You are on page 1of 20

Tube side velocity Calculation

Cooling water Line size 1.000 inch


cooling water flow 2.000 M3/Hr
Daimeter Of Tube 0.017 m
No of Tubes 74.000
No of pass 4
Tube cross sectional area 0.00024 m2
Total Flow Area per pass 0.00440 M2
Water Mass velocity 126.354 Kg/sm2
Density of water 1000 kg/m3
water linear velocity 0.126 m/s

Pressure Drop Calculation


Velocity in Tube Ut 0.126 m/Sec
Daimeter of the tube D 0.017 m
Viscosity of Water µ 0.001 mNs/M2~kg/m.s
Density of Tube side fluid ρ 1000 Kg/M3
Reynolds No Nre 2198.55
Correction factor jf 0.004 From Figure
No of Pass Np 4.0
Length L 2.0 m
Tube Side Pressure Drop 206.08 N/M2~Pa
Tube Side Pressure Drop 0.21 KPA
Tube Side Pressure Drop 0.00 bar
Temprature of Utility 10 °C
Tube side heat transfer Co efficient 702.65 W/M2°C
Tube side heat transfer Co efficient 604.28 Kcal/hr M2 °C

Heat exchanger Area 9 m2


Tube length 2 m
No. of tubes 73
Tube selected 3/4" 16 BWG Referance:-
OD 19.05 mm
Tube ID 17.399 mm
No. of passes 4
CHW Line size 2.000 inch
CHW flow 14 M3/Hr
Tube velocity 0.687 m/s
Tube side Pressure drop 0.06 Bar
Input
output
From Figure

Reference:-RC-6 Page No.:-667

https://www.engineeringpage.com/technology/thermal/tubesize.html
2.040816
Heat Exchanger Area Calculation
Solvent Name ACETONE
Boilup rate 500
Specific Heat Cp 0.52
Latent Heat λ 125
Inlet Temp T1 56
Outlet temp T2 30
CHW inlet Temp T3 10
CHW Outlet Temp T4 14
Overall HTC U 200
LMTD Tlm 29.7
Heat Heat Q 69260.0
Area A 11.7
CHW requirement 17.315
17315

Flow Rate 17
Velocity 2
0.003
0.055
Pipe nominal size 55
50NB
Length 1.5
No. of tubes 127

163
A B
Kg/Hr INPUT
Kcal/Kg
Kcal/Kg
°C 366
°C
°C Reference
°C 1 https://www.engineersedge.com/thermodynamics/overall_he
Kcal /hr. m2°C 2 applied process design-3 ludwig page No.95
°C
kcal/hr
m2
m3/Hr
Kg/Hr

m3/hr
m/s

m
mm

m
C

m/thermodynamics/overall_heat_transfer-table.htm
g page No.95