Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP1
Service Feeder 2

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 1600 A
CT Ratio: 1600/5

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring Open connections found
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Connections for indication lights missing
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Voltmeter, Energy Meter
Operation status:

Remarks:
Voltmeter disconnected
Holes in LV compartment which needs to seal

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP2
TR 1 Incoming

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 2500 A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Voltmeter, PF Meter, Ammeter
Operation status:

Remarks:
Flash marks on voltmeter
Voltmeter disconnected

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP3
Service Feeder 1

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 1600 A
CT Ratio: 1600/5

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Faulty indication lights found, hence replaced
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Ammeter
Operation status:

Remarks:
Satisfactory Results.

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP4
Spare

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker:
Rated Current Range:
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled

Electrical Checks:
Tripping mechanism OK N/A
Indication connected working Connections for indication lights missing
Electrical functional test OK N/A

Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Ammeter
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP5
PFI 1 Supply

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 1250 A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators:
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP6
PFI 2 Supply

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 1250 A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators:
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP7
Bus Coupler

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 1600 A
CT Ratio: 1600/5

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Connections for indication lights missing
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators: ON, OFF, TRIP
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP8
Spare

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker:
Rated Current Range:
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A

Electrical Checks:
Tripping mechanism OK N/A
Indication connected working N/A
Electrical functional test OK N/A

Indication/monitoring instruments:
Types of indicators:
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP9
Old TR2 Incoming

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 2500 A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Voltmeter, PF Meter
Operation status:

Remarks:
Ammeter missing

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP10
PP Feeder 1

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 1600 A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Indication lights found faulty hence replaced
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators: Energy Meter
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP11
PP Feeder 2

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 1600 A
CT Ratio: 1600/5

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Indication light found faulty
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip Energy Meter
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP12
Spare

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker:
Rated Current Range:
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A

Electrical Checks:
Tripping mechanism OK N/A
Indication connected working N/A
Electrical functional test OK N/A

Indication/monitoring instruments:
Types of indicators:
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP13
Spare

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker:
Rated Current Range:
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A

Electrical Checks:
Tripping mechanism OK N/A
Indication connected working N/A
Electrical functional test OK N/A

Indication/monitoring instruments:
Types of indicators:
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP14
Coupler

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 2500 A
CT Ratio: 2500/5

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK LOTO
Indication connected working Connections for indication lights missing
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP15
TR 3 Incoming

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 3200 A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Indication lights found faulty hence replaced
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Voltmeter, Ammeter
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP16
PW Feeder 1

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker:
Rated Current Range:
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Connections for indication lights missing
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Voltmeter, Ammeter, PF Meter
Operation status:

Remarks:
Ammeter selector switch missing

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP17
PW Feeder 2

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 1600 A
CT Ratio: 1600/5

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Indication lights found faulty hence replaced
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators: ON, OFF, Trip, Ammeter
Operation status:

Remarks:
2 bolts in yellow phase busbar missing

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP18
Spare

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker:
Rated Current Range:
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A

Electrical Checks:
Tripping mechanism OK N/A
Indication connected working N/A
Electrical functional test OK N/A

Indication/monitoring instruments:
Types of indicators Ammeter
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP19

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker:
Rated Current Range:
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A

Electrical Checks:
Tripping mechanism OK N/A
Indication connected working N/A
Electrical functional test OK N/A

Indication/monitoring instruments:
Types of indicators
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP20

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker:
Rated Current Range:
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A

Electrical Checks:
Tripping mechanism OK N/A
Indication connected working N/A
Electrical functional test OK N/A

Indication/monitoring instruments:
Types of indicators Ammeter
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP21
Service 2 Distribution Panel

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 3200 A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Phase Indications, Voltmeter
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP22
Service 1 Distribution Panel

Electrical Measuring/protection Device:


Panel Type: Isolator
Type of Circuit Breaker:
Rated Current Range: 1600 A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Faulty Indication lights hence replaced
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter, Voltmeter, PF Meter
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP23

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 250A,250A,250A,400A,400A,400A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Indication Lights found faulty hence replaced
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeters
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP24

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 160A,250A,250A,400A,400A,400A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Indication Lights found faulty hence replaced
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeters
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP25

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 160A,250A,250A,400A,400A,400A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Indication Lights found faulty hence replaced
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeters
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP32
WAPDA Incoming

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 4000A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeters, Phase Indications
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP33
Incoming Generator 1

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 2000A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeters, Phase Indications
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP34
Incoming Generator 2

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 2000A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP35
PCC - 002

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 2500A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP36

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 2000A, 800A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, PB ON, PB OFF
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP37

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 2500A, 800A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, PB ON, PB OFF
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP40
GEN-1 Spare

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 2000A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Indication lights found faulty hence replaced
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Phase Indication
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP41
TR1 load supply from generator

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker:
Rated Current Range:
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Indication lights found faulty hence replaced
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Phase Indication
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP42
Generator common bus

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 2000A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Phase Indication
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP43
TR2 load supply from generator

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 3200A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Phase Indication
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP44
Generator 3 Panel

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 2000A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Phase Indication
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP45
TR3 load supply from generator

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 3200A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Indication found faulty hence replaced
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Phase Indication
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: Switchboard Room 3LTP46
Generator common bus

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 2000A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Phase Indication
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP1
RBL Main Panel

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 630A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Phase Indication, Voltmeter
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP2
RBL Distribution Panel

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 800A x 10, 400 A x 2
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP3
RBL Distribution Panel

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 400 A x 8
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP4
Feeder 1 Distribution

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 630A x 3, 400A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Ammeters
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP5
Feeder 1 Distribution

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 100A, 250A, 400A, 630A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Ammeters
Operation status:

Remarks:
Exhaust Fan connection missing

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP6
Feeder 1 Distribution

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 100A, 160A, 250A, 250A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Ammeters
Operation status:

Remarks:
Exhaust Fan connection missing

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP7
Feeder 1 Distribution

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 100A, 160A, 400A, 630A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Ammeters
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP8
Feeder 1 Incoming

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 1600A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Ammeters
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP9
Bus Coupler

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 1600A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP10
Feeder 2 Incoming

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 1600A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Voltmeter, Phase Indication, VCB ON, VCB OFF, Trip
Operation status:

Remarks:
Voltmeter found disconnected

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP11
Feeder 2 Distribution

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 160A x 2, 200A, 250A x 3
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Ammeter
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP12
Feeder 2 Distribution

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 630A x 2, 250A, 800A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP13
Feeder 2 Distribution

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 100A x 4, 250A x 2
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Ammeter
Operation status:

Remarks:
No exhaust fan connection
Lugs found damaged, hence replaced

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP16
Soapery Lighting

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker:
Rated Current Range:
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Ammeter, Voltmeter
Operation status:

Remarks:
Panel locked

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP17

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 100A x 5, 30A x 3
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP18

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 100A x 5, 30A x 4
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring N/A
Components correctly labeled N/A

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP19
NP-1

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 500A x 8, 250A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Voltmeter, Phase Indication
Operation status:

Remarks:
LEEPACK breather (500A) reset button not working

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP20
NP-2

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 500A x 4, 250A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Blue indication light faulty, hence replaced
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Ammeter, Phase Indication
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP20.1
NP-2

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 500A x 8, 800A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Blue indication found faulty hence replaced
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Phase Indication
Operation status:

Remarks:
Satisfactory Results

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP21
NP-3

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 63A x 5, 250A, 100A x 2
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Blue indication found faulty
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Ammeter, Phase Indication
Operation status:

Remarks:
Blue indication light damaged

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP21.1

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 63A x 8
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators
Operation status:

Remarks:

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 28-Nov-2021


Order No:
Plant Section/Identification: PP Substation 18LTP22
MESPAK

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 100A x 4, 400A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Ammeter, Phase Indication
Operation status:

Remarks:

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: PW Substation 6LTP1

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 630A, 400A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed Open cables found
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Ammeters
Operation status:

Remarks:
No connection at selector switch

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: PW Substation 6LTP2
Line 3 Panel

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 1000A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Ammeters
Operation status:

Remarks:
No connection at selector switch & ammeters
2 Selector switch missing

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: PW Substation 6LTP3
Line 4 Panel

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 1000A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working N/A
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators Ammeter
Operation status:

Remarks:

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: PW Substation 6LTP4
PW LTP1 Distribution

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 100 A, 250A, 400A, 1250A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter
Operation status:

Remarks:
No connection at selector switch

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: PW Substation 6LTP5
PW LTP1 Distribution

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 400A x 3, 630A, 250A x 2
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter
Operation status:

Remarks:
Indication lights damaged
No connection at selector switch
Open connections found

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: PW Substation 6LTP6
PW LTP1 Distribution

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 400A x 3, 630A, 250A x 2
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter
Operation status:

Remarks:
MCBs found disconnected
No connection at selector switch

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: PW Substation 6LTP7
PW LTP1 Incoming

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 2500
CT Ratio: 2500/5

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Indication lights found faulty hence replaced
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter, Voltmeter, PF Meter
Operation status:

Remarks:
Short circuit marks on voltmeter
Red phase CT housing found damaged

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: PW Substation 6LTP8

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 1250 A, 1250 A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Connections for indication lights missing
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter
Operation status:

Remarks:
No connection at selector switch

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: PW Substation 6LTP9
PW LTP2 Distribution

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 400A x 3, 250
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Indication found faulty hence replaced
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter
Operation status:

Remarks:
Fuses connected with 400A breaker missing
No connection at selector switch
Loose connections found

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: PW Substation 6LTP10
PW LTP2 Distribution

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: MCCB
Rated Current Range: 400 A, 400 A, 1000A
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Connections for indication lights missing
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Ammeter
Operation status:

Remarks:
No connection at selector switch
Loose connections found

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I
Low Voltage Switchgear Test Report

Customer: Unilever RYK Test performed on: 29-Nov-2021


Order No:
Plant Section/Identification: PW Substation 6LTP11

Electrical Measuring/protection Device:


Panel Type:
Type of Circuit Breaker: ACB
Rated Current Range: 1600
CT Ratio:

Visual Checks:
YES NO Remarks
Cleaning & Greasing
Connection Tightness
All units earthed
Checking of control wiring
Components correctly labeled

Electrical Checks:
Tripping mechanism OK
Indication connected working Loose and open connections found
Electrical functional test OK

Indication/monitoring instruments:
Types of indicators ON, OFF, Trip, Voltmeter, Ammeter, PF Meter
Operation status:

Remarks:
Short circuit marks on voltmeter
CT wires found open, short circuit marks found.

______________________ ______________________
Siemens Representative Client’s Representative
Name: Wahaj Bin Shahbaz Name: Saifullah Khalid
Phone No: 021-32592970 Designation: A.M E&I