/SHA Password SNMPv3. After the authentication succeeds, the
DES/AES Password SMU can communicate with the NMS.

Trap Target Address IP address and port number used for reporting
alarm trap packets.
Trap Port

Trap Community If you use SNMPv1 or SNMPv2c, community


name used for reporting alarm trap packets.

Procedure
Step 1 Log in to the WebUI.
NOTE

The preset user name is admin, and the preset password is Changeme.

Step 2 Access the System Settings page and set SNMP.

Figure 4-6 SNMP Page

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 54


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

● There are two or more NMSs and the SNMP versions have both SNMPv1 or
SNMPv2c and SNMPv3: Set SNMP Version to ALL in SNMP, and set SNMP
Port Number, Read Community Name, and Write Community Name. Then
click Add in SNMPv3, and set User Name, MD5/SHA Password, and
DES/AES Password. Then click Confirm.

Figure 4-7 Choosing SNMP Version to ALL

● SNMPv1 or SNMPv2c: Set SNMP Version to SNMPv1&SNMPv2c in


SNMP,and set SNMP Port Number, Read Community Name, and Write
Community Name. Then click Confirm.

Figure 4-8 Choosing SNMP Version to SNMPv1 or SNMPv2c

● SNMPv3: Set SNMP Version to SNMPv3 in SNMP, click Add in SNMPv3, and
set User Name, MD5/SHA Password, and DES/AES Password. Then click
Confirm.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 55


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

Figure 4-9 SNMP Version to SNMPv3

Step 3 In SNMP Trap, click Add.


● If the SNMP Version is SNMPv1 or SNMPv2c, set Trap Target Address and
Trap Port and set Trap community.

Figure 4-10 Adding Trap address

● If the SNMP Version is SNMPv3, set Trap Target Address and Trap Port and
SNMPv3 User Name.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 56


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

Figure 4-11 Adding Trap address

NOTE

SNMP Version in this place can be different from the version in Step 2.

Step 4 In Mib files, click Export to export the Mib file and then import it into the NMS.

Figure 4-12 Exporting Mib files

NOTE

If there is only one NMS, perform 4.3.2 Setting SNMP Parameters once only.

----End

4.3.3 NMS Commissioning


You can query the power system operating status, active alarms, and the names of
user-defined dry contact inputs, and configure dry contact outputs on the network
management system (NMS) that is connected over the Simple Network
Management Protocol (SNMP).

4.4 NMS Management over YDN1363 Protocol

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 57


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

4.4.1 Connecting a Communications Cable


Procedure
Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU.
Step 2 Connect the other end to the corresponding port on the power and environment
monitoring device, as shown in Figure 4-13.

Figure 4-13 Connecting a communications cable

(1) Power and environment network (2) Power and environment (3) RS485/RS232 port on the SMU
management system (NMS) monitoring device

----End

4.4.2 Setting Parameters


Step 1 On the LCD, set the port mode, communications protocol type, baud rate, and
communications address on the LCD, as shown in Table 4-11.

Table 4-11 Communications parameters

Main Menu Second-Level Third-Level Fourth-Level Fifth-Level Default


Menu Menu Menu Menu Value

Parameters Comm. Serial Port Northbound Port Mode Manual


Settings Parameters
Protocol YDN1363
Type Protocol

YDN1363 Baud Rate - 9600


Protocol
Comm. Address - 1

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 58


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

----End

4.5 NMS Management over Modbus

4.5.1 Connecting a Communications Cable


Step 1 Connect one end of a network cable to the RS485/RS232 port on the SMU.

Step 2 Connect the other end to the corresponding port on the third-party device, as
shown in Figure 4-14.

Figure 4-14 Connecting a communications cable

(1) Network management (2) Third-party device (3) RS485/RS232 port on the
device SMU

----End

4.5.2 Setting Parameters


Step 1 On the LCD, set the port mode, communications protocol type, baud rate, and
communications address on the LCD, as shown in Table 4-12.

Table 4-12 Communications parameters

Main Menu Second-Level Third-Level Fourth-Level Fifth-Level Default


Menu Menu Menu Menu Value

Parameters Comm. Serial Port Northbound Port Mode Manual


Settings Parameters
Protocol Type Modbus
Protocol

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 59


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

Main Menu Second-Level Third-Level Fourth-Level Fifth-Level Default


Menu Menu Menu Menu Value

Modbus Baud Rate - 9600


Protocol
Comm. Address - 33

----End

4.6 NMS Management over TCP-Modbus

4.6.1 Connecting a Communications Cable


Procedure
Step 1 Connect the FE port on the SMU by using a network cable, as shown in Figure
4-15.

Figure 4-15 Connecting a communications cable

(1) FE port

----End

4.6.2 Setting Parameters


Procedure
Step 1 Log in to the WebUI.
NOTE

The preset user name is admin, and the preset password is Changeme.

Step 2 Choose System Settings > TCP-Modbus Config and set parameters. For details,
see Table 4-13.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 60


SMU02X V100R021C10 Site Monitoring Unit
User Manual 4 NMS Management

Table 4-13 Communications parameters


Parameter Value Setting Method

TCP-Modbus link Sever, Client, Sever ● Server: The SMU works as the server and can
Mode +Client connect to one client for communication.
● Client: The SMU works as a client and can connect
to the remote server for communication.
● Server+Client: The SMU works as the server and can
connect to one client for communication. At the
same time, the SMU works as a client and can
connect to the remote server for communication.

TCP-Modbus SSL Enable, Disable The default value is Enable.


server enable NOTE
This parameter is displayed only when TCP-Modbus link
Mode is set to Server and Server+Client.

TCP-Modbus SSL Enable, Disable The default value is Enable.


client enable NOTE
This parameter is displayed only when TCP-Modbus link
Mode is set to Client and Server+Client.

TCP-Modbus - The default value is 192.168.0.10. Set the NMS IP


client IP address address based on the actual situation.
NOTE
This parameter is displayed only when TCP-Modbus link
Mode is set to Client and Server+Client.

TCP-Modbus - The default value is 16100. It is recommended that


client IP port you not change the value. If necessary, set this
parameter based on the actual situation.
NOTE
This parameter is displayed only when TCP-Modbus link
Mode is set to Client and Server+Client.

Step 3 Upload CA certificate file, local certificate file and key file.

----End

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 61


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

5 Common Tasks

5.1 Common Installation Tasks

5.1.1 Using a USB Flash Drive for Site Deployment

Prerequisites
● The USB flash drive stores the upgrade and configuration files required for
site deployment.
● The upgrade and configuration files must be stored in the root directory of
the USB flash drive. Otherwise, the SMU cannot read the configuration file.
● The configuration file name starts with Config and ends with .tar.gz or .zip.
NOTE

The file name should have less than 80 characters, cannot start with fault, and cannot
contain single or double quotation marks, spaces, or the following special characters:< \ > | ;
$&`()%
● The USB flash drive and file have been scanned to ensure that they are not
infected with viruses.

Context
You can copy site configuration parameters from the LCD or WebUI to a USB flash
drive to rapidly set up other sites.

NOTE

● Export configuration parameters from the LCD to a USB flash drive: On the LCD, choose
Site Maintain > Export File to USB to export the configurations of the current
operating system into a configuration file and save the file in a USB flash drive.
● For details about how to export configuration parameters from the WebUI to a USB
flash drive, see 5.2.1 Backing Up the Current Settings.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 62


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Procedure
Step 1 Insert the USB flash drive into the SMU USB port. The LCD displays the Site
Maintain screen.
NOTE

When visiting Site Maintain on the LCD, enter the preset password 000001.

Step 2 Choose Site Maintain > U Disk Upgrade/Cfg.

Step 3 Select the upgrade or configuration file stored in the root directory of the USB

flash drive, and tap . Back up first. Go on? is displayed.

Step 4 Select YES and tap , Package Classifying is displayed and Config Processing is
displayed, indicating that upgrade or data configuration is in progress.
NOTE

The configuration or upgrade process will take about 5 minutes.

Step 5 After the upgrade or configuration is complete, Config Successful Rebooting in


15s. The SMU will restart 15 seconds later.

Step 6 After the restart is complete, remove the USB flash drive.

----End

5.1.2 Setting the Time Zone and Time


Set the date and time based on the local time and time zone.

Table 5-1 Setting the time zone and time

Main Menu Second-Level Menu Third-Level Menu Setting

Setting Wizard Date and Time Time Zone Set to the local time
zone.

Date and Time Set to the local date


and time.

5.1.3 Setting Basic Battery Parameters

Context
Basic battery parameters are fundamental for the monitoring unit to manage
batteries and should be set based on the number and capacity of battery strings
connected. The monitoring menus are related to the type of connected batteries
and the number of battery strings.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 63


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

NOTICE

Incorrectly setting basic battery parameters affects the battery charge and
discharge management and reduces the battery lifespan.

Procedure
Step 1 Set the battery type.

Table 5-2 Setting the battery type

Main Menu Second-Level Third-Level Fourth- Setting


Menu Menu Level Menu

Parameters Setup Basic Battery Set based on site


Settings Parameter Parameters Vendor requirements.
NOTE
Battery If lithium batteries and lead-acid
Model batteries are used together, set
Battery Vendor and Battery
Model based on the lead-acid
battery parameters.

Step 2 Set lead-acid battery parameters.

Table 5-3 Setting lead-acid battery parameters

Main Menu Second-Level Third-Level Setting


Menu Menu

Setting Wizard Batt Parameters Battery N Yes/No


Connected NOTE
Set the corresponding Battery N
Connected to Yes and the other
parameters to No based on the circuit
breaker or fuse to which lead-acid
batteries are connected.

Single-String Rated capacity of the batteries in a


Cap. battery string.
NOTE
The batteries controlled by one circuit
breaker or fuse are called a battery string.

For example:
● If battery routes 1 and 2 are respectively connected to a battery string (each battery string
consists of four 12 V, 150 Ah batteries in series), set Battery 1 Connected and Battery 2
Connected to Yes and others to No, and set Single-String Cap. to 150 Ah.
● If battery route 1 is connected to two battery strings in parallel (each battery string consists of
four 12 V, 150 Ah batteries in series), set Battery 1 Connected to Yes and others to No, and
set Single-String Cap. to 300 Ah.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 64


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Step 3 Set lithium battery parameters.

Table 5-4 Setting lithium battery parameters

Main Menu Second-Level Third-Level Third-Level Setting


Menu Menu Menu

Parameters Li Battery Basic Parameters Battery 1 Yes/No


Settings Connected NOTE
Set the corresponding
Battery 2 Battery N Connected to
Connected Yes and the other
parameters to No based on
the circuit breaker or fuse
to which lithium batteries
are connected.

Step 4 Set small-capacity lithium battery parameters.

Table 5-5 Setting small-capacity lithium battery parameters

Main Menu Second-Level Third-Level Fourth-Level Setting


Menu Menu Menu

Parameters Low Cap Li-ion Basic Battery 1 Yes/No


Settings Batt Parameters Connected NOTE
Set the corresponding Battery
Battery 2 N Connected to Yes and the
Connected other parameters to No based
on the circuit breaker or fuse to
which small-capacity lithium
batteries are connected.

Rated Capacity Rated capacity of the


batteries in a battery string.
NOTE
The batteries controlled by one
circuit breaker or fuse are
called a battery string.

NOTE

For example, if lithium batteries are connected to battery circuit breaker 1 and lead-acid
batteries are connected to battery circuit breaker 2, set lead-acid battery parameters
according to 5.1.3 Setting Basic Battery Parameters (set Battery 1 Connected to No and
Battery 2 Connected to Yes) and set lithium battery parameters according to 5.1.3 Setting
Basic Battery Parameters (set Battery 1 Connected to Yes and Battery 2 Connected to
No).

----End

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 65


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

5.1.4 Setting the Alarm Enable Option, Alarm Severity, and


Associated Relays
● You can enable or disable each alarm based on site requirements. If an alarm
is enabled, the monitoring unit generates the alarm when the alarm condition
is met. If an alarm is disabled, the monitoring unit does not generate the
alarm.
● You can set the severity of an alarm to critical, major, minor, or warning.
● You can associate an alarm with a specific dry contact output relay.
The following describes how to set alarm parameters for an AC Loop Fault.

Table 5-6 Setting the alarm enable option, alarm severity, and associated relays

Main Menu Second- Third-Level Fourth- Fifth-Level Sixth-Level Setting


Level Menu Level Menu Menu
Menu Menu

Parameters Alarm Alarm Site Unit AC Loop Alarm Enable Enable


Settings Parameters Config Fault
Alarm Major
Severity

Output Relay ALM1 No

Associated Camera 1
camera No

5.1.5 Setting Alarm Parameters for Dry Contacts


Context
● You can set associations between dry contact output status and alarm status.
● You can clear the associations between all alarms and the selected dry
contact inputs or outputs in one click.
● You can set associations between dry contact input status and alarm status.
Use DIN1 as an example. If you set DIN1 Alarm Condition to Close, the SMU
generates a DIN1 Alarm when the DIN1 is closed.

Procedure
Step 1 Set alarm actions for dry contact outputs. Use ALM1 as an example.

Table 5-7 Setting alarm actions for dry contact outputs

Main Menu Second-Level Third-Level Fourth-Level Setting


Menu Menu Menu

Parameters Alarm DO Dry Contact ALM1 Alarm Close


Settings Parameters Para. Action

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 66


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Step 2 Clear associations between alarms and dry contact outputs. Use ALM1 as an
example.

Table 5-8 Clearing associations between alarms and dry contact outputs
Main Menu Second-Level Third-Level Menu Fourth-Level Menu Setting
Menu

Parameters Alarm Clear ALM Asso. Clear ALM1 Asso. Yes


Settings Parameters

Step 3 Set alarm conditions for dry contact inputs. Use DIN1 as an example.

Table 5-9 Setting alarm conditions for dry contact inputs


Main Menu Second-Level Third-Level Fourth-Level Setting
Menu Menu Menu

Parameters Alarm DI Dry Contact DIN1 Alm. Cond. Close


Settings Parameters Para.

Step 4 Clear associations between alarms and dry contact inputs. Use DIN1 as an
example.

Table 5-10 Clearing associations between alarms and dry contact inputs
Main Menu Second-Level Third-Level Fourth-Level Setting
Menu Menu Menu

Parameters Alarm Clear DI Asso. Clear DIN1 Asso. Yes


Settings Parameters

----End

5.1.6 Setting Rectifier Addresses


Context
You can set rectifier addresses only on the LCD and only to the power system that
does not have a hardware address.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 67


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Figure 5-1 Rectifier addresses (twenty 100 A rectifiers are used in the example)

Parameters

Table 5-11 Rectifier address parameter description

Parameter Description Default Value Value Range

Rect. Address Settings Select Yes when you need No ● Yes


to manually set rectifier ● No
addresses.

N. Rectifier Address Set each rectifier address – 1~60


manually.

LCD Operations
Step 1 Set Rect. Address Settings to Yes.
Path: Main Menu > Setting Wizard > Rect. Address Settings

Step 2 Press to choose 1. Rectifier Address.


Step 3 Observe the indicators on rectifiers. If the power indicator (green) on a rectifier
blinks at 0.5 Hz, the rectifier is selected. Set the rectifier address to the value
shown in Figure 5-1 based on the rectifier position.
Step 4 Set the addresses for all rectifiers in the cabinet one by one.

Step 5 Press to choose Save Settings. Press to save the settings.

----End

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 68


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

5.1.7 Setting Basic DG Parameters


Procedure
Step 1 Set Genset and fuel tank number.

Table 5-12 Setting Genset and fuel tank number


Main Menu Second-Level Third-Level Fourth-Level Default Value
Menu Menu Menu Value Range

Parameters Setup Parameters Basic Genset Qty 0 0-2


Settings Parameters
Tank Qty 1 0-4

Step 2 Set basic Genset parameters.

Table 5-13 Setting basic Genset parameters


Main Second- Third-Level Fourth-Level Default Value Range
Menu Level Menu Menu Value
Menu

Parameters Genset Genset n Rated Power 12.5 kW 1 to 5000


Settings NOTE
Rated output power of
a single DG.

Run Hour for 9999h 0 to 10000


Maint

Days for Maint 500h 0 to 30000

Other Fuel Tank n Tank Type Cuboid Horizontal Cylinder,


Device Vertical Cylinder,
Config Irregular, Cuboid

Tank Length 1.50 m 0.50 to 20.00


NOTE
This parameter is
displayed only when
Tank Type is set to
Horizontal Cylinder.

Cyl Tank 1.13 m 0.00 to 4.00


Diameter NOTE
This parameter is
displayed only when
Tank Type is set to
Vertical Cylinder or
Horizontal Cylinder.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 69


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Main Second- Third-Level Fourth-Level Default Value Range


Menu Level Menu Menu Value
Menu

Cuboid Tank 1.00 m 0.00 to 10.00


Length NOTE
This parameter is
displayed only when
Tank Type is set to
Cuboid.

Cuboid Tank 1.00 m 0.00 to 10.00


Width NOTE
This parameter is
displayed only when
Tank Type is set to
Cuboid.

Tank Height 1.50 m 0.0 to 10.0


NOTE
This parameter is
displayed only when
Tank Type is set to
Vertical Cylinder or
Cuboid.

Rated Capacity 1500.00 L 0.00 to 6000.00


NOTE
This parameter is
displayed only when
Tank Type is set to
Irregular.

Under Fuel 15.0% 0.0 to 50.0


Level

Refuel Level 20.0% 0.0 to 50.0

Abnor Change 3.0 cm 1.0 to 1000.0


Thres

Abnor Change 10.0 Min 1.0 to 60.0


Dur

Level Filter 30 Min 1 to 1440


Time

Calibration 10 1 to 100
Num NOTE
This parameter is
displayed only when
Tank Type is set to
Irregular.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 70


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Main Second- Third-Level Fourth-Level Default Value Range


Menu Level Menu Menu Value
Menu

Height H n 0.00 cm 0.00 to 200.00


NOTE NOTE
Set this This parameter is
parameter displayed only when
to H0. Set Tank Type is set to
other Irregular.
parameters
based on
site
requirement
s.

Volum V n 0.00 L 0.00 to 6000.00


NOTE NOTE
Set this This parameter is
parameter displayed only when
to H0. Set Tank Type is set to
other Irregular.
parameters
based on
site
requirement
s.

Level Filter 3.00 cm 0.00 to 10.00


Thres

Refuel Calc Enb Yes Yes, No

----End

5.1.8 Starting a Genset Self-Check


Context
● There is no battery alarm on the monitoring unit, and battery power supply is
normal.
● If the mains power is used, ensure that the mains AC input circuit breaker on
the ATS is OFF.

Procedure
Step 1 Check and confirm the control mode is Automatic. If it is Manual, set control
mode to Automatic in diesel generator.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 71


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Table 5-14 Checking the DG control mode

Main Menu Second-Level Third-Level Fourth-Level Setting


Menu Menu Menu

Running Control Genset Genset Group Control Mode Automatic

Step 2 Start a Genset self-check.

Table 5-15 Starting a Genset self-check

Main Menu Second-Level Third-Level Fourth-Level Setting


Menu Menu Menu

Running Control Genset Genset Self Confirm Self Yes


Check Check

NOTE

A maximum of two DGs can be connected. The auto check process is as follows:
1. About 2 minutes after starting DG 1, the monitoring unit checks the DG running status
to determine whether the DG has started.
2. About 2 minutes after shutting down DG 1, the monitoring unit checks the DG running
status to determine whether the DG has shut down.
3. About 2 minutes after starting DG 2, the monitoring unit checks the DG running status
to determine whether the DG has started.
4. About 2 minutes after shutting down DG 2, the monitoring unit checks the DG running
status to determine whether the DG has shut down.
After the auto check is complete, the SMU displays the results on the screen:
● Control DG Number (0/1/2)
● DG 1 Start Result (Success/Fail)
● DG 1 Stop Result (Success/Fail)
● DG 2 Start Result (Success/Fail)
● DG 2 Stop Result (Success/Fail)
A single-DG self-check takes about 4 minutes, and a dual-DG self-check takes more than 8
minutes.

Step 3 Verify that the self-check result is consistent with the actual number of DGs and
the DGs work properly. If the DG self-check fails, refer to the DG manual for
troubleshooting and DG cable connection checking.

----End

5.1.9 Setting WiFi Parameters


You can locally access the WebUI over WiFi.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 72


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Table 5-16 Setting WIFI parameters


Main Menu Second-Level Third-Level Default Value Range
Menu Menu Value

Parameters WiFi Settings WIFI Enable Enable Enable,


Settings Disable

Wifi SSID POWER_SITE A maximum


of 31
characters,
including
lowercase
English letters
(a to z),
uppercase
English letters
(A to Z),
digits (0 to 9),
and special
characters
(@_#-.).

Password Changeme A maximum


of 31
characters,
including
lowercase
English letters
(a to z),
uppercase
English letters
(A to Z),
digits (0 to 9),
and special
characters
(@_#-.).
It is
recommended
that the
password
contain at
least two
types of
characters
and the
length exceed
eight
characters.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 73


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

5.2 Common Maintenance Tasks

5.2.1 Backing Up the Current Settings


The configuration file contains all user configuration information (such as
parameter values and alarm configurations) about the current system.

You can back up the configuration file to a local computer or a USB flash drive
over the WebUI, and use the configuration file to rapidly configure parameters for
other sites.

NOTICE

When importing the backup configuration file, ensure that the system types of the
exported and imported configuration files are consistent.

Figure 5-2 Backing up the current configuration

5.2.2 Importing a Configuration File


You can quickly configure site parameters by importing a configuration file.

Figure 5-3 Importing a configuration file

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 74


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

NOTE

If an encryption password is set during the export of a configuration file, the decryption
password entered during the import of the configuration file must be the same as the
encryption password of the exported configuration file.

5.2.3 Restoring Factory Defaults

NOTICE

After factory defaults are restored, the monitoring unit restarts.

After factory defaults are restored, all parameter values change to their default
factory values. You are advised to back up the current settings before restoring
factory defaults.

Figure 5-4 Restoring factory defaults

5.2.4 Upgrading Software


You can use the WebUI and LCD to upgrade software for the SMU BSP, SMU,
intelligent device SO library package, and southbound devices.

NOTICE

● To retain pre-upgrade parameters, back up the data before upgrading software.

● The SMU will restart automatically after the software for the BSP, SMU, and
intelligent device SO library package is upgraded.
● Exercise caution to choose the version rollback function during software
upgrade. After version rollback, the user accounts created are deleted, and the
initial user name and password are required for login.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 75


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Figure 5-5 Upgrading software

5.2.5 Changing a User Password


Context
For security purposes, change your password periodically.
Only the system administrator can change user passwords.

Changing a User Password


Step 1 Log in to the WebUI and choose Maintenance > User Management. The user
management page is displayed.

Figure 5-6 User management page

Step 2 Select the user whose password needs to be changed and click Modify. The dialog
box for modifying user information is displayed.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 76


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Figure 5-7 Changing the password

Step 3 Select Change Password, set New Password and Confirm Password, and click
Confirm. The Recertification dialog box is displayed.
NOTE

The administrator needs to set Old Password only when changing the administrator's own
password.

Change the password in compliance with the following rules:

a~z','A~Z','0~9','!@*-_?{}='(8–20 characters of at least two types.Different from the


user name or its reverse).

Step 4 Set New Password of Current Login User and click Submit.

----End

Changing WiFi Password

NOTICE

● You are advised to periodically change the WiFi password to improve account
security and prevent unauthorized network attacks, such as data tampering.
● We will not be liable for any losses incurred if you do not change the account
password in time or forget the new password. (Lost passwords cannot be
retrieved.)
● The WiFi function is disabled by default. Enable the WiFi function before using
it and disable it after using it to ensure network security.

Enable or disable the WiFi function: choose System Settings > Network Config >
WIFI.

Change the WiFi account password: choose System Settings > Network Config >
WIFI.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 77


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

5.2.6 Viewing Dry Contact Association Information


Context
● You can view the information about association between dry contact outputs
and alarms.
● You can also view the information about association between dry contact
inputs and devices.

Procedure
Step 1 View the information about association between dry contact outputs and alarms.

Figure 5-8 Viewing the information about association between dry contact
outputs and alarms

Step 2 View the information about association between dry contact inputs and devices.

Figure 5-9 View the information about association between dry contact inputs
and devices

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 78


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

----End

5.2.7 Viewing Active Alarms


Active alarms are the alarms that are not cleared.

Figure 5-10 Viewing active alarms

5.2.8 Viewing Historical Alarms

Prerequisites
Historical alarms refer to alarms that have generated and then been cleared
manually or automatically.

Procedure
Step 1 To filter out historical alarms.

Figure 5-11 Filtering out historical alarms

Step 2 View historical alarms.

Figure 5-12 Viewing historical alarms

----End

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 79


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

5.2.9 Viewing Version Information


View the monitoring version number to facilitate fault diagnosis and check
whether the upgrade is successful.

Figure 5-13 Viewing Version Information

5.2.10 Exporting Maintenance Information


Context
● You can export historical alarms, active alarms, performance data, operation
logs, and battery test records on the WebUI.
● You can view and export e-label information about the power subrack,
monitoring unit, and rectifiers on the WebUI.
● You can export version information and system operating information in one-
click mode on the WebUI to quickly collect information and identify system
faults.
● It takes about 5 minutes to collect fault information for each rectifier.

Procedure
Step 1 To export historical data.

Figure 5-14 Exporting historical data

Step 2 To export e-label information.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 80


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Figure 5-15 Exporting e-label information

Step 3 To collect rectifiers fault information.

Figure 5-16 Collecting fault information

Step 4 Collect lithium battery fault information.

Figure 5-17 Collect lithium battery fault information

Step 5 To export fault information.

Figure 5-18 Exporting fault information

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 81


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

NOTE

The exported fault information includes the black box information about rectifiers and
lithium batteries.
If information export fails due to a browser error, wait for a certain period (30 minutes at
most), log in, and try again.

----End

5.2.11 Setting Battery Test Parameters


Step 1 Set the standard test parameters.

Table 5-17 Set the standard test parameters

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Parameters Battery Standard Test Time Test Disable Schedulde Test,


Settings Para. Mode Planned Test,
Disable
NOTE
Set the parameter
based on site
requirements.

Sche. Test St. 21:00:00 00:00:00 to 23:59:59


Time NOTE
This parameter is
displayed when Time
Test Mode is set to
Scheduled Test.

Ammual 0 0 to 6
Battery Tests NOTE
This parameter is
displayed when Time
Test Mode is set to
Planned Test.

Planned Test 01-01 00:00 Set the parameter


Time based on site
requirements.
NOTE
This parameter is
displayed when Time
Test Mode is set to
Planned Test.

Sche. Test 90 2 to 999


Period (Day) NOTE
This parameter is
displayed when Time
Test Mode is set to
Scheduled Test.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 82


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Pre-BC Enable Enable, Disable


Enable

Constant Disable Enable, Disable


Cur. Test

Test End 46.0 44.2 to 53.0


Voltage (V)

Test End 20 0 to 99
Ca[acoty
(%)

Test End 480 1 to 6000


Time (min)

Test End 5 -5 to 15
Temperature
(degC)

Step 2 Set short test parameters.

Table 5-18 Set short test parameters


Second- Third-Level Fourth-Level Fifth-Level Menu Default Value Range
Level Menu Menu Menu Value

Parameters Battery Short Test Disable Disable Enable, Disable


Settings Para.
Short Test Period 30 1 to 360
(Day)

Short Test Time 5 1 to 240


(min)

Short Test End Volt 45.0 44.2 to 53.0


(V)

----End

5.2.12 Deleting Devices Devices Failing in Communication


Procedure
Step 1 Delete devices failing in communication.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 83


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Main Menu Second-Level Third-Level Menu Setting


Menu

Running Control Digital Power Digital Power Delete Communication


Failed Equipment
Cabinet(Subrack)

----End

5.3 Common Installation Tasks (MDU)

5.3.1 Common Functions


Enable the alarm buzzer.

The alarm severity, alarm name, fault code, settings, generation time, and
clearance time are displayed.

Table 5-19 Common Functions

Main Menu Second-Level Menu

Common Functions Buzzer On

Historical Alarms

5.3.2 Setting Common Parameters


The SMU supports English, Chinese, French, Spanish, Portuguese, Russian, Italian,
German, Turkish, and Japanese.

When the SMU is running properly, set the language, date, and time in the
following menu paths.

Table 5-20 Setting Common Parameters

Main Menu Second-Level Third-Level Setting


Menu Menu

System Settings Common Select a desired


Information language.

Set to the local


time zone.

Set to the local


date and time.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 84


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

5.3.3 Setting Basic Battery Parameters


Context
Basic battery parameters are fundamental for the monitoring unit to manage
batteries and should be set based on the number and capacity of battery strings
connected. The monitoring menus are related to the type of connected batteries
and the number of battery strings.

NOTICE

Incorrectly setting basic battery parameters affects the battery charge and
discharge management and reduces the battery lifespan.

Procedure
Step 1 Set lead-acid battery parameters.

Main Menu Second- Third-Level Fourth-Level Fifth-Level Setting


Level Menu Menu Menu
Menu

System Settings Battery Group Basic Parameters Single-string 5-12000


Information Cap. (Ah)

Float Charge 42.0-58.0


Coltage (V)

Boost Charge 42.0-58.0


Voltage (V)

Charge Limit 0.05-0.50


Coef. (C10)

Charge Auto. BC Enable/


Parameters Enable Disable

FC-BC Cur. 0.01-0.25


Coef. (C10)

FC-BC Cur. 2-1440


Duration (min)

FC-BC Cap. 50-100


Percent (%)

Timed BC Enable/
Enabled Disable

Timed BC 1-365
Interval (Day)

Timed BC 1-24
Duration (h)

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 85


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Main Menu Second- Third-Level Fourth-Level Fifth-Level Setting


Level Menu Menu Menu
Menu

BC-FC Cur. 0.01-0.25


Coef. (C10)

BC-FC Cur. 2-540


Duration (min)

BC-Max 5-48
Duration (h)

Mains Reco BC Enable/


En. Disable

Temperature TC Coefficient 0-150


Comp. para (mV/degC)

Nominal 5-45
Temperature
(degC)

TC Upper 40-45
Thres. (degC)

TC Lower 0-25
Thers. (degC)

Standard Test Time Test Disable/


Para Mode Planned Test/
Scheduled
Test

Annual Battery 0-6


Tests
NOTE
This parameter
is displayed
when Time
Test Mode is
set to Planned
Test.

Sche. Test ST. 00:00:00-23:5


Time 9:59
(HH:MM:SS)
NOTE
This parameter
is displayed
when Time
Test Mode is
set to
Scheduled
Test.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 86


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Main Menu Second- Third-Level Fourth-Level Fifth-Level Setting


Level Menu Menu Menu
Menu

Sche. Test 2-999


Period (Day)
NOTE
This parameter
is displayed
when Time
Test Mode is
set to
Scheduled
Test.

Pre-BC Endble Enable/


Disable

Constant Cur. Enable/


Test Disable

Test End 44.2-53.0


Voltage (V)

Test End 0-99


Caparity (%)

Test End -5-15


Temperature
(degC)

Test End Time 1-6000


(min)

Short Test Short Test Enable/


Parameters Enable Disable

Short Test 1-365


Period (Day)

Short Test 1-240


Time (min)

Short Test End 44.2-53.0


Volt. (V)

H/L Temp. Very HT Prot. Disable/


Protect Para Mode Reduce DC
Voltage/
Disconnect
Battery

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 87


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Main Menu Second- Third-Level Fourth-Level Fifth-Level Setting


Level Menu Menu Menu
Menu

Very HT Prot. 42.0-53.0


Volt. (V)
NOTE
This parameter
is displayed
when Very HT
Prot. Mode is
set to Reduce
DC Voltage.

HT Alarm 25-80
Thres. (degC)

Very HT Alarm 25-80


thres. (degC)

LT Alarm -20-20
Thres. (degC)

Very LT Alarm -20-20


Thres. (degC)

Alarm Overcur. Alm. 0.05-1.00


Parameters Thres. (C10)

Basic Control Reset Batt. Yes


Cap.

Clear Test Log Yes

Other battery Install Set this


Parameters Time (YYYY- parameter
MM-DD) based on the
actual
installation
time.

Step 2 Set lithium battery parameters.

Table 5-21 Set lithium battery parameters

Main Menu Second- Third-Level Fourth-Level Fifth-Level Setting


Level Menu Menu Menu
Menu

System Settings Lihtium Battery Basic iLock Enablde Disable/


Information Group Parameters Enabled

BMU Manage Host


Mode Manage/Auto
Manage

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 88


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Main Menu Second- Third-Level Fourth-Level Fifth-Level Setting


Level Menu Menu Menu
Menu

Charge Boost Charge 42.0-58.0


Parameters Voltage (V)

FC Voltage (V) 42.0-58.0

Chg Curr Limit 0.05-1.05


Coef (C10)

Standard Test Time Test Disable/


Parameters Mode Planned Test/
Scheduled
Test

Annual Battery 0-6


Tests
NOTE
This parameter
is displayed
when Time
Test Mode is
set to Planned
Test.

Sche. Test St. 00:00:


Time 00-23:59:59
(HH:MM:SS)
NOTE
This parameter
is displayed
when Time
Test Mode is
set to
Scheduled
Test.

Sche. Test 2-999


Period (Day)
NOTE
This parameter
is displayed
when Time
Test Mode is
set to
Scheduled
Test.

Test End
Voltage (V)

Test End Time


(mm)

Test End
Capacity (%)

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 89


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Main Menu Second- Third-Level Fourth-Level Fifth-Level Setting


Level Menu Menu Menu
Menu

Basic Control Batt. Standard Stop/Start


Test

Clear Test Log Yes

----End

5.3.4 Setting Rectifier Parameters


Table 5-22 Setting Rectifier Parameters
Main Menu Second- Third-Level Fourth-Level Fifth-Level Setting
Level Menu Menu Menu
Menu

System Settings Rectifier Group Basic Parameters Default Output 48.0-58.0


Information Volt (V)

High Rect 0-150


Temain Cap
(%)

Low Rect 0-150


Temain Cap
(%)

Seq Start Int 0-20


(s)

Rectifier 56.0-60.5
Protect Volt (V)

WALK-IN NO/Yes
Enabled

Hibernation Hibernation NO/Yes


Parameters Enb

Hibernation Intelligent
Mode Mode/Time
Mode/High
Efficiency
Mode

Min Work Rect 1-100


Qty

Rotation Period 1-365


(Day)

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 90


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Main Menu Second- Third-Level Fourth-Level Fifth-Level Setting


Level Menu Menu Menu
Menu

Best Efficiency 10-100


(%)

Min Rdnd Coef 0.05-1.00

Phase Balance Disable/


Absolute
Balance/
Relative
Balance

Hiber without NO/Yes


Batt

Hiber Stop 0.5-168.0


Duration (h)

Basic Control Reset Protect NO/Yes

5.3.5 Setting Mains Parameters


Table 5-23 Setting Mains Parameters
Main Menu Second- Third- Fourth-Level Fifth-Level Setting
Level Level Menu Menu
Menu Menu

System Settings Mains Basic Parameters AC Mode 2-Phase 2-Wire/1-


Information Phase/3-Phase 4-
Wire/3-Phase 3-
Wire

Alarm AC High Freq 40-70


Parameters Thres.(Hz)

AC Low Freq 40-70


Thres.(Hz)

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 91


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

5.3.6 Setting Overvoltage and Undervoltage Alarm Thresholds


for the DC Cabinet
Table 5-24 Setting Overvoltage and Undervoltage Alarm Thresholds for the DC Cabinet
Main Menu Second- Third-Level Fourth-Level Fifth-Level Setting
Level Menu Menu Menu
Menu

System Settings DC Cabinet n DC Output DC Over 53.0-60.0


Information Distribut. Voltage (V)

DC Under 36.0-57.0
Voltage (V)

Ultra Over Volt 53.0-60.0


(V)

Ultra Under 36.0-56.0


Volt (V)

5.3.7 Setting Overvoltage and Undervoltage Alarm Thresholds


for the Rectifier Cabinet
Table 5-25 Setting Overvoltage and Undervoltage Alarm Thresholds for the Rectifier Cabinet
Main Menu Second- Third-Level Fourth-Level Fifth-Level Setting
Level Menu Menu Menu
Menu

System Settings Rectifier Cab n DC Output DC Over Voltage 53.0-60.0


Information Distribut. (V)

DC Under 36.0-57.0
Voltage (V)

Ultra Over Volt 53.0-60.0


(V)

Ultra Under Volt 36.0-56.0


(V)

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 92


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

5.3.8 Setting Combined Cabinet Parameters


Table 5-26 Setting Combined Cabinet Parameters
Main Menu Second- Third-Level Fourth- Fifth-Level Setting
Level Menu Level Menu
Menu Menu

System Settings Combined Cab DC LLVD Enablde Disable/Enable


Information n Output
Distribut LLVD PD End Disable/Enable

LLVD HTD End Disable/Enable

DC Over Voltage 53.0-60.0


(V)

DC Under Volt 36.0-57.0


(V)

Ultre Over Volt 53.0-60.0


(V)

Ultre Under Volt 36.0-56.0


(V)

5.3.9 Setting Communications Parameters


Table 5-27 Setting Communications Parameters
Main Menu Second- Third-Level Menu Fourth- Fifth-Level Setting
Level Level Menu
Menu Menu

System Settings Communications IP IP Address Automatic (DHCP)/


Information Address Allocation Manual
Settings
IP Address 1.0.0.0–
223.255.255.255

Subnet Mask 0.0.0.0–


255.255.255.255

Gateway 1.0.0.0–
223.255.255.255

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 93


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

5.3.10 Quick Settings


Table 5-28 Quick Settings
Main Menu Second- Third-Level Fourth-Level Setting
Level Menu Menu
Menu

System Settings Quick Settings Battery Vendor Set to the actual


Information manufacturer of the
connected batteries.

Battery Model Set to the actual model of


the connected batteries.

FC Voltage (V) 42.0-58.0

Boost Charge 42.0-58.0


Voltage (V)

Date Formmat YYYY-MM-DD

Date Setting Set to the current date.

Time Zone Set to the local time zone.

Time Set to the local time.

5.3.11 Setting Sensor Parameters


Table 5-29 Setting Sensor Parameters
Main Menu Second- Third-Level Fourth- Fifth-Level Menu Setting
Level Menu Level
Menu Menu

System Settings Setup Sensor DC SPD Yes, No


Information Parameter Config NOTE
AC SPD Set these
parameters
Door Sensor to Yes or No
as required.
Water Sensor

Smoke Sensor

Ambient Temp.
Sendor

Ambient Humi.
Sensor

Batt. Temp. Sensor


n

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 94


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

5.3.12 Setting WAN Port


Table 5-30 Setting WAN Port
Main Menu Second- Third-Level Menu Fourth- Fifth-Level Setting
Level Level Menu
Menu Menu

System Settings Communications WAN WAN port GE, None


Information settings NOTE
● If this parameter
is set to None, all
GE, FE_1, and
FE_2 ports are
LAN ports. That
is, GE, FE_1, FE_2,
and MDU can
communicate
with each other.
By default, this
parameter is set
to None.
● If this parameter
is set to GE, the
GE port can
communicate
with the
cascading port
FE_1, and the GE
port is connected
to the external
network.
Cascading port
FE_1
communicates
with FE_2 and
MDU, connects
to the internal
network, and can
be accessed
locally through
FE_2.

5.4 Common Maintenance Tasks (MDU)

5.4.1 Viewing Version Information


On the System Information screen, tap About to view the model, manufacturer,
and SMU version. To view the detailed version information, tap Version Details.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 95


SMU02X V100R021C10 Site Monitoring Unit
User Manual 5 Common Tasks

Table 5-31 Viewing Version Information


Main Menu Second-Level Menu Third-Level Menu

System Information About SMU

Vendor

SMU Version

Version Details

5.4.2 Viewing Active Alarms


Table 5-32 Viewing Active Alarms
Main Menu Second-Level Menu Third-Level Menu

System Information Alarm Active Alarms

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 96


SMU02X V100R021C10 Site Monitoring Unit
User Manual 6 Hardware Replacement

6 Hardware Replacement

6.1 Replacing an SMU02C

CAUTION

Historical data may exist in the SMU. Cross-border transfer of damaged SMUs is
prohibited. We will not assume any liability for the leakage of sensitive personal
information caused by faulty parts handling.

Prerequisites
● An ESD wrist strap, ESD gloves, ESD box or bag, and cabinet door key are
available.
● The new SMU02C is intact.

Procedure
Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap
and ESD gloves.
NOTE

Record the software version of the old SMU. If the old SMU is damaged and cannot be
viewed, send the barcodes of the old SMU and the cabinet to service personnel for query.

Step 2 Disconnect the communications cable from the SMU02C panel.


Step 3 Push the locking latch leftwards.
Step 4 Pull the handle outwards and remove the SMU02C.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 97


SMU02X V100R021C10 Site Monitoring Unit
User Manual 6 Hardware Replacement

Figure 6-1 Removing the SMU02C

Step 5 Remove the SD card from the side of the SMU02C.


NOTE

● If no SD is installed, go to Step 7.
● In parallel scenarios, delete the devices failing in communication on a normal SMU. For
details, see 5.2.12 Deleting Devices Devices Failing in Communication.

Step 6 Insert the SD card into the new SMU02C.

Figure 6-2 Installing the SD card

Step 7 Place the new SMU02C in the slot, push the locking latch leftwards, and pull out
the handle.

Step 8 Gently push the SMU02C along guide rails until it is engaged. Close the handle,
and push the locking latch rightwards.

Figure 6-3 Installing the SMU02C

Step 9 Reconnect the communications cable to the SMU02C panel.


NOTE

After replacing the old SMU with a new spare part, power on the new SMU and check its
software version. If the software version of the new SMU is earlier than that of the old
SMU, upgrade the new SMU software.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 98


SMU02X V100R021C10 Site Monitoring Unit
User Manual 6 Hardware Replacement

Step 10 Reset SMU02C parameters.

----End

Follow-up Procedure
Pack the removed component and have it sent to the local warehouse.

6.2 Replacing a WIM01C1


Prerequisites
● An ESD wrist strap, ESD gloves, ESD box or bag, door key, and required tools
are available.
● The new WIM01C1 is intact.

Procedure
Step 1 Log in to the WebUI and record the WIM01C1 networking diagram.

Step 2 Connect the ground cable of the ESD wrist strap, and wear the ESD wrist strap and
ESD gloves.

Step 3 Record the connection positions of cables on the WIM01C1 panel and disconnect
the cables.

Step 4 Loosen the screws on both sides of the WIM01C1 panel and take out the
WIM01C1.

Figure 6-4 Removing the WIM01C1

Step 5 Disconnect the power cables between the WIM01C1 and the UIM.

Step 6 Loosen the screws that secure the WIM01C1 to the UIM and take out the
WIM01C1.

Step 7 Push the new WIM01C1 in place and secure it with holes aligned.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 99


SMU02X V100R021C10 Site Monitoring Unit
User Manual 6 Hardware Replacement

Step 8 Reconnect the cables between the WIM01C1 and the UIM.
Step 9 Push the UIM into the subrack.
Step 10 Reconnect the cables to the new WIM01C1 panel based on the recorded
information.
Step 11 Disconnect the ground cable of the ESD wrist strap, and remove the ESD wrist
strap and ESD gloves.
Step 12 Log in to the WebUI and check that there is no alarm about the WIM01C1 and
that its networking diagram is consistent with the recorded diagram.

----End

Follow-up Procedure
Pack the removed component and send it to the local warehouse.

6.3 Replacing a UIM02C Board


Prerequisites
● An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and
required tools are available.
● The new UIM02C board is intact.

Procedure
Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap
and ESD gloves.
Step 2 Record the position of signal cables connected to the UIM02C panel, and then
disconnect the signal cables.
Step 3 Unscrew and take out the UIM02C.

Figure 6-5 Taking out the UIM02C

Step 4 Disconnect the –48 V power cable from the UIM02C board.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 100


SMU02X V100R021C10 Site Monitoring Unit
User Manual 6 Hardware Replacement

Figure 6-6 Disconnecting the –48 V power cable

(1) -48 V power port

Step 5 Record the connection positions of all cables including cables for internal and
external circulation fans and flat cables on the UIM02C board, and then
disconnect the cables.

Step 6 Remove the UIM02C board.

Figure 6-7 Removing the UIM02C board

Step 7 Take out and install the new UIM02C board.

Step 8 Connect all the cables on the UIM02C board to the new UIM02C based on the
recorded information.

Step 9 Reconnect the –48 V power cable to the UIM02C board.

Step 10 Push the UIM02C in place and tighten the screws.

Step 11 Reconnect signal cables to the new UIM02C panel based on the recorded
information.

Step 12 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist
strap and ESD gloves.

----End

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 101


SMU02X V100R021C10 Site Monitoring Unit
User Manual 6 Hardware Replacement

Follow-up Procedure
Pack the removed component and have it sent to the local warehouse.

6.4 Replacing a UIM02D Board


The UIM02D consists of two user interface boards. This topic describes how to
replace the boards.

Procedure
Step 1 Record the positions where signal cables connect to the UIM02D panel, and then
disconnect the signal cables.

Step 2 Loosen the screws on the UIM02D panel and remove the UIM02D, as shown in
Figure 6-8.

Figure 6-8 Removing the UIM02D

Step 3 Disconnect the –48 V power cable from the UIM02D backplane.

Figure 6-9 Disconnecting the –48 V power cable

Step 4 Disconnect the flat cable from the UIM02D backplane.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 102


SMU02X V100R021C10 Site Monitoring Unit
User Manual 6 Hardware Replacement

Step 5 Remove the upper board from the UIM02D.


1. Unscrew and remove the upper board from the UIM02D, as shown in the
following figure.

Figure 6-10 Removing the upper board from the UIM02D

2. Disconnect the cables between upper and lower boards in the UIM02D.
Step 6 Remove the lower board from the UIM02D.
1. Record the positions of signal cables and communications cables connected to
the lower board, and disconnect the cables.
2. Unscrew and remove the lower board from the UIM02D, as shown in the
following figure.

Figure 6-11 Removing the lower board from the UIM02D

Step 7 Install a new lower board in the UIM02D.


1. Place a new lower board in the UIM02D, and tighten screws.
2. Reconnect the removed signal cables and communications cables to the lower
board based on the recorded information.
Step 8 Install a new upper board in the UIM02D.
1. Reconnect the removed cables between upper and lower boards in the
UIM02D.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 103


SMU02X V100R021C10 Site Monitoring Unit
User Manual 6 Hardware Replacement

2. Place a new upper board in the UIM02D, and tighten screws.


Step 9 Reconnect the –48 V power cable and signal cables to the UIM02D panel based on
the recorded information.
Step 10 Push the UIM02D into the slot until its front panel aligns with the front panel of
the monitoring unit, and tighten the screws.
Step 11 Connect the signal cables to the original positions on the UIM02D panel.
----End

Follow-up Procedure
Pack the removed component and have it sent to the local warehouse.

6.5 Replacing an UIM03D Board


Prerequisites
● An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and
required tools are available.
● The new user interface board is intact.

Procedure
Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap
and ESD gloves.
Step 2 Note where signal cables are connected to the UIM03D panel. Record these
positions and disconnect the cables.
Step 3 Unscrew and remove the UIM03D.
Step 4 Note where all cables are connected to the NIM02D. Record these positions and
remove and the cables and NIM02D.
NOTE

If no NIM02D is deployed, skip this step.

Figure 6-12 Removing the NIM02D

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 104


SMU02X V100R021C10 Site Monitoring Unit
User Manual 6 Hardware Replacement

Step 5 Record all cable connection positions on the user interface board and disconnect
the cables.

Step 6 Remove the user interface board, as shown in the following figure.

Figure 6-13 Removing the UIM03D

Step 7 Take out and install the new user interface board.

Step 8 Connect all the cables to the new user interface board based on the information
you recorded.

Step 9 Install the NIM02D and connect cables according to the information you recorded.
NOTE

If no NIM02D is deployed, skip this step.

Step 10 Push the UIM03D in position and tighten the screws.

Step 11 Reconnect the signal cables to the UIM03D panel based on the information you
recorded.

Step 12 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist
strap and ESD gloves.

----End

Follow-up Procedure
Pack the removed component and have it sent to the local warehouse.

6.6 Replacing an UIM05B1


Prerequisites
● The ESD wrist strap, ESD gloves, ESD box or bag, and toolbox are available.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 105


SMU02X V100R021C10 Site Monitoring Unit
User Manual 6 Hardware Replacement

● The new UIM05B1 is intact.

Procedure
Step 1 Connect the ESD wrist strap ground cable, and wear the ESD wrist strap and ESD
gloves.

Step 2 Record the connection positions of cables on the UIM05B1 panel and remove the
cables.

Step 3 Loosen the screws on the UIM05B1 panel, pull the handle until it is engaged, and
take out the UIM05B1.

Figure 6-14 Removing the UIM05B1

Step 4 Install the new UIM05B1.

Step 5 Install the cables based on the recorded information.

----End

Follow-up Procedure
Pack the removed component and have it sent to the local warehouse.

6.7 Replacing an NIM02D Board


Prerequisites
● An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and
required tools are available.
● The new NIM02D board is intact.

Procedure
Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap
and ESD gloves.

Step 2 Record the connection positions of cables on the NIM02D panel and disconnect
the cables.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 106


SMU02X V100R021C10 Site Monitoring Unit
User Manual 6 Hardware Replacement

Step 3 Loosen the screws on both sides of the UIM02C panel and pull out the UIM02C.
Step 4 Disconnect the power cables between the NIM02D board and the J1 port on the
UIM02C.
Step 5 Unscrew the NIM02D from the UIM02C board and take out the NIM02D board.

Figure 6-15 Removing the NIM02D board

Step 6 Push the new NIM02D board in place and secure it with holes aligned.
Step 7 Connect power cables between the power port on the NIM02D board and the J1
port on the UIM02C.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 107


SMU02X V100R021C10 Site Monitoring Unit
User Manual 6 Hardware Replacement

Figure 6-16 Connecting power cables

(1) Power port on the NIM02D board (2) J1 port on the UIM02C board

Step 8 Push the UIM02C into the subrack until its front panel is flush with that of the
monitoring unit subrack and then tighten the screws.
Step 9 Reconnect the cables to the new NIM02D panel based on the recorded
information.
Step 10 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist
strap and ESD gloves.

----End

Follow-up Procedure
Pack the removed component and have it sent to the local warehouse.

6.8 Replacing an NIM01C3


Prerequisites
● An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and
required tools are available.
● The new NIM01C3 is intact.

Procedure
Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap
and ESD gloves.
Step 2 Record the positions where signal cables connect to the NIM01C3 panel, and then
disconnect the signal cables.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 108


SMU02X V100R021C10 Site Monitoring Unit
User Manual 6 Hardware Replacement

Step 3 Loosen the screws on both sides of the NIM01C3 panel.

Step 4 Pull the handle rightwards to remove the NIM01C3.

Figure 6-17 Removing an NIM01C3

Step 5 Remove the SIM card from the SIM card slot of the NIM01C3, and insert it into the
SIM card slot of the new NIM01C3. Skip this step if no SIM card is installed.

Step 6 Place the new NIM01C3 at the entry to the appropriate slot in the monitoring unit
subrack, and push the NIM01C3 until its front panel is flush with the front panel
of the monitoring unit subrack.

Step 7 Push the handle inwards until it is engaged, and then tighten the screws.

Figure 6-18 Installing an NIM01C3

Step 8 Connect the signal cables to the original positions on the NIM01C3 panel.

Step 9 Disconnect the ground cable for the ESD wrist strap, and remove the ESD wrist
strap and ESD gloves.

----End

Follow-up Procedure
Pack the removed component and have it sent to the local warehouse.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 109


SMU02X V100R021C10 Site Monitoring Unit
User Manual 6 Hardware Replacement

6.9 Replacing a CIM02C


Prerequisites
● An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and
required tools are available.
● The new CIM02C is intact.

Procedure
Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap
and ESD gloves.

Step 2 Record the connection positions of cables on the CIM02C panel and disconnect the
cables.

Step 3 Loosen the screws on both sides of the CIM02C panel.

Step 4 Pull the handle rightwards and take out the CIM02C.

Figure 6-19 Removing a CIM02C

Step 5 Place the new CIM02C at the entry to the appropriate slot in the monitoring unit
subrack, and push the CIM02C until its front panel is flush with the front panel of
the monitoring unit subrack.

Step 6 Push the handle inwards until it is engaged, and then tighten the screws.

Figure 6-20 Installing a CIM02C

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 110


SMU02X V100R021C10 Site Monitoring Unit
User Manual 6 Hardware Replacement

Step 7 Reconnect the cables to the new CIM02C panel based on the recorded
information.

Step 8 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist
strap and ESD gloves.

----End

Follow-up Procedure
Pack the removed component and have it sent to the local warehouse.

6.10 Replacing a GIM01C


Prerequisites
● An ESD wrist strap, ESD gloves, ESD box or bag, cabinet door key, and
required tools are available.
● The new GIM01C is intact.

Procedure
Step 1 Connect the ground cable to the ESD wrist strap, and put on the ESD wrist strap
and ESD gloves.

Step 2 Record the connection positions of cables on the GIM01C panel and disconnect
the cables.

Step 3 Loosen the screws on both sides of the GIM01C panel.

Step 4 Pull the handle rightwards and take out the GIM01C.

Step 5 Place the new GIM01C at the entry to the appropriate slot in the monitoring unit
subrack, and push the GIM01C until its front panel is flush with the front panel of
the monitoring unit subrack.

Step 6 Push the handle inwards until it is engaged, and then tighten the screws.

Step 7 Reconnect the cables to the new GIM01C panel based on the recorded
information.

Step 8 Disconnect the ground cable from the ESD wrist strap, and remove the ESD wrist
strap and ESD gloves.

----End

Follow-up Procedure
Pack the removed component and have it sent to the local warehouse.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 111


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

A LCD Menu Hierarchy

WARNING

When you set parameters such as DG startup/shutdown, air conditioner startup/


shutdown, LLVD/BLVD voltage, AC circuit breaker capacity, mains capacity, load
connection/disconnection control, battery connection/disconnection control,
HVDC/PSU/SSU/MIMO/24 V module startup/shutdown, DG capacity, and rectifier
power limit on the WebUI, the site power supply may be affected.

NOTE

● The menu hierarchy and parameter display depend on the power supply scenario,
system type, system parameter settings, and device connections.
● # indicates that the parameter is displayed only when related devices are connected or
related parameters are set.

Figure A-1 LCD menu hierarchy

Table A-1 LCD menu description

Menu Item Description

Active Alarm Views active alarms in the system.

Running Views the operating status of the power system, rectifiers, batteries, and other
Information modules in the system.

Setting Wizard Quickly sets common parameters, such as the number of battery strings, rated
battery capacity, date, time, and network parameters.

Parameters Sets parameters for the power system, rectifiers, batteries, and other modules
Settings in the system.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 112


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Menu Item Description

Running Control Manually controls the power system, rectifiers, batteries, and other modules in
the system, such as switching between equalized charging and float charging,
starting or shutting down rectifiers, clearing historical alarms, and restarting
the SMU.

Site Maintain Performs USB-based operations such as upgrade, export, and site setup.

User Change LCD login password, user logout.


Management

A.1 Running Information


Table A-2 Running Information menu hierarchy
Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu
Level Menu

Site Unit Basic Information AC Input Power -

DC Output Power -

Total AC Comsuption -

Total DC Generation -

ATS 1 State -
NOTE
This parameter is displayed only when
the DG is connected.

Digital DC Power DC Output Voltage -


Power
Total Load Current -

Current Supply Type -

DC Output DC Output Voltage -


Distribution
Total Load Current -

DC Load n Pwr. Cons -


NOTE
This parameter is displayed only when
Load Shunts is set to 1, 2, 3, 4 or 5.

Shared Load Cons -


NOTE
This parameter is displayed only when
Include Public Load is set to Yes.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 113


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Shared Load Curr -


NOTE
This parameter is displayed only when
Include Public Load is set to Yes.

DC Load n Current -
NOTE
This parameter is displayed only when
Load Shunts is set to 1, 2, 3, 4 or 5.

Load n Last Mnth Elec. -


NOTE
This parameter is displayed only when
Load Shunts is set to 1, 2, 3, 4 or 5.

Load n Real-time Cur -


NOTE
This parameter is displayed only when
Load Shunts is set to 1, 2, 3, 4 or 5.

Last Mth Share Cons -


NOTE
This parameter is displayed only when
Include Public Load is set to Yes.

Load n Last Mnth Cons -


NOTE
This parameter is displayed only when
Load Shunts is set to 1, 2, 3, 4 or 5.

Load Fuse Status -

Load n Power -
NOTE
This parameter is displayed only when
Load Shunts is set to 1, 2, 3, 4 or 5.

LLVD Number -

Shared Load Power -


NOTE
This parameter is displayed only when
Include Public Load is set to Yes.

Total Load Power -

Total Load Energy Consumption -

AC Distribution Phase L1 Voltage -


NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 4-Wire.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 114


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Phase L2 Voltage -
NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 4-Wire.

Phase L3 Voltage -
NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 4-Wire.

Phase L1 Current -
NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 3-Wire or 3-
Phase 4-Wire.

Phase L2 Current -
NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 3-Wire or 3-
Phase 4-Wire.

Phase L3 Current -
NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 3-Wire or 3-
Phase 4-Wire.

AC Voltage -
NOTE
This parameter is displayed only when
AC Mode is set to 1-Phase or 2-Phase
2-Wire.

AC Current -
NOTE
This parameter is displayed only when
AC Mode is set to 1-Phase or 2-Phase
2-Wire.

Line L1-L2 Voltage -


NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 3-Wire.

Line L2-L3 Voltage -


NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 3-Wire.

Line L3-L1 Voltage -


NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 3-Wire.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 115


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

AC Frequency -

Active Power -

Total Energy Consum -

UIM DO Control Status ALM n Control Status -

Controller NetEco Link Mode - -

Rectifier Rectifier Group Total DC Output Current -

Total DC Out Power -

Total AC Input Power -

Rectifier Info Rectifier n DC Outp. Term.


Volt.

DC Output Current

DC Out Power

AC Volotage

Rated Efficiency

Real-time Efficiency

Rectifier Temp.

Cur. Limiting Status

Run Status

PSU Brand

Hardware Version

Software Version

Bar Code

Mains # Mains State - -

Phase L1 Volt - -
NOTE
This parameter is
displayed only when
AC Model is set to 3-
Phase 4-Wire.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 116


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Phase L2 Volt - -
NOTE
This parameter is
displayed only when
AC Model is set to 3-
Phase 4-Wire.

Phase L3 Volt - -
NOTE
This parameter is
displayed only when
AC Model is set to 3-
Phase 4-Wire.

Phase L1 Curr - -
NOTE
This parameter is
displayed only when
AC Model is set to 3-
Phase 3 Wire or 3-
Phase 4-Wire.

Phase L2 Curr - -
NOTE
This parameter is
displayed only when
AC Model is set to 3-
Phase 3 Wire or 3-
Phase 4-Wire.

Phase L3 Curr - -
NOTE
This parameter is
displayed only when
AC Model is set to 3-
Phase 3 Wire or 3-
Phase 4-Wire.

AC Voltage - -
NOTE
This parameter is
displayed only when
AC Model is set to 1-
Phase or 2-Phase 2-
Wire.

AC Curr - -
NOTE
This parameter is
displayed only when
AC Model is set to 1-
Phase or 2-Phase 2-
Wire.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 117


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Line L1-L2 Volt - -


NOTE
This parameter is
displayed only when
AC Model is set to 3-
Phase 3-Wire.

Line L2-L3 Volt - -


NOTE
This parameter is
displayed only when
AC Model is set to 3-
Phase 3-Wire.

Line L3-L1 Volt - -


NOTE
This parameter is
displayed only when
AC Model is set to 3-
Phase 3-Wire.

AC Freq - -

Active Power - -

Phase L1 Factor - -

Phase L2 Factor - -

Phase L3 Factor - -

Grid Quality Grade - -

Total Consumption - -

Total Supply Time - -

Genset # Genset Group Total Energy Yield -

Genset n Total Energy Yield -


NOTE
This parameter is Genset State -
displayed only when
an intelligent DG is Total Runtime -
connected.
Switch Reason -

Phase L1 Voltage -

Phase L2 Voltage -

Phase L3 Voltage -

Phase L1 Current -

Phase L2 Current -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 118


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Phase L3 Current -

Output Power -

AC Frequency -

Phase L1 Factor -

Phase L2 Factor -

Phase L3 Factor -

Genset Batt Volt -

Coolant Temp -

Rotation Speed -

Cabin Temp -

Load Rate -

Switch Rate -

Oil Pressure -

Oil Level -

Last Maint Time -

Hourly Fuel Consum -

Remain Runtime -

Genset n Total Energy Yield -


NOTE
This parameter is Genset State -
displayed only when a
traditional DG is Total Runtime -
connected.
Switch Reason -

Phase L1 Voltage -

Phase L2 Voltage -

Phase L3 Voltage -

Phase L1 Current -

Phase L2 Current -

Phase L3 Current -

Output Power -

AC Frequency -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 119


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Load Rate -

Last Maint Time -

Hourly Fuel Consum -

Remain Runtime -

Battery Battery Group Battery Status -

Total Batt. Current -

Total Rated Cap. -

Remaining Cap. -

Remain Cap. Percent -

Backup Time -

Cur. Limiting Status -

Test Status -

Battery Temp. 1 -

Total Dis Cap. -

Total Dis Times -

Battery Type -

Battery String Battery String n Rated Capacity

Middle Voltage

Battery Test Records - -

Backup Power Info - -

Combined Basic Information Qty of Rectifier -


Cab n
Qty of Rect (On) -

Qty of Rect (Off) -

Qty of Rect (Missing) -

DC Voltage -

Battery Temp -

Cabinet Model -

UIM Current Net Eco Conn. ALM n Control


Status

Controller Current Net Eco Conn. -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 120


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Battery String n Current -

Remaining Cap. -

Remaining Cap. Percent -

Middle Voltage -

Humiture Sensor Ambient Temperature -

Ambient Humidity -

DC Output Distribut. DC Output Voltage -

Total DC Load Curr. -

DC Load n Cons -

DC load n Current -

Nuber of LLVD -

Total Load Power -

Total DC Load Cons. -

DC Load n Power -

AC Distribution Phase L1 Voltage -


NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 4-Wire.

Phase L2 Voltage -
NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 4-Wire.

Phase L3 Voltage -
NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 4-Wire.

Phase L1 Current -
NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 3-Wire or 3-
Phase 4-Wire.

Phase L2 Current -
NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 3-Wire or 3-
Phase 4-Wire.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 121


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Phase L3 Current -
NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 3-Wire or 3-
Phase 4-Wire.

AC Voltage -
NOTE
This parameter is displayed only when
AC Mode is set to 1-Phase or 2-Phase
2-Wire.

AC Current -
NOTE
This parameter is displayed only when
AC Mode is set to 1-Phase or 2-Phase
2-Wire.

Line L1-L2 Voltage -


NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 3-Wire.

Line L2-L3 Voltage -


NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 3-Wire.

Line L3-L1 Voltage -


NOTE
This parameter is displayed only when
AC Mode is set to 3-Phase 3-Wire.

AC Frequency -

Active Power -

Total Energy Consum -

GPS Longitude - -

Latitude - -

Altitude - -

CollectorName - -
NOTE
This parameter is
displayed only when
the GPS is connected.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 122


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Factory Soft Version - -


NOTE
This parameter is
displayed only when
the GPS is connected.

Factory Name - -
NOTE
This parameter is
displayed only when
the GPS is connected.

iDCDU DCDU Group DCDU Number -

Total Load Number -

Unused Load Number -

DCDU Basic Information -

Load n -

Asset Info -

Low Cap Li- Li-ion Battery Group Total Batt. Current -


ion Batt #
Battery Status -
NOTE
This
Battery Temp. N -
parameter is
displayed
only when
Battery
Model is set
to BBS
4840Z.

Li Battery # Li Battery Group Battery Status -


NOTE
This Batt Voltage -
parameter is
displayed Batt Current -
only when
Battery Temperature -
Model is set
to ESM-A, Normal Comm. BMUs -
ESU-A or
ESM-BX.
Total Capacity -

Remain Cap. Percent -

Bakcup Time -

Total Discharge Times -

Total Dis Cap. -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 123


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Test Status -
NOTE
This parameter is displayed only when
Battery Model is set to ESU-A or ESM-
A.

Battery Test Records - -

DTS # DTS Group - -

DTS n Comm Status -

Running Mode -

Main Battery Voltage -

Back Battery Voltage -

Combined Voltage -

Power Supply Mode -

Hardware Version -

Software Version -

DCDB # DCDB Group DCDB Number -

Total Load Number -

Unused Load Number -

DCDB n Basic Information Comm Status

Input Voltage

Total Load Number

Unused Load
Number

Total Output
Current

Total Output Power

DCDB Slot No.

Load n Load n Used

Load n Current

Load n Power

Asset Info Software Version

Hardware Version

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 124


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Comm. Ex. NIM01C3 n Comm State -


Board #
Hardware Version -

Software Version -

COM1 Power Volt -

COM2 Power Volt -

iBOX # iBOX Equip n DIP Switch Address -

Hardware Version -

Software Version -

Communication Status -

RF Software Version -

NIM02D - - -

Efuse Group EFUSE n Basic Information Input Voltage


#
Load n Load n Used

Load n Current

Load n Status

Load n Power

Load n
Consumption

Asset Info Software Version

Hardware Version

EFUSE Name

Temp. Temp. Control Group Indoor Vent Temp. -


Control Info.
Outdoor Amb Temp. -

Fan Group Fan n Speed -

Heater Device Control Status -

Sensor Door Sensor # Door Status -

Water Sensor # Water Status -

Smoke Sensor # Smoke Sensor Status -

Infrared Sensor # IR Sensor Status -

Humiture Sensor # Ambient Temperature -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 125


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Ambient Humidity -

Glass Brk Snsr # Glass Broken Status -

Vibration Sensor # Vibration Sensor Status -

AIM n # AC Frequency - -

Phase L1 Voltage - -

Phase L2 Voltage - -

Phase L3 Voltage - -

Phase L1 Current - -

Phase L2 Current - -

Phase L3 Current - -

Active Power - -

Total Power Factor - -

Phase L1 Pwr. Factor - -

Phase L2 Pwr. Factor - -

Phase L3 Pwr. Factor - -

Active Electricity - -

SoftWare Version - -

Hardware Version - -

BootLoader Version - -

Phase L1 Power - -

Phase L2 Power - -

Phase L3 Power - -

Phase L1 Reactive - -
Power

Phase L2 Reactive - -
Power

Phase L3 Reactive - -
Power

ATS # ATS n Running Mode -

Power Supply Mode -

Work Scenario -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 126


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Software Version -

Hardware Version -

FSU Wireless Public IP - -

Virtual Network IP - -

MIMO MIMO 1 12DC Output Voltage -


Module #
12DC Output Current -

24AC Output Voltage -

24AC Output Current -

Software Version -

Hardware Version -

Historical - - -
Alarm

Performance Total AC Total AC Consumption -


Consumption

Total DC Generation Total DC Generation -

Total Consumption Total Consumption -

Acid Batt Dis. Cap. Acid Batt Dis. Cap. -

Batt Grou1 Dischg - -

Batt Grou2 Dischg - -

BackBatt3 Dis. Cap. - -

Solar Power Supply - -

Li Batt Dis. Cap. - -

Barcode Info Controller Monitor Brd Barcode -


NOTE
Only the PowerSubrack Barcode -
information
about Cabinet Barcode -
connected
components Ext. Board Barcode -
is displayed.
Rectifier n Bar Code -

EFUSE n Barcode -

ATS n Barcode Info -

GMU n GMU Barcode -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 127


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

AIM n Barcode -

Battery Group TCB Barcode -

Comm. Ex. Board NIM01C3 1 Comm Ex Brd


Barcode

NIM02D Barcode Info -

Camera # Camera Group Camera n -


NOTE
Applies Camera n Software Version -
when the
serial port Vendor Type -
camera is
connected. Port number -

Camera # Camera Group Camera n -


NOTE
Applies Camera n Software Version -
when the IP
camera is Vendor Type -
connected.
IP Address -

Mobile Data Connection Status - -


Info
Signal Strength - -

Data Mode - -

IP Address - -

Current SIM Card - -

SIM Card 1 Status - -

SIM Card 1 IMSI - -

SIM Card 1 Number - -

SIM 1 On-day Traffic - -

SIM Card 2 Status - -

SIM Card 2 IMSI - -

SIM Card 2 Number - -

SIM 2 On-day Traffic - -

Other Device iRELAY 1 SIREN-S Ctrl State -


Info
SIREN-L Ctrl State -

iDATA 1 12V DC Volt State -

Hall n Current -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 128


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

DC Voltage -

COM n State -

Port n D n State -

DI n State -

Blade Power n 48V DC Voltage -

48V DC Load Current -

48V Port Current -

System Type -

Software Version -

Hardware Version -

Phase L1 Voltage -

Phase L2 Voltage -

Phase L3 Voltage -

Phase L1 Current -

Phase L2 Current -

Phase L3 Current -

Power Unit n 57V Port DC Voltage -

Power Unit n 57V Port Load Current -

Power Frame Barcode -

Total Consumption -

Total Load Energy Consumption -

iACMETER Input n AC Frequency -

Input n phase L1 V. -

Input n phase L2 V. -

Input n phase L3 V. -

Ch n Ph L1 Current -

Ch n Ph L2 Current -

Ch n Ph L3 Current -

Ch n Active Power -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 129


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Ch n Power Factor -

Ch n Power Consump -

Dry Contact n Statuse -

WIM01C1 Current Net Standard -

DG Comm Ex Board Comm Status -

Hardware Version -

Software Version -

Barcode Info -

Air Conditioner n Consumption Readings -

AC Power Consumption -

Air Condition Runtime -

Running State -

Fuel Tank Remaining Fuel -

Fuel Level -

Total Fuel Consump -

Consump After Refuel -

Total Refueling -

A.2 Setting Wizard


Table A-3 Setting Wizard menu hierarchy
Second-Level Third-Level Menu Default Value Value Range
Menu

Site Unit Battery Vendor Other AGISSON, Coslight,


Dengta, Eltek, EnerSys,
Exide, LEOCH, Narada,
NorthStar, Shoto, Universal

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 130


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second-Level Third-Level Menu Default Value Value Range


Menu

Battery Model 12V VRLA DCB-A, DCB-A1, DCB-B,


DCB-Y, ESU-A, ESM-A,
ESM-BX, FCB-A, FCB-B,
SCB-A, SCB-A1, TCB-A,
TCB-B, TCB-C, 12V VRLA,
2V VRLA, FLOOD, 6-GFM-
X, 6-GFMF, Rebak-F4899T,
12TD-F, SBS-F, M12V-FT,
LPF12-H, 6-GFM-F, 12NDF,
Blue, Red, 6-FMX, 6-XFMJ,
GFM, BBS 4840Z

Mains Qty 1 0 to 2
NOTE
This parameter is
displayed only when DG
Number is set to 2.

Genset Qty 0 0 to 2

Tank Qty 1 0 to 4

Batt Parameters Battery N Connected Yes Yes, No

Single-String Cap. 150 Ah 5-10000

Battery Cable Length 1m 0-100

Batt Cable CS Area 35 mm2 1-1000

Genset Group Configuration Mode Active/Standby Active/Standby, Mutual


Para. Backup

Schedule Mode Cycle Mode Cycle Mode, Tradition


Mode, No Control Mode

Genset n Rated Power 12.5 kW 1.0 to 5000.0


Parameters

Date and Time Time Zone UTC +08:00 Beijing -

Date and Time - -

NTP Enable No Yes, No

NTP Primary IP 127.0.0.1 -


NOTE
This parameter is
displayed only when NTP
Enable is set to Yes.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 131


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second-Level Third-Level Menu Default Value Value Range


Menu

NTP Backup IP 127.0.0.1 -


NOTE
This parameter is
displayed only when NTP
Enable is set to Yes.

NTP Port Nummber 123 1-65535


NOTE
This parameter is
displayed only when NTP
Enable is set to Yes.

NTP Sync. Interval 1 Min 1-1440


NOTE
This parameter is
displayed only when NTP
Enable is set to Yes.

NetEco NetEco Primary IP 192.168.0.10 -


Parameters
NetEco Backup IP 192.168.0.10 -

Site ID - -

Network DHCP Enabled Disable Server, Client, Disable


Parameters
Backplane DHCP Enable Server Server, Client, Disable

Bridge Enabled Disable Disable, Enable

IP Type IPv4 IPv4, IPv6

IP Address 192.168.0.10 -

Subnet Mask 255.255.255.0 -

Default Gateway 192.168.0.1 -

Backplane IP Address 192.168.0.10 -

Backplane Subnet Mask 255.255.255.0 -

Backplane Default GW 192.168.0.1 -

IPv4 DSCP 46 0 to 63

VLAN Enable No Yes, No

VLAN ID 1 0 to 4094

VLAN Priority 5 0 to 7

Dial Parameters Carrier Operator Automatic Automatic, Others

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 132


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second-Level Third-Level Menu Default Value Value Range


Menu

SIMn Acc Point Name - A maximum of 28


NOTE characters, including
This parameter is lowercase English letters
displayed only when (a-z), uppercase English
Carrier Operator is set to letters (A-Z), digits (0-9),
Others.
and special characters
SIMn Access Point No *99# (@_#*-.).
NOTE
This parameter is
displayed only when
Carrier Operator is set to
Others.

SIMn User Name 3GNET


NOTE
This parameter is
displayed only when
Carrier Operator is set to
Others.

SIMn User Password - A maximum of 27


NOTE characters, including
This parameter is lowercase English letters
displayed only when (a-z), uppercase English
Carrier Operator is set to letters (A-Z), digits (0-9),
Others.
and special characters
(@_#*-.).
It is recommended that the
password contain at least
two types of characters
and the length exceed six
characters.

Rect Addr Setting Rect. Address Setting No Yes, No

n. Rectifire Address - 1~60


NOTE
This parameter is
displayed only when Rect.
Address Setting is set to
Yes.

Saving Settings Yes Yes


NOTE
This parameter is
displayed only when Rect.
Address Setting is set to
Yes.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 133


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

A.3 Parameters Settings


Table A-4 Parameters settings menu hierarchy
Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range
Level Menu Menu Menu
Menu

Site Unit User n User Cst Name - - -

User Cst ID - 0 0-65535

Enb Load - Disable Enable, Disable


Discon

Load Discon - Voltage Mode Voltage Mode,


Mode Power Mode,
Capacity Mode,
Time Mode

Load Discon - 44.0 V 36.0-56.0


Volt

Load Recon - 57.5 V 37.0-58.0


Voltage

Load Discon - 5.00 kwh 0.00-10000.00


Cons.

Load Discon - 15 % 0-99


Cap

Load Discon - 360 min 0-6000


Time

Enb HTD - Disable Enable, Disable

ETD Temp - 65.0 degC 25.0-80.0

Enb PD Disable Enable, Disable

PD Start Time 00:00:00


n

PD Duration n 0 min 0-1440

Exempt Period Disable Enable, Disable


NO BK

Exempt Start 00:00:00


Time

Exempt 0 min 0-1440


Duraion n

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 134


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Basic Site ID - - -
Parameters
Mains Qty - 1 0 to 2
NOTE
This parameter
is displayed
only when
Genset Qty is
set to 2.

Genset Qty - 0 0 to 2

Tank Qty - 1 0 to 4

Single/Parallel - Standalone Parallel System,


Standalone

Master/Slave - Slave Master/Slave


Flag

Parallel ID - - -

Local Cabinet - 1 1 to 16
No.

Digital Digital Turn-on Power - No Yes, No


Power Power Limit

AC Input Breaker Rated - 1000 A 1-10000


Distribution Curr

Derating Coef - 0.8 0.1-1.0

AC Voltage - Voltage Mode Voltage Mode,


Mode Percentage Mode

AC Phase OV - 280 V 60-300


Thres.

AC Phase UV - 180 V 60-300


Thres.

AC Phase OV - 130 % 110-200


Thres.

AC Phase UV - 80 % 1-90
Thres.

Rated AC freq - 50 Hz 40~70

Over AC Freq - 110 % 105~130

Under AC Freq - 90 % 70~95

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 135


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

DC Output Basic LLVD n Enable Enable, Disable


Distribut. Parameters Enablde

LLVD n Mode Voltage Mode Voltage Mode,


NOTE Capacity Mode,
This Time Mode
parameter is
displayed
only when
LLVD n
Enablde is
set to Enable.

LLVD n 280 V 60-300


Voltage
NOTE
This
parameter is
displayed
only when
LLVD n
Enablde is
set to Enable.

LLVD n 180 V 60-300


Reconnection
Voltage
NOTE
This
parameter is
displayed
only when
LLVD n
Enablde is
set to Enable.

LLVD n 25 % 0-99
Capacity

LLVD n Time 180 min 0-1000

LLVD n Plan Disable Enable, Disable


Disconnect
Enabled

LLVD n Plan 00:00:00 -


n
Disconnecct
Start Time

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 136


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

LLVD n Plan 0 min 0-1440


n
Disconnecct
Duration

LLVD n No Disable Enable, Disable


Backup on
Exempt
Period

LLVD n 00:00:00 -
Exempt
Peruid n Start
Time

LLVD n 0 min 0-1440


Exempt
Peruid n
Duration

LLVD n PD Disable Enable, Disable


Enb

LLVD n PD 00:00:00 -
Start Time

LLVD n PD 0 min 0-1440


Duration

LLVD n Disable Enable, Disable


Exempt No
Bk

LLVD n 00:00:00 -
Exempt
Time

LLVD n ED 0 min 0-1440

LLVD n High Disable Enable, Disable


Temp
Disconnect
Enabled

LLVD n 65.0 degC 25.0-80.0


Disconnect
Temperature

LLVD n HTD Disable Enable, Disable


Enb

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 137


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

LLVD n HTD 65.0 degC 25.0-80.0


Temp

DC Over Volt 58.0 V 53.5-60.0

DC Under 45.0 V 36.0-57.0


Volt

Ultre Over 59.0 V 53.0-60.0


Volt

Ultre Under 44.0 V 36.0-56.0


Volt

Load Over - - -
Point
Parameters

Branch Usage Branch n Customized Customized Load,


Confit Usage Cfg Load BLVD Load, LLVD n
Parameters n Load, Other, Power
Cascading Port, DC
D.G., Solar Energy,
Lithium Battery,
Lead-acid Battery

LOAD-iCBD n Customized 125 A 3-125


Capacity

Enb HTD Disable Enable, Disable

HTD Temp 65.0 degC 25.0-80.0

User Config User 1 None, User 1-User


10

Load Type None None, Type 1-Type


20

Enb PD Disable Enable, Disable

PD Start 00:00:00
Time n

PD Duration 0 min 0-1440

Exempt Disable Enable, Disable


Period No Bk

Exempt Start 00:00:00


Time n

Exempt 0 min 0-1440


Duration

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 138


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

BATT-iCBD n Customized 125 A 3-125


Capacity

Rectifier Rectifier Enable Lock Disable Enable, Disable


Group

DC DC Power Turn-on Power - Yes Yes, No


Power n Limit

iMix Enabled - Disable Enable, Disable


NOTE
This parameter
is displayed
only when
Hybrid
Scenario is set
to YES.

AC Input AC Voltage - Voltage Mode Percentage Mode,


Distribution Mode Voltage Mode

AC Phase OV - 280 V 60 to 300


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Voltage Mode
and AC Model
is 1-Phase, 2-
Phase 2-Wire
or 3-Phase 4-
Wire.

AC Phase UV - 180 V 60 to 300


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Voltage Mode
and AC Model
is 1-Phase, 2-
Phase 2-Wire
or 3-Phase 4-
Wire.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 139


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

AC Phase OV - 130% 110-200


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Percentage
Mode and AC
Model is 1-
Phase, 2-
Phase 2-Wire
or 3-Phase 4-
Wire.

AC Phase UV - 80% 1-90


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Percentage
Mode and AC
Model is 1-
Phase, 2-
Phase 2-Wire
or 3-Phase 4-
Wire.

AC Line OV - 280 V 60 to 600


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Voltage Mode
and AC Model
is 3-Phase 3-
Wire.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 140


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

AC Line UV - 180 V 60 to 600


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Voltage Mode
and AC Model
is 3-Phase 3-
Wire.

Rated Line - 220 V 60-600


Volt
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Percentage
Mode and AC
Model is 3-
Phase 3-Wire.

AC Line OV - 130% 110-200


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Percentage
Mode and AC
Model is 3-
Phase 3-Wire.

AC Line UV - 80% 1-90


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Percentage
Mode and AC
Model is 3-
Phase 3-Wire.

Rated AC - 50 Hz 40 to 70
Frequency

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 141


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Over AC Freq - 110% 105 to 130

Uder AC Freq - 90% 70 to 95

DC Output LLVD n - Enable Enable, Disable


Distribution Enabled

LLVD n Mode - Voltage Mode Voltage Mode,


NOTE Capacity Mode,
This parameter Time Mode
is displayed
only when
LLVD n
Enabled is set
to Enable.

LLVD n - 44.0 V 36.0 to 56.0


Voltage
NOTE
This parameter
is displayed
only when
LLVD n
Enabled is set
to Enable.

LLVD n Recon - 51.5 V 37.0 to 58.0


Volt
NOTE
This parameter
is displayed
only when
LLVD n
Enabled is set
to Enable.

LLVDn - 15% 0 to 99
Capacity
NOTE
This parameter
is displayed
only when
LLVD n Mode
is set to
Capacity
Mode.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 142


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

LLVDn Time - 360 min 5 to 1000


NOTE
This parameter
is displayed
only when
LLVD n Mode
is set to Time
Mode.

Load Shunts - 0 0-5

LLVD PD Enb - Disable Enable, Disable

LLVD PD Time - 23:00:00 00:00:00-23:00:00


NOTE
This parameter
is displayed
only when
LLVD PD Enb
is set to
Enable.

LLVD PD - 480 min 1 to 1439


Duration
NOTE
This parameter
is displayed
only when
LLVD PD Enb
is set to
Enable.

LLVD HTD Enb - Disable Enable, Disable

LLVD HTD - 65.0 degC 25.0 to 80.0


Temp
NOTE
This parameter
is displayed
only when
LLVD HTD Enb
is set to
Enable.

LLVD Delay - 60 s 5 to 90
Time
NOTE
This parameter
is displayed
only when
LLVD Enabled
is set to
Enable.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 143


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

DC Over - 58.0 V 53.0 to 60.0


Voltage

DC Under Volt - 45.0 V 36.0 to 57.0

Ultra Over - 59.0 V 53.0 to 60.0


Volt

Ultra Under - 44.0 V 36.0 to 57.0


Volt

UIM DG 1 - - ALM2 ALM1 to ALM8,


NOTE ON/OFF Ctrl None
This Do
parame
ter DG 1 Auxi - - None ALM1 to ALM8,
varies Preheat DO None
with the
system DG 1 Run. - - DIN4 DIN1 to DIN6, None
type. Status Det.

DG 2 - - None ALM1 to ALM


ON/OFF Ctrl 8, None
Do

DG 2 Auxi - - None ALM1 to ALM8,


Preheat DO None

DG 2 Run. - - None DIN1 to DIN6, None


Status Det.

ATS 1 Run - - None DIN1 to DIN6, None


Detection

ATS 2 Run - - None DIN1 to DIN6, None


Detection

ATS DI - - Close Open, Close


Cond. AC
Fail

Dry Contact - - DIN1 DIN1 to DIN6, None


Open AC

DIN1/ALM1 - - ALM ALM/DIN


Config

DIN2/ALM2 - - ALM ALM/DIN


Config

DIN3/ALM3 - - ALM ALM/DIN


Config

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 144


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Controll Buzzer - - No Yes, No


er Enable

Buzzer Alm. - - 10 min 1 to 100


Duration
NOTE
This
parameter is
displayed
only when
Buzzer
Enable is
set to Yes.

IP Network - - High High, Medium, Low


Priority

Inband Net - - Medium High, Medium, Low


Priority

Wireless Net - - Low High, Medium, Low


Priority

Run. Time - - 60 min 1 to 1440


Sw. Net.

Traffic Fluct - - 50 MB/Day 0 to 10000


Thres.

Heartbeat - - 120s 10 to 180


Duration

IP Net. - - 5 min 5 to 1440


Timeout

Inband Net. - - 5 min 5 to 1440


Timeout

Wire. Net. - - 30 min 30 to 1440


Timeout

North MS - - Enable Enable, Disable


Config

Rectifier Rectifier Default - 53.5 V 48.0 to 58.0


Group Output Volt NOTE
The default output
voltage of rectifiers
after the
communication with
the monitoring unit
fails.

OV Prot.Thres. - 59.5 V 56.0 to 60.5

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 145


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Sequential St. - 0s 0 to 20
Int NOTE
Interval for starting
the rectifiers
sequentially.

High Rect. - 5% 0 to 150


Capacity

Low Rect. - 75% 0 to 150


Capacity

Max. Limited - 121% 10 to 121


Current NOTE
Percentage of the
expected maximum
rectifier output
current to the rated
rectifier output
current.
For example, if a
power system is
configured with three
50 A rectifiers, and
you need an output
current of 120 A,
then set this
parameter to 80%,
which is obtained
from 120 A/(50 A x
3).

WALK-IN - No Yes, No
Enable

WALK-IN Time - 8s 8 to 200


NOTE
This parameter
is displayed
only when
WALK-IN
Enable is set
to Yes.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 146


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Energy Hibernation - NO Yes, No


Saving Enable NOTE
● No: Hibernation
is disabled.
● Yes: The
monitoring unit
hibernates
rectifiers when
the hibernation
condition is met.

Hibernation - Intelligent Intelligent Mode,


Mode Mode High Efficiency
NOTE Mode, Time Mode
This parameter NOTE
is displayed
● Time Mode:
only when
Rectifiers with
Hibernation
shorter runtime
Enable is set
take precedence
to Yes.
for work.
● High Efficiency
Mode: Rectifiers
with higher real-
time efficiency
take precedence
for work.
● Intelligent Mode:
The monitoring
unit instructs
rectifiers to
hibernate based
on the rectifier
runtime and real-
time efficiency.

Hiber. Without - No Yes, No


Batt. NOTE
NOTE Indicates whether
This parameter hibernation is
is displayed enabled when
only when batteries are not
Hibernation connected.
Enable is set NOTE
to Yes. If you enable
hibernation when
batteries are not
connected to the
power system, the
loads may experience
power failures.
Exercise caution
when using this
function.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 147


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Min. Rdnt. - 0.20 0.05 to 1.00


Coef. NOTE
NOTE Ratio of the
This parameter minimum redundant
is displayed current to the rated
only when rectifier current.
Hibernation For example, if the
Enable is set rated rectifier current
to Yes. is 50 A and a
redundant current of
10 A is required, set
Min. Redundant
Coefficient to 0.2
(10 A/50 A = 0.2).

Min. Working - 2 1 to 100


Rects. NOTE
NOTE Minimum number of
This parameter working rectifiers
is displayed allowed after
only when hibernation is
Hibernation enabled.
Enable is set
to Yes.

Best Efficiency - 55% 10 to 100


Pt. NOTE
NOTE Percentage of the
This parameter rectifier loading
is displayed capacity to the rated
only when capacity, at which
Hibernation the rectifier reaches
Enable is set maximum efficiency.
to Yes.

Hiber. Stop - 72.0 h 0.5 to 168.0


Duration NOTE
NOTE All rectifiers stop
This parameter hibernation if the
is displayed power system
only when experiences an
Hibernation exception. After the
Enable is set power system
to Yes. recovers, rectifiers
attempt to hibernate
again when the time
specified by
Hibernation Stop
Duration has
elapsed.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 148


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Circulation - 7 Day 1 to 365


Period NOTE
NOTE Period for alternating
This parameter hibernating rectifiers
is displayed with working
only when rectifiers. When the
Hibernation period expires, the
Enable is set monitoring unit
to Yes. starts all rectifiers.
When the rectifiers
have worked for 2
hours, the
monitoring unit
instructs some of
them to hibernate
again.

Phase Balance - Disable Relative Balance,


NOTE Absolute Balance,
This parameter Disable
is displayed NOTE
only when If the configuration
Hibernation of rectifiers meets
Enable is set the three-phase
to Yes. balance requirement
and intelligent
rectifier hibernation
is enabled in a three-
phase power system,
the rectifiers
corresponding to the
three phases try to
hibernate.
● Absolute
Balance: The
same quantity of
rectifiers must
correspond to any
two phases.
● Relative Balance:
The difference in
quantity between
the working
rectifiers
corresponding to
any two phases
must be less than
or equal to 1.

Rectifier n PSU Brand - - -, 0 to 9, a-z, A-Z

Staggeri Stag Elec - - Disable Enable, Disable


ng Elec Enb
Para

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 149


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Schedule - - Debug Debug Staggering,


Mode Staggering Fixed Staggering
NOTE
This
parameter is
displayed
only when
Stag Elec
Enb is set to
Enable.

Battery Disc - - Battery Life Battery Life Priority,


Mode Priority Staggering Priority
NOTE
This
parameter is
displayed
only when
Stag Elec
Enb is set to
Enable.

Max Disc - - 2 1 to 10
Times Per
Day
NOTE
This
parameter is
displayed
only when
Stag Elec
Enb is set to
Enable.

Max Disc - - 10% 5 to 50


Cap Per Day
NOTE
This
parameter is
displayed
only when
Stag Elec
Enb is set to
Enable.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 150


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Star Time - - 2000-01-01 -


NOTE 00:00:00
This
parameter is
displayed
only when
Schedule
Mode is set
to Debug
Staggering.

End Time - - 2000-01-01 -


NOTE 00:00:00
This
parameter is
displayed
only when
Schedule
Mode is set
to Debug
Staggering.

Batt Abn - - Disable Enable, Disable


Disable Stag
NOTE
This
parameter is
displayed
only when
Stag Elec
Enb is set to
Enable.

End Volt of - - 48.0 V 45.0 to 53.0


Stag Elec
NOTE
This
parameter is
displayed
only when
Batt Abn
Disable Sta
is set to
Enable.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 151


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

End SOH of - - 60% 0 to 90


Stag Elec
NOTE
This
parameter is
displayed
only when
Batt Abn
Disable Sta
is set to
Enable.

Time of - - 3 1 to 20
Disable Stag
NOTE
This
parameter is
displayed
only when
Batt Abn
Disable Sta
is set to
Enable.

Duration of - - 15 min 1 to 600


Disable Stag
NOTE
This
parameter is
displayed
only when
Batt Abn
Disable Sta
is set to
Enable.

AC Peak AC Mains Peak - No Yes, No


Shaving Parameters Shave Enb

Cap for Peak - 200.0 kW 1.0 to 999.0


Shave
NOTE
This parameter
is displayed
only when
Mains Peak
Shave Enb is
set to YES.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 152


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Breaker Rated - 1000 A 1 to 10000


Curr
NOTE
This parameter
is displayed
only when
Mains Peak
Shave Enb is
set to YES.

Derating Coef - 0.8 0.1 to 1.0


NOTE
This parameter
is displayed
only when
Mains Peak
Shave Enb is
set to YES.

Peak Rated Phase - 220 V 60 to 300


Shaving Volt
Para
Parallel No No, Yes
Reused Sys.

Peak Shaving - 30% 15 to 90


SOC

Peak Shaving - 15% 15 to 90


SOC (Mix.)

Power-On - 20% 10 to 85
Hysteresis for
LLVD in Peak
Shaving

Batt Backup - Yes Yes, No


Enable

Allow A/C - No Yes, No


Shutdown in
Peak Shaving

LLVD n for - Yes Yes, No


Peak Shaving
Enable

iDCDU iDCDU n Basic Load Setting All Branch All Branch, Single
Parameters Mode Branch

Load Discon Voltege Mode Voltege Mode, Time


Mode Mode, Capacity
Mode

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 153


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Load Off Load Discon Yes Yes, No


Enable Enb

Load PD Enb No Yes, No

Load On/Off Load Discon 44.0 V 36.0 to 56.0


Para Voltage

Load Recon 51.5 V 37.0 to 58.0


Voltage

Load PD 23:00:00 -
Time

Load PD 480 min 1 to 1440


Duration

Load Discon 15 % 0 to 99
Cap

Load Discon 6000 min 0 to 6000


Time

Load overcur Over Current 30.0 3.0 to 30.0


Thres

Consuption - - -
Config

Load Type Load n Type Nome Nome, Type1 -


Config Type20

Mains # AC Mode - - 3-Phase 4-Wire 2-Phase 2-Wire, 1-


Phase, 3-Phase 4-
Wire, 3-Phase 3-
Wire

AC Volt - - Voltage Mode Voltage Mode,


Mode Percentage Mode

Main Line - - 286 V 242 to 760


OV Thres.
NOTE
This
parameter is
available
only when
AC Volt
Mode is
Voltage
Mode and
AC Model is
3-Phase 3-
Wire.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 154


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Main Line - - 176 V 2 to 342


UV Thres.
NOTE
This
parameter is
available
only when
AC Volt
Mode is
Voltage
Mode and
AC Model is
3-Phase 3-
Wire.

Rated AC - - 220 V 104 to 520


Line Volt
NOTE
This
parameter is
available
only when
AC Volt
Mode is
Percentage
Mode and
AC Model is
3-Phase 3-
Wire.

Main Line - - 130% 110 to 200


OV Thres.
NOTE
This
parameter is
available
only when
AC Volt
Mode is
Percentage
Mode and
AC Model is
3-Phase 3-
Wire.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 155


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Main Line - - 80% 1 to 90


UV Thres.
NOTE
This
parameter is
available
only when
AC Volt
Mode is
Percentage
Mode and
AC Model is
3-Phase 3-
Wire.

Main Phase - - 286 V 242 to 440


OV Thres.
NOTE
This
parameter is
displayed
only when
AC Volt
Mode is
Voltage
Mode and
AC Model is
1 Phase, 2-
Phase 2-
Wire or 3-
Phase 4-
Wire.

Main Phase - - 176V 2 to 198


UV Thres.
NOTE
This
parameter is
displayed
only when
AC Volt
Mode is
Voltage
Mode and
AC Model is
1 Phase, 2-
Phase 2-
Wire or 3-
Phase 4-
Wire.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 156


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Rated AC - - 220 V 60 to 300


Volt
NOTE
This
parameter is
displayed
only when
AC Volt
Mode is
Percentage
Mode and
AC Model is
1 Phase, 2-
Phase 2-
Wire or 3-
Phase 4-
Wire.

Main Phase - - 130% 110 to 200


OV Thres.
NOTE
This
parameter is
displayed
only when
AC Volt
Mode is
Percentage
Mode and
AC Model is
1 Phase, 2-
Phase 2-
Wire or 3-
Phase 4-
Wire.

Main Phase - - 80% 1 to 90


UV Thres.
NOTE
This
parameter is
displayed
only when
AC Volt
Mode is
Percentage
Mode and
AC Model is
1 Phase, 2-
Phase 2-
Wire or 3-
Phase 4-
Wire.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 157


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

AC High - - 66Hz 40 to 70
Freq Thres.

AC Low Freq - - 45Hz 40 to70


Thres.

Power Limit - - No Yes, No


Enb

Mains - - 5000.0 kW 2.0 to 5000.0


Maximum
Power
NOTE
This
parameter is
displayed
only when
Power
Limit Enb is
set to
Enable.

Power - - 100.0% 0.0~100.0


Limitation
Rated
NOTE
This
parameter is
displayed
only when
Power
Limit Enb is
set to
Enable.

Imbalance - - 100.0% 10.0 to 150.0


Ratio
NOTE
This
parameter is
displayed
only when
Power
Limit Enb is
set to
Enable.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 158


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

PSU Conv - - 95.0% 90.0 to 98.0


Eff
NOTE
This
parameter is
displayed
only when
Power
Limit Enb is
set to
Enable.

UVT Point - - 39% 39 to 100

OVT Point - - 140% 100 to 159

Genset Genset DOD to Start - 60% 5 to 90


Group NOTE
● The DG is started
when the battery
DOD reaches the
value of this
parameter. This
ensures that the
battery capacity
stays above the
preset DOD,
thereby ensuring
the battery life
and backup time.
● The voltage when
batteries
discharge to the
DOD varies with
the environment
and battery
conditions.

Min Chg Time - 0 min 0 to 2880


NOTE
Minimum DG
runtime.

Max Chg Time - 1440 min 60 to 2880


NOTE
Maximum DG
runtime.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 159


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

On/Off Judge - 4 min 3 to 30


Time NOTE
Minimum interval
between DG
shutdown and
startup.
DG ON Judge Time
is the prerequisite for
DG soft-start. This
avoids fast startup
and shutdown within
a short period, which
will affect the DG
service life.

HT Start Enb - Disable Enable, Disable


NOTE
Indicates whether to
enable DG startup
upon high
temperature.

HT Start Temp - 45 degC 30 to 65


NOTE NOTE
This parameter The DG is started
is displayed when the onsite
only when HT ambient temperature
Start Enb is exceeds the value of
set to Enable. this parameter.

HT Stop Temp - 29 degC 25 to 60


NOTE NOTE
This parameter The DG is shut down
is displayed when the onsite
only when HT ambient temperature
Start Enb is is below the value of
set to Enable. this parameter.

Min HT - 480 min 0 to 1440


Runtime NOTE
NOTE Minimum DG
This parameter runtime after the DG
is displayed is started upon high
only when HT temperature.
Start Enb is
set to Enable.

LT Start Enb - Disable Enable, Disable


NOTE
Indicates whether to
enable DG startup
upon low
temperature.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 160


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

LT Start Temp - 5 degC -10 to +15


NOTE NOTE
This parameter The DG is started
is displayed when the onsite
only when LT ambient temperature
Start Enb is is below the value of
set to Enable. this parameter.

LT Stop Temp - 20 degC 0 to 25


NOTE NOTE
This parameter The DG is shut down
is displayed when the onsite
only when LT ambient temperature
Start Enb is exceeds the value of
set to Enable. this parameter.

Min. LT - 480 min 0 to 1440


Runtime NOTE
NOTE Minimum DG
This parameter runtime after the DG
is displayed is started upon low
only when LT temperature.
Start Enb is
set to Enable.

Time to Stop - Disable Enable, Disable


Enabled NOTE
Indicates whether to
enable scheduled DG
startup and
shutdown.
To prevent the
disturbance of DG
operation, ensure
that the DG is used
after the battery is
fully charged.

Stop Time - 22:00:00 HH:MM:SS


NOTE NOTE
This parameter Time for scheduled
is displayed DG shutdown.
only when
Time to Stop
Enabled is set
to Enable.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 161


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Runtime to - 360 min 0 to 720


Stop NOTE
NOTE Interval between
This parameter scheduled DG startup
is displayed and scheduled DG
only when shutdown.
Time to Stop For example, if
Enabled is set Runtime Before
to Enable. Timed DG Stop is 6
h and DG Off Time
is 22 h, DG On Time
is 16:00.

Night Mode Enable Enable, Disable


End

Night Finish 16:00:00 HH:MM:SS


Time

Night DG Start 45 V 36.0 to 51.0


Volt.

Soft Start - 1 min 1 to 5


Time NOTE
This parameter is
related to the DG
startup time and stop
time. The DG soft-
start time is equal to
or greater than the
DG startup time. You
can adjust the
parameter as
required.

Disch Time - Disable Enable, Disable


Protect NOTE
Indicates whether to
enable discharge
time protection to
prevent excessive
battery discharge.

Max Discharge - 1440 min 0 to 2880


Time NOTE
NOTE The DG is started
This parameter when the battery
is displayed discharge time
only when exceeds the value of
Disch Tiem this parameter.
Protect is set
to Enable.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 162


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

TMDS Enabled - Enable Enable, Disable


NOTE
Enables or disables
scheduled D.G.
maintenance.

TMDS Interval - 7 Day 1 to 30


NOTE NOTE
This parameter Indicates the time
is displayed interval between two
only when adjacent times of
TMDS Enable scheduled D.G.
is set to maintenance.
Enable.

TMDS - 15 min 10 to 300


Duration NOTE
NOTE Indicates the D.G.
This parameter runtime during each
is displayed time of scheduled
only when D.G. maintenance.
TMDS Enable
is set to
Enable.

Start by DI - Enable Enable, Disable


Enabled

Preheat - Disable Enable, Disable


Enabled NOTE
Indicates whether the
low-temperature
emergency power
backup function is
started when the
preset conditions are
met.

DOD Diff for - 10% 0 to 100


Preheat NOTE
NOTE The DG preheating
This parameter function is started
is displayed when the battery
only when DOD reaches the
Preheat value of this
Enabled is set parameter.
to Enable.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 163


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Preheat Temp - -5 degC -25 to +10


NOTE NOTE
This parameter The DG preheating
is displayed function is started
only when when the
Preheat temperature of water
Enabled is set in the DG radiator
to Enable. falls below the value
of this parameter.

RBC for LTE - Disable Enable, Disable


Enb NOTE
Indicates whether the
low-temperature
emergency power
backup function is
started when the
preset conditions are
met.

Temp for LTE - -5 degC -25 to -5


NOTE NOTE
This parameter The low-temperature
is displayed emergency power
only when RBC backup function is
for LTE Enb is started when the
set to Enable. ambient temperature
of the DG falls below
the value of this
parameter.

Start by Volt - Disable Enable, Disable


Enb NOTE
Indicates whether to
enable the
monitoring unit to
start the DG based
on battery voltage.

Voltage to - 47.5 V 36.0 to 51.0


Start NOTE
NOTE The DG is started
This parameter when the battery
is displayed voltage reaches the
only when value of this
Start by Volt parameter.
Enb is set to
Enable.

Imbalance - 100.0% 10.0 to 150.0


Rate NOTE
Imbalance between
the three phases of
the DG.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 164


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Configuration - Active/Standby Active/Standby,


Mode Mutual Backup

Schedule - Cycle Mode Cycle Mode,


Mode Tradition Mode, No
Control Mode
NOTE
DG startup/shutdown
control logic.
● No Control Mode:
The DG startup or
shut down is not
controlled.
● Tradition Mode:
The DG is started
when the mains
power fails and is
shut down when
the mains power
is normal.
● Cycle Mode:
Execute the DG
startup/shutdown
control logic in
cyclic mode.

Backup Genset - Disable Enable, Disable


Enb

HBT Start Enb - Disable Enable, Disable

HBT Start - 45 degC 30 to 65


Temp
NOTE
This parameter
is displayed
only when
HBT Start Enb
is set to
Enable.

HBT Stop - 29 degC 25 to 60


Temp
NOTE
This parameter
is displayed
only when
HBT Start Enb
is set to
Enable.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 165


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

BMin HT - 480 min 0 to 1440


Runtime
NOTE
This parameter
is displayed
only when
HBT Start Enb
is set to
Enable.

LBT Start Enb - Disable Enable, Disable

LBT Start - 5 degC -10 to +15


Temp
NOTE
This parameter
is displayed
only when LBT
Start Enb is
set to Enable.

LBT Stop Temp - 20 degC 0 to 25


NOTE
This parameter
is displayed
only when LBT
Start Enb is
set to Enable.

BMin LT - 480 min 0 to 1440


Runtime
NOTE
This parameter
is displayed
only when LBT
Start Enb is
set to Enable.

Low Load Stop - Disable Enable, Disable


Enb
NOTE
This parameter
is displayed
only when the
DG expansion
board of V110
or a later
version is
connected and
the Schedule
Mode is set to
Cycle Mode.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 166


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Solar Enb - Disable Enable, Disable


NOTE
This parameter
is displayed
only when the
SSU is
connected.

Genset n Rated Power - 12.5 kW 1.0 to 5000.0


NOTE NOTE
This Rated output power
parameter is of a single DG.
displayed
only when Power Limit - 80.0% 0.0 to 100.0
an Rate NOTE
intelligent Load rate of the DG
DG is with optimal fuel
connected. consumption.

Rated Phase - 230V 60 to 300


Volt

Rated Current - 22A 1 to 10000

Rated - 50Hz 45 to 65
Frequency

Rated Speed - 1500 r/min 100 to 4000

Over Voltage - 120% 110 to 200

Under Voltage - 80% 0 to 90

Over Freq - 110% 96 to 150

Under Freq - 94.0 % 85.0 to 108.0

Volt Unbal - 10% 1 to 200


Rate

Curr Unbal - 70% 1 to 200


Rate

Batt Under - 10.0V 8.0 to 36.0


Volt

Overload Rate - 115% 0 to 200

SC Curr Rate - 200% 100 to 500

Run Hour for - 9999h 0 to 10000


Maint

Days for Maint - 500h 0 to 30000

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 167


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Run Hour lst - 20h 0 to 1000


Maint

Oil Under - 20% 0 to 100


Level

Press Sensor - 0.0 Kpa 0.0 to 100.0


UL

Press Sensor - -10.0 Kpa -100.0 to 0.0


LL

AirIn Over - -4.0 Kpa -100.0 to 100.0


Pressure

AC Mode - 3Ph4Wire Single Phase, D-live


Lines, 3Ph4Wire

UV to Trip - 87% 70 to 100

OV to Trip - 125% 100 to 140

Manufacturer - - -

Brand - - -

Installation - 2010-01-01 YYYY-MM-DD


Time

Genset n Rated Power - 12.5 kW 1.0 to 5000.0


NOTE NOTE
This Rated output power
parameter is of a single DG.
displayed
only when a Power Limit - 80.0% 0.0 to 100.0
traditional Rate NOTE
DG is Load rate of the DG
connected. with optimal fuel
consumption.

Rated Phase - 230V 60 to 300


Volt

Rated - 50Hz 45 to 65
Frequency

Over Voltage - 120% 110 to 200

Under Voltage - 80% 0 to 90

Over Freq - 110% 96 to 150

Under Freq - 94% 85 to 108

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 168


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Run Hour for - 9999h 0 to 10000


Maint

Days for Maint - 500h 0 to 30000

AC Mode - 3Ph4Wire Single Phase, D-live


Lines, 3Ph4Wire

UV to Trip - 87% 70 to 100

OV to Trip - 125% 100 to 140

Manufacturer - - -

Brand - - -

Installation - 2010-01-01 YYYY-MM-DD


Time

GPS Longitude - - - -

Latitude - - - -

Altitude - - 0m -500 to +10000

Battery Basic Battery N - Yes Yes, No


Parameters Connected

Single-String - 150 Ah 5 to 10000


Cap.

Float Charge - 53.5 V 42.0 to 58.0


Voltage NOTE
When temperature
compensation is
effective, the valid
voltage range is
51.5–55.5 V.

Boost Charge - 56.4 V 42.0 to 58.0


Voltage NOTE
Charge voltage at
which lead-acid
batteries are being
charged in equalized
mode.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 169


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Charge Limit - 0.15 C10 0.05 to 0.50


Coef. NOTE
NOTE Battery charge
This parameter current limit
is not
displayed for
the fast charge
battery (FCB).
The
monitoring
unit
automatically
adjusts the
parameter
based on the
battery
charging status
and the
ambient
temperature.

Intelligent - Disable Disable, Enable


Dormancy NOTE
Indicates whether to
enable intelligent
battery hibernation
management.

Battery Cable - 1m 0 to 100


Length

Batt Cable CS - 35 mm2 1 to 1000


Area

SOC/SOH - Backup Scene Backup Scene, Cyclic


Calcu Scene Scene

Attenuation - 0.80 0.00 to 1.00


Coef

Block Voltage - 2V 2 V, 12 V

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 170


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Temp. TC Coefficient - 80 mV/degC 0 to 150


Comp. Para. NOTE
This parameter is: For
48 V battery string,
the amplitude of the
battery float charge
voltage that needs to
be adjusted for each
change of 1°C. Set
this parameter based
on the actual
specifications of the
battery.
For example, if the
temperature
compensation
coefficient of each 2
V battery is 3.33 mV/
degC and each 48 V
battery string
comprises 24 2 V
batteries, then set
this parameter to 80
mV/degC, which is
calculated as follows:
3.33 x 24 = 80.

Nominal - 25 degC 5 to 45
Temperature NOTE
This default
value varies in
accordance with
the battery
performance. 35
degC is set by
default for the
TCBs.

TC Upper - 45 degC 40 to 45
Thres.

TC Lower - 5 degC 0 to 25
Thres.

BLVD BLVD General - Enable Enable, Disable


Parameters Discon.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 171


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

BLVD - Voltage Mode Voltage Mode,


Disconnect Capacity Mode,
Mode Time Mode
NOTE
This parameter
is displayed
only when
BLVD General
Discon. is set
to Enable.

BLVD LVD - 43.2 V 36.0 to 56.0


Voltage NOTE
NOTE If the battery voltage
This parameter is below the value of
is displayed this parameter, the
only when BLVD route is
BLVD General disconnected.
Discon. is set The value of BLVD
to Enable. Voltage must be
lower than the value
of BLVD Connection
Voltage.

BLVD Con. - 51.5 V 37.0 to 58.0


Volt. NOTE
NOTE If the system voltage
This parameter exceeds the value of
is displayed this parameter, the
only when BLVD route is
BLVD General connected.
Discon. is set The value of BLVD
to Enable. Connection Voltage
must be higher than
the value of BLVD
Voltage.

BLVD Low - 5% 0 to 99
Capacity
NOTE
This parameter
is displayed
when BLVD
Disconnect
Mode is set to
Capacity
Mode.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 172


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

BLVD Time - 480min 5 to 1000


NOTE
This parameter
is displayed
when BLVD
Disconnect
Mode is set to
Time Mode.

BLVD Delay - 60s 3 to 90


Time
NOTE
This parameter
is displayed
only when
BLVD General
Discon. is set
to Enable.

Temp. Prot. Very HT Prot. - Reduce DC Reduce DC Voltage,


Para. Mode Voltage Disable, Disconnect
Battery

Very HT Prot. - 51.5V 42.0 to 53.0


Volt.

HT Alarm - 50 degC 25 to 80
Thres. NOTE
This default
value varies in
accordance with
the battery
performance. 55
degC is set by
default for the
TCB.

Very HT Alarm - 53 degC 25 to 80


Thres. NOTE
This default
value varies in
accordance with
the battery
performance.
58degC is set by
default for the
TCB.

LT Alarm - -10 degC -20 to +20


Thres.

Very LT Alarm - -20 degC -20 to +20


Thres.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 173


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Charge Auto. BC - Enable Enable, Disable


Parameters Enable NOTE
Indicates whether to
enable automatic
equalized charging.

FC-BC Cur. - 0.05 C10 0.01 to 0.25


Coef.
NOTE
This parameter
is displayed
only when
Auto. BC
Enable is set
to Enable.

FC-BC Cur. - 30 min 2 to 1440


Duration
NOTE
This parameter
is displayed
only when
Auto. BC
Enable is set
to Enable.

FC-BC Cap. - 70% 50 to 100


Percent
NOTE
This parameter
is displayed
only when
Auto. BC
Enable is set
to Enable.

Timed BC - Enable Enable, Disable


Enabled NOTE
Indicates whether to
enable scheduled
equalized charging.

Timed BC - 30 Day 1 to 365


Inteval
NOTE
This parameter
is displayed
only when
Timed BC
Enabled is set
to Enable.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 174


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Max Timed BC - 9h 1 to 24
Duration
NOTE
This parameter
is displayed
only when
Timed BC
Enabled is set
to Enable.

BC-FC Cur. - 0.01 C10 0.01 to 0.25


Coef. NOTE
If the duration within
which the battery
charge current is
lower than Equalized
to Float Charge
Current Coefficient
exceeds the value of
Equalized to Float
Charge Current
Duration, batteries
automatically enter
float charging.

BC-FC Cur. - 30 min 2 to 540


Duration

BC Max - 18 h 5 to 48
Duration NOTE
If the equalized
charging duration
exceeds the value of
this parameter,
batteries
automatically enter
float charging.

Mains Reco BC - Disable Disable, Enable


En. NOTE
Indicates whether to
perform equalized
charging after the AC
power is restored.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 175


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

AC Fail EC - 10 min 0 to 30
Duration NOTE
NOTE If the AC power
This parameter failure duration
is displayed exceeds the value of
only when this parameter,
Mains batteries
Recovery EC automatically enter
En is set to equalized charging
Enable. after the AC power is
restored.

Fast Charge - 0.40 C10 0.25 to 0.50


Coef.

Load Temp. - Disable Disable, Enable


Limit En.
NOTE
This parameter
is displayed
only in the
temperature
control
scenario.

Batt. Temp. - Disable Disable, Enable


Limit En.
NOTE
This parameter
is displayed
only in the
temperature
control
scenario.

Standard AC Fail Test - Disable Disable, Enable


Test Para. Enable NOTE
Indicates whether the
standard battery test
is allowed if an AC
power outage occurs.

Time Test - Disable Disable, Scheduled


Mode Test, Planned Test
NOTE
The mode in which
the monitoring unit
starts an automatic
test on schedule or
as planned.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 176


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Sche. Test St. - 21:00:00 HH:MM:SS


Time NOTE
NOTE Time when a
This parameter scheduled test starts.
is displayed
only when
Time Test
Mode is set to
Scheduled
Test.

Sche. Test - 90 Day 2 to 999


Period NOTE
NOTE Interval for starting a
This parameter scheduled test.
is displayed
only when
Time Test
Mode is set to
Scheduled
Test.

Annual Battery - 0 0 to 6
Tests NOTE
NOTE Number of planned
This parameter tests within a year.
is displayed
only when
Time Test
Mode is set to
Planned Test.

Pre-BC Enable - Enable Disable, Enable


NOTE
Indicates whether the
monitoring unit
allows charging
batteries in equalized
mode before a
standard battery test
starts.

Constant Cur. - Disable Disable, Enable


Test NOTE
Indicates whether
batteries are allowed
to discharge at a
constant current in a
standard battery test.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 177


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Constant Test - 9999 A 1 to 9999


Cur. NOTE
NOTE Batteries discharge at
This parameter this current in a
is displayed standard battery test.
only when
Constant Cur.
Test is set to
Enable.

Test End - 46.0 V 44.2 to 53.0


Voltage NOTE
If the battery voltage
is below the value of
this parameter, the
battery test ends.

Test End - 20% 0 to 99


Capacity NOTE
If the battery
capacity is below the
value of this
parameter, the
battery test ends.

Test End Time - 480 min 1 to 6000


NOTE
If the standard
battery test duration
reaches the value of
this parameter, the
battery test ends.

Test End - 5degC -5 to +15


Temperature NOTE
If the battery
temperature is lower
than Test End
Temperature, the
battery test ends.

Short Test Short Test - Disable Disable, Enable


Para. Enable NOTE
Indicates whether to
allow the monitoring
unit to perform short
tests automatically.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 178


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Short Test - 30 Day 1 to 360


Period
NOTE
This parameter
is displayed
only when
Short Test
Enable is set
to Enable.

Short Test - 5 min 1 to 240


Time NOTE
NOTE If the test duration
This parameter exceeds the value of
is displayed this parameter, the
only when monitoring unit exits
Short Test from the short test.
Enable is set
to Enable.

Short Test End - 45.0 V 44.2 to 53.0


Volt. NOTE
NOTE If the battery voltage
This parameter is below the value of
is displayed this parameter, the
only when monitoring unit exits
Short Test from the short test.
Enable is set
to Enable.

Alarm Overcur. Alm. - 0.25 C10 0.05 to 1.00


Parameters Thres.

Low Cap. Alm. - 30% 0 to 90


Thres.

Volt - Percentage Percentage Mode,


Unbalance Mode Voltage Mode
Mode

Volt. Imb. - 10% 5 to 30


Thres
NOTE
This parameter
is displayed
only when
Volt
Unbalance
Mode is set to
Percentage
Mode.

Cur. Imb. - 0.05 C10 0.00 to 1.00


Thres.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 179


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Volt. Imb. - 2.0 V 0.5 to 4.0


Thres
NOTE
This parameter
is displayed
only when
Volt
Unbalance
Mode is set to
Voltage Mode.

Batt Incorrect - 5.0 A 1.0 to 100.0


Curr.

Batt Incorrect - 5 min 1 to 60


Time

Other Battery Install - 2010-01-01 YYYY-MM-DD


Parameters Time

Product Time - 2010-01-01 YYYY-MM-DD

Volt. Detect - Middle Point Middle Point Volt.,


Mode Volt. Cell Volt. None
NOTE
When connecting a
signal cable for
monitoring middle
point voltages, select
Middle Point Volt..
When connecting a
signal cable for
monitoring battery
voltages, select Cell
Volt..

Power Backup - Time Mode Time Mode,


Mode Capacity Mode
NOTE
Specifies a mode for
detecting power
backup capability.
● Time Mode:
based on backup
time.
● Capacity Mode:
based on backup
capacity

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 180


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

LLVD Backup - 180 min 0 to 9999


Time NOTE
NOTE Sets the expected
This parameter duration from when
is displayed batteries start to
only when supply power to
Power Backup when loads are
Mode is set to disconnected.
Time Mode. For example, if you
require that loads be
powered for 200
minutes since
batteries start to
supply power, set this
parameter to
200Min.
If the actual power
supply duration is
shorter than the
expected duration,
the monitoring unit
generates a Backup
Warning alarm.

BLVD Backup - 480 min 0 to 9999


Time NOTE
NOTE Sets the expected
This parameter duration from when
is displayed batteries start to
only when supply power to
Power Backup when batteries are
Mode is set to disconnected.
Time Mode.
If the actual power
supply duration is
shorter than the
expected duration,
the monitoring unit
generates a Backup
Warning alarm.

LLVD Backup - 75% 5 to 100


Capacity
NOTE
This parameter
is displayed
only when
Power Backup
Mode is set to
Capacity
Mode.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 181


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

BLVD Backup - 95% 5 to 100


Capacity
NOTE
This parameter
is displayed
only when
Power Backup
Mode is set to
Capacity
Mode.

Battery Cable - 1m 0 to 100


Length

Battery Cable - 35 mm2 1 to 1000


CS Area

SOC/SOH - Backup Scene Cyclic Scene, Backup


Calcu Scene Scene

Attenuation - 0.80 0.00 to 1.00


Coef

Block Voltage - 2V 2, 12

Combine Basic Battery - Yes Yes, No


d Cab Parameters Connected n

UIM DG 1 ON/OFF - ALM2 ALM1 to ALM8,


Control Do None

DG 1 Auxi - None ALM1 to ALM8,


Preheat DO None

DG 1 Run. - DIN4 DIN1 to DIN6, None


Status Det.

DG 2 ON/OFF - ALM4 ALM1 to ALM


Control Do 8, None

DG 2 Auxi - ALM5 ALM1 to ALM8,


Preheat DO None

DG 2 Run - DIN5 DIN1 to DIN6, None


Status Det.

ATS 1 Run - DIN3 DIN1 to DIN6, None


Deterction

ATS 2 Run - DIN6 DIN1 to DIN6, None


Deterction

ATS DI Cond. - Close Open, Close


AC Fail

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 182


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Dry Contact - DIN1 DIN1 to DIN6, None


Open AC

Controller Buzzer Enable - No Yes, No

Buzzer Alm. - 10 min 1 to 100


Duration
NOTE
This parameter
is displayed
only when
Buzzer Enable
is set to Yes.

IP Network - High High, Medium, Low


Priority

Inband Net - Medium High, Medium, Low


Priority

Wireless Net - Low High, Medium, Low


Priority

Run. Time Sw. - 60 min 1 to 1440


Net.

IP Net. - 5 min 5 to 1440


Timeout

Inband Net. - 5 min 5 to 1440


Timeout

Wire. Net. - 30 min 30 to 1440


Timeout

North MS - Enable Enable, Disable


Config

Display Device - No Yes, No


Info

Humiture Amb. HT - 55 degC 25 to 69


Sensor Thres.

Amb. LT Thres. - -20 degC -20 to 54

Amb. Ultra HT - 70 degC 56 to 80


Thres.

Amb. HH - 95 % 11 to 100
Thres.

Amb. LH - 5% 0 to 89
Thres.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 183


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Env HT Count - 55 degC 25 to 80


Point

Env LT Count - -20 degC -20 to 20


Point

Amb Temp - Enable Disable, Enable


Rec Enable

Amb Temp - 5 Minutes 1 Minutes, 5


Rec Period Minutes, 15
Minutes, 30
Minutes, Hour

Amb Humid - Enable Disable, Enable


Rec Enable

Amb Humid - 5 Minutes 1 Minutes,


Rec Period 5 Minutes,
15 Minutes, 30
Minutes, Hour

DC Output LLVD Enabled - Disable Enable, Disable


Distribut.
LLVD n - 44.0 V 36.0 to 56.0
Voltage
NOTE
This parameter
is displayed
only when
LLVD Enabled
is set to
Enable.

LLVD n Recon - 51.5 V 37.0 to 58.0


Volt
NOTE
This parameter
is displayed
only when
LLVD Enabled
is set to
Enable.

LLVD PD Enb - Disable Enable, Disable

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 184


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

LLVD PD Time - 23:00:00 00:00:00-23:00:00


NOTE
This parameter
is displayed
only when
LLVD PD Enb
is set to
Enable.

LLVD PD - 480 min 1 to 1439


Duration
NOTE
This parameter
is displayed
only when
LLVD PD Enb
is set to
Enable.

LLVD HTD Enb - Disable Enable, Disable

LLVD HTD - 65.0 degC 25.0 to 80.0


Temp
NOTE
This parameter
is displayed
only when
LLVD HTD Enb
is set to
Enable.

LLVD Delay - 60 s 5 to 90
Time
NOTE
This parameter
is displayed
only when
LLVD Enabled
is set to
Enable.

DC Over - 58.0 V 53.0 to 60.0


Voltage

DC Under Volt - 45.0 V 36.0 to 57.0

Ultra Over - 59.0 V 53.0 to 60.0


Volt

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 185


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

LLVD PD - 480 min 1 to 1439


Duration
NOTE
This parameter
is displayed
only when
LLVD PD Enb
is set to
Enable.

LLVD HTD Enb - Disable Enable, Disable

LLVD HTD - 65.0 degC 25.0 to 80.0


Temp
NOTE
This parameter
is displayed
only when
LLVD HTD Enb
is set to
Enable.

LLVD Delay - 60 s 5 to 90
Time
NOTE
This parameter
is displayed
only when
LLVD Enabled
is set to
Enable.

DC Over - 58.0 V 53.0 to 60.0


Voltage

DC Under Volt - 45.0 V 36.0 to 57.0

Ultra Over - 59.0 V 53.0 to 60.0


Volt

Ultra Under - 44.0 V 36.0 to 56.0


Volt

Total Load - 2750 A 10 to 10000


Over Curr

AC AC Voltage - Voltage Mode Percentage Mode,


Distribution Mode Voltage Mode

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 186


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

AC Phase OV - 280 V 60 to 300


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Voltage Mode
and AC Model
is 1-Phase, 2-
Phase 2-Wire
or 3-Phase 4-
Wire.

AC Phase UV - 180 V 60 to 300


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Voltage Mode
and AC Model
is 1-Phase, 2-
Phase 2-Wire
or 3-Phase 4-
Wire.

AC Phase OV - 130% 110-200


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Percentage
Mode and AC
Model is 1-
Phase, 2-
Phase 2-Wire
or 3-Phase 4-
Wire.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 187


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

AC Phase UV - 80% 1-90


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Percentage
Mode and AC
Model is 1-
Phase, 2-
Phase 2-Wire
or 3-Phase 4-
Wire.

AC Line OV - 280 V 60 to 600


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Voltage Mode
and AC Model
is 3-Phase 3-
Wire.

AC Line UV - 180 V 60 to 600


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Voltage Mode
and AC Model
is 3-Phase 3-
Wire.

Rated Line - 220 V 60-600


Volt
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Percentage
Mode and AC
Model is 3-
Phase 3-Wire.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 188


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

AC Line OV - 130% 110-200


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Percentage
Mode and AC
Model is 3-
Phase 3-Wire.

AC Line UV - 80% 1-90


Thres.
NOTE
This parameter
is displayed
only when AC
Voltage Mode
is set to
Percentage
Mode and AC
Model is 3-
Phase 3-Wire.

Rated AC - 50 Hz 40 to 70
Frequency

Over AC Freq - 110% 105 to 130

Uder AC Freq - 90% 70 to 95

Setup Basic Genset Qty - 0 0 to 2


Paramet Parameters
er Tank Qty - 1 0 to 4

A/C Off for - Disable Disable, Enable


Small DG
NOTE
This parameter
is related to
the system
type.

TCB auto- - Yes Yes, No


sensing

Hybrid - No Yes, No
Scenario

AC Supply - Mains Supply Mains Supply


Priority Priority Priority, DG Supply
Priority

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 189


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Battery Vendor - Other AGISSON, Coslight,


Dengta, Eltek,
EnerSys, Exide,
LEOCH, Narada,
NorthStar, Shoto,
Other

Battery Mode - 12 V VRLA DCB-A, DCB-A1,


DCB-B, DCB-Y, ESU-
A, ESM-A, ESM-BX,
FCB-A, FCB-B, SCB-
A, SCB-A1, TCB-A,
TCB-B, TCB-C, 12V
VRLA, 2V VRLA,
FLOOD, 6-GFM-X,
6-GFMF, Rebak-
F4899T, 12TD-F,
SBS-F, M12V-FT,
LPF12-H, 6-GFM-F,
12NDF, Blue, Red, 6-
FMX, 6-XFMJ, GFM,
BBS 4840Z
NOTE
This parameter is
related to battery
manufacturers.

Load Elec Stat - No No, DCDB, DC


Src Ammeter, EFUSE,
Shunt

Include Public - No Yes, No


Load
NOTE
This parameter
is displayed
only when
Load Elec Stat
Src is set to
DCDB, DC
Ammeter,
EFUSE or
Shunt.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 190


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Load Elec Stat - 1 1 to 28


Star
NOTE
This parameter
is displayed
only when
Load Elec Stat
Src is set to
DCDB, DC
Ammeter,
EFUSE or
Shunt.

Enable Sign - Enable Enable, Disable


Verify

TLS 1.0 - Disable Enable, Disable

Report Hist. - Disable Enable, Disable


Alarms

Non-smart - 0 0 to 2
ATS Qty

Back Network - Yes Yes, No


Port Enable

Mobile Mobile DG - Disable Enable, Disable


Genset Para Auto-Sense

Mobile DG - Enable Enable, Disable


Chg. Batt
NOTE
This parameter
is available
only when
Mobile DG
Auto-Sense is
Enable and
Genset Qty is
0.

Read Mains - 50.0 Hz 40.0 to 70.0


Freq
NOTE
This parameter
is displayed
only when
Mobile DG
Auto-Sense is
set to Enable.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 191


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Mains Freq - 0.5 Hz 0.1 to 5.0


Fluct Rng
NOTE
This parameter
is displayed
only when
Mobile DG
Auto-Sense is
set to Enable.

Sensor AC SPD - Yes Yes, No


Config
DC SPD - Yes Yes, No

Door Sensor - Yes Yes, No

Water Sensor - No Yes, No

Smoke Sensor - No Yes, No

Ambient - No Yes, No
Temp. Sensor

Ambient - No Yes, No
Humi. Sensor

Temp1 Sensor - No Yes, No

Temp2 Sensor - No Yes, No

Batt. Temp. - No Yes, No


Sensor 1

Batt. Temp. - No Yes, No


Sensor 2

Vibration - No DIN1-6, No
Sensor

Audible Visual - No ALM1-7, No


Alarm

IR sensor - No DIN1-6, No
connected

Glass Brk Snsr - No DIN1-6, No


Cnnct

Water Sensor - No DIN1-6, No


connect

Smoke Sensor - No DIN1-6, No


connect

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 192


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Nonintelligent - No Yes, No
Lock

Door Lock No Yes, No


State
NOTE
This parameter
is displayed
only when
Nonintelligen
t Lock is set to
YES.

Nonintel. Lock - No ALM1-8, No


ALM
NOTE
This parameter
is displayed
only when
Nonintelligen
t Lock is set to
YES.

iDCDU - - - - -

DTS # DTS Group Backup Batt - Yes Yes, No


Enable

LeBatt - Discharge apart Discharge apart,


Transfer Mode Discharge together

LiBatt Transfer - Active/Standby Active/Standby,


Mode Mutual backup

DTS Transfers - 20 1 to 100


Limit

MainBatt Swit. - 43.2 V 35.0 to 56.0


Volt

BackBattN - 43.2 V 35.0 to 56.0


Swit. Volt

DTSn MainBatt UV - 46.0 V 46.0 to 57.0


Thres

MainBatt UV - 1.0 1.0 to 5.0


HY

BackBatt UV - 46.0 V 46.0 to 57.0


Thres

BackBatt UV - 1.0 1.0 to 5.0


HY

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 193


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

DCDB # DCDB n Basic Load Setting All Branch All Branch, Single
Parameters Mode Branch

Load Off Voltage Mode Voltage Mode, Time


Mode Mode

Load Off Load Off Yes Yes, No


Enable Enable
NOTE
This
parameter is
available only
when Load
Setting
Mode is All
Branch.

Load N Off Yes Yes, No


Enable
NOTE
This
parameter is
available only
when Load
Setting
Mode is
Single
Branch.

Load TD No Yes, No
Enable
NOTE
This
parameter is
available only
when Load
Setting
Mode is All
Branch.

Load N TD No Yes, No
Enable
NOTE
This
parameter is
available only
when Load
Setting
Mode is
Single
Branch.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 194


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Load On/Off Load On 51.5 V 37.0 to 58.0


Para. Voltage
NOTE
This
parameter is
available only
when Load
Setting
Mode is All
Branch.

Load N On 51.5 V 37.0 to 58.0


Volt
NOTE
This
parameter is
available only
when Load
Setting
Mode is
Single
Branch.

Load Off 43.2 V 36.0 to 56.0


Voltage
NOTE
This
parameter is
available only
when Load
Setting
Mode is All
Branch.

Load N Off 43.2 V 36.0 to 56.0


Volt
NOTE
This
parameter is
available only
when Load
Setting
Mode is
Single
Branch.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 195


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Load Off 6000 min 0 to 6000


Time
NOTE
This
parameter is
available only
when Load
Setting
Mode is All
Branch and
Load Off
Mode is
Time Mode.

Load N Off 6000 min 0 to 6000


Time
This
parameter is
available only
when Load
Setting
Mode is
Single
Branch and
Load Off
Mode is
Time Mode.

Load TD HH:MM:SS HH:MM:SS


Time
NOTE
This
parameter is
available only
when Load
Setting
Mode is All
Branch.

Load N TD HH:MM:SS HH:MM:SS


Time
NOTE
This
parameter is
available only
when Load
Setting
Mode is
Single
Branch.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 196


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Load TD 480 min 1 to 1439


Duration
NOTE
This
parameter is
available only
when Load
Setting
Mode is All
Branch.

Load N TD 480 min 1 to 1439


Duration
NOTE
This
parameter is
available only
when Load
Setting
Mode is
Single
Branch.

Load Overcur Load OvCur Yes Yes, No


Thres Prot En
NOTE
This
parameter is
available only
when Load
Setting
Mode is All
Branch.

Load N Yes Yes, No


OvCur Prot
En
NOTE
This
parameter is
available only
when Load
Setting
Mode is
Single
Branch.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 197


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Load Br OC 30 A 3 to 40
Thres.
NOTE
This
parameter is
available only
when Load
Setting
Mode is All
Branch.

Load N OC 30 A 3 to 40
Thres.
NOTE
This
parameter is
available only
when Load
Setting
Mode is
Single
Branch.

Load OvTmp Load OvTmp Yes Yes, No


Para. Proc En
NOTE
This
parameter is
available only
when Load
Setting
Mode is All
Branch.

Load N Yes Yes, No


OvTmp Proc
En
NOTE
This
parameter is
available only
when Load
Setting
Mode is
Single
Branch.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 198


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Consumption Load User No No, User 1 to User 6


Config Config
NOTE
This
parameter is
available only
when Load
Setting
Mode is All
Branch.

Load N to No No, User 1 to User 6


User Config
NOTE
This
parameter is
available only
when Load
Setting
Mode is
Single
Branch.

Load N to No No, Branch 1 to


Branch Branch 6
NOTE
This
parameter is
available only
when Load
Setting
Mode is
Single
Branch.

Low Cap Basic Rated Capacity - 40 Ah 1 to 300


Li-ion Parameters
Batt # Charging - 54.0 V 53.5 to 56.5
Voltage
NOTE
This
BLVD Enable - Yes Yes, No
parame
ter is
Battery N - Yes Yes, No
displaye
d only Connected
when
Battery BLVD BLVD Mode - Voltage Mode Voltage Mode, Time
Model Parameters Mode
is set to
BBS
4840Z.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 199


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

BLVD Time - 480 min 5 to 1000


NOTE
This parameter
is displayed
only when
BLVD Mode is
set to Time
Mode.

BLVD Capacity - 5% 0 to 100

BLVD Voltage - 43.2 V 35.0 to 47.8

BLVD Con. - 51.5 V 37.0 to 53.0


Volt.

Alarm HT Alarm - 50 degC 25 to 80


Parameters Thres.

LT Alarm - -10 degC -35 to +20


Thres.

Other Installation - 2010-01-01 YYYY-MM-DD


Parameters Time

Shunt Max. - 75 mV 5 to 150


Volt.

Shunt Max. - 300 A 5 to 3000


Cur.

Li Basic Battery N - No Yes, No


Battery Parameters Connected
#
Batt Atten - 0.80 0.00 to 1.00
Coef

Discharge - Constant Volt Auto, Constant Volt


Mode Dischg Dischg

Priority - Disabale Enable, Disabale


Charger

iLock Enable - Lock Disable Lock Enable, Lock


NOTE Disable
This parameter
is displayed
only when the
battery anti-
theft function
is supported.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 200


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu
NOTE BMU Manage - Host Manage Host Manage, Auto
● This Model Manage
para
NOTE
met
This parameter
er is
is displayed
displ
only when the
ayed
battery anti-
only
theft function
whe
is supported.
n
Batt
iLock Verify - 72 10 to 720
ery
Mod Timeout
el is NOTE
set This parameter
to is displayed
ESM only when the
-A, battery anti-
ESU theft function
-A is supported.
or
ESM Battery Group - - -
-BX. Vendor
● Ther
e BMU Quantity - 0 0 to 32
are
diffe Cycle Mode - Li-Ion And Acid Li-Ion And Acid
renc NOTE cycle cycle, Li-Ion
es in This parameter primary, Li-Ion
the only displayed standby
defa when iMix
ult Enabled is set
para to Enable.
met
ers Charge Charge - 1.00 0.80 to 1.00
of Parameters Efficiency
the
batt NOTE
ery This parameter
whe only displayed
n when Hybrid
the Scenario is set
Batt to No.
ery
Mod EC Voltage - 52.1V 42.0 to 58.0
el or NOTE
Batt This parameter
ery only displayed
Cap when Hybrid
acity Scenario is set
is to No.
diffe
rent. Chg Curr Limit - 0.15 C10 0.05 to 1.00
Coef

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 201


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Load - Disable Disable, Enable


Temp.Limit En.
NOTE
This parameter
is displayed
only in the
temperature
control
scenario.

Batt. - Disable Disable, Enable


Temp.Limit En.
NOTE
This parameter
is displayed
only in the
temperature
control
scenario.

Alarm HT Alarm - 50 degC 35 to 70


Parameters Thres.

LT Alarm - 0 -50 to 10
Thres.

Low Cap. Alm. - 30% 0 to 90


Thres.

Camera Camera Image Quality - Excellent Average, Fair, Good,


# Equip n Excellent
NOTE NOTE
Applies Image definition.
when
the Image Format - 640 x 480 160 x 120, 320 x
serial 240, 640 x 480
port
camera
is
Snapshot - 20s 1 to 600
connect Interval NOTE
ed. Interval for taking
pictures.

Number After - 5 Pcs 1 to 30


Alarm NOTE
Sets how many
pictures taken after
alarm generation will
be saved.

Cabinet Name - - -

Forbid Camera - No Yes, No

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 202


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Camea # Camera Capture - 40s 20 to 60


NOTE Equip n Interval
Applies
when Forbid Camera - No Yes, No
the IP
camera
is
connect
ed.

iBOX iBOX Equip iBAT Number - 1 1 to 8


n Per Cell

iBAT Volt. Rec. - No No, Yes


En.

iBAT Res. Rec. - No No, Yes


En.

iBAT Temp. - No No, Yes


Rec. En.

iBAT SOH Rec. - No No, Yes


En.

Efuse EFUSE n Basic Load Off Voltage Mode Time Mode, Voltage
Group # Parameters Mode Mode

On/Off Single All, Single


Setting

Load Overcur Single All, Single


Setting

Load n Off Yes Yes, No


Enable
NOTE
This
parameter is
displayed
only when
On/Off
Setting is
Single.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 203


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Load Off No Yes, No


Enable
NOTE
This
parameter is
displayed
only when
On/Off
Setting is
ALL.

Load n TD No Yes, No
Enable
NOTE
This
parameter is
displayed
only when
On/Off
Setting is
Single.

Load TD No Yes, No
Enable
NOTE
This
parameter is
displayed
only when
On/Off
Setting is
ALL.

Load Off Load n Off 43.2 V 35.0 to 56.0


Voltage Volt
NOTE
This
parameter is
displayed
only when
On/Off
Setting is
Single.

Load Off 43.2 V 35.0 to 56.0


Voltage
NOTE
This
parameter is
displayed
only when
On/Off
Setting is All.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 204


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Load On Load n On 51.5 V 37.0 to 58.0


Voltage Volt
NOTE
This
parameter is
displayed
only when
On/Off
Setting is
Single.

Load On 51.5 V 37.0 to 58.0


Voltage
NOTE
This
parameter is
displayed
only when
On/Off
Setting is All.

Load Off Time Load n Off 6000 min 0 to 6000


NOTE Time
This parameter NOTE
is displayed This
only when parameter is
Load Off displayed
Mode is Time only when
Mode. On/Off
Setting is
Single.

Load Off 6000 min 0 to 6000


Time
NOTE
This
parameter is
displayed
only when
On/Off
Setting is All.

Load Time Load TD - -


Down Time
NOTE NOTE
This parameter This
is displayed parameter is
only when displayed
Load TD only when
Enable is Yes. On/Off
Setting is All.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 205


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Load TD 480 min 1 to 1439


Duration
NOTE
This
parameter is
displayed
only when
On/Off
Setting is All.

Load n TD - -
Time
NOTE
This
parameter is
displayed
only when
On/Off
Setting is
Single.

Load n TD 480 min 1 to 1439


Duration
NOTE
This
parameter is
displayed
only when
On/Off
Setting is
Single.

Load Overcur Load n 15.0 A 0.5 to 20.0


Thres Overcur
Thres
NOTE
This
parameter is
displayed
only when
Load
Overcur.
Setting is
Single.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 206


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Load Overcur. 15.0 A 0.5 to 20.0


Thres.
NOTE
● This
parameter
is
displayed
only when
Load
Overcur.
Setting is
All.
● When the
actual
current
exceeds
the 1.2
times of
the load
overcurre
nt
threshold,
the EFUSE
automatic
ally
enables or
disables
the
output.
The
appropriat
e current
can be
manually
resumed
only after
the
overcurre
nt fault is
rectified.

Consumption All Loads to None None, User 1-6


Config User NOTE
User SNs must be
consecutive; In a
multi-LLVD scenario,
use SNs must map to
LLVD SNs.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 207


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Load n to None None, User 1-6


User NOTE
NOTE User SNs must be
This consecutive.
parameter is
displayed
only when
Load Elec
Stat Src is
EFUSE.

Load n to None None, Branch1-10


Branch
NOTE
This
parameter is
displayed
only when
Load Elec
Stat Src is
No EFUSE.

Other Input OV 58.0 V 58.0 to 60.0


Parameters Thres

Input UV 42.0 V 38.0 to 45.0


Thres

Set Cabinet - -
Name

Temp. Temp. Indoor Vent TS - Yes Yes, No


Control Control
Group Outdoor Amb. - No Yes, No
TS

TC Mode - Standard Mode Standard mode,


NOTE Mute mode
This parameter
is displayed
only in the
temperature
control
scenario.

Backup Mode - Disable Enable. Disable


enable
NOTE
This parameter
is displayed
only in the
temperature
control
scenario.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 208


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

A/C Config. - Disable Enable. Disable


Mode En
NOTE
This parameter
is displayed
only in the
temperature
control
scenario.

Low-Temp - Disable Enable. Disable


Mode Enable
NOTE
This parameter
is displayed
only in the
temperature
control
scenario.

Fan Group In_Recycle - 35 degC -20 to 50


Work Temp

In_Recycle - 30 degC -20 to 50


Stop Temp

Ex_Recycle - 35 degC -20 to 50


Work Temp

Ex_Recycle - 30 degC -20 to 50


Stop Temp

Dr. Alm. Fan - Disable Enable. Disable


Stp. En

Heater Heater Start - 5 degC -10 to 5


Device Temp.

Heater Stop - 15 degC 5 to 15


Temp.

AIM n AC Rated - - 50 Hz 50, 60


Frequency

Detected - - AC Total Input AC Total Input,


Object None, AC Other
Equipment, AC TC
Equipment, AC
Main Equipment

AC OV - - 280V 60~300
Thres.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 209


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

AC UV - - 180V 60~300
Thres.

AC Source - - Other Other, DG, Mains

ATS ATS Group AC Supply - DG Supply DG Supply Priority,


Priority Priority Mains Supply
Priority

ATS 1 Work Scenario - Mains+DG Mains+DG,


DG1+DG2

Mains UVT - 39% 39 to 100

Mains OVT - 140% 100 to 159

DG UVT - 87% 70 to 100

DG OVT - 125% 100 to 140

Sensor Humiture Amb. HT Thres - 55 degC 25 to 80


Sensor #
Amb. LT Thres - -20 degC -20 to +20

Amb. Ultra HT - 70 degC 25 to 80


Thres.

Amb. HH - 95% 0 to 100


Thres.

Amb. LH - 5% 0 to 100
Thres.

Env HT Count - 55 degC 25 to 80


Point

Env LT Count - -20 degC -20 to +20


Point

Water Water Alarm - Close Close, Open


Sensor # Cond

Door Sensor Door Alarm - Open Close, Open


# Cond

Smoke Smoke Alarm - Close Close, Open


Sensor # Cond

Glass Brk Glass Brk Snsr - Close Close, Open


Snsr # Cond

IR Sensor # IR Sensor - Close Close, Open


Cond

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 210


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Vibration Vibration - Close Close, Open


Sensor # Sensor Cond

MIMO 12DC Out. - - 12.0 V 12.0 to 13.2


Group # Volt.

24AC Out. - - 24.0 V 24.0 to 26.3


Volt.

Other iRELAY 1 Blink Duration - 30s 5 to 120


Device
Config RF-A Max - 8 dBm 0 to 15
Tran. P.

Duration to - 720 min 1 to 1440


Connect

iFUEL-RS485 - - - -

iDATA n Blink Duration - 30s 5 to 120

DI n Alm. - Closed Open, Closed


Cond.

PORT n – DI n - Closed Open, Closed


Alm Cond

Node A Max - 8 dBm 0 to 15


Power

Node B Max - 6 dBm 0 to 15


Power

Port n Config - DI_MODE DI_MODE, IR


_MODE,
Smoke_MODE,
Voltage_MODE,
NTC_MODE

I/O n Config - INPUT_MODE INPUT_MODE,


OUTPUT_MODE

DO n Alarm - Closed Opened, Closed


Action
NOTE
This parameter
is displayed
only when I/O
n Config is set
to
OUTPUT_MO
DE.

Hall n Type - 100A 100A, 200A

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 211


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

PORT n-NTC - TF820E10J TF820E10J,


NOTE NTSA0103FZD19A
This parameter
is displayed
only when
PORT is set to
NTC.

Blade Power 48V Side DC - DC Power DC Power, Li Batt,


n Input Type Normal Lead Acid

AC Mode - Three Phases Single Phase, D-Live


Lines

Dynamic - Disable Enable, Disable


Adjust Voltage
Enabled

AC Overvolt. - 280 V 60-305


Thres.

AC Undervolt. - 180 V 60-305


Thres.

48V DC - 58.0 V 53.0-60.0


Overvolt.
Thres.

48V DC - 45.0 V 36.0-57.0


Undervolt.
Thres.

47V DC - 73.0 V 58.0-75.0


Overvolt.
Thres.

47V DC - 53.0 V 50.0~59.0


Undervolt.
Thres.

Time Set - 2000-01-01 -


00:00:00

LLVD n - Enable Enable, Disable


Enabled

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 212


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

LLVD n Mode - Voltage Mode Voltage Mode, Time


NOTE Voltage
This parameter
is displayed
only when
LLVD n
Enabled is set
to Enable.

LLVD n - 44.0 V 36.0~56.0


Voltage
NOTE
This parameter
is displayed
only when
LLVD n
Enabled is set
to Enable.

LLVD n Recon - 51.5V 37.0~58.0


Volt
NOTE
This parameter
is displayed
only when
LLVD n
Enabled is set
to Enable.

48V - 45.0 V 35.0~56.0


Disconnect
Voltage

48V Port Set - 53.5 V 48.0~55.0


Volt

AC Peak - Disable Enable, Disable


Shaving
Enabled

AC Capacity - 1000 kW 1-10000


NOTE
This parameter
is displayed
only when AC
Peak Shaving
Enabled is set
to Enable.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 213


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Breaker Rated - 1000 A 1-10000


Curr
NOTE
This parameter
is displayed
only when AC
Peak Shaving
Enabled is set
to Enable.

Derating Coef - 0.8 0.1-1.0


NOTE
This parameter
is displayed
only when AC
Peak Shaving
Enabled is set
to Enable.

Rated Phase - 220 V 60-300


Volt
NOTE
This parameter
is displayed
only when AC
Peak Shaving
Enabled is set
to Enable.

Power Unit n - 57.0 V 57.0-60.0


Output
Voltage

WIM n Duration to - 720 min 1 to 1440


Connect

RF-A Max - 8 dBm 0 to 15


Tran. P

RF-B Max - 6 dBm 0 to 15


Tran. P

WAN Port - No No, GE 2, GE 1


Settings

DG Mains Detect - Disable Enable, Disable


Controller n Enable

Fuel Level UL - 300.0 cm 0.0 to 1000.0

Fuel Level LL - 0.0 cm 0.0 to 1000.0

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 214


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

DG Comm AI 1 Insert - Tank 1 Oil Level None, Tank 1 Oil


Ex Board Sensor Level, Tank 2 Oil
Level, Dg1 AirIn
Press, Dg2 AirIn
Press

AI 2 Insert - Tank 2 Oil Level None, Tank 1 Oil


Sensor Level, Tank 2 Oil
Level, Dg1 AirIn
Press, Dg2 AirIn
Press

Fuel Level UL - 300.0 cm 0.0-1000.0


AI1

Fuel Level LL - 0.0 cm 0.0-1000.0


AI1

Fuel Level UL - 300.0 cm 0.0-1000.0


AI2

Fuel Level LL - 0.0 cm 0.0-1000.0


AI2

Fuel Tank n Tank Type - Cuboid Horizontal Cylinder,


Vertical Cylinder,
Irregular, Cuboid

Tank Length - 1.50 m 0.50 to 20.00


NOTE
This parameter is
displayed only when
Tank Type is set to
Horizontal Cylinder.

Cyl Tank - 1.13 m 0.00 to 4.00


Diameter NOTE
This parameter is
displayed only when
Tank Type is set to
Vertical Cylinder or
Horizontal Cylinder.

Cuboid Tank - 1.00 m 0.00 to 10.00


Lenght NOTE
This parameter is
displayed only when
Tank Type is set to
Cuboid.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 215


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Cuboid Tank - 1.00 m 0.00 to 10.00


Width NOTE
This parameter is
displayed only when
Tank Type is set to
Cuboid.

Tank Height - 1.50 m 0.0 to 10.0


NOTE
This parameter is
displayed only when
Tank Type is set to
Vertical Cylinder or
Cuboid.

Rated Capacity - 1500.00 L 0.00 to 6000.00


NOTE
This parameter is
displayed only when
Tank Type is set to
Irregular.

Under Fuel - 15.0% 0.0 to 50.0


Level

Refuel Level - 20.0% 0.0 to 50.0

Abnor Change - 3.0 cm 1.0 to 1000.0


Thres

Abnor Change - 10.0 min 1.0 to 60.0


Dur

Level Filter - 30 min 1 to 1440


Time

Calibration - 10 1 to 100
Num NOTE
This parameter is
displayed only when
Tank Type is set to
Irregular.

Height H n - 0.00 cm 0.00 to 200.00


NOTE NOTE
Set this This parameter is
parameter to displayed only when
H0. Set other Tank Type is set to
parameters Irregular.
based on site
requirements.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 216


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Volum V n - 0.00 L 0.00 to 6000.00


NOTE NOTE
Set this This parameter is
parameter to displayed only when
H0. Set other Tank Type is set to
parameters Irregular.
based on site
requirements.

Level Filter - 3.00 cm 0.00 to 10.00


Thres

Refuel Calc - Yes Yes, No


Enb

EPS-D Fuel Sensor - Current type Current type, Smart


Interface Type Type, Resistance
Brd n type

Oil Pump - 4s 1 to 8
Runtime

OilClean - 2h 1 to 50
Period

Auto Add Oil - Yes Yes, No

Fuel Level UL - 25.7 cm 0.0 to 1000.0

Fuel Level LL - 2.7 cm 0.0 to 200.0

Fuel Tank - 300.0 L 0.0 to 600.0


Capacity

Tank CSA - 1.20 m2 0.00 to 10.00

Alarm DI Dry DIN n Alm. - Close Close, Open


Paramet Contact Cond.
ers Para.
Heater Alarm - DIN5 DIN1-6, None
Asso.
NOTE
This parameter
varies with the
system type.

DIN5 Reuse - None None, Heater Fault


NOTE
This parameter
varies with the
system type.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 217


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

DIN6 Reuse - None None, LLVD Forcibly


NOTE Connection, TCUA
This parameter Alarm, TEC Alarm
varies with the
system type.

DO Dry ALM n Alarm - Close Close, Open


Contact Action
Para.

Alarm Site Unit - - -


Config
UIM - - -

Controller - - -

Door Sensor - - -

Smoke Sensor - - -

Other Virtual - - -
Equip

Rectifier - - -

Rectifier - - -
Group

Battery Group - - -

Battery String - - -

Temp. Control - - -
Group

Fan Group - - -

Heater Device - - -

Comm. Ex. - - -
Board Group

Comm. Ex. - - -
Board

Mains - - -

Genset - - -
Summary

Genset - - -

EFUSE - - -

EFuse Group - - -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 218


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

AIM - - -

ATS Group - - -

ATS - - -

GPS - - -

Nonintelligent - - -
Lock

DG - - -
Controller

Blade Power - - -

Blade Power - - -
Group

DG Comm Ex - - -
Board

AC - - -
Distribution

DC Output - - -
Distribution

DC Power - - -

Fuel Tank - - -

SIEE Data - - -

Alarm Level Cri. Alm. Asso. - No No, ALM1-ALM8


DO Para. DO

Major Alm. - No No, ALM1-ALM8


Asso. DO

Minor Alm. - No No, ALM1-ALM8


Asso. DO

Warn. Alm. - No No, ALM1-ALM8


Asso. DO

Clear ALM Clear ALM n - Yes Yes


Asso. Asso.

Clear DI Clear DIN n - Yes Yes


Asso. Asso.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 219


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Comm. Network DHCP Enabled - Disable Disable, Client,


Paramet Parameters Server
ers
Backplane - Disable Disable, Client,
DHCP Enabled Server

Bridge - Disable Disable, Enable


Enabled

Bridge IP Type - IPv4 IPv4, IPv6

Bridge - 192.168.0.10 -
IP Address

Bridge - 255.255.255.0 -
Subnet Mask

Bridge Default - 192.168.0.1 -


GW

IP Type - IPv4 IPv4, IPv6

IP Address - 192.168.0.10 -

Subnet Mask - 255.255.255.0 -

Default - 192.168.0.1 -
Gateway

IPv4 DSCP - 46 0 to 63

VLAN Enable - No Yes, No

VLAN ID - 0 0 to 4094

VLAN Priority - 5 0 to 7

NetEco - 192.168.0.10 -
Primary IP

NetEco - 192.168.0.10 -
Backup IP

NetEco Port - 31220 1 to 65535


Number

FAE Tel - - :, _, 0 to 9, a to z, A
Number 1 to Z

FAE Tel - - :, _, 0 to 9, a to z, A
Number 2 to Z

FAE Tel - - :, _, 0 to 9, a to z, A
Number 3 to Z

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 220


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

FAE Tel - - :, _, 0 to 9, a to z, A
Number 4 to Z

FAE Tel - - :, _, 0 to 9, a to z, A
Number 5 to Z

Serial Port Northbound Port Mode Manual Manual, Automatic

Protocol Type Modbus M/S Protocol,


NOTE Protocol YDN1363 Protocol,
This Modbus Protocol
parameter is
displayed
only when
Port Mode is
set to
Manual.

YDN1363 Baud Rate - 9600 1200, 2400, 4800,


Protocol 14400, 115200,
9600, 19200

Comm. - 1 1 to 254
Address

Modbus Baud Rate - 9600 1200, 2400, 4800,


Protocol 14400, 115200,
9600, 19200

Comm. - 33 0 to 254
Address

M/S Baud Rate - 9600 1200, 2400, 4800,


Protocol 14400,115200,9600,
19200

Comm. - 3 0 to 31
Address

Mobile Data Carrier - Automatic Automatic, Others


Operator

SIMn Acc - - A maximum of 28


Point Name characters,
NOTE including lowercase
This parameter English letters (a to
is displayed z), uppercase
only when English letters (A to
Carrier
Z), digits (0 to 9),
Operator is
set to Others. and special
characters (@_#*-.).

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 221


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

SIMn Access - -
Point No
NOTE
This parameter
is displayed
only when
Carrier
Operator is
set to Others.

SIMn User - -
Name
NOTE
This parameter
is displayed
only when
Carrier
Operator is
set to Others.

SIMn User - - A maximum of 27


Password characters,
NOTE including lowercase
This parameter English letters (a to
is displayed z), uppercase
only when English letters (A to
Carrier
Z), digits (0 to 9),
Operator is
set to Others. and special
characters (@_#-.).
It is recommended
that the password
contain at least two
types of characters
and the length
exceed six
characters.

WiFi WIFI Enable - - Enable Enable, Disable


Settings
Wifi SSID - - POWER_SITE A maximum of 31
NOTE
This characters,
parame including lowercase
ter is English letters (a to
displaye z), uppercase
d only English letters (A to
when
Z), digits (0 to 9),
the
WIFI is and special
connect characters (@_#-.).
ed.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 222


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Password - - Changeme A maximum of 31


characters,
including lowercase
English letters (a to
z), uppercase
English letters (A to
Z), digits (0 to 9),
and special
characters (@_#-.).
It is recommended
that the password
contain at least two
types of characters
and the length
exceed eight
characters.

Local Language - - English English, Chinese,


Paramet Russian, Spanish,
ers Portuguese, French,
Italian, German,
Turkish, Japanese

Site ID Site ID - - -

System Type - - - -

Date and Time Zone - UTC +08:00 Time zones of all


Time Beijing the major cities in
the world. For
details, see the
WebUI.

Date and Time - - -

NTP Enable - No Yes, No

NTP Primary 127.0.0.1 -


IP
NOTE
This parameter
is displayed
only when
NTP Enable is
set to YES.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 223


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

NTP Backup IP - 127.0.0.1 -


NOTE
This parameter
is displayed
only when
NTP Enable is
set to YES.

NTP Port - 123 1 to 65535


Number
NOTE
This parameter
is displayed
only when
NTP Enable is
set to YES.

NTP Sync. - 1 min 1 to 1440


Tnterval
NOTE
This parameter
is displayed
only when
NTP Enable is
set to YES.

LCD Contrast - 5 0 to 10
Contrast

Reset Web - - - -
Password
NOTE
Only
displayed
when
logged in as
an
administrat
or.

Restore Restore - - Yes Yes


Settings Factory Set.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 224


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

A.4 Running Control


Table A-5 Running Control menu hierarchy
Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range
Level Menu Menu Menu
Menu

Site Unit - - - - -

DC Power DC Power Control Mode - Automatic Automatic,


Manual,
Maintenance

DC Output - - - -
Distribution

DMU

Rectifier Rectifier Group OV Lock Reset - Yes Yes


NOTE
This parameter is
displayed only
when the rectifier
type is a CAN
communications
module.

Collect Fault Info - Yes Yes

Rectifier n - - - -

Controller Block Alarm - - No Yes, No

Reset SMU - - Yes Yes

Switch to IP - - Yes Yes


Net.

Sw. to - - Yes Yes


WirelssNet.
NOTE
This parameter
is displayed
only when the
Comm Exp
Board is
connected.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 225


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Sw. to Inband - - Yes Yes


Net.
NOTE
This parameter
is displayed
only when the
BBU is
connected.

Upload Sensor - - Stop Start, Stop


Logs

Combined Controller Block Alarm - No Yes, No


Cab
Reset SMU - Yes Yes

Switch to IP Net. - Yes Yes

Sw. to Inband - Yes Yes


Net.
NOTE
This parameter is
displayed only
when the BBU is
connected.

Sw. to WirelssNet. - Yes Yes


NOTE
This parameter is
displayed only
when the Comm
Exp Board is
connected

DC Output
Distribut

Battery BC Control - - Stop Stop, Start

Reset Batt. - - Yes Yes


Cap.

Battery - - Stop Stop, Start


Standard Tes

Short Test - - Stop Stop, Start


Control

Clear Test Log - - Yes Yes

Fast Charge - - Stop Stop, Start


Control

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 226


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Clear Backup - - Yes Yes


Log

Clear Batt Not Yes Yes


Exidy

GPS Del Com. Fail - - Yes Yes


GPS
NOTE
This parameter
is displayed
only when the
GPS fails to
communicate.

iDCDU iDCDU Group Clear iDCDU Loss - Yes Yes


Alm.

Mains Delete Mains - - Yes Yes

Genset Genset Group Control Mode - Automatic Automatic,


Manual

Genset n Fault Reset - Yes Yes

Maint Confirm - Yes Yes

Genset Self Confirm Self - Yes Yes


Check Check

Comm Comm Exp Module Reset - Yes Yes


Exp Board Board Group

Comm Exp Module Reset - Yes Yes


Board

iBOX # iBOX Equip n Del. Com. Fail Dev - Yes Yes


NOTE
This parameter
appears only if a
communications
failure iBOXalarm
is generated.

DTS # DTS Group DTS Control - Auto Auto, To


NOTE Battery
This parameter is Group1-4
displayed only
when Batt
Transfer Mode is
set to Discharge
Apart or
Discharge together
.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 227


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Del Com. Fail DTS - Yes Yes


NOTE
This parameter
appears only if a
communications
failure alarm is
generated.

DTSn Reset - Reset Reset

DCDB # DCDB Group Delete Com Fail - Yes Yes


DCDB
NOTE
This parameter
appears only if a
communications
failure alarm is
generated.

Clear DCDB Loss - Yes Yes


Alm.
NOTE
This parameter
appears only if a
DCDB loss alarm is
generated.

DCDB Reset - Yes Yes

DCDBn Basic Control Reset Yes Yes

Load Consum Clr All Load Yes Yes


Ctl Consum Clr

Load n Yes Yes


Consum
Clear

Camera Camera Group - - - -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 228


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Low Cap - - - - -
Li-ion
Batt
NOTE
This
paramete
r is
displayed
only
when
Battery
Model is
set to
BBS
4840Z.

Li Battery Li Battery Battery Standard - Stop Start, Stop


# Group Test
NOTE
This Clear Test Log - Yes Yes
paramete
r is Delete BMU - Yes Yes
displayed NOTE
only This parameter
when appears only if a
Battery communications
Model is failure alarm is
set to generated.
ESM-A,
ESU-A or Clear BMU Loss - Yes Yes
ESM-BX. Alm.
NOTE
This parameter
appears only if an
ESMU loss alarm is
generated.

AIM n Board Reset - - Yes Yes

Nonintelli DO Open Door - - Yes Yes


gent Lock
Rset Illg - - Yes Yes
DrOpen Alm

ATS ATS Group - - - -

ATS n - - - -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 229


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Efuse Efuse Group Clear EFUSE # - Yes Yes


Group # NOTE
This parameter is
displayed only
when the EFUSE
fails to
communicate.

EFUSE n - - - -

Temp. Fan Group Fan Control Mode - Automatic Manual,


Control Automatic

Heater Device Control Mode - Automatic Manual,


Automatic

Heater Control - Off On. Off


NOTE
This parameter is
displayed only
when Control
Mode is set to
Manual.

Sensor Smoke Sensor Reset Smoke - Yes Yes


# Sensor

MIMO MIMO Group Turn On/Off - Module On Module On,


Module Turn Off

Clear Mod Loss - Yes Yes


Alarm
NOTE
This parameter is
displayed only
when there is an
MIMO Lost alarm.

Clr Comm. Fail - Yes Yes


Equip
NOTE
This parameter is
displayed only
when the MIMO
fails to
communicate.

MIMO n Turn On/Off - On On, Off

24V AC Output - On On, Off


Control

12V DC Output - On On, Off


Control

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 230


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Clear Historical Delete His. - Yes Yes


Alarm Alarm Alarms

Active Alarm - - Clear Alarm Clear Alarm

Clear Clear Test Log - - Yes Yes


Batt. Test
Log

Output Test Enable - - No No, Yes


Relay Test
Test Duration - - 1 min 1-15
NOTE
This parameter
is displayed
only when Test
Enable is set to
Yes.

ALMn - - Open Open, Close


NOTE
This parameter
is displayed
only when Test
Enable is set to
Yes.

Hiber. Rect. Hiber. - - - -


Test Para. Speedup

Other iRELAY Ctrl to connect - Stop Star, Stop


Device Nodes
Control
Single Board - Yes Yes
Reset

Blink Control - Star Star, Stop

SIREN-S Ctrl - Opened Opened,


Closed

SIRNE-L Ctrl - Opened Opened,


Closed

iFUEL-RS485 1 - - - -

iDATA Board Reset - Yes Yes

Blink Ctr. - Stop Star, Stop

iACMETER Board Reset - Yes Yes

Sensor Blink - Stop Star, Stop

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 231


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Auto Adjust - Yes Yes


Sequence

WIM01C1 Ctrl to connect - On On, Off


Nodes

Board Reset - Yes Yes

WiFi Switch - Off On, Off

DG Comm Ex - - - -
Board

Blade Power Del Comm Failed - Yes Yes


Eq

A.5 Site Maintain


Table A-6 Site Maintain menu hierarchy
Second-Level Third-Level Fourth-Level Default Value Value Range
Menu Menu Menu

U Disk - - - -
Upgrade/Cfg

U Disk Hist Last Export - - -


Record Result

Upgrade/Cfg - - -
Result

Export File to - - - -
USB

Genset Self Confirm Self - Yes Yes


Check Check

Module Check Check Result Comm OK Equip - -


Num

Comm Fail Equip - -


Num

Normal Equip - - -
List

Abnormal Equip - - -
List

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 232


SMU02X V100R021C10 Site Monitoring Unit
User Manual A LCD Menu Hierarchy

A.6 User Management


Table A-7 User Management menu hierarchy
Second-Level Menu Default Value Range

Change Password - 0-9, a-z, A-Z

User Logout Yes Yes


NOTE
● Log out the current user.
● This parameter is displayed
only when you log in as an
administrator or engineer.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 233


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

B MDU Menu Hierarchy

Figure B-1 MDU menu hierarchy

Table B-1 MDU menu description

Menu Item Description

System Status View the running data of the power system and modules in the power system,
such as rectifiers and batteries.

Runnign View the running status of the AC input, rectifiers, batteries, and loads.

Alarm View the current alarms, historical alarms, and buzzer switch status.

Settings Set parameters for devices in the power system, such as rectifiers and
batteries.

Maintenance Export system running data and calibrate the touchscreen.

About View the model and version of the monitoring unit in the current system.

Common Set the buzzer and query historical alarms.


Functions

B.1 Running
Table B-2 Running menu hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

System Site ID - -
Overview

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 234


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

System Type - -

DC Output Voltate - -
(V)

Battery Status - -

Total Batt. Current - -


(A)

Ambient - -
Temperature (degC)

Ambient Humidity - -
(%)

Mains Mains State - -

AC Voltage

Phase L1 Voltage - -
NOTE
This parameter is not
displayed in the
single-phase, dual–live
wire, or three–live wire
scenario.

Phase L2 Voltage - -
NOTE
This parameter is not
displayed in the
single-phase, dual–live
wire, or three–live wire
scenario.

Phase L3 Voltage - -
NOTE
This parameter is not
displayed in the
single-phase, dual–live
wire, or three–live wire
scenario.

Line L1-L2 Volt (V) - -


NOTE
This parameter is not
displayed in the
single-phase, dual–live
wire, or three–live wire
scenario.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 235


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Line L2-L3 Volt (V) - -


NOTE
This parameter is not
displayed in the
single-phase, dual–live
wire, or three–live wire
scenario.

Line L3-L1 Volt (V) - -


NOTE
This parameter is not
displayed in the
single-phase, dual–live
wire, or three–live wire
scenario.

AC Current - -
NOTE
This parameter is not
displayed in the three-
phase or three–live
wire scenario.

Phase L1 Curr (A) - -


NOTE
This parameter is not
displayed in the
single-phase, dual–live
wire, or three–live wire
scenario.

Phase L2 Curr (A) - -


NOTE
This parameter is not
displayed in the
single-phase, dual–live
wire, or three–live wire
scenario.

Phase L3 Curr (A) - -


NOTE
This parameter is not
displayed in the
single-phase, dual–live
wire, or three–live wire
scenario.

AC Freq (Hz) - -

Battery Lead-Acid Battery Battery Status -


Group Info
Total Batt. Current (A) -

Total Rated Cap. (Ah) -

Remain Cap. Percent (%) -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 236


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Backup Time (h)

Cur. Limiting Status

Test Statis

Battery Temperature (degC)

LithiumBatte Basic Parameters Battery Status -


ry Group
Batt Voltage (V) -

Batt Current (A) -

Average Temperature (degC) -

Remain Cap. Percent (%) -

Backup Time (h) -

Total Capacity (Ah) -

Test Statis -

Basic LiBatt Li Battery n Batt Voltage (V) -


Cabinet n
Batt Currnet (A) -

Cell Pkg Volt (V) -

Cell Pkg Curr (A) -

Remain Cap. Percent (%) -

Cell n Temp (degC) -

Cell n Volt (V) -

Status -

Capacity (Ah) -

Rectifier Basic Parameters Total DC Curr (A) -


Group
Total Power (kW) -

Total AC Input Power (W) -

AC Cabinet n AC Distribution Line LI-L2 Volt (V) -

Line L2-L3 Volt (V) -

Line L3-L1 Volt (V) -

Phase L1 Current (A) -

Phase L2 Current (A) -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 237


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Phase L3 Current (A) -

AC Frequency (Hz) -

DC Cabinet n DC Cabinet Info DC Voltage (V) -

Total Load Current (A) -

DC Output Distribut. DC Load n Current (A) -


n
Load n Power (kW) -

DC Load n Cons (kWh) -

Rectifier Cab Rectifier Cabinet Info Qty of Rectifier -


n
Qty of Rect (On) -

Qty of Rect (Off) -

DC Output Distribut. DC Load n Current (A) -

Load n Power (kW) -

DC Load n Cons (kWh) -

AC Distribution Line LI-L2 Volt (V) -

Line L2-L3 Volt (V) -

Line L3-L1 Volt (V) -

Phase L1 Current (A) -

Phase L2 Current (A) -

Phase L3 Current (A) -

AC Frequency (Hz) -

Rectifier n Running State -

Line LI-L2 Volt (V) -

Line L2-L3 Volt (V) -

Line L3-L1 Volt (V) -

DC Output Curr (A) -

Rated Efficiency (%) -

Realtime Efficiency (%) -

Temperature (degC) -

Curr Limit State -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 238


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Menu Fourth-Level Menu Fifth-Level Menu


Level Menu

Barcode -

Combined DC Output Distribut. DC Load n Current (A) -


Cab n
Load n Power (kW) -

DC Load n Cons (kWh) -

AC Distribution Line LI-L2 Volt (V) -

Line L2-L3 Volt (V) -

Line L3-L1 Volt (V) -

Phase L1 Current (A) -

Phase L2 Current (A) -

Phase L3 Current (A) -

AC Frequency (Hz) -

Rectifier n Running State -

Line LI-L2 Volt (V) -

Line L2-L3 Volt (V) -

Line L3-L1 Volt (V) -

DC Output Curr (A) -

Rated Efficiency (%) -

Realtime Efficiency (%) -

Temperature (degC) -

Curr Limit State -

Barcode -

B.2 Alarm
Table B-3 Alarm menu hierarchy

Second-Level Third-Level Menu Default Value Value Range


Menu

Active Alarms - - -

Historical Alarms - - -

Buzzer On - - -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 239


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

B.3 Settings
Table B-4 settings menu hierarchy
Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range
Level Menu Menu Menu
Menu

Commo LUI - - - -
n Language

Date - - - -
Format

Date - - - -
Setting

Time Zone - - - -

Time - - - -

Current - - - -
User's
Password

Battery Basic Single-String - 2000


Group Parameters Cap. (Ah)

Float Charge - 53.5 42.0 to 58.0


Voltage (V)

Boost Charge - 56.4 42.0 to 58.0


Voltage (V)

Charge Limt - 0.15 0.05 to 0.50


Coef. (C10)

Charge Auto. BC - Enable Enable/Disable


Parameters Enable

FC-BC Cur. - 0.05 0.01 to 0.25


Coef. (C10)

FC-BC Cur. - 30 2 to 1440


Duration
(min)

FC-BC Cap. - 70 50 to 100


Percent (%)

Timed BC - Enable Enable/Disable


Enable

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 240


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Timed BC - 30 1 to 365
Interval (Day)

Timed BC - 9 1 to 24
Duration (h)

BC-FC Cur. - 0.01 0.01 to 0.25


Coef. (C10)

BC-FC Cur. - 30 2 to 540


Duration
(min)

BC Max - 18 5 to 48
Duration (h)

Mains Reco BC - Disable Enable/Disable


En.

AC Fail BC - 10 0 to 30
Duration
(min)

Temperatur TC Coefficient - 80 0 to 150


e Comp. (mV/degC)
Para
Nominal - 25 5 to 45
Temperature
(degC)

TC Upper - 45 40 to 45
Thres. (degC)

TC Lower - 5 0 to 25
Thres. (degC)

BLVD BLVD General - Enable Enable, Disable


Parameters Discon.

BLVD - Voltage Mode Voltage Mode,


Disconnect Capacity Mode,
Mode Time Mode
NOTE
This parameter
is displayed
only when
BLVD General
Discon. is set
to Enable.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 241


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

BLVD LVD - 43.2 V 36.0 to 56.0


Voltage NOTE
NOTE If the battery voltage
This parameter is below the value of
is displayed this parameter, the
only when BLVD route is
BLVD General disconnected.
Discon. is set The value of BLVD
to Enable. Voltage must be
lower than the value
of BLVD Connection
Voltage.

BLVD Con. - 51.5 V 37.0 to 58.0


Volt. NOTE
NOTE If the system voltage
This parameter exceeds the value of
is displayed this parameter, the
only when BLVD route is
BLVD General connected.
Discon. is set The value of BLVD
to Enable. Connection Voltage
must be higher than
the value of BLVD
Voltage.

BLVD n Time - 480 min 5 to 1000


(min)
NOTE
This parameter
is displayed
only when
BLVD n Mode
is set to Time
Mode

BLVD Delay - 60s 3 to 90


Time (s)
NOTE
This parameter
is displayed
only when
BLVD General
Discon. is set
to Enable.

BLVD Capacity - 5 0 to 99
(%)

Standard Time Test - Disable Disable/Planned


Test Para Mode Test/Scheduled Test

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 242


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Annual Battery - 0 0 to 6
Tests
NOTE
This parameter
is displayed
only when
Time Test
Mode is set to
Planned.

Sche. Test St. - 21:00:00 00:00:00 to 23:59:59


Time
(HH:MM:SS)
NOTE
This parameter
is displayed
only when
Time Test
Mode is set to
Scheduled
Test.

Sche. Test St. - 90 Day 2 to 999


Period NOTE
NOTE Interval for starting a
This parameter scheduled test.
is displayed
only when
Time Test
Mode is set to
Scheduled
Test.

Pre-BC Enable - Enable Enable/Disable

Constant Cur. - Disable Enable/Disable


Test

Test End - 46.0 44.2 to 53.0


Voltage (V)

Test End - 20 0 to 99
Capacity (%)

Test End - 5 -5 to 15
Temperature
(degC)

Test End Time - 480 1 to 6000


(min)

Short Test Short Test - Disable Enable/Disable


Parameters Enable

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 243


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Short Test - 30 1 to 365


Period (Day)

Short Test - 5 1 to 240


Time (min)

Short Test End - 45.0 V 44.2 to 53.0


Volt. (V)

H/L Temp. Very HT Prot. - Reduce DC Disable/Reduce DC


Protect Para Mode Voltage Voltage/Disconnect
Battery

Very HT Prot. - 51.5 42.0 to 53.0


Volt. (V)
NOTE
This parameter
is displayed
only when
Very HT Prot.
Mode is set to
Low Volt.

HT Alarm - 50 25 to 80
Thres. (degC)

Very HT Alarm - 53 25 to 80
Thres. (degC)

LT Alarm - –10 –20 to 20


Thres.
(degC)

Very LT Alarm - –20 –20 to 20


Thres. (degC)

Alarm Overcur. Alm. - 0.25 0.05 to 0.50


Parameters Thres.(C10)

Basic Reset Batt. - - Yes


Control Cap.

Clear Test Log - - Yes

Other Battery lnstall - - -


Parameters Time (YYYY-
MM-DD)

Lithium Basic ILock Enablde - Disablde Enablde/Disablde


Battery Parameters
Group BMU Manage - Host Manage Host Manage/ Auto
Model Manage

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 244


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

iLock Verify - 72 8 to 720


Timeout (h)

Stable Output - 57 48.0 to 57.0


Voltcvs (V)

Work Mode - 57V Mode 48V Mode/57V


Mode

Charge Boost Charge - 56.4 42.0 to 58.0


Parameters Voltage (V)

FV Voltage (V) - 53.5 42.0 to 58.0

Chg Curr Limt - 0.40 0.05 to 1.05


Coef. (C10)

Standard Time Test - Disable Disable/Planned


Test Para Mode Test/Scheduled Test

Annual Battery - 0 0 to 6
Tests
NOTE
This parameter
is displayed
only when
Time Test
Mode is set to
Planned.

Sche. Test St. - 21:00:00 00:00:00 to 23:59:59


Time
(HH:MM:SS)
NOTE
This parameter
is displayed
only when
Time Test
Mode is set to
Scheduled
Test.

Sche. Test - 365 Day 2 to 999


Period (Day)
NOTE
This parameter
is displayed
only when
Time Test
Mode is set to
Scheduled.

Test End - 50.0 44.2 to 53.0


Voltage (V)

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 245


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Test End Time - 480 1 to 6000


(min)

Test End - 15 0 to 99
Capacity (%)

Basic Del Batt Fail - Yes -


Control Comm

Rectifier Basic Default - 53.5 48.0 to 58.0


Group Parameters Output Volt
(V)

High Rect. - 5 0 to 150


Capacity (%)

Low Rect. - 75 0 to 150


Capacity
(%)

Sequential St. - 0 0 to 20
Int. (s)

OV Prot. - 59.5 58.5 to 60.5


Thres. (V)

WALK-IN - No Yes/No
Enable

WALK-IN Time - 8 8 to 200


(s)
NOTE
This parameter
is displayed
only when
WALK-IN
Enable is set
to Yes.

Lost Phase - - -
Enable

Hibernation Hibernation - No Yes/No


Parameters Enable NOTE
● No: Hibernation is
disabled.
● Yes: The
monitoring unit
hibernates
rectifiers when
the hibernation
condition is met.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 246


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Hibernation - Intelligent Intelligent Mode/


Mode Mode High Efficiency
NOTE Mode/Time Mode
This parameter ● Time Mode:
is displayed
Rectifiers with
only when
Hibernation shorter runtime
Enable is set take precedence
to Yes. for work.
● High Efficiency
Mode: Rectifiers
with higher real-
time efficiency
take precedence
for work.
● Intelligent
Mode: The
monitoring unit
instructs
rectifiers to
hibernate based
on the rectifier
runtime and
real-time
efficiency.

Min. Work - 2 1 to 100


Rect Qtu. NOTE
(Day) Minimum number of
NOTE working rectifiers
This parameter allowed after
is displayed hibernation is
only when enabled.
Hibernation
Enable is set
to Yes.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 247


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Rotation - 7 1 to 365
Period (Day) NOTE
NOTE Period for alternating
This parameter hibernating rectifiers
is displayed with working
only when rectifiers. When the
Hibernation period expires, the
Enable is set monitoring unit
to Yes. starts all rectifiers.
When the rectifiers
have worked for 2
hours, the
monitoring unit
instructs some of
them to hibernate
again.

Best Efficiency - 55 10 to 100


(%) NOTE
NOTE Percentage of the
This parameter rectifier loading
is displayed capacity to the rated
only when capacity, at which the
Hibernation rectifier reaches
Enable is set maximum efficiency.
to Yes.

Min. Rdnt. - 0.20 0.05 to 1.00


Coef. NOTE
Ratio of the
minimum redundant
current to the rated
rectifier current.
For example, if the
rated rectifier current
is 50 A and a
redundant current of
10 A is required, set
Min. Redundant
Coefficient to 0.2
(10 A/50 A = 0.2).

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 248


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Phase Balance - Disable Disable/Absolute


NOTE Balance/Relatove
This parameter Balance
is displayed NOTE
only when If the configuration
Hibernation of rectifiers meets
Enable is set the three-phase
to Yes. balance requirement
and intelligent
rectifier hibernation
is enabled in a three-
phase power system,
the rectifiers
corresponding to the
three phases try to
hibernate.
● Absolute
Balance: The
same quantity of
rectifiers must
correspond to any
two phases.
● Relative Balance:
The difference in
quantity between
the working
rectifiers
corresponding to
any two phases
must be less than
or equal to 1.

Hiber. without - No Yes/No


Batt.
NOTE
This parameter
is displayed
only when
Hibernation
Enable is set
to Yes.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 249


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Hiber. Stop - 72.0 0.5 to 168.0


Duration (h) NOTE
NOTE All rectifiers stop
This parameter hibernation if the
is displayed power system
only when experiences an
Hibernation exception. After the
Enable is set power system
to Yes. recovers, rectifiers
attempt to hibernate
again when the time
specified by
Hibernation Stop
Duration has
elapsed.

Basic Reset Protect - Yes Yes


Control

Mains Basic AC Mode - 3-Phase 3-Wire 2-Phase 2-Wire, 1-


Parameters Phase, 3-Phase 4-
Wire, 3-Phase 3-
Wire

Alarm AC High Freq - 66 40 to 70


Parameters Thres.(Hz)

AC Low Freq - 45 40 to 70
Thres.(Hz)

DC DC Output LLVD Enabled - Enable Enable, Disable


Cabinet Distribut.
n LLVD Mode - Voltage Mode Voltage Mode,
NOTE Capacity Mode,
This parameter Time Mode
is displayed
only when
LLVD Enabled
is set to
Enable.

LLVD Voltage - 44.0 36.0 to 56.0


(V)

LLVD Recon - 51.5 37.0 to 58.0


Volt (V)

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 250


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

LLVD Time - 360 5 to 1000


(min)
NOTE
This parameter
is displayed
only when
LLVD Mode is
set to Time
Mode.

LLVDn - 15% 0 to 99
Capacity (%)
NOTE
This parameter
is displayed
only when
LLVD Mode is
set to
Capacity
Mode.

LLVD PD Enb - Disable Enable/Disable

LLVD PD Time - 23:00:00 00:00:00 to 23:59:59

LLVD PD - 480 1 to 1439


Duration
(min)

LLVD HTD Enb - Disable Enable/Disable

LLVD HTD - 65.0 25.0 to 80.0


Temp (degC)

DC Over - 58.0 53.0 to 60.0


Voltage (V)

DC Under - 45.0 36.0 to 57.0


Voltage (V)

Ultra Over - 59.0 53.0 to 60.0


Volt (V)

Ultra Under - 44.0 36.0 to 56.0


Volt (V)

Rectofoe DC Output LLVD Enabled - Disable Enable, Disable


r Cab n Distribut.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 251


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

LLVD Mode - Voltage Mode Voltage Mode,


NOTE Capacity Mode,
This parameter Time Mode
is displayed
only when
LLVD Enabled
is set to
Enable.

LLVD Voltage - 44.0 36.0 to 56.0


(V)

LLVD Recon - 51.5 37.0 to 58.0


Volt (V)

LLVD Time - 360 5 to 1000


(min)
NOTE
This parameter
is displayed
only when
LLVD Mode is
set to Time
Mode.

LLVDn - 15% 0 to 99
Capacity (%)
NOTE
This parameter
is displayed
only when
LLVD Mode is
set to
Capacity
Mode.

LLVD PD Enb - Disable Enable/Disable

LLVD PD Time - 23:00:00 00:00:00 to 23:59:59

LLVD PD - 480 1 to 1439


Duration
(min)

LLVD HTD Enb - Disable Enable/Disable

LLVD HTD - 65.0 25.0 to 80.0


Temp (degC)

DC Over - 58.0 53.0 to 60.0


Voltage (V)

DC Under - 45.0 36.0 to 57.0


Voltage (V)

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 252


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Ultra Over - 59.0 53.0 to 60.0


Volt (V)

Ultra Under - 44.0 36.0 to 56.0


Volt (V)

Combine DC Output LLVD Enabled - Disable Enable/Disable


d Cab n Distribut.
LLVD Voltage - 44.0 36.0 to 56.0
(V)

LLVD Recon - 51.5 37.0 to 58.0


Volt (V)

LLVD PD Enb - Disable Enable/Disable

LLVD PD Time - 23:00:00 00:00:00 to 23:59:59

LLVD PD - 480 1 to 1439


Duration
(min)

LLVD HTD Enb - Disable Enable/Disable

LLVD HTD - 65.0 25.0 to 80.0


Temp (degC)

DC Over - 58.0 53.0 to 60.0


Voltage (V)

DC Under - 45.0 36.0 to 57.0


Voltage (V)

Ultra Over - 59.0 53.0 to 60.0


Volt (V)

Ultra Under - 44.0 36.0 to 56.0


Volt (V)

Commu IP Address IP Address - Automatic Automatic (DHCP)/


nications Settings Allpcation (DHCP) Manual

IP Address - - -

Subnet Mask - - -

Gateway - - -

Quick Battery - - Other AGISSON, Coslight,


Settings Vendor Dengta, Eltek,
EnerSys, Exide,
LEOCH, Narada,
NorthStar, Shoto,
Other

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 253


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Battery - - 12 V VRLA DCB-A, DCB-A1,


Mode DCB-B, DCB-Y, ESU-
A, ESM-A, ESM-BX,
FCB-A, FCB-B, SCB-
A, SCB-A1, TCB-A,
TCB-B, TCB-C, 12V
VRLA, 2V VRLA,
FLOOD, 6-GFM-X,
6-GFMF, Rebak-
F4899T, 12TD-F,
SBS-F, M12V-FT,
LPF12-H, 6-GFM-F,
12NDF, Blue, Red, 6-
FMX, 6-XFMJ, GFM,
BBS 4840Z
NOTE
This parameter is
related to battery
manufacturers.

FC Voltage - - 53.5 42.0 to 58.0


(V)

Boost - - 56.4 42.0 to 58.0


Charge
Voltage (V)

Date - - - -
Format

Date - - - -
Setting

Time Zone - - - -

Time - - - -

Setup Sensor DC SPD - Yes Yes, No


Paramet Config
er AC SPD - Yes Yes, No

Door Sensor - No Yes, No

Water Sensor - No Yes, No

Smoke Sensor - No Yes, No

Ambient - Yes Yes, No


Temp. Sensor

Ambient - Yes Yes, No


Humi. Sensor

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 254


SMU02X V100R021C10 Site Monitoring Unit
User Manual B MDU Menu Hierarchy

Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range


Level Menu Menu Menu
Menu

Batt. Temp. - Yes Yes, No


Sensor 1

Clr - - - - -
Comm
Fail
Device

AC Slor AC Cabinet - - 1 1 go 8
Config n

DC Slor DC Cabinet - - 1 1 to 8
Config n

B.4 Maintenance
Table B-5 Maintenance menu hierarchy
Second- Third-Level Fourth-Level Fifth-Level Default Value Value Range
Level Menu Menu Menu
Menu

USB - - - - -
Wizard

B.5 About
Table B-6 About menu hierarchy
Second-Level Third-Level Fourth-Level Default Value Value Range
Menu Menu Menu

SMU - - - -

Vendor - - - -

SMU Version - - - -

Version Details - - - -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 255


SMU02X V100R021C10 Site Monitoring Unit
User Manual C Technical Specifications

C Technical Specifications

Table C-1 SMU02C technical specifications


Category Item Specifications

Environmental Operating temperature –40°C to +70°C


conditions
Transportation –40°C to +70°C
temperature

Storage temperature –40°C to +70°C

Operating humidity 5%–95% RH (non-condensing)

Storage humidity 5%–95% RH (non-condensing)

Altitude 0–4000 m
When the altitude ranges from 3000 m to 4000 m,
the operating temperature decreases by 1ºC for
each additional 200 m.

Power supply Input voltage range 36–72 V DC

Maximum current 0.5 A DC

Structure Dimensions (H x W x 40.8 mm x 99 mm x 194.3 mm


D)

Weight ≤ 1.5 kg

MTBF (mean time between failures) ≥ 250,000 hours

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 256


SMU02X V100R021C10 Site Monitoring Unit
User Manual D FAQ

D FAQ

D.1 How Do I Prepare the WebUI Operating


Environment?
Before logging in to the WebUI, you need to prepare the WebUI operating
environment to connect to the monitoring unit.

Operating Environment
Supported operating system: Windows 10 or later

Browser: Internet Explorer 8.0 or later, FireFox 13 or later, and Chrome 20

NOTE

Internet Explorer is used as an example to illustrate all WebUI operations mentioned in this
document.

Setting a LAN

NOTICE

If the monitoring unit is connected to a LAN and a proxy server has been selected,
cancel the proxy server settings.

If the monitoring unit is connected to the Internet but your computer is connected
to a LAN, do not cancel the proxy server settings. Otherwise, you cannot access
the SMU.

To cancel proxy server settings, perform the following steps:

1. Open Internet Explorer.


2. Choose Tools > Internet Options.
3. Choose Connections tab, click LAN Settings.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 257


SMU02X V100R021C10 Site Monitoring Unit
User Manual D FAQ

4. Clear Use a proxy server for your LAN.

Figure D-1 Canceling proxy server settings

5. Click OK.

Setting Internet Explorer Security

NOTICE

Set Internet Explorer security before you perform the following operations:

● Export historical logs, historical data, statistics, and battery test records.
● Upload system configuration files.
● Download system configuration files.
● Upgrade software.
To set Internet Explorer security, perform the following steps:
1. Open Internet Explorer.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 258


SMU02X V100R021C10 Site Monitoring Unit
User Manual D FAQ

2. Choose Tools > Internet Options.


3. Choose Security Tab.
4. Click Internet and click Custom level. After you specify Internet security
settings, click Local intranet and click Custom level.

Figure D-2 Internet Explorer security

5. Specify the security settings.


Enable the following:
– Initialize and script ActiveX controls not marked as safe for scripting
– Allow previously unused ActiveX controls to run without prompt
– Include local directory path when uploading files to a server

Figure D-3 Internet Explorer security setting 1

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 259


SMU02X V100R021C10 Site Monitoring Unit
User Manual D FAQ

Figure D-4 Internet Explorer security setting 2

Figure D-5 Internet Explorer security setting 3

6. Click OK.
7. Click the Advanced tab, and select Use SSL 3.0, Use TLS 1.0, Use TLS 1.1,
and Use TLS 1.2.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 260


SMU02X V100R021C10 Site Monitoring Unit
User Manual D FAQ

Figure D-6 Internet Explorer security setting 5

8. Click OK.

D.2 What Should I Do If I Forgot the Password?


The monitoring unit allows users to change passwords mutually on the WebUI
and LCD. For example, if you forgot the WebUI login password, you can change
the WebUI password on the LCD.

Table D-1 Resetting the WebUI password on the LCD


Main Menu Second-Level Third-Level Menu Setting
Menu

Parameters Local Reset Web Password Set based on site


Settings Parameters NOTE requirements.
The menu is displayed
only when the login
account is an
administrator account.

For details about how to change the LCD password on the WebUI, see 5.2.5
Changing a User Password. Select the user whose login source is LCD for
changing.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 261


SMU02X V100R021C10 Site Monitoring Unit
User Manual D FAQ

NOTE

● There are 2 LCD account, see 3.1.4 Password.


● The WebUI account is admin and the password is Changeme by default.

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 262


SMU02X V100R021C10 Site Monitoring Unit
User Manual E Acronyms and Abbreviations

E Acronyms and Abbreviations

A -
AC Alternating current
B -
BBU Baseband unit
BLVD Battery low voltage disconnected
C -
CAN Control area network
D -
DC Direct current
DCB Deep cycle battery
DIN Dry contact input
DOD Depth of discharge
DTS DC transfer switch
E -
ESD Electrostatic discharge
ESM Energy storage module
ESU Energy storage unit
F -
FCB Fast charge battery
FE Fast Ethernet
H -
HTTPS Hypertext Transfer Protocol Secure
I -

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 263


SMU02X V100R021C10 Site Monitoring Unit
User Manual E Acronyms and Abbreviations

IMEI international mobile equipment


identity
IP Internet Protocol
L -
LCD Liquid crystal display
LLVD Load low voltage disconnected
N -
NMS Network management system
S -
SCB Solar cycle battery
SMU Site monitoring unit
SNMP Simple Network Management Protocol
SOH State of health
SPM Site Power Management
U -
UI User interface
UIM User interface module
USB Universal Serial Bus

Issue 03 (2021-08-28) Copyright © Huawei Technologies Co., Ltd. 264