EQUIPMENT
1.Steam Valves
2. Lube Oil System
3. EHC Oil System
4. Turbine Protection
5. Surveillance Test
1. Steam Valves
MSV-A
MSV
HP
Turbine
Steam Flow
From Boiler
HP
Turbine
CV
CV
Seat Diameter : 254.0 mm (10”) MSV Valve Seat
Valve Stroke : 88.9 mm CV Sleeve
Total Stem Stroke : 88.9 mm
CV Valve Seat
CV Actuator
Servo Controlled, Single Acting, CV Valve Disc
CV Upper Head
Spring return (Fail to Close)
Piston Diameter : 240 mm
Rod Diameter : 90 mm
CEOT : 10 mm CV CV Valve Stem
MSV Actuator
Servo Controlled, Single Acting,
Spring return (Fail to Close)
Piston Diameter : 220 mm
Rod Diameter : 90 mm
CEOT : 10 mm
CV
Seat Diameter : 254.0 mm (10”)
Valve Stroke : 88.9 mm
Steam Flow
Total Stem Stroke : 88.9 mm From Boiler
CV Actuator
Servo Controlled, Single Acting,
Spring return (Fail to Close)
Piston Diameter : 240 mm
Rod Diameter : 90 mm HP Turbine
CEOT : 10 mm CV
Dump
Valve
Limit
Switch
LVDT
Servo
Valve
From
Boiler
FILTER
To CV
To HP Turbine
LVDT
TRIP OIL
SUPPLY
EHC CONTROL
OIL SUPPLY
(FAS) Trip Dump
Solenoid Valve Valve
Servo FILTER
Valve
ENERGIZED
LVDT
CLOSED
Main Stop Valve / Control valve- EHC : Normal Operation (Ref. 10098-00-I-71-MA)
(Required Opening < Actual Opening)
CLOSE Trip Solenoid Valve
To drainTrip
the Trip Oil when
Solenoid Valvethe Dump Valve.
tripped, to open
Operated by the EHC signal.
De-Energized to Trip.
LVDT
ENERGIZED
EHC CONTROL
Dump Valve
OIL SUPPLY To drain the control oil from
(FAS) Actuator Cylinder when
Tripped.
TRIP OIL
Actuated by Trip Oil via Pilot
SUPPLY
Dump Valve.
Open to Trip
EHC CONTROL
OIL DRAIN (FCD)
CLOSED
Main Stop Valve / Control valve- EHC : Trip Mode (Ref. 10098-00-I-71-MA)
CLOSE
Trip Solenoid Valve
TRIP OIL is drained thru Dump
Valve to Drain system.
LVDT TRIP OIL is interrupted by Trip
Solenoid Valve.
DE-ENERGIZED
EHC CONTROL
OIL SUPPLY
(FAS)
TRIP OIL
SUPPLY
Dump Valve
EHC CONTROL As Dump Valve opened by De-
OIL DRAIN (FCD) Energizing Trip Solenoid Valve,
Control Oil Supply between Servo
Valve and Cylinder is connected to
TRIP OIL DRAIN
Drain system.
OPENED
MSV-A
To
IP Turbine
From To
Reheater IP Turbine
ICV
Seat Diameter : 533.40 mm (21”) Valve Seat RSV Bypass Valve
Valve Stroke : 127 mm
(Common Seat) RSV Valve Disc
ICV Actuator
Servo Controlled, Single Acting,
Back Seat
Spring return (Fail to Close)
Piston Diameter : 160 mm RSV Valve Stem
Rod Diameter : 60 mm
CEOT : 10 mm
RSV Actuator
Servo Controlled, Single Acting,
Spring return (Fail to Close)
Piston Diameter : 190 mm
Rod Diameter : 90 mm
CEOT : 10 mm
ICV
Seat Diameter : 533.40 mm (21”)
Valve Stroke : 127 mm
ICV Actuator
IP Turbine
Servo Controlled, Single Acting,
Spring return (Fail to Close)
Piston Diameter : 160 mm
Rod Diameter : 60 mm
CEOT : 10 mm
Reheater
From
FILTER Reheater
To IP
Turbine
Trip
RSV Solenoid Valve
LVDT
Dump
Limit Switch Valve
MSV-A
OLV Actuator
Oil Tray
STAND
To HP
Turbine OLV Casing
From From
From From
MSV (B) MSV (A)
MSV (B) MSV (A)
HP
Turbine
OLV
Seat Diameter : 127 mm (5”)
Valve Stroke : 6.5 mm
OLV Actuator
Servo Controlled, Single Acting,
Spring return (Fail to Close)
Piston Diameter : 190 mm
Rod Diameter : 90 mm
Valve Disc
CEOT : 10 mm
OLV
Seat Diameter : 127 mm (5”)
Valve Stroke : 6.5 mm
OLV Actuator
Servo Controlled, Single Acting,
Spring return (Fail to Close)
Piston Diameter : 190 mm
Rod Diameter : 90 mm
CEOT : 10 mm MSV (B) MSV (A)
HP Turbine
TRIP OIL
SUPPLY
Trip
Solenoid Valve EHC CONTROL
OIL SUPPLY
Dump (FAS)
Valve
LVDT
Shutoff
Solenoid valve
Energized
Servo Valve OLV
FILTER
From
MSV
Shutoff Solenoid Valve
Not to open OLV during
turbine low load operation.
Shutoff valve is equipped for Overload Valve (OLV) To HP
interlock purpose. Servo Valve control Turbine
for valve positioning.
Front Standard
Lube Oil System – Main Oil Tank Flow Diagram (Ref. 10098-00-M-51-MAV)
VAPOUR EXTRACTOR A
MAIN OIL STRAINER A
VAPOUR EXTRACTOR B
MAIN OIL STRAINER B
Transfer Valve
From Oil Conditioner
FROM / TO GEN
H2 SEAL OIL
SYSTEM
Top View
OIL RETURN PIPE
VAPOUR EXTRACTOR B
BRG OIL FEED
VAPOUR EXTRACTOR A
Switch Panel
Side View
Coupling Flange
Bearing
Shaft
Frame
Impeller
Pump Casing
Suction Strainer
Centrifugal pump
Vertical installation Typical Assembly Drawing
For MOP & EOP
Oil Sight
Front View
No.1 BRG Oil
Pressure Indicator
Center Section
29 / TOSHIBA Energy Systems & Solutions Corporation
Copyright © 2018 Toshiba Corporation. All rights reserved.
2-4
Coalescer Filter
Filter Pump
To Main Oil Tank
Top View
Coalescer Filter
Level Gauge
Suction Strainer
Side View
CV-A CV-B
System pressure
16.5 Mpa
Working Fluid
Fatty Acid-polyol
Ester Oil
(Quintlubric 888-46
or 822-300SC)
EHC Oil Tank
Accumulator A Accumulator B
Switch Panel
4. Turbine Protection
PS-3A
MOP-B
40MAV10CP102
EOP PS-3E
40MAV10CP103
HFP
EHC Oil Tank
Turbine Protection –Bearing Oil Pressure Low-Low Turbine Trip Turbine Trip
Signal to
D-EHC
FROM / TO GEN
H2 SEAL OIL
SYSTEM
(2 out of 3
system)
PS-10A,B,C
< 69 kPa
(Turbine On
Center)
From Main Oil Tank
40MAV10CP101A
At normal operation, bearing oil pressure is 0.18 MPa (turbine on center). 40MAV10CP101B
If bearing oil pressure is reduced to bearing oil pressure “low-low turbine 4-MAV10CP101C
trip (69 kPa)” STG turbine shall be tripped.
40 / TOSHIBA Energy Systems & Solutions Corporation
Copyright © 2018 Toshiba Corporation. All rights reserved.
4-3
Turbine Protection –HFP Discharge Pressure Low-Low Turbine Trip Turbine Trip
PS-101A~C
To EHC System 40MAX10CP101A
At normal operation,
HFP discharge 40MAX10CP101B
pressure is 16.5MPa. 40MAX10CP101C
If HFP discharge
pressure is reduced, Signal to
STG turbine shall be D-EHC
tripped.
2 out of 3 system
PS-101A~C
< 11.4 MPa
HFP
EHC Oil Tank
5. Surveillance Test
Close signal
Servo Valve
(MSV, CV, RSV, ICV) Open signal
De-Energized
Trip Solenoid
Valve
(MSV, CV, RSV, ICV)
Pump Test
Surveillance Test – Lube Oil System MOP Automatic Start Test
Pressure Switch
PS-3A,
40MAV10CP102
Switch Panel
PS-3A
To
Main Oil Tank
(Drain)
Pump Test
Surveillance Test – Lube Oil System EOP Automatic Start Test
Pressure Switch
PS-3E,
40MAV10CP103
Switch Panel
PS-3E
To
Main Oil Tank
(Drain)
To
Main Oil Tank
From MOP Discharge
Normal Operation
Pump Test
Surveillance Test –EHC Oil Unit - HFP Automatic Start Test
PS-102
To EHC System Automatic test
To PS-102
EHC Oil Tank
(Drain) PS-102
40MAX10CP106
Normal Operation
PS-102