LOCAL LOCAL
TIME SUN TIME SUN
SIZE * SQ FT= CU.FT ESTIMATE FOR TIME PEAK LOAD TIME
6.00pm-
HOURS OF OPERATION January
AREA OF SUN GAIN
QUANTITY OR TEMP
ITEM (SQ FT) DIFF FACTOR BTU/HOUR . CONDITION DB WB %RH DP GR/LB
O
SOLAR HEAT GAIN GLASS OUTDOOR (OA) 34.7685 C 60.62 150
O
GLASS 38.736 19.8 0.5 383.4864 ROOM (RM) 24 C 50 66
S:South GLASS 38.736 0 0 DIFFERENCE 84
GLASS
GLASS VENTILATION PEOPLE* CFM/PERSON =
GLASS SQ FT* CFM/SQ FT =
GLASS
GLASS
GLASS
CFM VENTILATION =
SOLAR &TRANS GAIN--- WALL &ROOF
SWINGING
REVOLVING
WALL-Exposed 117.1764 19.8 0.1 232.009272 DOOR PEOPLE * CFM/PERSON =
WALL- Shaded 38.9781 19.8 0.1 77.176638
WALL INFILTRATION OPEN DOORS DOORS * CFM/DOOR =
WALL EXHAUST FAN
ROOF -SUN CRACK FEET * CFM/FT =
ROOF -SHADED
APPARATUS DEWPOINT
EFFECTIVE
SENS HEAT
TRANS GAIN - EXCEPT WALLS & ROOF ESHF FACTOR = ERSH/ERTH =
ALL GLASS 10 0
PARTITION WALL 220.13346 10 0.44 968.587224 ADP INDICATED ADP = SECLECTED ADP =
CEILING 236.72 10 0.39 923.208
FLOOR
INFILTRATION 67.02 19.8 1.08 1433.15568 DEHUMIDIFIED AIR QUANTITY
TEMP RISE (1-BF) * (TRM -TADP )=
INTERNAL HEAT
NUMBER HEAT BTU/HR
PEOPLE 1 250 250 DEHUM CFM ERSH/1.08*TEMP RISE= CFMDA
LIGHTS 3.4 0 0
APPLIANCES 473.44 3.4 1 1609.696 OUTLET TEMP DIFF RSH/1.08* CFMDA=
F(RM-OUTLET AIR)
LIGHTS-CORRIDOR 0 3.4 0.35 0
SUPPLY AIR QUANTITY
SUPPLY CFM RSH/1.08* F DESIRE DIFF= CFMSA
SUB TOTAL 5877.31921
STORAGE BYPASS FACTORCFMSA - CFMDA = CFMBA
SUB TOTAL
SAFETY FACTOR 15% 881.597882 RESULTING ENT & LVG CONDITIONS AT APPARATUS
SUB TOTAL . 6758.9171
EDB TRM + CFMOA/CFM*
(TOA-TRM)= TEDB
ROOM SENSIBLE HEAT LDB TADP+ BF* (TEDB-TADP)= TLDB
SUPPLY
DUCT
SUPPLY DUCT HEAT LEAKAGE
GAIN % + LOSS % + FAN H.P % FROM PSYCH CHART: TEWB, TLWB
RETURN DEHUM&
DUCT HEAT RETURN DUCT PIPE LOSS
GAIN %+ LEAKAGE GAIN %+ HP PUMP%+%