ANNEX D (ii)- ELECTRICAL DRAWINGS

LIST OF DRAWINGS
00 T-101-016-C-E00 Drawing List

01 T-101-016-C-E01 ELECTRICAL NOTES - 1

02 T-101-016-C-E02 ELECTRICAL NOTES - 2

03 T-101-016-C-E03 LIGHTING LAYOUT

04 T-101-016-C-E04 LIGHTING SCHEDULE

POWER ALARM LAYOUT


05 T-101-016-C-E05

06 T-101-016-C-E06 DISTRIBUTION BOARD SCHEMATIC

07 T-101-016-C-E07 SOLAR POWER SCHEMATIC

08 T-101-016-C-E08 SOLAR DESIGN


GENERAL
THE DESIGN DRAWINGS SHALL BE READ IN CONJUNCTION CABLE SIZES, MCB's,MCCBs AND ISOLATORS SHOWN ON CONDUITS, CABLE TRAYS AND TRUNKING
WITH THE RELEVANT SPECIFICATIONS AND THE DRAWINGS ARE BASED ON DESIGNED LOADS. THE THE MINIMUM SIZE OF CONDUIT USED FOR ANY SYSTEM
ARCHITECTURAL, INTERIOR DESIGN, STRUCTURAL, CIVIL & CONTRACTOR SHALL PROVIDE THE SIZE OF CABLE, MCB, WIRING SHALL BE 20MM INTERNAL DIAMETER.
MECHANICAL DRAWINGS AND SPECIFICATIONS. MCCB AND ISOLATOR BASED ON ACTUAL LOADS OF THE PVC CONDUITS SHALL BE HEAVY GAUGE, POLISHED AND
THESE NOTES ARE GENERALLY APPLICABLE TO THE EQUIPMENT APPROVED BY THE ENGINEER AT NO EXTRA SMOOTH INSIDE AND OUTSIDE, FLAME-RETARDANT AND
OVERALL SYSTEMS INSTALLATION. ANY ADDITIONAL COST.
NOTES ON INDIVIDUAL DRAWINGS WHICH ARE
SUPPLEMENTARY TO THESE NOTES SHALL BE READ WITH FOR SPECIAL SYSTEMS, THE CONTRACTOR IS TO SUBMIT RIGID STEEL CONDUITS (RSC) SHALL BE HEAVY GAUGE,
THE INSTRUCTIONS STATED HEREIN. SHOP DRAWINGS PREPARED BY SPECIALISTS HOT DIP GALVANIZED TO CLASS 4 PROTECTION BOTH
THE FINAL POSITION OF ALL EQUIPMENT, PANELS, EXPERIENCED IN THE DESIGN OF THE RELEVANT SYSTEMS INSIDE AND OUTSIDE.
LUMINAIRES, DETECTORS, SWITCHES, OUTLETS AND AND AS PER THE MANUFACTURERS REQUIREMENTS. ALL PVC BOXES SHALL BE RIGID, FLAME-RETARDANT,
OTHER ACCESSORIES SHALL BE COORDINATED WITH THE CABLES SMOOTH AND ACCORDING TO LATEST
ARCHITECTURAL, MECHANICAL AND INTERIOR DESIGN STANDARDS/SPECIFICATIONS.
DETAILS AND WILL BE APPROVED AT SITE BY THE ALL WIRES AND CABLES SHALL BE STRANDED COPPER CONDUCTORS, ALL STEEL BOXES SHALL BE HEAVY GAUGE, HOT DIP
ENGINEER. PVC INSULATED COMPLYING WITH BS 6004 OR XLPE INSULATED AS PER GALVANIZED ACCORDING TO LATEST
UNLESS OTHERWISE SPECIFIED ALL EQUIPMENT AND IEC 502 AS SHOWN ON DRAWINGS OR SCHEDULES, EXCEPT FOR STANDARDS/SPECIFICATIONS.
MATERIALS TO BE USED SHALL BE SUITABLE AND RATED INFLAMABLE/EXPLOSIVE AND OTHER EXCEPTIONAL SITUATIONS.
BRASS BUSHINGS AND RINGS SHALL BE USED TO SECURE
FOR THE SITE AMBIENT CONDITIONS. COLOUR CODE OF ELECTRICAL WIRES AND CABLES SHALL
STEEL CONDUITS WITH STEEL BOXES.
ALL ELECTRICAL WORKS SHALL COMPLY WITH THE BE RED, YELLOW, BLUE, BLACK AND GREEN/YELLOW FOR
RELEVANT MINISTRY OF BUBLIC WORKS REGULATIONS, L1, L2, L3, NEUTRAL AND EARTH RESPECTIVELY IN A ALL STEEL COUPLERS SHALL BE PAINTED SUITABLY,
LATEST EDITION OF IEE WIRING REGULATIONS, THREE PHASE CONFIGURATION. IMMEDIATELY AFTER INSTALLATION.
INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC) THE CONDUCTOR SIZES FOR ALL CABLES SHALL BE IN
NO CONDUIT RUN SHALL BE LONGER THAN 15M
STANDARDS AND ISO RECOMMENDATIONS. ACCORDANCE WITH THE PANEL BOARD/CABLE
SCHEDULES AND SINGLE LINE DIAGRAMS.
THE INSTALLATION SHALL COMPLY IN ALL RESPECTS TO OTHERWISE IT MUST BE PASSED THROUGH PULL OR
THE REQUIREMENTS OF THE MANUFACTURERS AND THE THE MINIMUM SIZE OF ALL CIRCUIT CONDUCTORS SHALL DRAW BOX SUFFICIENT TO PERMIT EASY PULLING OF
CODES REFERRED IN THE SPECIFICATIONS. BE COORDINATED WITH THE STARTING AND OPERATING WIRES.
CHARACTERISTICS OF THE EQUIPMENT THEY SERVE.
ANY EQUIPMENT DIMENSIONS AND ELECTRICAL LOAD THE TOTAL FILL OF THE WIRES DRAWN IN CONDUIT SHALL
STATED ON THE DRAWINGS SHALL BE UNLESS OTHERWISE INDICATED, MINIMUM WIRE SIZE BE AS PER IEE REGULATIONS AND NORMALLY NOT TO
COORDINATED/CONFIRMED WITH THE ACTUAL EXCEED 40% OF THE INTERNAL CROSS-SECTIONAL AREA
DIMENSIONS AND ACTUAL ELECTRICAL LOAD OF OF THE CONDUIT.
EQUIPMENT FROM RESPECTIVE MANUFACTURER(S). LIGHTING AND SMALL POWER INSTALLATION SHALL BE ALL CONDUITS AND RECEWAYS PASSING THROUGH THE
ALL MATERIALS AND EQUIPMENT MUST BE OF THE BEST CARRIED OUT USING SINGLE CORE PVC INSULATED BUILDING EXPANSION JOINTS SHALL BE PROVIDED WITH
QUALITY AND ACCORDING TO THE LATEST INTERNATIONAL WIRES IN RIGID PVC CONDUITS EMBEDDED IN CONCRETE. EXPANSION JOINT COUPLING AND EXECUTED AS PER
STANDARDS. THE CONTRACTOR SHALL SUBMIT SAMPLES STANDARD DETAILS, APPROVED BY THE ENGINEER ON
ALL MULTICORE CABLES INSIDE THE BUILDING SHALL BE SITE.
AND CATALOGUES OF ALL MATERIALS AND OBTAIN INSTALLED ON CABLE TRAYS OR CABLE LADDERS. RAISED
ENGINEER'S APPROVAL BEFORE THE COMMENCEMENT OF SUN SHADES (COVERS) SHALL BE PROVIDED FOR ALL ALL BENDS IN DUCTS, CONDUITS AND OTHER RACEWAYS
ANY WORK. ROOF MOUNTED CABLE TRAYS/LADDERS. SHALL BE SUITABLE TO ALLOW MINIMUM CABLE BENDING
IT SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY RADIUS IN ACCORDANCE WITH MANUFACTURER'S
THE WIRES/CABLES FOR LV CIRCUITS INSIDE BUILDINGS RECOMMENDATIONS.
TO LIASE WITH THE LOCAL ELECTRICITY SUPPLY
SHALL BE INSTALLED AT A MINIMUM DISTANCE OF 300MM
AUTHORITY FOR THE ELECTRICITY SUPPLY CONNECTION ALL ENDS OF BURIED DUCTS AND CONDUITS SHALL HAVE
FROM HOT WATER LINES AND 150MM FROM OTHER
TO THE FACILITY AND MAKE PROVISIONS IN INSTALLATION BELL MOUTH PIPE ENDS AND SHALL BE SEALED BY A
SERVICE PIPES.
TO SATISFY THEIR REQUIREMENTS. THE SERVICES PROPRIETARY PIPE SEALING PRODUCT.
PROVIDED SHALL CONFORM IN ALL RESPECTS WITH THE WHERE EXTERNAL CABLES ARE DIRECT BURIED IN THE
LOCAL CODES AND REGULATIONS. GROUND, THESE SHALL RUN THROUGH UNDERGROUND CABLE LADDERS AND CABLE TRAYS SHALL BE INSTALLED
IT SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY CONCRETE ENCASED UPVC DUCTS WHEN PASSING UNDER WHERE NECESSARY AND ARE NOT LIMITED TO WHAT IS
TO LIASE WITH LOCAL TELEPHONE AUTHORITY FOR THE ROADS AND BUILDINGS. SHOWN ON THE DRAWINGS. WIDTH, LENGTH, NUMBERS
REQUIRED TELEPHONE LINES TO THE FACILITY AND MAKE AND ROUTES OF CABLE TRAYS, LADDERS, PIPES AND
PROVISIONS IN INSTALLATION TO SATISFY THEIR OTHER CABLE RACEWAYS SHALL BE SHOWN ON SHOP
REQUIREMENTS. THE SERVICES PROVIDED SHALL DRAWINGS AS PER STANDARDS FOR APPROVAL.
CONFORM IN ALL RESPECTS WITH THEIR
STANDARDS/REGULATIONS. WHERE OPENINGS ARE PROVIDED IN STRUCTURE TO
THE LIGHTING, POWER AND LOW CURRENT SYSTEMS CROSS CABLE TRAYS, PIPES, ETC. THE OPENING SHALL BE
SHALL BE INSTALLED SEPARATELY FROM EACH OTHER. i.e. SEALED BY FIRE STOP MATERIAL SUITABLY RATED, AFTER
CONDUITS, RACEWAYS, WIRES, BOXES, ETC. INSTALLATION OF CABLES.
WIRING DEVICES

THE LOCATION OF ALL SWITCHES, OUTLETS AND OTHER MINIATURE CIRCUIT BREAKERS (MCB) WITH APPROPRIATE GENERATORS/MOTORS/MECHANICAL
WIRING DEVICES SHALL BE COORDINATED WITH THE SHORT CIRCUIT CURRENT RATING SHALL BE PROVIDED THE CONTROLS OF STANDBY GENERATOR FEEDING FIRE
FURNITURE LAYOUTS/ID DRAWINGS ON SITE. FOR LIGHTING, SWITCHED SOCKET OUTLETS, ELECTRIC PUMPS SHALL BE SO ARRANGED THAT THE GENERATOR
MOUNTING HEIGHTS FOR SWITCHES, SOCKETS, ETC., WATER HEATERS/COOLERS, REFRIGERATORS, COOKERS, SHALL CONTINUE RUNNING WHEN FM200 OR C02 GAS (FOR
FROM THE CENTRE OF THE DEVICE TO ABOVE FINISHED DOMESTIC WATER PUMPS AND SIMILAR EQUIPMENT. FIRE SUPPRESSION) IS RELEASED, UNLESS THE
FLOOR LEVEL SHALL BE AS FOLLOWS, UNLESS THE OVERALL POWER FACTOR OF EVERY ELECTRICAL GENERATOR IS MANUALLY SHUTDOWN. A MANUAL
OTHERWISE SPECIFIED OR DIRECTED BY THE ENGINEER: SUBSTATION SHALL BE MAINTAINED WITHIN THE RANGE SHUTDOWN SWITCH SHALL BE PROVIDED NEAR THE DOOR
OF 0.9 LAGGING AND UNITY. PROVIDE AUTOMATIC P.F. FOR SUCH GENERATOR.
IMPROVEMENT PLANT. DURING COMMERCIAL/NORMAL POWER FAILURE, ALL
THE CONTRACTOR HAS TO CHECK THE PHYSICAL ELEVATORS SHALL BE AUTOMATICALLY SWITCHED OVER
DIMENSION OF THE PANELS WITH THE SPACE TO EMERGENCY SOURCE AND CALLED TO MAIN EGRESS
AVAILABILITY PRIOR TO PLACING THE ORDER. DRAWINGS LEVEL IN SEQUENCE. SAID OPERATION TO BE CARRIED
FOR PANELS SHALL BE SUBMITTED TO THE ENGINEER FOR OUT THROUGH ELEVATOR CONTROLS AS PER ELEVATOR
APPROVAL. SPECIFICATIONS.
ALL ROTATING MACHINERY OPERATED THROUGH
THE ELECTRICAL CONTRACTOR SHALL INDICATE THE STARTER SHALL HAVE A NO VOLTAGE RELEASE
EXACT LOCATION, HEIGHT,... ETC OF ALL OUTLETS ON HIS LIGHTING INCORPORATED WITHIN ITS STARTER PANEL.
WORK SHOP DRAWINGS AFTER COORDINATING WITH THE ALL LIGHTING FIXTURES SHALL BE PROVIDED WITH ALL HVAC UNITS/PLANT/EQUIPMENT SUCH AS FCU'S,
EQUIPMENT SPECIALIST CONTRACTOR'S DETAIL POWER SUPPLY. AHU'S, CONDENSING UNITS, CHILLERS, ETC. SHALL BE
DRAWINGS. ALL WIRING FOR LIGHTING INSTALLATIONS SHALL FOLLOW CONNECTED VIA SUITABLE ISOLATORS AND CONNECTION
ALL SOCKET OUTLETS LOCATED ABOVE WORKTOPS SHALL "LOOP-IN" SYSTEM. BOXES INSTALLED CLOSE TO THEM. PROVIDE UNDER
BE MOUNTED 1200MM ABOVE FINISHED FLOOR LEVEL OR ALL SELF CONTAINED TYPE EMERGENCY/EXIT LIGHTING VOLTAGE RELAYS AND AUTO RESET TIMER WITH
300MM ABOVE WORK TOP AS APPROVED ON SITE. FIXTURES SHALL BE PROVIDED WITH CHARGER/INVERTER ADJUSTABLE TIME SETTING BETWEEN 5 AND 10 MINUTES,
WHERE OUTLET IS PROVIDED FOR CONNECTION TO A MODULE AND BATTERY BACK-UP FOR A MINIMUM OF 3 FOR EACH UNIT.
FIXED APPLIANCE BY MEANS OF A FLEXIBLE CABLE, THE HOURS CONTINUOUS OPERATION AND TO BE COMPATIBLE
RESPECTIVE OUTLET SHALL BE POSITIONED AS CLOSE AS WITH EMERGENCY LIGHTING SYSTEM. ELV SYSTEMS
PRACTICABLE TO THE CABLE ENTRY OF THE FIXED
APPLIANCE. EARTHING/GROUNDING ACTIVATION OF THE FIRE ALARM SYSTEM SHALL START
ALL ELECTRICAL OPERATED PLANT AND EQUIPMENT THE EARTHING SYSTEM SHALL FOLLOW THE PRINCIPLES AND SHUTDOWN HVAC PLANT, AS PER HVAC
SHALL BE PROVIDED WITH MEANS OF LOCAL ISOLATION OF TT SYSTEM i.e. SEPARATE EARTH AND NEUTRAL SPECIFICATIONS AND DRAWINGS. PROPER COORDINATION
INSTALLED AS CLOSE AS POSSIBLE TO THE EQUIPMENT CONDUCTOR, AS SHOWN ON DRAWINGS. THE OVERALL BETWEEN THE TWO SYSTEMS SHALL BE CARRIED OUT
BEING SERVED. SYSTEM EARTH RESISTANCE SHALL BE DURING EXECUTION.
FOR EXACT LOCATION OF ISOLATORS AND DISCONNECT
1 OHM OR LESS. ALL LOW CURRENT SYSTEMS WIRING AND CABLES SHALL
SWITCHES FOR PUMPS, AHUS, MCCS AND OTHER
MECHANICAL/HVAC EQUIPMENT, THE CONTRACTOR SHALL EARTHING OF ELECTRICAL SUBSTATIONS SHALL BE BE AS PER THE SPECIFICATIONS AND
COORDINATE WITH MECHANICAL WORKS. PROVIDED IN ACCORDANCE WITH REGULATIONS. MANUFACTURER'S/SUPPLIER'S RECOMMENDATIONS.
ISOLATORS FOR HVAC EQUIPMENT SHALL BE HEAVY DUTY PROVIDE COMPLETELY INDEPENDENT AND CLEAN ALL CABLING/WIRING SERVING THE LIFE SAFETY SYSTEMS
'ON-LOAD' TYPE AND SUITABLY RATED, TAKING INTO EARTHING SYSTEM FOR LOW CURRENT/COMMUNICATION SUCH AS FIRE ALARM, SMOKE MANAGEMENT, FIRE PUMPS,
CONSIDERATION NORMAL AND STARTING CURRENTS OF SYSTEMS, WHEN REQUIRED AS PER MANUFACTURER'S ETC., SHALL BE THREE HOURS FIRE RATED AS PER NFPA.
THE EQUIPMENT AND THE AMBIENT TEMPERATURE OF THE RECOMMENDATIONS OR LOCAL AUTHORITY REGULATIONS. SEPARATE CONDUIT SHALL BE RUN FOR EACH LOW
OPERATING AREA. A SEPARATE GROUNDING CONDUCTOR SHALL BE RUN CURRENT SYSTEM. MINIMUM SIZE OF CONDUIT SHALL BE
ALL ISOLATORS/EQUIPMENT INSTALLED IN WET AND/OR WITH EACH CIRCUIT. ALL LIGHTING FIXTURES, 20mm DIA.
POSSIBLE WET LOCATIONS SUCH AS TOILETS, PUMP RECEPTACLES, SWITCHES, METALLIC JUNCTION BOXES ALL LOW CURRENT CABLES SHALL BE LAID AT A DISTANCE
ROOMS, ROOF, EXTERNAL/EXPOSED AREAS, ETC. SHALL AND FITTINGS SHALL BE EFFECTIVELY AND PROPERLY OF NOT LESS THAN 300MM FROM LOW VOLTAGE POWER
BE WEATHERPROOF TYPE TO APPROPRIATE IP RATING EARTHED. CABLES AND 60OMM FROM MEDIUM VOLTAGE POWER
EARTH CONTINUITY CONDUCTORS AND BONDING
(MINIMUM IP-54). CABLES.
CONDUCTORS SHALL BE SINGLE CORE, PVC INSULATED.
SWITCHGEAR/DISTRIBUTION BOARDS ALL FIRE ALARM SYSTEM INSTALLATIONS INCLUDING
ALL LIGHTING AND POWER DISTRIBUTION BOARDS (DB) EARTHING CONDUCTOR OF THE RESPECTIVE CIRCUIT WIRING AND DEVICES SHALL BE IN ACCORDANCE WITH
SHALL BE FLUSH MOUNTED TYPE IN ALL PUBLIC AND SHALL RUN IN THE SAME TRENCH/PIPE/TRUNKING OR ON NFPA 72 AND LOCAL CIVIL DEFENSE REQUIREMENTS.
CIRCULATION AREAS AND SURFACE MOUNTED IN SAME CABLE TRAY/LADDER AS THE ASSOCIATED CABLE.
ELECTRICAL/MECHANICAL AND PLANT ROOMS, UNLESS ALL TELEPHONE AND DATA SYSTEM INSTALLATIONS
EXTRANEOUS METALWORK AS METALLIC PIPES, DUCTING, INCLUDING WIRING AND DEVICES SHALL BE IN
OTHERWISE INDICATED. THESE SHALL BE PROVIDED WITH
CABLE TRAYS, METALWORK IN TOILETS, ETC. SHALL BE ACCORDANCE WITH EIA/TIA REGULATIONS AND LOCAL
LOCKABLE DOORS.
BONDED TO EARTHING SYSTEM BY PVC INSULATED CABLE AUTHORITY REQUIREMENTS.
THE TOTAL LOAD ON THE THREE PHASES SHALL BE IN ACCORDANCE WITH APPLICABLE STANDARDS.
BALANCED AS EVENLY AS PROVIDED ON ALL SWITCHGEAR
AND DISTRIBUTION BOARDS.
CIR A4 CIR A4 CIR A4
E E E

4
CIR A1 B B B B A A A 4
CIR B1
CIR A1
BL

BL
CIR A1 4 CIR A3 A E CIR A4
A CIR B1 CIR B1 A CIR A3 CIR A3 CIR A3

A CIR A3 4
B B B CIR B1 B A A A
CIR B1
BL

BL

CIR A1 CIR A1 2 CIR A3


X

CIR A1 A 2 2 2
4
A 2
2
CIR A3
2
CIR B1
A A A A CIR A3
A
CIR A1
CIR B1 A
BL

BL

CIR A4 E CIR A1 CIR A1 2 X 2 2 2 CIR A3


2 4

X
2
CIR A3
A
A A A A A 4
CIR A2 CIR A2
2
CIR A3
CIR A2
A
CIR A1

CIR A2 A A CIR A4
CIR A3
CIR A1 E
BL

BL
BL

BL

CIR A1 CIR A1
B B CIR A3
CIR A1 CIR A2
CIR A1 V V 2

CIR A2
A A CIR A2 CIR A3
B D A
BL

BL
BL

BL

CIR A1 CIR A1 E CIR A4


B B D
CIR A1 CIR A1 2
4 4 4 4 4 2
A A
CIR A2 CIR A2 CIR A3
2

E E
CIR A4 CIR A4
E
CIR A4

E
CIR A4

E
4 D
W

FLL

TYPE SYMBOL DESCRIPTION MOUNTING


TYPE SYMBOL IMAGE DESCRIPTION MOUNTING

1X18W 1200MM LED PLAIN BATTEN FITTING SURFACE MOUNTED


TYPE A A COMPLETE WITH LED LAMP AS THOMSON LED ON CEILING
(1750LM MIN.)

2X18W 1200MM LED PLAIN BATTEN FITTING SURFACE MOUNTED


TYPE B B COMPLETE WITH LED LAMP AS THOMSON ON CEILING
LED(2X1750LM MIN.)

3X18W 600mm x 1200mm LED CAT2 LOUVER LIGHT SURFACE MOUNTED


TYPE C C FITTING COMPLETE WITH LED LAMP AS THOMSON ON CEILING
LED (3X1750LM MIN.)

8.5W LED SPHERICAL BALL FITTING COMPLETE SURFACE MOUNTED


TYPE 4 WITH LED LAMP AS THOMSON LED (800LM MIN.) ON CEILING
4

2X18W IP65 1200MM LED WATERPROOF FITTING SURFACE MOUNTED


TYPE W W WITH ACRYLIC DIFFUSER AND COMPLETE WITH LED ON CEILING
LAMP AS THOMSON LED (2X1750LM MIN.)

9W 600MM IP54 LED ALUMINUM NIGHT LIGHT 1500MM FFL WALL


TYPE BL BL
FITTING WITH WHITE FINISH AND COMPLETE WITH MOUNTED
INTEGRAL SWITCH AND LED LAMP AS EATON MBPL
(800LM MIN.)

1X9W 600MM LED PLAIN BATTEN FITTING SURFACE MOUNTED


TYPE D D COMPLETE WITH LED LAMP AS THOMSON LED ON CEILING
(800LM MIN.)

1X18W IP65 1200MM LED WATERPROOF FITTING SURFACE MOUNTED


TYPE V V WITH ACRYLIC DIFFUSER AND COMPLETE WITH LED ON CEILING
LAMP AS THOMSON LED (1750LM MIN.)
HL CIR A5 CIR A5 HL HL CIR A8 CIR A8 HL
CIR B2 CIR B2 CIR B3 CIR B4 CIR A8

CIR A8
HL HL CIR A9
CIR A7 CIR A8
HL CIR A5 CIR A5 HL CIR A8 CIR A8
CIR B2 CIR B2 CIR B3
CIR B3 CIR B4 CIR B4 PVC CONDUIT
CIR A15

HL CIR A5 CIR A5 HL
CIR B2 CIR B2

CIR A7
200X50MM 16SWG
GALVANIZED STEEL
200X50MM 16SWG 200X50MM 16SWG
CABLE TRAY IN CEILING
GALVANIZED STEEL GALVANIZED STEEL
VOID DB'A' CU'B' PVC CONDUIT
CABLE TRAY IN CABLE TRAY IN
CEILING VOID CEILING VOID
CIR A6 CIR A6 CIR A7
HL CIR A6 HL HL CIR A7 HL CIR A9
CIR A7 CIR A7 AB

50A DP
CIR
A10/11 CIR A13 M CIR A9
C
HL CIR A6 HL HL HL CIR A14
CIR A6 CIR A7 CIR A9 PVC CONDUIT
C CIR A12 C
CIR A6 CIR A7 KPLC
CIR A7 50A DP CIR A9 CIR A9
C C

CIR A9

SYMBOL DESCRIPTION MOUNTING SYMBOL DESCRIPTION MOUNTING


HEIGHT HEIGHT PVC CONDUIT
13AMP TWIN SOCKET OUTLET 300MM CENTRE CONVENTIONAL SMOKE DETECTOR CEILING MOUNT
AS MK FFL SD
300MM CENTRE PVC CONDUIT
TV OUTLET POINT FFL HD CONVENTIONAL HEAT DETECTOR CEILING MOUNT
300/1200/2100MM 1800MM CENTRE
DOUBLE POLE SWITCH AS MK FAB
FFL CONVENTIONAL MANUAL CALL POINT FFL

RECESSED MOUNTED TPN DISTRIBUTION FABG 1350MM CENTRE


1800MM FFL CONVENTIONAL SOUNDER
BOARD TO SCHEMATIC DETAILS FFL
AB
RECESSED MOUNTED SPN CONSUMER
UNIT TO SCHEMATIC DETAILS 1800MM FFL 1500MM CENTRE
FAP 4-ZONE CONVENTIONAL FIRE PANEL
FFL
13AMP TWIN SOCKET OUTLET 1200MM CENTRE
HL AS MK FFL
KPLC
3X4.0MM SQ PVC INSULATED COPPER CABLES
CIR A1 3X1.5MM SQ PVC INSULATED COPPER CABLES CIR A10
10A 20A
GEYSER HEATING ELEMENT OUTLET

3X4.0MM SQ PVC INSULATED COPPER CABLES


CIR A2 3X1.5MM SQ PVC INSULATED COPPER CABLES CIR A11
10A 20A
GEYSER HEATING ELEMENT OUTLET

3X4.0MM SQ PVC INSULATED COPPER CABLES


CIR A3 3X1.5MM SQ PVC INSULATED COPPER CABLES CIR A12
10A 20A
GEYSER HEATING ELEMENT OUTLET

3X4.0MM SQ PVC INSULATED COPPER CABLES


CIR A4 3X1.5MM SQ PVC INSULATED COPPER CABLES CIR A13
10A 20A
UNDER SINK HEATER ELEMENT OUTLET

2C, 10SQ.MM PVC/SWA/PVC INSULATED COPPER


CIR A5 CIR A14
30A HG PVC CONDUITS IN RING MAIN FOR 13A SOCKET OUTLETS 50A
GRID TIED INVERTER

2C, 6SQ.MM PVC/SWA/PVC INSULATED COPPER


CIR A6 CIR A15
30A HG PVC CONDUITS IN RING MAIN FOR 13A SOCKET OUTLETS 50A
GUARD HOUSE CONSUMER UNIT

2C, 4SQ.MM PVC/SWA/PVC INSULATED COPPER


CIR A7 CIR A16
30A HG PVC CONDUITS IN RING MAIN FOR 13A SOCKET OUTLETS 50A
BOOSTER PUMP

CIR A8 SPARE WAYS


30A HG PVC CONDUITS IN RING MAIN FOR 13A SOCKET OUTLETS

CIR A9 SPARE WAYS


30A HG PVC CONDUITS IN RING MAIN FOR 13A SOCKET OUTLETS

4C, 10SQ.MM PVC/SWA/PVC


COPPER CABLES DRAWN IN PVC
DUCTS FROM MDB IN POWER HOUSE SPARE WAYS

M 63A TPN MAIN


INTEGRAL
ISOLATOR
20A TIMER CIR B1 3x1.5mm sq PVC INSULATED COPPER CABLES DRAWN
2C 10 SQ.MM PVC INSULATED SWITCH IN CU 10A
COPPER CABLES DRAWN IN T
CIR B2 3x1.5mm sq PVC INSULATED COPPER CABLES DRAWN
10A
INVERTER

CIR B3 3x2.5mm sq PVC INSULATED COPPER CABLES


30A
MAIN FOR 13A SOCKET OUTLETS
CIR B4 3x2.5mm sq PVC INSULATED COPPER CABLES
30A
MAIN FOR 13A SOCKET OUTLETS

63A SPN SPARE WAY

INTEGRAL
ISOLATOR SPARE WAY

SPARE WAY

SPARE WAY
SPACE REQUIREMENTS:
EASTLEIGH MATERNITY BLOCK
1. SOLAR PANELS - 12.3SQ.M
2. BATTERY BANKS - 0.12CU.M
6X270W PV SOLAR PANELS; CABLES:
1X6 CONFIGURATION
WEIGHT REQUIREMENTS:
1. 4SQ.MM SC XLPE/SWA/XLPE COPPER CABLE
2. 4SQ.MM 2C XLPE/SWA/XLPE COPPER CABLE 1. SOLAR PANELS - 128KG
3. 6SQ.MM 2C PVC INSULATED COPPER CABLE 2. BATTERY BANKS - 132KG
4. 16SQ.MM SC PVC INSULATED COPPER CABLE

MAINS
CHARGING
1 1 CIRCUIT

20A AC
ISOLATOR
1
COMBINER 10A DC 20A AC
2 3 3 3 ISOLATOR 3 SOLAR POWER
BOX ISOLATOR CONSUMER
UNIT CU'C'
63A SPN
1no. 4500W
1no. 48VDC, INTEGRAL
INVERTER
DC 80A CHARGE ISOLATOR
EARTHING CONTROLLER
4 4

AC
EARTHING

4X12V BATTERY
BANKS; 1X4
CONFIGURATION 25x3mm 25x3mm
EQUIPOTENTIAL
BONDING COPPER TAPE
UN OPS
LIST OF DRAWINGS Operational excellence
East Africa Hub ( EAH ) , Nairobi
UNOPS Building , UN lane ,
Off Avenue P .O . Box 783 ,
for results that matter

Village Market , 00621


Nairobi , Kenya .

GENERAL NOTES
1 . All dimensions are in centimetres ,
unless otherwise stated .

2 . All dimensions to be checked and


confirmed on site before commencement
00 T-101-016-D-E00 Drawing List of any work .

3 . Written dimensions overrides scaled


dimensions ,thus all dimensions are
to be read and not at any time scaled from
the drawing .
01 T-101-016-D-E01 ELECTRICAL NOTES - 1 4 . Any discrepancy to be reported to the
Engineer promptly before proceeding .

NO . REVISION DATE APPR .


02 T-101-016-D-E02 ELECTRICAL NOTES - 2

03 T-101-016-D-E03 LIGHTING LAYOUT

04 T-101-016-D-E04 LIGHTING SCHEDULE CLIENT

POWER LAYOUT
UNICEF
05 T-101-016-D-E05
PROJECT

PROPOSED REHABILITATION
TO KAYOLE II HOSPITAL
06 T-101-016-D-E07 DISTRIBUTION BOARD SCHEMATIC NAIROBI COUNTY .

DRAWING TITLE

RAW POWER CONSUMER UNIT DRAWING LIST


07 T-101-016-D-E08
DESIGN SERVICES UNIT

08 T-101-016-D-E09 SOLAR POWER SCHEMATIC DRAWN BY Cephanie M.


CHECKED BY PhilipM .
APPROVED BY MoyizE .
09 T-101-016-D-E10 SOLAR DESIGN DATE MAY 2016
DRAWING NUMBER :

T-101-016-D-E00

COPYRIGHT RESERVED
THIS DESIGN AND DETAIL ARE , AND
AT ALL TIMES THE EXCLUSIVE
PROPERTY OF THE UNOPS / EAH ,NAIROBI
AND CANNOT BE USED OR REPRODUCED
WITHOUT WRITTEN CONSENT .

TENDER DRAWINGS
GSPublisherEngine 0.0.100.100
Operational
UN OPS
excellence for results that matter
East Africa Hub ( EAH ) , Nairobi
1.0 GENERAL UNOPS Building , UN lane ,
1.1 THE DESIGN DRAWINGS SHALL BE READ IN CONJUNCTION 3.0 CONDUITS, CABLE TRAYS AND TRUNKING
1.12 CABLE SIZES, MCB's,MCCBs AND ISOLATORS SHOWN ON Off Avenue P .O . Box 783 ,
WITH THE RELEVANT SPECIFICATIONS AND THE DRAWINGS ARE BASED ON DESIGNED LOADS. THE 3.1 THE MINIMUM SIZE OF CONDUIT USED FOR ANY SYSTEM Village Market , 00621
ARCHITECTURAL, INTERIOR DESIGN, STRUCTURAL, CIVIL & CONTRACTOR SHALL PROVIDE THE SIZE OF CABLE, MCB, WIRING SHALL BE 20MM INTERNAL DIAMETER. Nairobi , Kenya .
MECHANICAL DRAWINGS AND SPECIFICATIONS. MCCB AND ISOLATOR BASED ON ACTUAL LOADS OF THE 3.2 PVC CONDUITS SHALL BE HEAVY GAUGE, POLISHED AND
1.2 THESE NOTES ARE GENERALLY APPLICABLE TO THE
EQUIPMENT APPROVED BY THE ENGINEER AT NO EXTRA SMOOTH INSIDE AND OUTSIDE, FLAME-RETARDANT AND GENERAL NOTES
OVERALL SYSTEMS INSTALLATION. ANY ADDITIONAL
COST. SUITABLE FOR USE AT AMBIENT TEMPERATURE OF 50°C. 1 . All dimensions are in centimetres ,
NOTES ON INDIVIDUAL DRAWINGS WHICH ARE
1.13 FOR SPECIAL SYSTEMS, THE CONTRACTOR IS TO SUBMIT 3.4 RIGID STEEL CONDUITS (RSC) SHALL BE HEAVY GAUGE, unless otherwise stated .
SUPPLEMENTARY TO THESE NOTES SHALL BE READ WITH
SHOP DRAWINGS PREPARED BY SPECIALISTS HOT DIP GALVANIZED TO CLASS 4 PROTECTION BOTH 2 . All dimensions to be checked and
THE INSTRUCTIONS STATED HEREIN.
1.3 THE FINAL POSITION OF ALL EQUIPMENT, PANELS, EXPERIENCED IN THE DESIGN OF THE RELEVANT SYSTEMS INSIDE AND OUTSIDE. confirmed on site before commencement
of any work .
LUMINAIRES, DETECTORS, SWITCHES, OUTLETS AND AND AS PER THE MANUFACTURERS REQUIREMENTS. 3.5 ALL PVC BOXES SHALL BE RIGID, FLAME-RETARDANT,
OTHER ACCESSORIES SHALL BE COORDINATED WITH THE 2.0 CABLES SMOOTH AND ACCORDING TO LATEST 3 . Written dimensions overrides scaled
ARCHITECTURAL, MECHANICAL AND INTERIOR DESIGN STANDARDS/SPECIFICATIONS. dimensions ,thus all dimensions are
2.1 ALL WIRES AND CABLES SHALL BE STRANDED COPPER CONDUCTORS, 3.6 ALL STEEL BOXES SHALL BE HEAVY GAUGE, HOT DIP to be read and not at any time scaled from
DETAILS AND WILL BE APPROVED AT SITE BY THE the drawing .
PVC INSULATED COMPLYING WITH BS 6004 OR XLPE INSULATED AS PER
ENGINEER. GALVANIZED ACCORDING TO LATEST
1.4 UNLESS OTHERWISE SPECIFIED ALL EQUIPMENT AND IEC 502 AS SHOWN ON DRAWINGS OR SCHEDULES, EXCEPT FOR 4 . Any discrepancy to be reported to the
STANDARDS/SPECIFICATIONS.
MATERIALS TO BE USED SHALL BE SUITABLE AND RATED INFLAMABLE/EXPLOSIVE AND OTHER EXCEPTIONAL SITUATIONS. Engineer promptly before proceeding .
3.7 BRASS BUSHINGS AND RINGS SHALL BE USED TO SECURE
FOR THE SITE AMBIENT CONDITIONS. 2.2 COLOUR CODE OF ELECTRICAL WIRES AND CABLES SHALL
STEEL CONDUITS WITH STEEL BOXES. NO . REVISION DATE APPR .
1.5 ALL ELECTRICAL WORKS SHALL COMPLY WITH THE BE RED, YELLOW, BLUE, BLACK AND GREEN/YELLOW FOR
RELEVANT MINISTRY OF BUBLIC WORKS REGULATIONS, L1, L2, L3, NEUTRAL AND EARTH RESPECTIVELY IN A 3.8 ALL STEEL COUPLERS SHALL BE PAINTED SUITABLY,
LATEST EDITION OF IEE WIRING REGULATIONS, THREE PHASE CONFIGURATION. IMMEDIATELY AFTER INSTALLATION.
INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC) 2.3 THE CONDUCTOR SIZES FOR ALL CABLES SHALL BE IN
3.9 NO CONDUIT RUN SHALL BE LONGER THAN 15M
STANDARDS AND ISO RECOMMENDATIONS. ACCORDANCE WITH THE PANEL BOARD/CABLE
(STRAIGHT) OR WITH MORE THAN TWO 90° BENDS,
1.6 THE INSTALLATION SHALL COMPLY IN ALL RESPECTS TO SCHEDULES AND SINGLE LINE DIAGRAMS.
OTHERWISE IT MUST BE PASSED THROUGH PULL OR
THE REQUIREMENTS OF THE MANUFACTURERS AND THE 2.4 THE MINIMUM SIZE OF ALL CIRCUIT CONDUCTORS SHALL
DRAW BOX SUFFICIENT TO PERMIT EASY PULLING OF
CODES REFERRED IN THE SPECIFICATIONS. BE COORDINATED WITH THE STARTING AND OPERATING
WIRES.
1.7 ANY EQUIPMENT DIMENSIONS AND ELECTRICAL LOAD CHARACTERISTICS OF THE EQUIPMENT THEY SERVE. 3.10 THE TOTAL FILL OF THE WIRES DRAWN IN CONDUIT SHALL
STATED ON THE DRAWINGS SHALL BE 2.5 UNLESS OTHERWISE INDICATED, MINIMUM WIRE SIZE BE AS PER IEE REGULATIONS AND NORMALLY NOT TO CLIENT
COORDINATED/CONFIRMED WITH THE ACTUAL SHALL BE 2.5MM² EXCEED 40% OF THE INTERNAL CROSS-SECTIONAL AREA
DIMENSIONS AND ACTUAL ELECTRICAL LOAD OF FOR LIGHTING AND 2.5MM² FOR POWER. OF THE CONDUIT.
3.11 ALL CONDUITS AND RECEWAYS PASSING THROUGH THE
UNICEF
EQUIPMENT FROM RESPECTIVE MANUFACTURER(S). 2.6 LIGHTING AND SMALL POWER INSTALLATION SHALL BE
1.8 ALL MATERIALS AND EQUIPMENT MUST BE OF THE BEST CARRIED OUT USING SINGLE CORE PVC INSULATED BUILDING EXPANSION JOINTS SHALL BE PROVIDED WITH
QUALITY AND ACCORDING TO THE LATEST INTERNATIONAL EXPANSION JOINT COUPLING AND EXECUTED AS PER
WIRES IN RIGID PVC CONDUITS EMBEDDED IN CONCRETE. PROJECT

STANDARDS. THE CONTRACTOR SHALL SUBMIT SAMPLES STANDARD DETAILS, APPROVED BY THE ENGINEER ON
2.7 ALL MULTICORE CABLES INSIDE THE BUILDING SHALL BE PROPOSED REHABILITATION
AND CATALOGUES OF ALL MATERIALS AND OBTAIN SITE. TO KAYOLE II HOSPITAL
INSTALLED ON CABLE TRAYS OR CABLE LADDERS. RAISED
ENGINEER'S APPROVAL BEFORE THE COMMENCEMENT OF 3.12 ALL BENDS IN DUCTS, CONDUITS AND OTHER RACEWAYS NAIROBI COUNTY .
SUN SHADES (COVERS) SHALL BE PROVIDED FOR ALL
ANY WORK. SHALL BE SUITABLE TO ALLOW MINIMUM CABLE BENDING
ROOF MOUNTED CABLE TRAYS/LADDERS.
1.9 IT SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY RADIUS IN ACCORDANCE WITH MANUFACTURER'S DRAWING TITLE
2.8 THE WIRES/CABLES FOR LV CIRCUITS INSIDE BUILDINGS
TO LIASE WITH THE LOCAL ELECTRICITY SUPPLY RECOMMENDATIONS.
SHALL BE INSTALLED AT A MINIMUM DISTANCE OF 300MM ELECTRICAL NOTES 1
AUTHORITY FOR THE ELECTRICITY SUPPLY CONNECTION 3.13 ALL ENDS OF BURIED DUCTS AND CONDUITS SHALL HAVE
FROM HOT WATER LINES AND 150MM FROM OTHER
TO THE FACILITY AND MAKE PROVISIONS IN INSTALLATION BELL MOUTH PIPE ENDS AND SHALL BE SEALED BY A
SERVICE PIPES.
TO SATISFY THEIR REQUIREMENTS. THE SERVICES PROPRIETARY PIPE SEALING PRODUCT.
PROVIDED SHALL CONFORM IN ALL RESPECTS WITH THE 2.9 WHERE EXTERNAL CABLES ARE DIRECT BURIED IN THE DESIGN SERVICES UNIT
GROUND, THESE SHALL RUN THROUGH UNDERGROUND 3.14 CABLE LADDERS AND CABLE TRAYS SHALL BE INSTALLED
LOCAL CODES AND REGULATIONS. DRAWN BY Cephanie M.
1.10 IT SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY CONCRETE ENCASED UPVC DUCTS WHEN PASSING UNDER WHERE NECESSARY AND ARE NOT LIMITED TO WHAT IS
TO LIASE WITH LOCAL TELEPHONE AUTHORITY FOR THE ROADS AND BUILDINGS. SHOWN ON THE DRAWINGS. WIDTH, LENGTH, NUMBERS CHECKED BY PhilipM .
REQUIRED TELEPHONE LINES TO THE FACILITY AND MAKE AND ROUTES OF CABLE TRAYS, LADDERS, PIPES AND
PROVISIONS IN INSTALLATION TO SATISFY THEIR OTHER CABLE RACEWAYS SHALL BE SHOWN ON SHOP
APPROVED BY MoyizE .
REQUIREMENTS. THE SERVICES PROVIDED SHALL DRAWINGS AS PER STANDARDS FOR APPROVAL. DATE MAY 2016
CONFORM IN ALL RESPECTS WITH THEIR DRAWING NUMBER :
3.15 WHERE OPENINGS ARE PROVIDED IN STRUCTURE TO
STANDARDS/REGULATIONS.
1.11 THE LIGHTING, POWER AND LOW CURRENT SYSTEMS CROSS CABLE TRAYS, PIPES, ETC. THE OPENING SHALL BE T-101-016-D-E01
SHALL BE INSTALLED SEPARATELY FROM EACH OTHER. i.e. SEALED BY FIRE STOP MATERIAL SUITABLY RATED, AFTER
COPYRIGHT RESERVED
CONDUITS, RACEWAYS, WIRES, BOXES, ETC. INSTALLATION OF CABLES. THIS DESIGN AND DETAIL ARE , AND
AT ALL TIMES THE EXCLUSIVE
PROPERTY OF THE UNOPS / EAH ,NAIROBI
AND CANNOT BE USED OR REPRODUCED
WITHOUT WRITTEN CONSENT .

TENDER DRAWINGS
GSPublisherEngine 0.0.100.100
Operational
UN OPS
excellence for results that matter
4.0 WIRING DEVICES
East Africa Hub ( EAH ) , Nairobi
4.1 THE LOCATION OF ALL SWITCHES, OUTLETS AND OTHER 5.3 MINIATURE CIRCUIT BREAKERS (MCB) WITH APPROPRIATE 8.0 GENERATORS/MOTORS/MECHANICAL UNOPS Building , UN lane ,
WIRING DEVICES SHALL BE COORDINATED WITH THE SHORT CIRCUIT CURRENT RATING SHALL BE PROVIDED 8.1 THE CONTROLS OF STANDBY GENERATOR FEEDING FIRE Off Avenue P .O . Box 783 ,
FURNITURE LAYOUTS/ID DRAWINGS ON SITE. FOR LIGHTING, SWITCHED SOCKET OUTLETS, ELECTRIC Village Market , 00621
PUMPS SHALL BE SO ARRANGED THAT THE GENERATOR
4.2 MOUNTING HEIGHTS FOR SWITCHES, SOCKETS, ETC., WATER HEATERS/COOLERS, REFRIGERATORS, COOKERS, Nairobi , Kenya .
SHALL CONTINUE RUNNING WHEN FM200 OR C02 GAS (FOR
FROM THE CENTRE OF THE DEVICE TO ABOVE FINISHED DOMESTIC WATER PUMPS AND SIMILAR EQUIPMENT. FIRE SUPPRESSION) IS RELEASED, UNLESS THE
FLOOR LEVEL SHALL BE AS FOLLOWS, UNLESS 5.4 THE OVERALL POWER FACTOR OF EVERY ELECTRICAL GENERAL NOTES
GENERATOR IS MANUALLY SHUTDOWN. A MANUAL
OTHERWISE SPECIFIED OR DIRECTED BY THE ENGINEER: SUBSTATION SHALL BE MAINTAINED WITHIN THE RANGE SHUTDOWN SWITCH SHALL BE PROVIDED NEAR THE DOOR 1 . All dimensions are in centimetres ,
SWITCHES 1350MM AFFL OF 0.9 LAGGING AND UNITY. PROVIDE AUTOMATIC P.F. FOR SUCH GENERATOR. unless otherwise stated .
SOCKETS (STANDARD) 300MM AFFL IMPROVEMENT PLANT. 8.2 DURING COMMERCIAL/NORMAL POWER FAILURE, ALL
2 . All dimensions to be checked and
SOCKETS (HIGH LEVEL TV) 1800MM AFFL 5.5 THE CONTRACTOR HAS TO CHECK THE PHYSICAL ELEVATORS SHALL BE AUTOMATICALLY SWITCHED OVER confirmed on site before commencement
SOCKETS (KITCHENETTE) 1200MM AFFL OR 300MM ABOVE WORK TOP DIMENSION OF THE PANELS WITH THE SPACE TO EMERGENCY SOURCE AND CALLED TO MAIN EGRESS of any work .
ISOLATORS/DISCONNECT SWITCHES 1600MM AFFL AVAILABILITY PRIOR TO PLACING THE ORDER. DRAWINGS LEVEL IN SEQUENCE. SAID OPERATION TO BE CARRIED 3 . Written dimensions overrides scaled
DISTRIBUTION BOARDS (TOP OF DB) 1800MM AFFL FOR PANELS SHALL BE SUBMITTED TO THE ENGINEER FOR OUT THROUGH ELEVATOR CONTROLS AS PER ELEVATOR dimensions ,thus all dimensions are
FIRE ALARM PANEL (MID OF PANEL) 1600MM AFFL APPROVAL. SPECIFICATIONS. to be read and not at any time scaled from
8.3 ALL ROTATING MACHINERY OPERATED THROUGH the drawing .
4.3 THE ELECTRICAL CONTRACTOR SHALL INDICATE THE STARTER SHALL HAVE A NO VOLTAGE RELEASE 4 . Any discrepancy to be reported to the
6.0 LIGHTING INCORPORATED WITHIN ITS STARTER PANEL. Engineer promptly before proceeding .
EXACT LOCATION, HEIGHT,... ETC OF ALL OUTLETS ON HIS
WORK SHOP DRAWINGS AFTER COORDINATING WITH THE 6.1 ALL LIGHTING FIXTURES SHALL BE PROVIDED WITH 8.4 ALL HVAC UNITS/PLANT/EQUIPMENT SUCH AS FCU'S,
POWER SUPPLY. AHU'S, CONDENSING UNITS, CHILLERS, ETC. SHALL BE NO . REVISION DATE APPR .
EQUIPMENT SPECIALIST CONTRACTOR'S DETAIL
6.2 ALL WIRING FOR LIGHTING INSTALLATIONS SHALL FOLLOW CONNECTED VIA SUITABLE ISOLATORS AND CONNECTION
DRAWINGS.
4.4 ALL SOCKET OUTLETS LOCATED ABOVE WORKTOPS SHALL "LOOP-IN" SYSTEM. BOXES INSTALLED CLOSE TO THEM. PROVIDE UNDER
BE MOUNTED 1200MM ABOVE FINISHED FLOOR LEVEL OR 6.3 ALL SELF CONTAINED TYPE EMERGENCY/EXIT LIGHTING VOLTAGE RELAYS AND AUTO RESET TIMER WITH
300MM ABOVE WORK TOP AS APPROVED ON SITE. FIXTURES SHALL BE PROVIDED WITH CHARGER/INVERTER ADJUSTABLE TIME SETTING BETWEEN 5 AND 10 MINUTES,
4.5 WHERE OUTLET IS PROVIDED FOR CONNECTION TO A MODULE AND BATTERY BACK-UP FOR A MINIMUM OF 3 FOR EACH UNIT.
FIXED APPLIANCE BY MEANS OF A FLEXIBLE CABLE, THE HOURS CONTINUOUS OPERATION AND TO BE COMPATIBLE
RESPECTIVE OUTLET SHALL BE POSITIONED AS CLOSE AS WITH EMERGENCY LIGHTING SYSTEM. 9.0 ELV SYSTEMS
PRACTICABLE TO THE CABLE ENTRY OF THE FIXED
7.0 EARTHING/GROUNDING 9.1 ACTIVATION OF THE FIRE ALARM SYSTEM SHALL START
APPLIANCE.
4.6 ALL ELECTRICAL OPERATED PLANT AND EQUIPMENT 7.1 THE EARTHING SYSTEM SHALL FOLLOW THE PRINCIPLES AND SHUTDOWN HVAC PLANT, AS PER HVAC CLIENT
SHALL BE PROVIDED WITH MEANS OF LOCAL ISOLATION OF TT SYSTEM i.e. SEPARATE EARTH AND NEUTRAL SPECIFICATIONS AND DRAWINGS. PROPER COORDINATION
INSTALLED AS CLOSE AS POSSIBLE TO THE EQUIPMENT
BEING SERVED.
CONDUCTOR, AS SHOWN ON DRAWINGS. THE OVERALL BETWEEN THE TWO SYSTEMS SHALL BE CARRIED OUT UNICEF
4.7 FOR EXACT LOCATION OF ISOLATORS AND DISCONNECT SYSTEM EARTH RESISTANCE SHALL BE DURING EXECUTION.
1 OHM OR LESS. 9.2 ALL LOW CURRENT SYSTEMS WIRING AND CABLES SHALL
SWITCHES FOR PUMPS, AHUS, MCCS AND OTHER
7.2 EARTHING OF ELECTRICAL SUBSTATIONS SHALL BE BE AS PER THE SPECIFICATIONS AND PROJECT
MECHANICAL/HVAC EQUIPMENT, THE CONTRACTOR SHALL
PROVIDED IN ACCORDANCE WITH REGULATIONS. MANUFACTURER'S/SUPPLIER'S RECOMMENDATIONS. PROPOSED REHABILITATION
COORDINATE WITH MECHANICAL WORKS.
4.8 ISOLATORS FOR HVAC EQUIPMENT SHALL BE HEAVY DUTY 7.3 PROVIDE COMPLETELY INDEPENDENT AND CLEAN 9.3 ALL CABLING/WIRING SERVING THE LIFE SAFETY SYSTEMS TO KAYOLE II HOSPITAL
'ON-LOAD' TYPE AND SUITABLY RATED, TAKING INTO EARTHING SYSTEM FOR LOW CURRENT/COMMUNICATION SUCH AS FIRE ALARM, SMOKE MANAGEMENT, FIRE PUMPS, NAIROBI COUNTY .
CONSIDERATION NORMAL AND STARTING CURRENTS OF SYSTEMS, WHEN REQUIRED AS PER MANUFACTURER'S ETC., SHALL BE THREE HOURS FIRE RATED AS PER NFPA.
THE EQUIPMENT AND THE AMBIENT TEMPERATURE OF THE RECOMMENDATIONS OR LOCAL AUTHORITY REGULATIONS. 9.4 SEPARATE CONDUIT SHALL BE RUN FOR EACH LOW DRAWING TITLE

OPERATING AREA. 7.4 A SEPARATE GROUNDING CONDUCTOR SHALL BE RUN CURRENT SYSTEM. MINIMUM SIZE OF CONDUIT SHALL BE
ELECTRICAL NOTES 2
4.9 ALL ISOLATORS/EQUIPMENT INSTALLED IN WET AND/OR WITH EACH CIRCUIT. ALL LIGHTING FIXTURES, 20mm DIA.
POSSIBLE WET LOCATIONS SUCH AS TOILETS, PUMP RECEPTACLES, SWITCHES, METALLIC JUNCTION BOXES 9.5 ALL LOW CURRENT CABLES SHALL BE LAID AT A DISTANCE
ROOMS, ROOF, EXTERNAL/EXPOSED AREAS, ETC. SHALL AND FITTINGS SHALL BE EFFECTIVELY AND PROPERLY OF NOT LESS THAN 300MM FROM LOW VOLTAGE POWER
BE WEATHERPROOF TYPE TO APPROPRIATE IP RATING DESIGN SERVICES UNIT
7.5 EARTHED.
EARTH CONTINUITY CONDUCTORS AND BONDING CABLES AND 60OMM FROM MEDIUM VOLTAGE POWER
(MINIMUM IP-54). CONDUCTORS SHALL BE SINGLE CORE, PVC INSULATED. CABLES. DRAWN BY Cephanie M.
5.0 SWITCHGEAR/DISTRIBUTION BOARDS 9.6 ALL FIRE ALARM SYSTEM INSTALLATIONS INCLUDING CHECKED BY PhilipM .
5.1 ALL LIGHTING AND POWER DISTRIBUTION BOARDS (DB) 7.6 EARTHING CONDUCTOR OF THE RESPECTIVE CIRCUIT WIRING AND DEVICES SHALL BE IN ACCORDANCE WITH
SHALL BE FLUSH MOUNTED TYPE IN ALL PUBLIC AND SHALL RUN IN THE SAME TRENCH/PIPE/TRUNKING OR ON NFPA 72 AND LOCAL CIVIL DEFENSE REQUIREMENTS. APPROVED BY MoyizE .
CIRCULATION AREAS AND SURFACE MOUNTED IN SAME CABLE TRAY/LADDER AS THE ASSOCIATED CABLE. MAY 2016
9.7 ALL TELEPHONE AND DATA SYSTEM INSTALLATIONS DATE
ELECTRICAL/MECHANICAL AND PLANT ROOMS, UNLESS 7.7 EXTRANEOUS METALWORK AS METALLIC PIPES, DUCTING, INCLUDING WIRING AND DEVICES SHALL BE IN DRAWING NUMBER :
OTHERWISE INDICATED. THESE SHALL BE PROVIDED WITH CABLE TRAYS, METALWORK IN TOILETS, ETC. SHALL BE ACCORDANCE WITH EIA/TIA REGULATIONS AND LOCAL T-101-016-D-E02
LOCKABLE DOORS. BONDED TO EARTHING SYSTEM BY PVC INSULATED CABLE
5.2 THE TOTAL LOAD ON THE THREE PHASES SHALL BE AUTHORITY REQUIREMENTS.
IN ACCORDANCE WITH APPLICABLE STANDARDS. COPYRIGHT RESERVED
BALANCED AS EVENLY AS PROVIDED ON ALL SWITCHGEAR
THIS DESIGN AND DETAIL ARE , AND
AND DISTRIBUTION BOARDS. AT ALL TIMES THE EXCLUSIVE
PROPERTY OF THE UNOPS / EAH ,NAIROBI
AND CANNOT BE USED OR REPRODUCED
WITHOUT WRITTEN CONSENT .

TENDER DRAWINGS
GSPublisherEngine 0.0.100.100
CIR A17
E
CIR A17
E
CIR A17
E
Operational
UN OPS
excellence for results that matter
CIR C2
CIR B6

BL

BL
CIR B6 4 4 4 4 East Africa Hub ( EAH ) , Nairobi
SLUICE
STERILIZATION
CIR C1 CIR C1 4 4 4 4 UNOPS Building , UN lane ,
A A A W W W W B CIR A16 CIR A16
ROOM CIR A16 CIR A16 Off Avenue P .O . Box 783 ,
CIR B6 Village Market , 00621
CIR B6 1ST STAGE CIR B6 DELIVERY DELIVERY B NURSERY WASHROOMS
W Nairobi , Kenya .
ROOM ROOM V . V
CIR
A A A CIR B7 CIR B7 B
2222
A16 GENERAL NOTES
W W W W BL BL BL
E CIR
2 CIR C1 CIR C1 4 A17 1 . All dimensions are in centimetres ,
2 2 CIR A16 CIR A16 CIR A16 unless otherwise stated .
2 2

X
CIR 2 . All dimensions to be checked and
confirmed on site before commencement
A16 of any work .
4 A CIR C1 A A A A
CIR C1 CIR B7
CIR B6 WARD 3 3 . Written dimensions overrides scaled
X

CIR A17 E
2
WAITING AREA B B
dimensions ,thus all dimensions are
to be read and not at any time scaled from
2
1 .5 M WIDE PASSAGE
22
CIR the drawing .
A CIR B7 A A16
EXAMINATION CU'B' CU'C' 4 . Any discrepancy to be reported to the
ROOM A Engineer promptly before proceeding .
B B 2

A 2 CIR B7
CIR B6 A NO . REVISION DATE APPR .
CIR A16 CIR A16 CIR A16
MILKB7
CIR
BL BL BL
D CIR B7
BL BL BL
2

4 B W
CIR B6 CIR CIR CIR
4 CIR B6 TOILET NURSING
PASSAGE CIR B7 CIR B7 STATION A16 A16 A16
KITCHEN CIR A16
A PANTRY
CIR B6
D C PASSAGE
SAMPLES CIR B6 A DB'A' E CIR
TOILET LINENA CIR A16 WARD 2 A17 CLIENT
B B
CIR
2

X
A A16 UNICEF
CIR B6 E CIR 2

B B A17 PROJECT
A A CIR A16 PROPOSED REHABILITATION
EXAMINATION CIR A16 CIR A16
BL BL BL TO KAYOLE II HOSPITAL
CIR B6 NAIROBI COUNTY .
CIR A17 E
WAITING AREA CIR A16 BL BL BL
CIR A17 CIR A17 CIR A17 DRAWING TITLE
WAITING AREA
A LIGHTING LAYOUT
D D A
WARD 1
2

CIR B6
RECORDS REGISTRYCIR B6 DESIGN SERVICES UNIT
CIR A16
B B B
22
CIR CIR DRAWN BY Cephanie M.
E A17 A17 E CIR CHECKED BY PhilipM .
CIR A
A17 A17 APPROVED BY MoyizE .
DATE MAY 2016
CIR A17 CIR A17 CIR A17 CIR A17 DRAWING NUMBER :

CIR A16 BL BL BL BL T-101-016-D-E03

E COPYRIGHT RESERVED
FLL
KAYOLE II HOSPITAL scale 1 :100
CIR C9 THIS DESIGN AND DETAIL ARE , AND
AT ALL TIMES THE EXCLUSIVE
PROPERTY OF THE UNOPS / EAH ,NAIROBI
AND CANNOT BE USED OR REPRODUCED
WITHOUT WRITTEN CONSENT .

TENDER DRAWINGS
GSPublisherEngine 0.0.100.100
TYPE SYMBOL IMAGE DESCRIPTION MOUNTING Operational
UN OPS
excellence for results that matter
East Africa Hub ( EAH ) , Nairobi
UNOPS Building , UN lane ,
Off Avenue P .O . Box 783 ,
1X18W 1200MM LED PLAIN BATTEN FITTING SURFACE MOUNTED Village Market , 00621
TYPE A A COMPLETE WITH LED LAMP AS THOMSON LED ON CEILING Nairobi , Kenya .
(1750LM MIN.)
GENERAL NOTES
1 . All dimensions are in centimetres ,
unless otherwise stated .

2X18W 1200MM LED PLAIN BATTEN FITTING SURFACE MOUNTED 2 . All dimensions to be checked and
confirmed on site before commencement
TYPE B B COMPLETE WITH LED LAMP AS THOMSON ON CEILING of any work .

LED(2X1750LM MIN.) 3 . Written dimensions overrides scaled


dimensions ,thus all dimensions are
to be read and not at any time scaled from
the drawing .

4 . Any discrepancy to be reported to the


3X18W 600mm x 1200mm LED CAT2 LOUVER LIGHT SURFACE MOUNTED Engineer promptly before proceeding .
TYPE C C FITTING COMPLETE WITH LED LAMP AS THOMSON ON CEILING
NO . REVISION DATE APPR .
LED (3X1750LM MIN.)

8.5W LED SPHERICAL BALL FITTING COMPLETE SURFACE MOUNTED


TYPE 4 WITH LED LAMP AS THOMSON LED (800LM MIN.) ON CEILING
4

CLIENT

UNICEF
2X18W IP65 1200MM LED WATERPROOF FITTING SURFACE MOUNTED
TYPE W W ON CEILING
WITH ACRYLIC DIFFUSER AND COMPLETE WITH LED PROJECT

LAMP AS THOMSON LED (2X1750LM MIN.) PROPOSED REHABILITATION


TO KAYOLE II HOSPITAL
NAIROBI COUNTY .

DRAWING TITLE
9W 600MM IP54 LED ALUMINUM BED SIDE LIGHT 1500MM FFL WALL
TYPE NL BL MOUNTED LIGHTING SCHEDULE
FITTING WITH WHITE FINISH AND COMPLETE WITH
INTEGRAL SWITCH AND LED LAMP AS EATON MBPL
(800LM MIN.) DESIGN SERVICES UNIT
DRAWN BY Cephanie M.
1X9W 600MM LED PLAIN BATTEN FITTING SURFACE MOUNTED CHECKED BY PhilipM .
TYPE D D COMPLETE WITH LED LAMP AS THOMSON LED ON CEILING APPROVED BY MoyizE .
(800LM MIN.) DATE MAY 2016
DRAWING NUMBER :

T-101-016-D-E04

SURFACE MOUNTED COPYRIGHT RESERVED


1X18W IP65 1200MM LED WATERPROOF FITTING
TYPE V V ON CEILING THIS DESIGN AND DETAIL ARE , AND
AT ALL TIMES THE EXCLUSIVE
WITH ACRYLIC DIFFUSER AND COMPLETE WITH LED PROPERTY OF THE UNOPS / EAH ,NAIROBI
LAMP AS THOMSON LED (1750LM MIN.) AND CANNOT BE USED OR REPRODUCED
WITHOUT WRITTEN CONSENT .

TENDER DRAWINGS
GSPublisherEngine 0.0.100.100
UN OPS
CIR B2 CIR C4 C C C C

HL CIR B2 HL DELIVERY
CIR C3 CIR A9
SLUICE ROOM

DP
DELIVERY CIR B3 C
ROOM NURSERY Operational excellence for results that matter
ROOM CIR C4 CIR C4
CIR C3
WASHROOMS East Africa Hub ( EAH ) , Nairobi
CIR B2 + 2 .10 CIR A 10/ UNOPS Building , UN lane ,
1ST STAGE TD 02 8 no . 11/12/13 Off Avenue P .O . Box 783 ,
Village Market , 00621

DP
C DP DP DP DP

CIR B5 CIR C3 CIR B3


STERILIZATION CIR C4 Nairobi , Kenya .
HL HL HL
CIR A3 CIR A3 CIR A3
GENERAL NOTES
1 . All dimensions are in centimetres ,
unless otherwise stated .

WARD 3 2 . All dimensions to be checked and


WAITING AREA confirmed on site before commencement
of any work .
CIR B1 1 .5 M WIDE PASSAGE 3 . Written dimensions overrides scaled
EXAMINATION CU'B' CU'C'
dimensions ,thus all dimensions are
to be read and not at any time scaled from
ROOM the drawing .

MILK CIR A3 CIR A3 CIR A3 4 . Any discrepancy to be reported to the


Engineer promptly before proceeding .
CIR B1 CIR A4 KITCHEN CIR A4 HL HL HL
TOILET PANTRY AB NO . REVISION DATE APPR .
CIR A5 HL HL HL
CIR B1 C
PASSAGE
CIR A2 CIR A2 CIR A2
CIR A6

DP
SAMPLES CIR B1 C
CIR A4
TOILET PASSAGE ADAPTABLE
32Ø MM HG DB'A' BOX LINKED
NURSING
LINEN PVC CONDUIT STATION TO ROOF WARD 2

CIR B1
EXAMINATION CLIENT

50SQ.MM SC PVC INSULTED


CIR B1
EQUIPOTENTIAL EARTH LEAD CU UNICEF
CABLE FOR GRID TIED SYSTEM CIR A2 CIR A2 CIR A2
WAITING AREA HL HL HL
CIR B1 PROJECT

HL HL HL PROPOSED REHABILITATION
WAITING AREA CIR A1 CIR A1 CIR A1 TO KAYOLE II HOSPITAL
NAIROBI COUNTY .

DRAWING TITLE

RECORDS REGISTRY CIR B1 POWER AND FIRE ALARM LAYOUT


WARD 1
DESIGN SERVICES UNIT
DRAWN BY Cephanie M.
CHECKED BY PhilipM .
CIR A18 CIR A1
CIR A1 CIR A1 CIR A1 CIR A1
DP

C
HL
APPROVED BY MoyizE .
HL HL HL HL
DATE MAY 2016
1800/ 300MM CENTRE FFL
DRAWING NUMBER :
HL TV OUTLET POINT 1800/ 300MM CENTRE FFL
300/1200/2100MM FFL 13AMP TWIN SOCKET OUTLET AS MK
T-101-016-D-E05
DOUBLE POLE SWITCH AS MK HL 1200MM CENTRE FFL
DP

RECESSED MOUNTED TPN DISTRIBUTION RECESSED MOUNTED SPN CONSUMER COPYRIGHT RESERVED
1800MM FFL UNIT TO SCHEMATIC DETAILS 1800MM FFL
BOARD TO SCHEMATIC DETAILS THIS DESIGN AND DETAIL ARE , AND
AT ALL TIMES THE EXCLUSIVE
PROPERTY OF THE UNOPS / EAH ,NAIROBI
AND CANNOT BE USED OR REPRODUCED
WITHOUT WRITTEN CONSENT .

TENDER DRAWINGS
GSPublisherEngine 0.0.100.100 KAYOLE
Operational
UN OPS
excellence for results that matter
East Africa Hub ( EAH ) , Nairobi
3X4.0MM SQ PVC INSULATED COPPER CABLES UNOPS Building , UN lane ,
3X2.5MM SQ PVC INSULATED COPPER CABLES CIR A10 DRAWN IN 20MMØ HG PVC CONDUITS IN SPUR FOR Off Avenue P .O . Box 783 ,
CIR A1 DRAWN IN 25MMØ HG PVC CONDUITS IN RING
30A 20A Village Market , 00621
MAIN FOR 13A SOCKET OUTLETS GEYSER HEATING ELEMENT OUTLET
Nairobi , Kenya .

3X2.5MM SQ PVC INSULATED COPPER CABLES 3X4.0MM SQ PVC INSULATED COPPER CABLES
CIR A11 DRAWN IN 20MMØ HG PVC CONDUITS IN SPUR FOR
GENERAL NOTES
CIR A2 DRAWN IN 25MMØ HG PVC CONDUITS IN RING
30A 20A 1 . All dimensions are in centimetres ,
MAIN FOR 13A SOCKET OUTLETS GEYSER HEATING ELEMENT OUTLET
unless otherwise stated .

2 . All dimensions to be checked and


3X2.5MM SQ PVC INSULATED COPPER CABLES 3X4.0MM SQ PVC INSULATED COPPER CABLES confirmed on site before commencement
CIR A3 CIR A12 DRAWN IN 20MMØ HG PVC CONDUITS IN SPUR FOR
DRAWN IN 25MMØ HG PVC CONDUITS IN RING 20A
of any work .
30A GEYSER HEATING ELEMENT OUTLET
MAIN FOR 13A SOCKET OUTLETS 3 . Written dimensions overrides scaled
dimensions ,thus all dimensions are
to be read and not at any time scaled from
3X2.5MM SQ PVC INSULATED COPPER CABLES 3X4.0MM SQ PVC INSULATED COPPER CABLES the drawing .
CIR A4 CIR A13 DRAWN IN 20MMØ HG PVC CONDUITS IN SPUR FOR
DRAWN IN 25MMØ HG PVC CONDUITS IN RING 20A
30A GEYSER HEATING ELEMENT OUTLET 4 . Any discrepancy to be reported to the
MAIN FOR 13A SOCKET OUTLETS Engineer promptly before proceeding .

3X6.0MM SQ PVC INSULATED COPPER CABLES CIR A14 3x10SQ.MM SC PVC INSULATED COPPER CABLES
NO . REVISION DATE APPR .
CIR A5 DRAWN IN 25MMØ HG PVC CONDUITS IN SPUR FOR
30A 50A DRAWN IN 38MMØ HG PVC CONDUIT TO CU'B'
COOKER OUTLET

3X4.0MM SQ PVC INSULATED COPPER CABLES 2C, 10SQ.MM PVC/SWA/PVC INSULATED COPPER
CIR A6 CIR A15
DRAWN IN 25MMØ HG PVC CONDUITS IN SPUR FOR CABLES DRAWN IN 38MMØ HG PVC CONDUIT TO
20A 50A
UNDERSINK HEATER OUTLET GRID TIED INVERTER

CIR A7 CIR A16 3X1.5MM SQ PVC INSULATED COPPER CABLES


SPARE WAYS 10A DRAWN IN 20MMØ HG PVC CONDUITS FOR LIGHTING CLIENT

UNICEF
CIR A8 CIR A17 3X1.5MM SQ PVC INSULATED COPPER CABLES
SPARE WAYS 10A DRAWN IN 20MMØ HG PVC CONDUITS FOR LIGHTING
PROJECT

PROPOSED REHABILITATION
TO KAYOLE II HOSPITAL
3X4.0MM SQ PVC INSULATED COPPER CABLES 2C, 4SQ.MM PVC/SWA/PVC INSULATED COPPER NAIROBI COUNTY .
CIR A9 CIR A18
DRAWN IN 25MMØ HG PVC CONDUITS IN SPUR FOR CABLES DRAWN IN 32MMØ HG PVC CONDUIT TO
20A 20A
SPACE HEATER OUTLET BOOSTER PUMP DRAWING TITLE

DISTRIBUTION BOARD SCHEMATIC


4C, 10SQ.MM PVC/SWA/PVC
COPPER CABLES DRAWN IN PVC
DUCTS FROM MDB IN POWER HOUSE DESIGN SERVICES UNIT
SPARE WAYS
DRAWN BY Cephanie M.
CHECKED BY PhilipM .
APPROVED BY MoyizE .

9-WAYS 63A TPN KPLC POWER DISTRIBUTION DATE

DRAWING NUMBER :
MAY 2016

63A TPN MAIN


BOARD DB`A' IN NURSE CALL STATION WITH T-101-016-D-E06

THREE TPN SPARE WAYS COPYRIGHT RESERVED


THIS DESIGN AND DETAIL ARE , AND
INTEGRAL AT ALL TIMES THE EXCLUSIVE
PROPERTY OF THE UNOPS / EAH ,NAIROBI
AND CANNOT BE USED OR REPRODUCED
WITHOUT WRITTEN CONSENT .
ISOLATOR TENDER DRAWINGS
GSPublisherEngine 0.0.100.100
Operational
UN OPS
excellence for results that matter
East Africa Hub ( EAH ) , Nairobi
UNOPS Building , UN lane ,
Off Avenue P .O . Box 783 ,
3x10 SQ.MM SC PVC INSULATED Village Market , 00621
Nairobi , Kenya .
COPPER CABLES DRAWN IN GENERAL NOTES
38MMØ HG PVC CONDUIT FROM 1 . All dimensions
unless otherwise
are in centimetres
stated .
,

FROM DB'A' CIR B1 3x2.5mm sq PVC INSULATED COPPER CABLES 2 . All dimensions to be checked and
30A DRAWN IN 20mmØ HG PVC CONDUITS IN RING confirmed on site before commencement
of any work .
MAIN FOR 13A SOCKET OUTLETS
3 . Written dimensions overrides scaled
dimensions ,thus all dimensions are
CIR B2 3x2.5mm sq PVC INSULATED COPPER CABLES to be read and not at any time scaled from
30A DRAWN IN 20mmØ HG PVC CONDUITS IN RING the drawing .

MAIN FOR 13A SOCKET OUTLETS 4 . Any discrepancy to be reported to the


Engineer promptly before proceeding .

CIR B3 3x2.5mm sq PVC INSULATED COPPER CABLES NO . REVISION DATE APPR .


30A DRAWN IN 20mmØ HG PVC CONDUITS IN RING
MAIN FOR 13A SOCKET OUTLETS

CIR B4 3x4.0mm sq PVC INSULATED COPPER CABLES


63A SPN 20A DRAWN IN 25mmØ HG PVC CONDUITS IN SPUR
INTEGRAL FOR UNDERSINK HEATER OUTLET
ISOLATOR
CIR B5 3X4.0MM SQ PVC INSULATED COPPER CABLES
20A DRAWN IN 20MMØ HG PVC CONDUITS IN SPUR
CLIENT

FOR GEYSER HEATING ELEMENT OUTLET UNICEF


CIR B6 3x1.5mm sq PVC INSULATED COPPER CABLES
10A DRAWN IN 20mmØ HG PVC CONDUITS FOR PROJECT

PROPOSED REHABILITATION
LIGHTING TO KAYOLE II HOSPITAL
NAIROBI COUNTY .
CIR B7 3x1.5mm sq PVC INSULATED COPPER CABLES
10A DRAWN IN 20mmØ HG PVC CONDUITS FOR DRAWING TITLE

LIGHTING RAW POWER CONSUMER UNIT

SPARE WAY DESIGN SERVICES UNIT


DRAWN BY Cephanie M.
CHECKED BY PhilipM .
8-WAY 63A SPN RAW POWER CONSUMER UNIT
APPROVED BY MoyizE .
DATE MAY 2016
DRAWING NUMBER :
CU`B' FOR KPLC POWER T-101-016-D-E07

COPYRIGHT RESERVED
THIS DESIGN AND DETAIL ARE , AND
AT ALL TIMES THE EXCLUSIVE
PROPERTY OF THE UNOPS / EAH ,NAIROBI
AND CANNOT BE USED OR REPRODUCED
WITHOUT WRITTEN CONSENT .

TENDER DRAWINGS
GSPublisherEngine 0.0.100.100
INTEGRAL

ISOLATOR

Operational
UN OPS
excellence for results that matter
East Africa Hub ( EAH ) , Nairobi
UNOPS Building , UN lane ,
Off Avenue P .O . Box 783 ,
Village Market , 00621
Nairobi , Kenya .

GENERAL NOTES
SPACE REQUIREMENTS:
KAYOLE 2 MATERNITY BLOCK 1 . All dimensions are in centimetres ,
unless otherwise stated .
1. SOLAR PANELS - 12.3SQ.M
2 . All dimensions to be checked and
2. BATTERY BANKS - 0.12CU.M confirmed on site before commencement
6X270W PV SOLAR PANELS;
CABLES: of any work .
1X6 CONFIGURATION
WEIGHT REQUIREMENTS: 3 . Written dimensions overrides scaled
1. 4SQ.MM SC XLPE/SWA/XLPE COPPER CABLE dimensions ,thus all dimensions are
to be read and not at any time scaled from
2. 4SQ.MM 2C XLPE/SWA/XLPE COPPER CABLE 1. SOLAR PANELS - 128KG the drawing .
3. 6SQ.MM 2C PVC INSULATED COPPER CABLE 2. BATTERY BANKS - 132KG 4 . Any discrepancy to be reported to the
4. 16SQ.MM SC PVC INSULATED COPPER CABLE Engineer promptly before proceeding .

NO . REVISION DATE APPR .

MAINS
CHARGING
1 1 CIRCUIT

20A AC
ISOLATOR
1
COMBINER 10A DC 20A AC
BOX 2 3 3 3 ISOLATOR3 SOLAR POWER
ISOLATOR CONSUMER
SURGE
ARRESTOR MAIN EARTH
DC
MCB
ARRAY

POSITIVE
BUS
BAR

M UNIT CU'C' CLIENT


TERMINAL

MAIN MAIN
POSITIVE NEGATIVE

63A SPN
TERMINAL TERMINAL

1no. 4500W
UNICEF
KwH

INTEGRAL
1no. 48VDC, INVERTER ISOLATOR
DC 80A CHARGE
CONTROLLER +
-

EARTHING
4 4 PROJECT

PROPOSED REHABILITATION
TO KAYOLE II HOSPITAL
AC NAIROBI COUNTY .
EARTHING DRAWING TITLE

4X12V BATTERY SOLAR DESIGN


BANKS; 1X4
CONFIGURATION
25x3mm 25x3mm
EQUIPOTENTIAL
BONDING COPPER TAPE DESIGN SERVICES UNIT
DRAWN BY Cephanie M.
CHECKED BY PhilipM .
APPROVED BY MoyizE .
DATE MAY 2016
DRAWING NUMBER :

T-101-016-D-E09

COPYRIGHT RESERVED
THIS DESIGN AND DETAIL ARE , AND
AT ALL TIMES THE EXCLUSIVE
PROPERTY OF THE UNOPS / EAH ,NAIROBI
AND CANNOT BE USED OR REPRODUCED
WITHOUT WRITTEN CONSENT .

TENDER DRAWINGS
GSPublisherEngine 0.0.100.100
Operational
UN OPS
excellence for results that matter
East Africa Hub ( EAH ) , Nairobi
UNOPS Building , UN lane ,
Off Avenue P .O . Box 783 ,
Village Market , 00621
Nairobi , Kenya .

GENERAL NOTES
1 . All dimensions are in centimetres ,
20A TIMER CIR C1 3x1.5mm sq PVC INSULATED COPPER CABLES DRAWN unless otherwise stated .

2C 10 SQ.MM PVC INSULATED SWITCH IN CU 10A IN 20mmØ HG PVC CONDUITS FOR LIGHTING 2 . All dimensions to be checked and
confirmed on site before commencement
T
COPPER CABLES DRAWN IN of any work .

CIR C2 3x1.5mm sq PVC INSULATED COPPER CABLES DRAWN


38MMØ HG PVC CONDUIT FROM 10A IN 20mmØ HG PVC CONDUITS FOR LIGHTING
3 . Written dimensions overrides scaled
dimensions ,thus all dimensions are
to be read and not at any time scaled from
INVERTER the drawing .

4 . Any discrepancy to be reported to the


Engineer promptly before proceeding .

CIR C3 3x2.5mm sq PVC INSULATED COPPER CABLES NO . REVISION DATE APPR .


30A DRAWN IN 20mmØ HG PVC CONDUITS IN RING
MAIN FOR 13A SOCKET OUTLETS

CIR C4 3x2.5mm sq PVC INSULATED COPPER CABLES


30A DRAWN IN 20mmØ HG PVC CONDUITS IN RING
MAIN FOR 13A SOCKET OUTLETS

SPARE WAY
63A SPN CLIENT

INTEGRAL
ISOLATOR UNICEF
SPARE WAY
PROJECT

PROPOSED REHABILITATION
TO KAYOLE II HOSPITAL
SPARE WAY NAIROBI COUNTY .

DRAWING TITLE

SOLAR POWER SCHEMATIC


SPARE WAY

DESIGN SERVICES UNIT


8-WAY 63A SPN SOLAR POWER CONSUMER DRAWN BY Cephanie M.
CHECKED BY PhilipM .
UNIT CU`C' FOR SOLAR LIGHTING APPROVED BY MoyizE .
DATE MAY 2016
DRAWING NUMBER :

T-101-016-D-E08

COPYRIGHT RESERVED
THIS DESIGN AND DETAIL ARE , AND
AT ALL TIMES THE EXCLUSIVE
PROPERTY OF THE UNOPS / EAH ,NAIROBI
AND CANNOT BE USED OR REPRODUCED
WITHOUT WRITTEN CONSENT .

TENDER DRAWINGS
GSPublisherEngine 0.0.100.100
LIST OF DRAWINGS

00 T-101-016-E-E00 Drawing List

01 T-101-016-E-E01 ELECTRICAL NOTES - 1

02 T-101-016-E-E02 ELECTRICAL NOTES - 2

03 T-101-016-E-E03 LIGHTING LAYOUT

04 T-101-016-E-E04 LIGHTING SCHEDULE

POWER LAYOUT
05 T-101-016-E-E05

06 T-101-016-E-E06 DISTRIBUTION BOARD SCHEMATIC

07 T-101-016-E-E07 SOLAR POWER SCHEMATIC

08 T-101-016-E-E08 SOLAR DESIGN

09 T-101-016-E-E09 NURSE CALL SCHEMATIC


GENERAL
THE DESIGN DRAWINGS SHALL BE READ IN CONJUNCTION CABLE SIZES, MCB's,MCCBs AND ISOLATORS SHOWN ON CONDUITS, CABLE TRAYS AND TRUNKING
WITH THE RELEVANT SPECIFICATIONS AND THE DRAWINGS ARE BASED ON DESIGNED LOADS. THE THE MINIMUM SIZE OF CONDUIT USED FOR ANY SYSTEM
ARCHITECTURAL, INTERIOR DESIGN, STRUCTURAL, CIVIL & CONTRACTOR SHALL PROVIDE THE SIZE OF CABLE, MCB, WIRING SHALL BE 20MM INTERNAL DIAMETER.
MECHANICAL DRAWINGS AND SPECIFICATIONS. MCCB AND ISOLATOR BASED ON ACTUAL LOADS OF THE PVC CONDUITS SHALL BE HEAVY GAUGE, POLISHED AND
THESE NOTES ARE GENERALLY APPLICABLE TO THE EQUIPMENT APPROVED BY THE ENGINEER AT NO EXTRA SMOOTH INSIDE AND OUTSIDE, FLAME-RETARDANT AND
OVERALL SYSTEMS INSTALLATION. ANY ADDITIONAL COST.
NOTES ON INDIVIDUAL DRAWINGS WHICH ARE
SUPPLEMENTARY TO THESE NOTES SHALL BE READ WITH FOR SPECIAL SYSTEMS, THE CONTRACTOR IS TO SUBMIT RIGID STEEL CONDUITS (RSC) SHALL BE HEAVY GAUGE,
THE INSTRUCTIONS STATED HEREIN. SHOP DRAWINGS PREPARED BY SPECIALISTS HOT DIP GALVANIZED TO CLASS 4 PROTECTION BOTH
THE FINAL POSITION OF ALL EQUIPMENT, PANELS, EXPERIENCED IN THE DESIGN OF THE RELEVANT SYSTEMS INSIDE AND OUTSIDE.
LUMINAIRES, DETECTORS, SWITCHES, OUTLETS AND AND AS PER THE MANUFACTURERS REQUIREMENTS. ALL PVC BOXES SHALL BE RIGID, FLAME-RETARDANT,
OTHER ACCESSORIES SHALL BE COORDINATED WITH THE CABLES SMOOTH AND ACCORDING TO LATEST
ARCHITECTURAL, MECHANICAL AND INTERIOR DESIGN STANDARDS/SPECIFICATIONS.
DETAILS AND WILL BE APPROVED AT SITE BY THE ALL WIRES AND CABLES SHALL BE STRANDED COPPER CONDUCTORS, ALL STEEL BOXES SHALL BE HEAVY GAUGE, HOT DIP
ENGINEER. PVC INSULATED COMPLYING WITH BS 6004 OR XLPE INSULATED AS PER GALVANIZED ACCORDING TO LATEST
UNLESS OTHERWISE SPECIFIED ALL EQUIPMENT AND IEC 502 AS SHOWN ON DRAWINGS OR SCHEDULES, EXCEPT FOR STANDARDS/SPECIFICATIONS.
MATERIALS TO BE USED SHALL BE SUITABLE AND RATED INFLAMABLE/EXPLOSIVE AND OTHER EXCEPTIONAL SITUATIONS.
BRASS BUSHINGS AND RINGS SHALL BE USED TO SECURE
FOR THE SITE AMBIENT CONDITIONS. COLOUR CODE OF ELECTRICAL WIRES AND CABLES SHALL
STEEL CONDUITS WITH STEEL BOXES.
ALL ELECTRICAL WORKS SHALL COMPLY WITH THE BE RED, YELLOW, BLUE, BLACK AND GREEN/YELLOW FOR
RELEVANT MINISTRY OF BUBLIC WORKS REGULATIONS, L1, L2, L3, NEUTRAL AND EARTH RESPECTIVELY IN A ALL STEEL COUPLERS SHALL BE PAINTED SUITABLY,
LATEST EDITION OF IEE WIRING REGULATIONS, THREE PHASE CONFIGURATION. IMMEDIATELY AFTER INSTALLATION.
INTERNATIONAL ELECTROTECHNICAL COMMISSION (IEC) THE CONDUCTOR SIZES FOR ALL CABLES SHALL BE IN
NO CONDUIT RUN SHALL BE LONGER THAN 15M
STANDARDS AND ISO RECOMMENDATIONS. ACCORDANCE WITH THE PANEL BOARD/CABLE
SCHEDULES AND SINGLE LINE DIAGRAMS.
THE INSTALLATION SHALL COMPLY IN ALL RESPECTS TO OTHERWISE IT MUST BE PASSED THROUGH PULL OR
THE REQUIREMENTS OF THE MANUFACTURERS AND THE THE MINIMUM SIZE OF ALL CIRCUIT CONDUCTORS SHALL DRAW BOX SUFFICIENT TO PERMIT EASY PULLING OF
CODES REFERRED IN THE SPECIFICATIONS. BE COORDINATED WITH THE STARTING AND OPERATING WIRES.
CHARACTERISTICS OF THE EQUIPMENT THEY SERVE.
ANY EQUIPMENT DIMENSIONS AND ELECTRICAL LOAD THE TOTAL FILL OF THE WIRES DRAWN IN CONDUIT SHALL
STATED ON THE DRAWINGS SHALL BE UNLESS OTHERWISE INDICATED, MINIMUM WIRE SIZE BE AS PER IEE REGULATIONS AND NORMALLY NOT TO
COORDINATED/CONFIRMED WITH THE ACTUAL EXCEED 40% OF THE INTERNAL CROSS-SECTIONAL AREA
DIMENSIONS AND ACTUAL ELECTRICAL LOAD OF OF THE CONDUIT.
EQUIPMENT FROM RESPECTIVE MANUFACTURER(S). LIGHTING AND SMALL POWER INSTALLATION SHALL BE ALL CONDUITS AND RECEWAYS PASSING THROUGH THE
ALL MATERIALS AND EQUIPMENT MUST BE OF THE BEST CARRIED OUT USING SINGLE CORE PVC INSULATED BUILDING EXPANSION JOINTS SHALL BE PROVIDED WITH
QUALITY AND ACCORDING TO THE LATEST INTERNATIONAL WIRES IN RIGID PVC CONDUITS EMBEDDED IN CONCRETE. EXPANSION JOINT COUPLING AND EXECUTED AS PER
STANDARDS. THE CONTRACTOR SHALL SUBMIT SAMPLES STANDARD DETAILS, APPROVED BY THE ENGINEER ON
ALL MULTICORE CABLES INSIDE THE BUILDING SHALL BE SITE.
AND CATALOGUES OF ALL MATERIALS AND OBTAIN INSTALLED ON CABLE TRAYS OR CABLE LADDERS. RAISED
ENGINEER'S APPROVAL BEFORE THE COMMENCEMENT OF SUN SHADES (COVERS) SHALL BE PROVIDED FOR ALL ALL BENDS IN DUCTS, CONDUITS AND OTHER RACEWAYS
ANY WORK. ROOF MOUNTED CABLE TRAYS/LADDERS. SHALL BE SUITABLE TO ALLOW MINIMUM CABLE BENDING
IT SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY RADIUS IN ACCORDANCE WITH MANUFACTURER'S
THE WIRES/CABLES FOR LV CIRCUITS INSIDE BUILDINGS RECOMMENDATIONS.
TO LIASE WITH THE LOCAL ELECTRICITY SUPPLY
SHALL BE INSTALLED AT A MINIMUM DISTANCE OF 300MM
AUTHORITY FOR THE ELECTRICITY SUPPLY CONNECTION ALL ENDS OF BURIED DUCTS AND CONDUITS SHALL HAVE
FROM HOT WATER LINES AND 150MM FROM OTHER
TO THE FACILITY AND MAKE PROVISIONS IN INSTALLATION BELL MOUTH PIPE ENDS AND SHALL BE SEALED BY A
SERVICE PIPES.
TO SATISFY THEIR REQUIREMENTS. THE SERVICES PROPRIETARY PIPE SEALING PRODUCT.
PROVIDED SHALL CONFORM IN ALL RESPECTS WITH THE WHERE EXTERNAL CABLES ARE DIRECT BURIED IN THE
LOCAL CODES AND REGULATIONS. GROUND, THESE SHALL RUN THROUGH UNDERGROUND CABLE LADDERS AND CABLE TRAYS SHALL BE INSTALLED
IT SHALL BE THE CONTRACTOR'S SOLE RESPONSIBILITY CONCRETE ENCASED UPVC DUCTS WHEN PASSING UNDER WHERE NECESSARY AND ARE NOT LIMITED TO WHAT IS
TO LIASE WITH LOCAL TELEPHONE AUTHORITY FOR THE ROADS AND BUILDINGS. SHOWN ON THE DRAWINGS. WIDTH, LENGTH, NUMBERS
REQUIRED TELEPHONE LINES TO THE FACILITY AND MAKE AND ROUTES OF CABLE TRAYS, LADDERS, PIPES AND
PROVISIONS IN INSTALLATION TO SATISFY THEIR OTHER CABLE RACEWAYS SHALL BE SHOWN ON SHOP
REQUIREMENTS. THE SERVICES PROVIDED SHALL DRAWINGS AS PER STANDARDS FOR APPROVAL.
CONFORM IN ALL RESPECTS WITH THEIR
STANDARDS/REGULATIONS. WHERE OPENINGS ARE PROVIDED IN STRUCTURE TO
THE LIGHTING, POWER AND LOW CURRENT SYSTEMS CROSS CABLE TRAYS, PIPES, ETC. THE OPENING SHALL BE
SHALL BE INSTALLED SEPARATELY FROM EACH OTHER. i.e. SEALED BY FIRE STOP MATERIAL SUITABLY RATED, AFTER
CONDUITS, RACEWAYS, WIRES, BOXES, ETC. INSTALLATION OF CABLES.
WIRING DEVICES

THE LOCATION OF ALL SWITCHES, OUTLETS AND OTHER MINIATURE CIRCUIT BREAKERS (MCB) WITH APPROPRIATE GENERATORS/MOTORS/MECHANICAL
WIRING DEVICES SHALL BE COORDINATED WITH THE SHORT CIRCUIT CURRENT RATING SHALL BE PROVIDED THE CONTROLS OF STANDBY GENERATOR FEEDING FIRE
FURNITURE LAYOUTS/ID DRAWINGS ON SITE. FOR LIGHTING, SWITCHED SOCKET OUTLETS, ELECTRIC PUMPS SHALL BE SO ARRANGED THAT THE GENERATOR
MOUNTING HEIGHTS FOR SWITCHES, SOCKETS, ETC., WATER HEATERS/COOLERS, REFRIGERATORS, COOKERS, SHALL CONTINUE RUNNING WHEN FM200 OR C02 GAS (FOR
FROM THE CENTRE OF THE DEVICE TO ABOVE FINISHED DOMESTIC WATER PUMPS AND SIMILAR EQUIPMENT. FIRE SUPPRESSION) IS RELEASED, UNLESS THE
FLOOR LEVEL SHALL BE AS FOLLOWS, UNLESS THE OVERALL POWER FACTOR OF EVERY ELECTRICAL GENERATOR IS MANUALLY SHUTDOWN. A MANUAL
OTHERWISE SPECIFIED OR DIRECTED BY THE ENGINEER: SUBSTATION SHALL BE MAINTAINED WITHIN THE RANGE SHUTDOWN SWITCH SHALL BE PROVIDED NEAR THE DOOR
OF 0.9 LAGGING AND UNITY. PROVIDE AUTOMATIC P.F. FOR SUCH GENERATOR.
IMPROVEMENT PLANT. DURING COMMERCIAL/NORMAL POWER FAILURE, ALL
THE CONTRACTOR HAS TO CHECK THE PHYSICAL ELEVATORS SHALL BE AUTOMATICALLY SWITCHED OVER
DIMENSION OF THE PANELS WITH THE SPACE TO EMERGENCY SOURCE AND CALLED TO MAIN EGRESS
AVAILABILITY PRIOR TO PLACING THE ORDER. DRAWINGS LEVEL IN SEQUENCE. SAID OPERATION TO BE CARRIED
FOR PANELS SHALL BE SUBMITTED TO THE ENGINEER FOR OUT THROUGH ELEVATOR CONTROLS AS PER ELEVATOR
APPROVAL. SPECIFICATIONS.
ALL ROTATING MACHINERY OPERATED THROUGH
THE ELECTRICAL CONTRACTOR SHALL INDICATE THE STARTER SHALL HAVE A NO VOLTAGE RELEASE
EXACT LOCATION, HEIGHT,... ETC OF ALL OUTLETS ON HIS LIGHTING INCORPORATED WITHIN ITS STARTER PANEL.
WORK SHOP DRAWINGS AFTER COORDINATING WITH THE ALL LIGHTING FIXTURES SHALL BE PROVIDED WITH ALL HVAC UNITS/PLANT/EQUIPMENT SUCH AS FCU'S,
EQUIPMENT SPECIALIST CONTRACTOR'S DETAIL POWER SUPPLY. AHU'S, CONDENSING UNITS, CHILLERS, ETC. SHALL BE
DRAWINGS. ALL WIRING FOR LIGHTING INSTALLATIONS SHALL FOLLOW CONNECTED VIA SUITABLE ISOLATORS AND CONNECTION
ALL SOCKET OUTLETS LOCATED ABOVE WORKTOPS SHALL "LOOP-IN" SYSTEM. BOXES INSTALLED CLOSE TO THEM. PROVIDE UNDER
BE MOUNTED 1200MM ABOVE FINISHED FLOOR LEVEL OR ALL SELF CONTAINED TYPE EMERGENCY/EXIT LIGHTING VOLTAGE RELAYS AND AUTO RESET TIMER WITH
300MM ABOVE WORK TOP AS APPROVED ON SITE. FIXTURES SHALL BE PROVIDED WITH CHARGER/INVERTER ADJUSTABLE TIME SETTING BETWEEN 5 AND 10 MINUTES,
WHERE OUTLET IS PROVIDED FOR CONNECTION TO A MODULE AND BATTERY BACK-UP FOR A MINIMUM OF 3 FOR EACH UNIT.
FIXED APPLIANCE BY MEANS OF A FLEXIBLE CABLE, THE HOURS CONTINUOUS OPERATION AND TO BE COMPATIBLE
RESPECTIVE OUTLET SHALL BE POSITIONED AS CLOSE AS WITH EMERGENCY LIGHTING SYSTEM. ELV SYSTEMS
PRACTICABLE TO THE CABLE ENTRY OF THE FIXED
APPLIANCE. EARTHING/GROUNDING ACTIVATION OF THE FIRE ALARM SYSTEM SHALL START
ALL ELECTRICAL OPERATED PLANT AND EQUIPMENT THE EARTHING SYSTEM SHALL FOLLOW THE PRINCIPLES AND SHUTDOWN HVAC PLANT, AS PER HVAC
SHALL BE PROVIDED WITH MEANS OF LOCAL ISOLATION OF TT SYSTEM i.e. SEPARATE EARTH AND NEUTRAL SPECIFICATIONS AND DRAWINGS. PROPER COORDINATION
INSTALLED AS CLOSE AS POSSIBLE TO THE EQUIPMENT CONDUCTOR, AS SHOWN ON DRAWINGS. THE OVERALL BETWEEN THE TWO SYSTEMS SHALL BE CARRIED OUT
BEING SERVED. SYSTEM EARTH RESISTANCE SHALL BE DURING EXECUTION.
FOR EXACT LOCATION OF ISOLATORS AND DISCONNECT
1 OHM OR LESS. ALL LOW CURRENT SYSTEMS WIRING AND CABLES SHALL
SWITCHES FOR PUMPS, AHUS, MCCS AND OTHER
MECHANICAL/HVAC EQUIPMENT, THE CONTRACTOR SHALL EARTHING OF ELECTRICAL SUBSTATIONS SHALL BE BE AS PER THE SPECIFICATIONS AND
COORDINATE WITH MECHANICAL WORKS. PROVIDED IN ACCORDANCE WITH REGULATIONS. MANUFACTURER'S/SUPPLIER'S RECOMMENDATIONS.
ISOLATORS FOR HVAC EQUIPMENT SHALL BE HEAVY DUTY PROVIDE COMPLETELY INDEPENDENT AND CLEAN ALL CABLING/WIRING SERVING THE LIFE SAFETY SYSTEMS
'ON-LOAD' TYPE AND SUITABLY RATED, TAKING INTO EARTHING SYSTEM FOR LOW CURRENT/COMMUNICATION SUCH AS FIRE ALARM, SMOKE MANAGEMENT, FIRE PUMPS,
CONSIDERATION NORMAL AND STARTING CURRENTS OF SYSTEMS, WHEN REQUIRED AS PER MANUFACTURER'S ETC., SHALL BE THREE HOURS FIRE RATED AS PER NFPA.
THE EQUIPMENT AND THE AMBIENT TEMPERATURE OF THE RECOMMENDATIONS OR LOCAL AUTHORITY REGULATIONS. SEPARATE CONDUIT SHALL BE RUN FOR EACH LOW
OPERATING AREA. A SEPARATE GROUNDING CONDUCTOR SHALL BE RUN CURRENT SYSTEM. MINIMUM SIZE OF CONDUIT SHALL BE
ALL ISOLATORS/EQUIPMENT INSTALLED IN WET AND/OR WITH EACH CIRCUIT. ALL LIGHTING FIXTURES, 20mm DIA.
POSSIBLE WET LOCATIONS SUCH AS TOILETS, PUMP RECEPTACLES, SWITCHES, METALLIC JUNCTION BOXES ALL LOW CURRENT CABLES SHALL BE LAID AT A DISTANCE
ROOMS, ROOF, EXTERNAL/EXPOSED AREAS, ETC. SHALL AND FITTINGS SHALL BE EFFECTIVELY AND PROPERLY OF NOT LESS THAN 300MM FROM LOW VOLTAGE POWER
BE WEATHERPROOF TYPE TO APPROPRIATE IP RATING EARTHED. CABLES AND 60OMM FROM MEDIUM VOLTAGE POWER
EARTH CONTINUITY CONDUCTORS AND BONDING
(MINIMUM IP-54). CABLES.
CONDUCTORS SHALL BE SINGLE CORE, PVC INSULATED.
SWITCHGEAR/DISTRIBUTION BOARDS ALL FIRE ALARM SYSTEM INSTALLATIONS INCLUDING
ALL LIGHTING AND POWER DISTRIBUTION BOARDS (DB) EARTHING CONDUCTOR OF THE RESPECTIVE CIRCUIT WIRING AND DEVICES SHALL BE IN ACCORDANCE WITH
SHALL BE FLUSH MOUNTED TYPE IN ALL PUBLIC AND SHALL RUN IN THE SAME TRENCH/PIPE/TRUNKING OR ON NFPA 72 AND LOCAL CIVIL DEFENSE REQUIREMENTS.
CIRCULATION AREAS AND SURFACE MOUNTED IN SAME CABLE TRAY/LADDER AS THE ASSOCIATED CABLE.
ELECTRICAL/MECHANICAL AND PLANT ROOMS, UNLESS ALL TELEPHONE AND DATA SYSTEM INSTALLATIONS
EXTRANEOUS METALWORK AS METALLIC PIPES, DUCTING, INCLUDING WIRING AND DEVICES SHALL BE IN
OTHERWISE INDICATED. THESE SHALL BE PROVIDED WITH
CABLE TRAYS, METALWORK IN TOILETS, ETC. SHALL BE ACCORDANCE WITH EIA/TIA REGULATIONS AND LOCAL
LOCKABLE DOORS.
BONDED TO EARTHING SYSTEM BY PVC INSULATED CABLE AUTHORITY REQUIREMENTS.
THE TOTAL LOAD ON THE THREE PHASES SHALL BE IN ACCORDANCE WITH APPLICABLE STANDARDS.
BALANCED AS EVENLY AS PROVIDED ON ALL SWITCHGEAR
AND DISTRIBUTION BOARDS.
CIR A4 CIR A4 CIR A4
E E E

CIR A1 CIR A1 4
BL

BL
BL

BL
CIR A1 CIR A1
B B B B A A A CIR A3
CIR B1 CIR B1 A B
CIR A3 CIR A3

BL

BL
CIR A3
BL

BL
CIR A1
BL

BL

A CIR A1 A CIR A1 CIR A3


CIR A1 CIR A1 CIR A3

CIR A1 CIR A1
A 2
2 2
B CIR B1 B 2 2
B CIR B1 B A A A 2

4
BL

BL
BL

BL
CIR A1 CIR A1 CIR A1 CIR A1 A CIR A3
CIR A3
CIR B1 CIR A2
2 22 2 2
E
CIR A3
X2 XX A
CIR A1 CIR A1
E A A A V
A A A CIR A2 A A
X 22 22 CIR A2 CIR A2
22 2
BL

BL
BL

BL

CIR A1 CIR A1 CIR A1 CIR A1


CIR A1 CIR A1
B B B CIR A2 B B
CIR A2
BL

BL
BL

BL

CIR A1 A CIR A1 CIR A1 A CIR A1 V V CIR A3


CIR A2 CIR A2 CIR A3
A CIR A3

B B B B B
BL

BL
BL

BL

CIR A1 CIR A1 CIR A1 CIR A1 4 4 4 4 4


CIR A2 CIR A2 2
2

E E X
E
CIR A4 CIR A4 CIR A4
B

CIR A2
B

2
TYPE SYMBOL IMAGE DESCRIPTION MOUNTING

1X18W 1200MM LED PLAIN BATTEN FITTING SURFACE MOUNTED


TYPE A A COMPLETE WITH LED LAMP AS THOMSON LED ON CEILING
(1750LM MIN.)

2X18W 1200MM LED PLAIN BATTEN FITTING SURFACE MOUNTED


TYPE B B COMPLETE WITH LED LAMP AS THOMSON ON CEILING
LED(2X1750LM MIN.)

3X18W 600mm x 1200mm LED CAT2 LOUVER LIGHT SURFACE MOUNTED


TYPE C C FITTING COMPLETE WITH LED LAMP AS THOMSON ON CEILING
LED (3X1750LM MIN.)

8.5W LED SPHERICAL BALL FITTING COMPLETE SURFACE MOUNTED


TYPE 4 WITH LED LAMP AS THOMSON LED (800LM MIN.) ON CEILING
4

2X18W IP65 1200MM LED WATERPROOF FITTING SURFACE MOUNTED


TYPE W W WITH ACRYLIC DIFFUSER AND COMPLETE WITH LED ON CEILING
LAMP AS THOMSON LED (2X1750LM MIN.)

9W 600MM IP54 LED ALUMINUM NIGHT LIGHT 1500MM FFL WALL


TYPE BL BL
FITTING WITH WHITE FINISH AND COMPLETE WITH MOUNTED
INTEGRAL SWITCH AND LED LAMP AS EATON MBPL
(800LM MIN.)

1X9W 600MM LED PLAIN BATTEN FITTING SURFACE MOUNTED


TYPE D D COMPLETE WITH LED LAMP AS THOMSON LED ON CEILING
(800LM MIN.)

1X18W IP65 1200MM LED WATERPROOF FITTING SURFACE MOUNTED


TYPE V V WITH ACRYLIC DIFFUSER AND COMPLETE WITH LED ON CEILING
LAMP AS THOMSON LED (1750LM MIN.)
HL CIR A5 CIR A5 HL HL CIR A5 CIR A7 HL
200X50MM 16SWG
NC

NC
NC

NC
CIR A9
GALVANIZED STEEL CIR A9
NCMS CABLE TRAY IN
CIR A9
HL CIR A5 CIR A5 HL HL CIR A5 CIR A7 HL CEILING VOID HL CIR A9 HL
CIR B3
NC

NC
NC

NC

NC
NC
CIR A7
CIR B3
HL CIR A5 HL CIR A5 150X50MM 16SWG 150X50MM 16SWG
CIR A5 HL CIR A7 HL
NC

GALVANIZED STEEL GALVANIZED STEEL


NC
NC

NC
CABLE TRAY IN CABLE TRAY IN
CEILING VOID CEILING VOID

200X50MM 16SWG 200X50MM 16SWG 150X50MM 16SWG


GALVANIZED STEEL GALVANIZED STEEL GALVANIZED STEEL
CABLE TRAY IN CEILING CABLE TRAY IN CABLE TRAY IN CEILING
VOID DB'A' CU'B' VOID
CEILING VOID CIR A8
HL CIR A6 CIR A6 HL HL CIR A6 CIR A7 HL
NC

NC
NC

NC

CIR A8
CIR A12 CIR A8
HL CIR A6 CIR A6 HL HL CIR A6 CIR A7 HL CIR A8
CIR CIR A9
NC

NC
NC

NC

C
A10/11
150X50MM 16SWG CIR A9
CIR A7 GALVANIZED STEEL
HL CIR A6 HL HL CIR A6 HL CABLE TRAY IN CIR A8 CIR A8
CIR A6
NC

NC

NC

NC

CEILING VOID
150X50MM 16SWG 150X50MM 16SWG CIR A13
GALVANIZED STEEL C C CIR A9
GALVANIZED STEEL C
CABLE TRAY IN CEILING CABLE TRAY IN CEILING
VOID VOID

SYMBOL DESCRIPTION MOUNTING SYMBOL DESCRIPTION MOUNTING


HEIGHT HEIGHT CONDUIT IN
13AMP TWIN SOCKET OUTLET 300MM CENTRE RECESSED MOUNTED SPN CONSUMER
CEILING VOID
1800MM FFL
AS MK FFL UNIT TO SCHEMATIC DETAILS
300MM CENTRE 13AMP TWIN SOCKET OUTLET 1200MM CENTRE
TV OUTLET POINT FFL HL AS MK FFL
300/1200/2100MM TP KPLC
DOUBLE POLE SWITCH AS MK FFL
METER
RECESSED MOUNTED TPN DISTRIBUTION
M
1800MM FFL
BOARD TO SCHEMATIC DETAILS
3X4.0MM SQ PVC INSULATED COPPER CABLES
CIR A1 3X1.5MM SQ PVC INSULATED COPPER CABLES CIR A10
10A 20A
GEYSER HEATING ELEMENT OUTLET

3X4.0MM SQ PVC INSULATED COPPER CABLES


CIR A2 3X1.5MM SQ PVC INSULATED COPPER CABLES CIR A11
10A 20A
GEYSER HEATING ELEMENT OUTLET

3X4.0MM SQ PVC INSULATED COPPER CABLES


CIR A3 3X1.5MM SQ PVC INSULATED COPPER CABLES CIR A12
10A 20A
GEYSER HEATING ELEMENT OUTLET

3X4.0MM SQ PVC INSULATED COPPER CABLES


CIR A4 3X1.5MM SQ PVC INSULATED COPPER CABLES CIR A13
10A 20A
UNDER SINK HEATER ELEMENT OUTLET

CIR A5 CIR A14 SPARE WAY


30A HG PVC CONDUITS IN RING MAIN FOR 13A SOCKET OUTLETS

3X2.5MM SQ PVC INSULATED COPPER CABLES


CIR A6 CIR A15
30A HG PVC CONDUITS IN RING MAIN FOR 13A SOCKET OUTLETS 15A
NURSE CALL POWER OUTLET

2C, 4SQ.MM PVC/SWA/PVC INSULATED COPPER


CIR A7 CIR A16
30A HG PVC CONDUITS IN RING MAIN FOR 13A SOCKET OUTLETS 20A
BOOSTER PUMP

2C, 10SQ.MM PVC/SWA/PVC INSULATED COPPER


CIR A8 CIR A17
30A HG PVC CONDUITS IN RING MAIN FOR 13A SOCKET OUTLETS 50A
GRID TIED INVERTER

2C, 10SQ.MM PVC/SWA/PVC INSULATED COPPER


CIR A9 CIR A18
30A HG PVC CONDUITS IN RING MAIN FOR 13A SOCKET OUTLETS 30A
GUARD HOUSE CONSUMER UNIT

4C, 10SQ.MM PVC/SWA/PVC


COPPER CABLES DRAWN IN PVC
DUCTS FROM MDB IN POWER HOUSE

63A TPN MAIN


INTEGRAL
ISOLATOR
20A TIMER CIR B1 3x1.5mm sq PVC INSULATED COPPER CABLES DRAWN
2C 10 SQ.MM PVC INSULATED SWITCH IN CU 10A
COPPER CABLES DRAWN IN T
CIR B2 3x1.5mm sq PVC INSULATED COPPER CABLES DRAWN
10A
INVERTER

CIR B3 3x2.5mm sq PVC INSULATED COPPER CABLES


30A
MAIN FOR 13A SOCKET OUTLETS
CIR B4 3x2.5mm sq PVC INSULATED COPPER CABLES
30A
MAIN FOR 13A SOCKET OUTLETS

63A SPN SPARE WAY

INTEGRAL
ISOLATOR SPARE WAY

SPARE WAY

SPARE WAY
SPACE REQUIREMENTS:
NGARA MATERNITY BLOCK
1. SOLAR PANELS - 12.3SQ.M
2. BATTERY BANKS - 0.12CU.M
6X270W PV SOLAR PANELS; CABLES:
1X6 CONFIGURATION
WEIGHT REQUIREMENTS:
1. 4SQ.MM SC XLPE/SWA/XLPE COPPER CABLE
2. 4SQ.MM 2C XLPE/SWA/XLPE COPPER CABLE 1. SOLAR PANELS - 128KG
3. 6SQ.MM 2C PVC INSULATED COPPER CABLE 2. BATTERY BANKS - 132KG
4. 16SQ.MM SC PVC INSULATED COPPER CABLE

MAINS
CHARGING
1 1 CIRCUIT

20A AC
ISOLATOR
1
COMBINER 10A DC 20A AC
2 3 3 3 ISOLATOR 3 SOLAR POWER
BOX ISOLATOR CONSUMER
UNIT CU'C'
63A SPN
1no. 4500W
1no. 48VDC, INTEGRAL
INVERTER
DC 80A CHARGE ISOLATOR
EARTHING CONTROLLER
4 4

4X12V BATTERY
BANKS; 1X4 AC
CONFIGURATION 25x3mm 25x3mm EARTHING
EQUIPOTENTIAL
BONDING COPPER TAPE
NURSE CALL SYSTEM SCHEMATIC DIAGRAM

CABLE 04

POWER SUPPLY THIRD PRIORITY


TRANSFORMER CONTROL UNIT PATIENT PATIENT PATIENT
STATION STATION STATION
CABLE 03

CABLE 01
PATIENT PATIENT PATIENT LEGEND OF CABLES:
STATION STATION STATION
POWER MASTER 1. CABLE 01 - 1.0SQ.MM 2C, PVC
CONTROL UNIT STATION INSULATED COPPER CABLE
CONTROL UNIT 2. CABLE 02 - 1.0SQ.MM 6C, PVC
CABLE 02 PATIENT PATIENT PATIENT INSULATED COPPER CABLE
STATION STATION STATION 3. CABLE 03 - 1.0SQ.MM 4C,
PVC/SWA/PVC COPPER CABLE
4. CABLE 04 - 1.0SQ.MM 2C,
SHIELDED PVC INSULATED
CABLE 03 PATIENT PATIENT PATIENT COPPER CABLE
STATION STATION STATION

CABLE 04