SCHEDULE OF GUARANTEED TECHNICAL PARTICULARS

OF 630KVA, 11/0.433 KV COPPER WOUND TRANSFORMER


No. Description UNIT Particulars
1. Name of the manufacturer
2. Service Outdoor
3. KVA Rating :
(a) HV Winding KVA 630
(b) LV Winding KVA 630
4. Rated Voltage :
(a) HV Winding KV 11
(b) LV Winding KV 0.433
5. Rated frequency Hz 50
6. Number of phases 3
7. Connection
(a) HV Winding Delta
(b) LV Winding Star
8. Connection symbol
(a) HV – LV Dyn-11
9. Tappings (on HV side)
(a) Range +7.5% to -7.5%
(b) Numbers of steps/position 7

10. Reference ambient temperatures:


(a) Maximum ambient air temperature ºC 50 ºC
(b) Maximum daily average ambient air ºC 40 ºC
temperature
(c) Maximum yearly weighted average ºC 32 ºC
ambient temperature
(d) Minimum ambient air temperature ºC - 5 ºC
(e) Maximum cooling water temperature ºC NA
11. Type of cooling ONAN
12. Temperature rise
(a) Top Oil ºC 50 ºC
(b) Windings ºC 55 ºC
13. Impedance voltage at rated current for the
principal tapping
(a) HV – LV % 4.5
No. Description UNIT Particulars
14. No load current at rated voltage and rated
frequency % 2 % of full load current
15. Insulation level
(a) Separate source power frequency
voltage withstand
(i) HV winding Kv rms 28 Kv rms
(ii) LV winding Kv rms 3 Kv rms
(b) Induced over voltage withstand
(i) HV winding Kv rms 22 Kv rms
(ii) LV winding Kv rms 0.866 Kv rms
(c) Full wave lightning impulse withstand
voltage
(i) HV winding KVP 75
KVP N.A.
(ii) LV winding
16. Efficiencies at 75ºC at unity power factor
(a) At full load % 98.98%
(b) At ¾ full load % 98.15%
(c) At ½ full load % 99.28%
17. Regulation at full load at 75ºC
(a) At unity power factor % 0.977
(b) At 0.8 power factor lagging % 3.397
18. Terminal arrangements
(a) High Voltage Open bushing on top cover
(b) Low Voltage Open bushing on side wall
(c) Neutral Open bushing on side wall
19. Approximate overall dimensions
(a) Length mm 2000
(b) Breadth mm 1500
(c) Height mm 1900
20. Reference standards IS:2026

Note : 1. All electrical performance are subject to tolerance as per IS:2026


2. Weights & dimension are subject to tolerance of + 10%.