Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring Open connections found
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Connections for indication lights missing
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Voltmeter, Energy Meter
Operation status:
Remarks:
Voltmeter disconnected
Holes in LV compartment which needs to seal
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Voltmeter, PF Meter, Ammeter
Operation status:
Remarks:
Flash marks on voltmeter
Voltmeter disconnected
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Faulty indication lights found, hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Ammeter
Operation status:
Remarks:
Satisfactory Results.
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled
Electrical Checks:
Tripping mechanism OK N/A
Indication connected working Connections for indication lights missing
Electrical functional test OK N/A
Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Ammeter
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators:
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators:
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Connections for indication lights missing
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: ON, OFF, TRIP
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A
Electrical Checks:
Tripping mechanism OK N/A
Indication connected working N/A
Electrical functional test OK N/A
Indication/monitoring instruments:
Types of indicators:
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Voltmeter, PF Meter
Operation status:
Remarks:
Ammeter missing
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Indication lights found faulty hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: Energy Meter
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Indication light found faulty
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip Energy Meter
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A
Electrical Checks:
Tripping mechanism OK N/A
Indication connected working N/A
Electrical functional test OK N/A
Indication/monitoring instruments:
Types of indicators:
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A
Electrical Checks:
Tripping mechanism OK N/A
Indication connected working N/A
Electrical functional test OK N/A
Indication/monitoring instruments:
Types of indicators:
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK LOTO
Indication connected working Connections for indication lights missing
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Indication lights found faulty hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Voltmeter, Ammeter
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Connections for indication lights missing
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Voltmeter, Ammeter, PF Meter
Operation status:
Remarks:
Ammeter selector switch missing
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Indication lights found faulty hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Ammeter
Operation status:
Remarks:
2 bolts in yellow phase busbar missing
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A
Electrical Checks:
Tripping mechanism OK N/A
Indication connected working N/A
Electrical functional test OK N/A
Indication/monitoring instruments:
Types of indicators Ammeter
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A
Electrical Checks:
Tripping mechanism OK N/A
Indication connected working N/A
Electrical functional test OK N/A
Indication/monitoring instruments:
Types of indicators
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A
Electrical Checks:
Tripping mechanism OK N/A
Indication connected working N/A
Electrical functional test OK N/A
Indication/monitoring instruments:
Types of indicators Ammeter
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Phase Indications, Voltmeter
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Faulty Indication lights hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter, Voltmeter, PF Meter
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Indication Lights found faulty hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeters
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Indication Lights found faulty hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeters
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Indication Lights found faulty hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeters
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeters, Phase Indications
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeters, Phase Indications
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, PB ON, PB OFF
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, PB ON, PB OFF
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Indication lights found faulty hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Phase Indication
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Indication lights found faulty hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Phase Indication
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Phase Indication
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Phase Indication
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Phase Indication
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Indication found faulty hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Phase Indication
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Phase Indication
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Phase Indication, Voltmeter
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Ammeters
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Ammeters
Operation status:
Remarks:
Exhaust Fan connection missing
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Ammeters
Operation status:
Remarks:
Exhaust Fan connection missing
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Ammeters
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Ammeters
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Voltmeter, Phase Indication, VCB ON, VCB OFF, Trip
Operation status:
Remarks:
Voltmeter found disconnected
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Ammeter
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Ammeter
Operation status:
Remarks:
No exhaust fan connection
Lugs found damaged, hence replaced
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Ammeter, Voltmeter
Operation status:
Remarks:
Panel locked
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Voltmeter, Phase Indication
Operation status:
Remarks:
LEEPACK breather (500A) reset button not working
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Blue indication light faulty, hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Ammeter, Phase Indication
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Blue indication found faulty hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Phase Indication
Operation status:
Remarks:
Satisfactory Results
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Blue indication found faulty
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Ammeter, Phase Indication
Operation status:
Remarks:
Blue indication light damaged
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators
Operation status:
Remarks:
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Ammeter, Phase Indication
Operation status:
Remarks:
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed Open cables found
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Ammeters
Operation status:
Remarks:
No connection at selector switch
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Ammeters
Operation status:
Remarks:
No connection at selector switch & ammeters
2 Selector switch missing
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators Ammeter
Operation status:
Remarks:
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter
Operation status:
Remarks:
No connection at selector switch
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter
Operation status:
Remarks:
Indication lights damaged
No connection at selector switch
Open connections found
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter
Operation status:
Remarks:
MCBs found disconnected
No connection at selector switch
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Indication lights found faulty hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter, Voltmeter, PF Meter
Operation status:
Remarks:
Short circuit marks on voltmeter
Red phase CT housing found damaged
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Connections for indication lights missing
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter
Operation status:
Remarks:
No connection at selector switch
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Indication found faulty hence replaced
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter
Operation status:
Remarks:
Fuses connected with 400A breaker missing
No connection at selector switch
Loose connections found
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Connections for indication lights missing
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter
Operation status:
Remarks:
No connection at selector switch
Loose connections found
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report
Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled
Electrical Checks:
Tripping mechanism OK
Indication connected working Loose and open connections found
Electrical functional test OK
Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Voltmeter, Ammeter, PF Meter
Operation status:
Remarks:
Short circuit marks on voltmeter
CT wires found open, short circuit marks found.
______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I