SUNSYSTEM solar collectors

FLAT-PLATE COLLECTOR РК series


EVACUATED-TUBE COLLECTOR VTC series

TECHNICAL PASSPORT
INSTALLATION and OPERATION MANUAL

v0.1

model:

serial number:

Downloaded from www.Manualslib.com manuals search engine


TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL TE

TABLE OF CONTENTS
1. Explanation of symbols and safety instructions ............................................... 3
1.1. Explanation of symbols ........................................................................................ 3
1.2. Requirements to collector installation place ....................................................... 3
1.2.1. Instructions to collector installer.......................................................................... 3
1.2.2. Instructions to installation user ........................................................................... 4
2. Description of flat-plate collector PK ................................................................... 4
2.1. Absorber coating ................................................................................................. 4
2.2. Heat-carrier pipe system....................................................................................... 4
2.3. Protective heat-tempered solar glass Durasolar® P+ ........................................... 4
2.4. Insulation ............................................................................................................. 5
2.5. Durable construction ........................................................................................... 5
3. Description of evacuated-tube collector VTC ...................................................... 5
3.1. Evacuated tube. Absorber coating ....................................................................... 5
3.2. Heat-carrier pipe system ...................................................................................... 5
3.3. Temperature sensor ............................................................................................. 6
3.4. Heat transfer plates ............................................................................................. 6
4. Transportation of the collector .......................................................................... 6
5. Delivery of the collector ..................................................................................... 6
6. Installation ........................................................................................................... 8
6.1. Installation of flat-plate collector РК .................................................................... 9
6.2. Installation of evacuated-tube collector VTC ..................................................... 10
6.3. Connecting multiple collector series ................................................................. 12
7. Connect the collector to the hot water system and / or central heating ........... 13
7.1. Protecting collector of lightning, hail, frost, overheating .................................. 13
7.2. Manifold connections ........................................................................................ 14
7.3. Stagnation temperature..................................................................................... 15
7.4. Mounting the temperature sensor vacuum tube collector VTC ........................ 15
7.5. Installation of safety valve for temperature ....................................................... 16
7.6. Pressure. Temperature control. Venting .................................................................. 16
7.7. Filling the installation .................................................................................................. 16
7.8. Connection diagrams .................................................................................................. 17
8. Commissioning ............................................................................................................. 21
9. Prevention and maintenance of collectors .............................................................. 21
10. Warranty terms ............................................................................................................ 21
11. Technical features ........................................................................................................ 23
11.1. Technical features of Flat-plate collector РК ........................................................... 23
11.2. Technical features of Evacuated-tube collector VTC .............................................. 25
12. Recycling ........................................................................................................................ 27

2
Downloaded from www.Manualslib.com manuals search engine
AL TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

1. EXPLANATION OF SYMBOLS AND • local construction regulations on


SAFETY INSTRUCTIONS installation on building – mass of the
1.1. Explanation of symbols system to comply with the building
structure.
CAUTION! - Important • regulations and norms concerning
recommendation or warning safety installation and operation of solar
concerning safety conditions during collectors - protective gloves, eyewear
installation and operation of the solar should be used; make sure collector is
collector. securely attached to the building.

DANGER! - fault or improper use


may cause injury or be hazardous to  Use only original SUNSYSTEM parts
life of humans or animals. DANGER of structure damage /
injury from fall.
INFORMATION - Important The weight of collector/collectors
information on the proper operation must comply with the building
structure, namely the distribution
of the product. of weight; strong and secure
fixation of collector support to
1.2. Requirements to solar collector
installation place
 the roof/façade of building. We
recommend the securing of the
This manual contains important area during installation and the
construction of roof barriers
information for the safe and correct protecting against downslide of
installation, start-up and trouble-free snow mass. Failure to comply with
operation and maintenance of the solar these recommendations can lead to
collector. fatal consequences.
The solar collector can be used to produce Risk of injury, burn upon
domestic hot water and support of space installation and maintenance of
heating system only in the manner solar collectors:
described in this manual. - On contact with broken glass/
The application and any other was the vacuum tube
area of operation is not recommended by - On contact with collector in
the manufacturer and is not responsible function because of its high
for the occurrence of defects or failures. temperature.
Note the collector type data on the  We recommend the use of
protective equipment, gloves,
factory rating label and the technical data
eyewear (goggles), clothing.
provided in chapter 12 in order to ensure Installation and maintenance of
proper operation of the product. collectors must be carried out in
the early morning hours. When the
1.2.1. Instructions to collector installer collector is still cold you can cover it
During installation and operation, the with tarpaulin to avoid its heating
country-specific requirements and by direct sunlight.
regulations must be observed:
3
Downloaded from www.Manualslib.com manuals search engine
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL TE

FIRE HAZARD through contact of


accumulated waste (dry leaves,
plastic bags, paper) with the
 hot parts of the collectors. We
recommend the regular inspection
and cleaning of collector installation
sites.
DANGER of slipping, fall. In Diagram 1.
most cases, collectors are The heart of each solar collector – the
installed in hardly accessible and absorber – is the key factor for the overall
dangerous places. We recommend
 that installation and service
performance of the unit. Made entirely of
copper tubes and copper sheets. Copper
maintenance be carried out by
authorized service technicians sheets join copper pipe with ultrasonic
observing all safety measures. welding and silver soldering.
Model PK Standard CL absorber is with
1.2.2. Instructions to installation user Black solar coating. PK Standard CL
collectors are an ecological and cost
CAUTION! Danger of injury
/ damage of system due to effective solution for domestic hot water
incompetent operation. supply during the warm season.
- The solar collector must be The PK Select CL collector is furnished by
 serviced only by persons familiar
with the operation manual.
high efficiency absorber coating of TiO
– Titans oxidation. This special coating
- Structural changes to collector is temperature- and wear-proof. Its
by user can cause damage to absorptance rate is 95%, while its thermal
equipment or injury. loss is barely 5%.

Safety rules for user operation: 2.2. Heat-carrier pipe system


- The solar collector can be used to
produce hot water and support the
heating system only in the manner
described in this manual.
- Installation and maintenance must be
performed by a technician / service shop
authorized for such operations.
Diagram 2.
2. DESCRIPTION OF PK TYPE FLAT-PLATE Copper is irreplaceable when it comes
COLLECTOR to heat transfer. The liquid tight harp of
copper tubing ensures high efficiency
2.1. Absorber coating and reliability. Pipe harp with low
flow resistance. 100% tested for liquid
tightness.
4
Downloaded from www.Manualslib.com manuals search engine
AL TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

2.3. Protective heat-tempered solar glass 3. DESCRIPTION OF VTC TYPE


Durasolar® P+. EVACUATED - TUBE COLLECTOR

3.1. Evacuated tube. Absorber coating

Diagram 3.
Solar-grade heat tempered glass
Durasolar® P+. The glass used in Diagrаm 5
SUNSYSTEM flat-plate collectors is Evacuated tubes are two concentrically
distinguished by decreased iron content positioned borosilicate glass tubes
providing for better transparency to enclosing a gap of evacuated air. The
the sun rays. Durasolar® P+ has prism- internal glass tube is coated on its external
textured surface, which directs even the surface with an environmentally friendly,
rays reaching the glass in unfavorable highly selective layer and thus functioning
angle straight to the absorber. as an efficient absorber.

2.4. Insulation of rock wool keeps the 3.2. Heat-carrier pipe system
heat from leaving the collector body.

2.5. Durable construction

Diagrаm 6
Copper heat-carrier tubes type Heat Pipe
TU 1. The pipe system is manufactured
Diagram 4 with a minimum number of welds for
The collector case is made of robust perfect air-tightness and reduced deposits
aluminum frame, and the bottom is made accumulation possibility.
of embossed aluminum sheet. This way Heat Pipe technology is characterized by
the collector body has the necessary its high efficiency:
constructive strength to withstand improved heat-absorbing capacity of
the year-round whims of weather not collector, low heat losses and stable
sacrificing on light-weight. performance in harsh climate conditions.

5
Downloaded from www.Manualslib.com manuals search engine
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL TE

PK: Protective plastic corners are fit on


each panel collector frame to protect it
from rubbing against another collector
frame.Panel collectors are stacked on
each other horizontally on a pallet.
Dimensions of pallets match dimensions
of the collectors. Stacked collectors are
Diagrаm 7 secured onto the pallet by steel L-shape
Heat carrier fluid runs from evacuated corner bars fixed to the four corners
tubes to the manifold pipe and hence the of each pallet. The maximum admitted
system. Both outlets of Manifold pipe number of panel collectors on pallet is 20
can be connected as heat-carrier input or pcs. The so arranged panels are secured
output in any direction. to the pallet via 4 straps of width 15 mm.
Then the panel case (pallet with secured
3.3. Temperature sensor can be mounted on to it collectors) is stretch-wrapped with
left or right, depending on the position of five layers of stretch-film. The so wrapped
the heat-carrier outlet. cases are loaded on the vehicle, whereas
each two adjacent cases are strapped
3.4. Heat transfer plates resistant to high together with hauling ratchet straps.
temperatures of stagnation. Transportation of Evacuated-tube
collectors VTC: Evacuated glass pipes and
3.5. High-efficiency insulation of Manifold are packed in separated boxes.
collector pipe.

3.6. Durable construction made of 5. DELIVERY OF COLLECTOR


resistant to harsh climatic conditions,
materials. - Inspect the integrity of the packaging
upon delivery.
- Check whether all components have
4. TRANSPORTATION OF COLLECTOR been delivered to you.

We recommend to transport the collector


to the installation site in its packaging.
During transport and installation,
depending on the weight, suitable safety
devices should be used in accordance with
Directive 2006/42/EC. When transporting
items weighing more than 30 kg, the use
of pallet jack, fork truck or other hoisting
devices is a must.
Transportation of Flat-plate collectors
6
Downloaded from www.Manualslib.com manuals search engine
AL TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

Table 1
РК type Collector VTC type Collector
Check whether protective glazing is Check to assure that evacuated tubes are all intact and the
intact bottom of each tube is still silver-colored. If a tube has a
white clear bottom, that means it is damaged and should
be replaced. As soon as the evacuated tubes are removed
from the box, please put on the rubber tube caps, found
inside the manifold box. This will protect the bottom tip of
the glass tube from breaking on impact
Both outlets of Manifold pipe wear Both outlets of Manifold pipe are fit with plastic
plastic protectors. Remove inlet/ protectors. Remove inlet/outlet pipe plastic protectors
outlet pipe plastic protectors before before connecting collectors to system.
collector connection to system.
Before installing PK type collectors, Do not take out or expose the tubes to sunlight during in-
remove the protective plastic cor- stallation, otherwise the inner tube and heat transfer fin
ners from collector frames. will become very hot.
Delivery includes: It may be necessary to purchase bolts
1) PK type Collector or VTC type Collector. or other fasteners to suit the installation
2) Technical passport. User manual. surface.
3) Warranty card Delivery of collector PK type includes:
If any of the above items are missing, Flat-plate collector PK Standard CL or Flat-
contact your supplier. plate collector PK Select CL
Delivery of Evacuated-tube collector VTC type includes:
Diagram 8

А - Manifold – 1pc. G - Wood screws – 4 pcs.


В - Mounting sheet(plate) – 4 pcs. H - Bottom track – 1 pc.
C - Press pad – 4 pcs. J - Bolts – 13 pcs.
D - Тube holder – 15/20/30 pcs. K - Silicon pad – 4 pcs.
E - Heat conduction glue – 1 pc M - Heat pipe vacuum tube – 15/20/30 pcs.
F - Front track – 2 pcs.
7
Downloaded from www.Manualslib.com manuals search engine
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL TE

6. INSTALLATION Table 2
Must be performed by an autho- Recommended
Collector application mounting angle
 rized service technician/service
shop for such operations. Domestic Hot Water /
DWG+pool 30°÷45°
DANGER of slipping. In most cases, Domestic Hot Water
collectors are installed in hardly ac- + Central Heating / 45°÷60°
cessible and dangerous places. We DWG+CH+pool
 recommend that installation and
service maintenance be carried out
Avoid shading from neighboring buildings,
trees, collectors etc.
by an authorized service technician
The applicable minimum clearances in
observing all safety measures.
your country may differ from the ones
Danger of burns during installation specified bellow. Please, consult your
and maintenance of solar collector: installer. The minimum distance from the
We recommend the use of protec- collector construction to roof end must be
tive equipment, gloves, eyewear at least 1 meter;
(goggles), clothing. The collector should be positioned as close
 Installation and servicing of collec-
tors should be carried out in early
as possible to the DWG /CH consumer
to minimize heat loss. Efficiency heat
morning hours. While the collec- transfer pipes insulation is recommended.
tors are still cold you can cover
them with tarpaulin to avoid their
heating by direct sunlight.

Recommendations:
The collectors can be installed in places
where the values for:
wind load Vm (mean wind speed) does
not exceed 150 km/h and snow loads Sk
(weight of snow mass) does not exceed
1,25 kN/m, according to ENV 1991-1-3
and 1991-1-4.
Recommended orientation: Diagrаm 9
Facing the equator
Recommended mounting angle: 10 ° ÷ 90° Collector support must be grounded to
according to collector application. the buiding grounding system.
Installation of collector on a special
support must be in one single plane.

8
Downloaded from www.Manualslib.com manuals search engine
AL TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

6.1. Installation of PK type flat-plate Mounting Instructions.


collector Adjust the support angle as needed.
Place the collector on the support. Fix the
collector to support using the clamping
clips. Make sure all connections are
properly secured and will not loosen
under harsh weather conditions.

6.1.2. Inclined roof PK type collector


installation

Diagram 10
Flat-plate solar collector РК can be
with vertical or horizontal orientation.
Collectors are mounted on specially
designed support systems, adapted to
different roof slopes.

6.1.1. Flat roof PK type collector


installation

Diagram 12
Installation is carried out by at least two
people.
We recommend consulting with a roofing
expert.
Fix the support onto the roof as indicated
in the Collector Support Installation
Instructions.
On sloped roof the collector slope must
coincide with roof slope angle.
Place the collector on the support.
Diagram 11 Fix the collector to support using the
Installation is carried out by at least two clamping clips.
people. We recommend consulting with Make sure all connections are properly
a roofing expert. Mount the support onto secured and will not loosen under harsh
the roof according to the the Collector weather conditions.
Support
9
Downloaded from www.Manualslib.com manuals search engine
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL TE

6.2. Installation of VTC type evacuated- placing the manifold on the top and the
tube collectors. rubber protectors in the bottom part.
Evacuated tube collectors are mounted Such collectors have vertical orientation.

Diagram 13
Collectors VTC type are mounted on specially designed support systems, adapted to
different roof slopes.

Diagram 14

6.2.1. Flat roof VTC type collector Fix the support onto the roof as indicated
installation in the Collector Support Installation
Instructions. Adjust the support angle as
needed.
Onto the support stand mount the
collector frame with manifold and pipe
holders. Fix the collector to support
using the clamping clips. Make sure all
connections are properly secured and
will not come loose under harsh weather
conditions.
Diagram 15
Evacuated tubes are installed last, after
Installation is carried out by at least two the system has been connected and
people. tested for leakage.
We recommend consulting with a roofing
expert.
10
Downloaded from www.Manualslib.com manuals search engine
AL TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

6.2.2. Inclined roof VTC type collector other the two side rails F.
installation For each rail put two silicone pads K, in
places where the bar rests on the roof tile.
Install the two side rails F to fixing straps
B. Use the screws and therefore provided
orifices in the rails. /Diagram 17/

Step 3. At the bottom of both side rails


F insert bottom rail H and in the top
part - the VTC collector manifold A. Both
collector manifold A and bottom rail H
must lay perpendicular to the side rails
F. Fixation orifices of collector manifold A
and bottom rail H should match the side
rails F, while observing the correct weight
Diagram 16 distribution scheme.
Installation is carried out by at least two Fix A and H to side rails F using two
people. clamping clips C for each.
We recommend consulting with a roofing In this way the collector framework is
expert. composed. /Diagram 18/

G
F

C
B K
A

K
Diagram 18

Diagram 17
Step 1. Install the four fixing straps B to
the roof using the screws G. /Diagram 17/

Step 2. Put alongside and parallel to each


11
Downloaded from www.Manualslib.com manuals search engine
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL TE

Step 4. Take the plastic tube hangers D.


Their number is equal to the number of
pipes. Place them in the holes on the
bottom rail H. /Diagram 20/
Step 5. Carefully take evacuated tube M
out of the box. The upper end of the tube
with a silver probe-like tip as must fit in
the manifold nest. The lower end of the
D tube must pass through tube holder D.
Diagram 19 Place the plastic protector on the bottom
Once you have installed the of tube M. Carefully screw the protector
framework and the manifold, put onto the holder.
the system together and check its Repeat this until you install all glass
 integrity and correct function. If no evacuated tubes M. /Diagram 20/
leaks are detected, you can install
the evacuated tubes. 6.2.3. Installation of VTC type evacuated
tube collectors on façade
E Installation should be carried out by
M
at least two people. We recommend
consulting with a carrier wall expert.

6.3. Collector array connection


For connecting several collectors in
array, it is necessary to use the flexible
pipes between two collectors because
of material expansion upon heating and
contraction upon cooling.

Diagram 20

Diagram 21
12
Downloaded from www.Manualslib.com manuals search engine
AL TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

Table 3 7. CONNECTING THE COLLECTOR TO


Number of collectors in one array DOMESTIC HOT WATER/CENTRAL
Number of col- Number of collec- HEATING SYSTEM
lectors PK type in tors VTC type in
one array: one array: 7.1. Collector protection against
РК 2,0/ lightning, hail, frost, overheating
10 pcs VTC 15 8 pcs
РК 2,15
РК 2,5/ Must be performed by an autho-
РК 2,7
8 pcs VTC 20 7 pcs
 rized service technician/service
shop for such operations.
VTC 30 5 pcs
Our warranty does not cover dam-
- To prevent shading in two or more age from extremely strong acts of
rows of collectors, follow the distance L  nature. We recommend that dam-
between the rows. age of collectors be included as a
clause in your building insurance.

•  Collector protection against


lightning. The lightning rod should be 1.5
meter higher and 3 meter far away from
the solar collectors.

Diagram 22
• Collector protection against hail,
Table 4 strong wind and snow mass. Each solar
collector is tested for resistance to harsh
Collector Distance L between
the rows weather conditions:
mounting angle Collector orientation - Hail resistance: size up to 25 mm /1”
ɑ V, m H, m when collector mounting angle is ≥40°.
25° 4,7 2,6 In areas with frequent hailstorms it is
recommended to install a protective net
30° 5,2 9
over collectors.
35° 5,2 3 - Strong wind resistance: wind speed up
40° 6 3 to 120 km/h
45° 6 3,5 In areas with strong, steady winds it is
50° 6,5 3,6 recommended to further strengthen the
collector support fixation to the building
55° 6,7 3,7
structure, as well as frequent inspection
60° 7 3,8 to prevent any loosening of connections.
- Snow mass resistance: load up to 30 cm
Diagram 23
– 1.25 kN/m2
13
Downloaded from www.Manualslib.com manuals search engine
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL TE

In areas with heavy snowfalls it is a device for heat dissipation or to add


recommended to further strengthen the more users to the hot water circuit in the
collector support fixation to the building summer (swimming pool or other similar
structure, as well as frequent inspection consumers).
to prevent any loosening of connections.
7.2. Collector outlets/connections
Upon design of vertical risers it is
•  Collector protection against frost. recommended that the heat carrier flow
To protect the collector against frost speed
(closed loop) Propylene Glycol PG heat- be between 0.5 and 0,8 m/s, and the riser
carrier fluid is recommended. pipes be made of copper.
For example: for 20 m 2 of collector area
the required flow rate is 1000 l/h at a heat
carrier speed of 0,5 m/s - recommended
pipe section is ø28x1 Cu.
We recommend - two and/or more
collector fields to be connected using the
Tichelmann principle.

When installing the collector it is


Table 5 mandatory that on its highest point
Relation between Propylene Glycol and wa- an automatic air purge be installed to
ter
facilitate system charging.
PG / Propylene Connection of collectors is carried out
Freezing point
Glycol /: Water using Hollander joints.
20% : 80% - 7 ℃
30% : 70% - 13 ℃
40% : 60% - 23℃
50% : 50% - 34℃
If you choose water as heat carrier, it is
recommended to connect to the system
a controller unit supporting antifreeze
Diagram 24
function working with water as heat-
carrier.
For PK New Line model using adapter
•   Collector protection against nipples for copper pipe ø22.
For PK Classic model using Hollander
overheating. If the system is designed to
power a central heating circuit it would joints at 1/2“
produce more hot water than necessary The use of galvanized pipes and fittings
in the summer period. In this case, we for connecting collectors to water tanks
recommend that the system be fitted with is forbidden due to electrical corrosion
hazard.
14
Downloaded from www.Manualslib.com manuals search engine
AL TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

Fixing the fittings: at which point hot water will be dumped


- Always use two opposing spanners when from the system. If a PTRV is not installed
tightening the compression fittings. Do on the collector, steam will form in the
not twist the copper pipe (inlet/outlet) header. Eventually some steam may feed
as the header maybe damaged. back to the storage tank via the return
- Tighten with standard length spanners line.
using moderate torque force. Do not The PTRV on the tank will open to release
overtighten the fittings. pressure or heat as required. Under such
- Flood the circuit with water and check conditions the manifold will normally
the for leaks at the compression reach a maximum temperature of around
fittings. If leaking then loosen the 160°C/320°F. Generally the heat returning
fitting completely, and wrap the Teflon from the collector in the form of steam is
plumbing tapes or a suitable sealing not enough to affect a continued increase
compound. in tank temperature (ie. Heat input <tank
- For several collectors connections, it heat losses)Under normal use stagnation
is necessary to use the flexible pipes should rarely occur as a result of pump
between two collectors because of the stoppage, since power blackouts normally
Expansion on heating and contraction happen during storms and not clear
on cooling. sunny weather. High tank temperature
- Heat loss from the piping can be protection should only occur when hot
significant and should be taken to water is notused for several days (when
insulate any possible points of heat loss. on holiday), and only during strong
Ensure the insulation material is tight periods of sunlight (summer). If leaving
against the pipeline, inlet and outlet. the house for an extended period of time
Using the silicone sealant to form a (more than 2 - 3 days), it is advisable to
water-tight seal on the temperature cover the collector panel or design the
sensor. The insulation foam should be system with a heat dissipation device
protected against the UV. The circulation or alternative use for the heat, thus
pump should be also insulated otherwise preventing overheating of the system
it could be a source of heat loss. and collector stagnation. Stagnation of
the solar collector will NOT damage the
7.3. Stagnation temperature solar collector, however insulation used
Stagnation refers to the condition that on the piping close to the manifold inlet
occurs when the pump stops running, and outlet should be able to withstand
due to pump failure, power blackout, or temperatures of up to 200°C/395°F.
as a result of a high tank temperature (Eg. Glass wool or mineral wool-with
protection feature built into the an exterior wrap of aluminium foil, thus
controller, which turns the pump off. protecting against the elements).
If a PTRV is installed on collector inlet
or outlet the collector will continue to 7.4. Mounting of Temperature sensor of
increase in temperature until the limit of VTC type collector
the temperaure relief valve is reached, The solar collector temperature sensor
15
Downloaded from www.Manualslib.com manuals search engine
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL TE

should be coated with a thick layer of without effort.


thermal paste and inserted into the Collector working (operating) pressure
sensor sleeve to the full depth. If the fit is should be secured using a pressure relief
too loose, slide a piece of copper plate or valve at 6 bars.
wire in beside the sensor, Seal the sensor An expansion vessel must be mounted in
sleeve opening with silicone sealant order to take up the extra volume of fluid
to prevent water ingress. Ensure that caused by heat expansion. Recommended
sensors used on the collector are high capacity of expansion vessel is 4 ÷ 5 L/m2
temperature rated (up to 250°C/486°F), in of PK type collector area, and 8 ÷ 10 L/m2
particular the cable. of VTC type collector area.
To avoid damage to system and heat
7.5. Mounting of Safety temperature carrier circuit, all air purge valves must
valve be closed upon purging of air from the
It is recommended, and may be required system. This will prevents the release of
by regulations, that a temperature control steam and the penetration of oxygen
device (safety tempetarure value) be from the ambient air.
fitted into the hot water pipe between
the water heater and bathrooms and 7.7. Filling of system.
en-suites to reduce the risk of scalding. To prevent overheating, the filling
This is achieved by controlling the water of system must be carried out in the
temperature to below 50°C/122°F morning or evening in the absence of
(temperature may be adjustable). direct sunlight.
Direct use of collector for hot water
7.6. Pressure control. Temperature preparation is not allowed because of the
control. Relief valve. eventual clogging of pipes over a short
Regardless of the installation time by limescale deposits.
configuration, pressure release values, Inside collector pipes and risers circulates
expansion vessels and/or other pressure a certain fluid (water, propylene glycol or
control devices must be installed. The Tyfocor of freezing point corresponding
solar loop should be designed to operate to the requirements of certain installation
at no more than 800kPa - PRV may be (see section 7.1 of this manual.)When
850kPa. (800kPa = 8bar = 116psi) using any other heat carrier fluid to fill the
For installation where mains pressure collector manufacturer does not take any
water is used, the system should ideally responsibility for product warranty.
be designed to operate at a pressure of
<500 kPa, achieved by use of a pressure
limiting/reduction value.
For the reliable operation of system, we
recommend you check the lever of the
pressure and temperature return valve
(PTRV) every six months. The PTRV lever
should be raised and dropped gently
16
Downloaded from www.Manualslib.com manuals search engine
AL TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

7.8. Connection diagrams Must be performed by an autho-


 rized service technician/service
shop for such operations.

Diagram 25. Connection of Flat-plate collector РK to solid fuel boiler WBS, combi tank KSC2 and
three-way valve
17
Downloaded from www.Manualslib.com manuals search engine
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL TE

Diagram 26. Connection of Evacuated-tube collector VTC to solid fuel boiler WBS, combi tank
KSC2 and three-way valve
18
Downloaded from www.Manualslib.com manuals search engine
AL TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

Diagram 27. Connection of Flat-plate collector РK to solid fuel boiler WBS, solar water tank
SON, buffer tank P and three-way valve

19
Downloaded from www.Manualslib.com manuals search engine
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL TE

Diagram 28. Connection of Flat-plate collector РK to solid fuel boiler WBS, solar water tank
SON, buffer tank P and three-way valve
20
Downloaded from www.Manualslib.com manuals search engine
AL TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

8. COMMISSIONING - Checkup of heat carrier fluid,


replacement thereof.
Must be performed by an
 authorized service technician/
service shop for such operations.
9.2. Cleaning of collectors from dust
deposits, fallen dry leaves and twigs
Keeping the collector surface (type PK
Before commissioning of solar collector or VTC) clean is a prerequisite for good
into operation, check: performance. A dusty collector (due to
- The air-tightness of all connections lack of rainfall, dusty ambience) can be
- System air purging cleaned up in early morning hours before
- Insulation of pipelines: must be UV it is heated by sunlight using:
resistant and temperature shock proof - Warm water, soap/glass cleaner solution
as well as bird- and rodent-proof in and a soft cloth when the collector is
structure. mounted in an easily accessible and safe
- Electrical connections: controller, pump place;
- Pressurized water jet when the collector
is mounted in a hardly accessible place.
9. DAMAGE PREVENTION AND SERVICE
MAINTENANCE OF COLLECTORS 9.3. Replacing a broken tube on VTC type
heat pipe collector
Any changes in design or con- In any event of broken collector tube
struction of solar collectors are it needs to be replaced as quickly as
strictly prohibited. Detection of possible. Despite the damaged tube, the
such makes warranty null and collector can still operate, but its efficiency
void. As changes in design and will drop. Clean broken glass to prevent
construction shall be considered future injuries. We recommend that
replacement of the broken collector tube
 the removal of any manufacturer-
embedded items, incorporation be carried out by an authorized installer /
of additional components in the service observing all safety norms.
collector, replacement of any com-
ponents with similar or analogues
not explicitly approved by the 10. WARRANTY TERMS
manufacturer.
Failure to observe the installation
9.1. It is recommended that yearly and operating requirements de-
maintenance be carried out by  scribed in the manual and the ser-
an authorized service. All service vice booklet voids the warranty.
maintenance must be logged on the
warranty card. 10.1. Manufacturing defects and
- Checkup of operating pressure, pump materials guarantee
operation, hydraulic connections.
NES Ltd. expressly guarantees that
21
Downloaded from www.Manualslib.com manuals search engine
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL TE

the products it manufactures shall - Improper installation or use as well


be free from defects in materials and as changes especially if they are not
workmanship which can prevent from made by authorized after-sale service
normal operation under proper and personnel of NES Ltd.
normal use, installation and maintenance - Testing and operation pressures greater
for the intended functions of the products than the values established by NES Ltd.
for a period set out in the warranty and set forth in product manuals.
certificate of the respective model of the
collector you have bought. Freeze, flood, natural disasters or third
The warranty period begins from the party actions as well as any interventions
date indicated in the purchase invoice. into normal functioning conditions of
If a product or any component thereof collectors and the control of NES Ltd.
is determined to be defective in
manufacture or materials, NES Ltd. Will 10.2.3. The warranty certificate is
repair or replace the defective component considered void as well for collectors
or product. whose serial identification number has
been modified, removed or blurred, or
10.2. Exclusions and Limitations of cannot be expressly attested.
Warranty Coverage
10.2.4. Damages in the appearance
11.2.1. The customer can claim warranty of products shall not be considered as
during warranty period of respective defects giving right for laying claim except
product immediately after any defects for those ones which cause problems
have been determined, except for in case in functioning or change technical
of noticeable defects at the moment of characteristics of collectors.
purchase, in which case the customer 10.2.5. NES Ltd. preserves the right, in
must make the claim at the shop case of replacement, to deliver another
immediately after noticing the defect, as model of collector in order to fulfill
it is provided for in the general conditions approved warranty claims in case the
of sale. original model is not being manufactured.

10.2.2. This warranty certificate is 10.3. Claiming warranty


considered void in cases when defects Every customer who has purchased a
and errors in functioning of products are collector from NES Ltd., and who has
caused by: good reasons to lay a warranty claim, shall
- Accidents as a result of improper proceed as follows:
storage, transportation, unsuitable or
incorrect use. 10.3.1. Immediately notify in writing:
- Failure to observe the installation, use, - The installer, or the company that has
and maintenance instructions set forth sold the collector to him;
in the installation manual of respective - The distributor firm;
product. - The commercial representative of NES
22
Downloaded from www.Manualslib.com manuals search engine
AL TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

Ltd. in the region. 10.3.4. If on customer’s request, and


For this purpose the claimant shall fill when there is reason for urgency,
out a claim form; the latter shall be the customer demands immediate
accompanied by the document proving replacement of the product he has
the purchase of the collector (invoice) claimed warranty for, before receiving the
with the date of purchase in it. decision as to the claim, said request shall
be accompanied by a Purchase requisition
10.3.2. After receiving the claim form, from the Commercial Department. After
NES Ltd. considers it and makes decision decision for satisfaction of the claim has
whether the claim has grounds or not, and been made, the Purchase requisition
whether the defect is within the scope of mentioned above will be annulled by
the warranty set forth in this certificate issuing a receipt for returned goods; with
for limited warranty; after which informs this receipt the customer can purchase
the customer as to its decision. another product with the same price in
case the claim has proved grounded.
10.3.3. The return of a product cannot
be done without written authorization
issued by the Claim Department.
11. TECHNICAL FEATURES
11.1. Technical features of PK type flat-plate collector

1. Aluminum casing
2. Silicon seal
3. Protective solar glass
4. Absorber with selective coating
(PK Select)
Or with black solar coating (PK
Standard)
5. High efficiency insulation
6. Bottom of the collector
7. Absorber pipe harp
8. Inlet/Outlet sleeve
9. Corner protector
10. Connection thread R ½” (CL
model)
11. Connection „New Line“ Cu ø 22
(NL CL model)

Diagram 29. Elements of PK type flat-plate collector


23
Downloaded from www.Manualslib.com manuals search engine
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL TE

Table 6. Technical parameters of PK type Flat-plate collector


SUNSYSTEM SUNSYSTEM
STANDARD SELECT
РК 2.15 РК 2.7 РК 2.0 РК 2.15 РК 2.5 РК 2.7
Width L1 mm 1020 1248 1020 1020 1248 1248
Overall
Height H mm 2125 2125 2000 2125 2000 2125
dimensions
Thickness D mm 90 90 90 90 90 90
Collector case width L2 mm 1000 1228 1000 1000 1228 1228
Distance b/n collecting pipes C mm 2025 2025 1900 2025 1900 2025
Overall surface m2 2.15 2.7 2.0 2.15 2.5 2.7
Absorber surface m 2
1.94 2.41 1.8 1.94 2.20 2.41
Heat carrier volume L 1.6 2.1 1.4 1.6 2.0 2.1
Test pressure Mpa 2.5
Max. Operating pressure Mpa 0.6
Inlet/Outlet N,P R1/2”
Inlet/Outlet New Line N,P Cu ø22
Heat carrier flow rate l/m h 2
50
Weight kg 33 38 31 33 36 38
Thickness of solar glass mm 4.2
Material of solar glass K Heat tempered prismatic glass Durasolar P+
Absorber pipes G, pcs. 8 10 8 8 10 10
Distance between absorber
F, mm 114 114 114 114 114 114
pipes
Number of collecting pipes pcs. 2 2 2 2 2
Material of collector case Powder coated Aluminium - RALL 9006
Material of absorber Copper
Coating of absorber Black solar coating Black solar coating
Thermal loss coefficient -к1 W/m K 6.18
2
6.18 3.83 3.83 4.23 4.23
Thermal loss coefficient –к2 W/m K 0.0227 0.0227 0.0080 0.0080 0.0035 0.0035
2 2

Insolation Rock wool g=30kg/m3 δ=40mm DIN 181165


Heat carrier fluid Propylene Glycol PG 50% (freezing point - 34°C)
Stagnation temperature °C 170 200
Standards and EN 12975:2006- EN 12975:2006-06;
Certificates 06 CEN - Keymark 011-7S381 F

24
Downloaded from www.Manualslib.com manuals search engine
AL TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

11.2. Technical features of VTC type Evacuated-tube collector


Diagram 30. Elements of VTC type Evacuated-tube collector

1. Manifold
2. Inlet/Outlet sleeve
3. Evacuated glass tube
4. Holder and protector of evacuated glass tube
5. Frame of VTC collector
6. Temperature sensor sleeve

25
Downloaded from www.Manualslib.com manuals search engine
TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL TE

Table 7. Technical parameters of VTC type Evacuated-tube collector

Model VTC 15 VTC 20 VTC 30


Number of evacuated tubes pcs. 15 20 30
Height H mm 1980 1980 1980
Width L / Thickness D mm 1190/125 1570/125 2300/125
Overall surface m2 2.36 3.11 4.55
Aperture surface m2 1.412 1.882 2.824
Absorber surface m2 1.215 1.62 2.429
Heat carrier fluid PG 50% (freezing point: -34°С)
Heat carrier volume L 0.94 1.24 1.82
Heat carrier flow rate L/m2h 60÷80 60÷80 60÷80
Heat-tempered borosilicate glass SU-
Evacuated tube material
SS-ALN/AIN
Collector frame material / type Aluminium / Adjustable
Plastic parts material UV resistant plastic RAL 9005
Heat carrier pipes material / type Copper / Heat pipe TU 1
Coating of absorber Selective coating
Anodized aluminum / Polyurethane
Manifold unit - box material/insulation
foam 30 mm
Efficiency ƞ0a in relation to aperture % 66
Thermal loss coefficient, а1а W/(m K)
2
1.500
Thermal loss coefficient, а2а W/(m K )
2 2
0.020
Kθ,trans /Kθ,trans (50°), in relation to aperture 0,92/1,43
Stagnation temperature tstg °С 221
Max. operating temperature °С 180
Test pressure/ Max. operating pressure Bar 25/12
Pressure loss Δр Pa 150 200 600
Weight kg 43 57 86
Evacuated tube diameter/length Ø, mm/mm 58/1800
Distance b/n evacuated tubes mm 75
Heat carrier pipes diameter/number Ø, mm/pcs. 14/15 14/20 14/30
Collecting pipe material/diameter Ø, mm Copper/ 22
Heat carrier Inlet/outlet diameter Ø, mm 22
Temperature sensor sleeve Ø, mm 8
Evacuated tube holder pcs. 15 20 30
Number of outlets 2
EN 12975: 2006-06 / CEN - Keymark
Standards and Certificates
No 011-7S1807-R

26
Downloaded from www.Manualslib.com manuals search engine
AL TECHNICAL PASSPORT. INSTALLATION and OPERATION MANUAL

12. RECYCLING AND WASTE DISPOSAL According to Directive 2002/96/EC on


waste electrical and electronic equipment
12.1. Recycling of collector packaging (WEEE) they are to be disposed of outside
Parts of the packaging made of wood or the normal flow of solid domestic waste.
paper can be used as combustible for the Obsolete equipment shall be collected
boiler. Submit the rest of the packaging separately from other recyclable waste
material for recycling according to the containing materials with adverse effect
local regulations and requirements. on health and environment.
Replaced heating installation components Metal details, as well as non-metal ones
must be submitted for processing to an shall be sold to licensed recyclable metal or
authorized factory which complies with non-metal waste collection organizations.
the environmental protection regulation. Those should not be treated as domestic
waste.
12.2. Recycling and waste disposal
At the end of life cycle of each product its
components are due to be disposed of in
conformity with regulatory prescriptions.

27
Downloaded from www.Manualslib.com manuals search engine
ISO 9001:2008
BUREAU VERITAS
Certification

12 Madara Blvd., 129 Vitosha Blvd.,


9700 Shumen, Bulgaria 1000 Sofia, Bulgaria
t: +359 54 874 555 t: +359 02 952 24 05
f: +359 54 874 556 f: +359 02 952 67 20
e-mail: ftrade@sunsystem.bg e-mail: sunsofia@sunsystem.bg

www.sunsystem.bg