PAGAMUTAN NG DASMARIÑAS

OFFICE OF THE ENGINEERING AND MAINTENANCE


Barangay Burol II, City of Dasmariñas, Cavite
Trunkline: (046) 481-4400 Loc. 771

For : Hon. Jennifer A. Barzaga


City Mayor

From : Reynor S. Calzado


Officer-In-Charge

Date : April 1, 2022

Re : Engineering & Maintenance Monthly Accomplishment Report –


March 2022

1. Reference: Office Memorandum Order No.: 244-S-2019 dated July 12, 2019.

2. In compliance to the above reference, respectfully submitting is the Monthly


Accomplishment Report of the Engineering and Maintenance Unit for the period
of March 1, 2022 to March 31, 2022.

3. For this period, this Unit continuously providing engineering related services in
the Pagamutan ng Dasmariñas and to LGU field offices that requires engineering
and electrical related assistance. Preventive Maintenance and corrective
measures are also being regularly performed to ensure 100% operability of the
following machines:

Pagamutan:

- Cistern of Pagamutan and Dasmariñas Community Affairs (DasCA)


Building
- Deep well and Water Care System
- Three (3) Water Fountains at DasCA Compound
- Six (6) elevators of Pagamutan
- Fire Distribution and Alarm System (FDAS) of Pagamutan
- Oxygen Manifold System
- Two (2) 500KVA Generators at Power Room
- Four (4) 5,000 Gallons Capacity Water Tanks at the Roof Deck
- Sewage Treatment Plant (STP) Facilities
- 196 units Air Conditioning Unit and 2 units Climaveneta
- Perimeter Lights at DasCA Compound

#DisiplinaMuna
Outside Pagamutan:

- All Air Conditioning Units installed at the City Hall and Field Offices
- Fifteen (15) elevators of Dasmariñas City
- Two (2) 150KVA Mobile Generators
- Generator installed at the City Hall and Slaughter House
- Six (6) sets of LED Signage installed at Welcome Arch
- Seventy-five (75) CCTV System installed at 75 units of Toyota FX issued
to Barangay
- Eighteen (18) units Mobile Police Outpost.

Hospital Medical Equipment:

Unit / Concerns Number Status

Dialysis Center:
- Repaired high temperature of Pharmaceutical 1 Operational
Refrigerator.
- Defective compressor of Pharmaceutical 1 BER
Refrigerator.
Dr. Ronaldo M. Mateo Operating Room Complex:
- Repaired defective OR Machine. 1 Operational
- Repaired loosed connection of OR Light. 1 Operational
ER Department:
- Repaired defective Adult BP Apparatus 1 Operational
(Manual) at ER-N.
- Repaired loosed wiring of Pulse Oximeter at 1 Operational
ER-N.
- Repaired malfunctioned Oxygen Regulator at 5 Operational
ER-P (COVID-19 Triage).
- Defective Thermoscanner at ER-P (COVID-19 2 BER
Triage).
- Defective BP Apparatus (Adult) at ER-P 1 BER
(COVID-19 Triage).
- Defective Adult BP Apparatus (Manual) at ER- 1 BER
N.
- Defective and broken Oxygen Flowmeter at 1 BER
ER-P (COVID-19 Triage).
- Defective Pulse Oximeter at ER-N. 2 BER
General Laboratory Department:
- Checked and assessed not cooling 1 For reprocess
Pharmaceutical Refrigerator.
Isolation Ward:
- Repaired leak of Wall Oxygen at Patient’s Bed 1 Operational
No. 3 of OB High Risk Ward.
#DisiplinaMuna
- Repaired defective BP Apparatus. 1 Operational
- Defective Control Knob of BP Apparatus. 1 BER
- Broken BP Apparatus. 1 BER
- Broken Handle of Laryngoscope. 1 BER
LR/DR/NICU Complex:
- Repaired error, replaced Oxygen Sensor and 1 Operational
calibrated Anesthesia Machine at Delivery
Room.
- Replaced busted Shadowless Bulb of OR Light 2 Operational
at Delivery Room.
Medicine Ward:
- Repaired and replaced broken nipple filter of 1 Operational
Oxygen Regulator.
- Repaired defective Infusion Pump, Serial Nos.: 2 Operational
710220070012 and HEPN0710220070013.
- Repaired defective Digital BP Apparatus. 1 Operational
- Defective Infusion Pump, Serial Nos.: 5 BER
81040117040039, 81040117040061,
81040117040047, 81040117040040 and
8104011740041.
- Defective BP Cuff of Digital BP Apparatus. 1 BER
OB Ward Department:
- Repaired defective Droplight at OB Ward 1 Operational
Annex.
Physical Therapy (PT) Rehabilitation Department:
- Replaced broken Acoustic Board of Ceiling. 3 Operational
- Replaced busted LED Driver Model: (4-7) x1w 12 Operational
of LED Square Directional Light.
Radiology Department:
- Repaired loosed connection of X-ray Machine 1 Operational
C-Arm.
- Cleaned X-ray Machine at X-ray Section. 1 Operational

Hospital Facilities:

Location / Concerns Number Status

2nd Floor Area:


- Replaced busted LED Driver Model: DD (4-7) 1 Operational
x1w of LED Circular Light at Hallway.
3rd Floor Area:
- Replaced LED Driver Model: (8-12) x1w of 1 Operational
LED Circle Panel Light at Public Female
Restroom.

#DisiplinaMuna
- Replaced busted LED Driver Model: DD (4-7) 1 Operational
x1w of LED Circular Light at Hallway.
- Replaced busted LED Driver Model: DD (4-7) 1 Operational
x1w of LED Circular Light in front of Audio-
Visual Room (AVR).
- Replaced busted LED Driver Model: DD (4-7) 1 Operational
x1w of LED Circular Light in front of Chapel.
th
5 Floor Area:
- Repaired clogged Urinal at Public Male 1 lot Operational
Restroom.
- Repaired clogged Sink at Public Male 1 Operational
Restroom.
- Replaced busted LED Driver Model: (8-12) 2 Operational
x1w of LED Square Directional Light at
Hallway.
- Replaced busted LED Circular Light, 9w at 1 Operational
Hallway beside Elevator No. 2.
6th Floor Area:
- Cleaned drain pipe at 6th Floor Area of our 1 Operational
Hospital.
Administration Department:
- Repainted Side Table at Chief of Hospital 3 Operational
Office.
- Replaced busted LED Square Panel Light. 1 Operational
- Replaced broken Acoustic Board at Chief of 1 lot Operational
Hospital Office.
- Replaced LED Circle Panel Light, 9w at Chief 10 Operational
of Clinic.
Admitting and Information Office:
- Repaired broken Arm Rest of Office Chair. 1 Operational
Billing and Cashier Department:
- Defective Railings of Cash Drawer. 1 BER
Blood Bank Department:
- Repaired misaligned Shelf/Rack. 1 Operational
CDRRM – Operation Center (OpCen):
- Replaced busted LED Fluorescent Equivalent 2 Operational
T8 at Radio Room.
Cardio-respiratory Department:
- Replaced busted LED Driver Model: DD (4-7) 2 Operational
x1w of LED Square Directional Light.
Dialysis Center:
- Repaired stuck-up Sliding Door at Patient’s 1 Operational
Bed No. 5.
- Repaired flush valve leak of Urinal at 1 Operational
Restroom.

#DisiplinaMuna
- Repaired defective LED Circle Panel Light, 1 Operational
9w.
- Repaired broken Office Chair. 2 Operational
- Relocated and installed Cabinet. 1 Operational
- Checked and assessed LED Square Panel 17 Operational
Light which are good as per assessment.
- Checked and assessed LED Driver Model: (8- 2 Operational
12) x1w which are good as per assessment.
- Replaced busted LED Driver Model: (8-12) 4 Operational
x1w of LED Square Panel Light (Patient Bed
Nos. 9 and 10, Hallway and Nurse Station).
- Replaced Acoustic Board.
- Replaced busted LED Circular Light at Pantry 4 Operational
of Dialysis Center. 1 Operational
- Replaced busted LED Driver Model: (8-12)
x1w of LED Square Panel Light. 1 Operational
- Replaced broken Acoustic Board.
- Broken Office Chair. 5 Operational
2 BER
Doctor’s Quarter:
- Repaired defective Hand Dryer at Restroom 1 Operational
of 3rd Floor Doctor’s Quarter.
- Replaced busted LED Driver Model: (8-12) 10 Operational
x1w of LED Square Directional Light at 4 th
Floor Doctor’s Quarter.
- Replaced busted LED Driver Model: DD (4-7) 1 Operational
x1w of LED Square Directional Light at 3 rd
Floor Male Doctor’s Quarter.
- Replaced broken Acoustic Board at 3 rd Floor 2 Operational
Male Doctor’s Quarter.
Dr. Ronaldo M. Mateo Operating Room Complex:
- Repaired defective Extension Cord. 1 Operational
- Repaired Bidet leak at Male Dressing Room. 1 Operational
- Repaired and adjusted low water pressure of 1 Operational
Toilet Flush Bowl at Male Dressing Room.
- Repaired and adjusted closing speed of Front 1 Operational
Door.
- Replaced LED Driver Model: (8-12) x1w of 1 Operational
LED Square Directional Light at Hallway.
- Replaced broken Caster Wheel of Stainless 1 Operational
Stool.
- Broken Ladder. 1 BER
Drug Testing Laboratory Department:
- Repaired loosed screw of Office Chair. 2 Operational
- Repaired loosed screw of Office Chair. 1 Operational
- Replaced broken Acoustic Board. 1 Operational
#DisiplinaMuna
- Broken Handle and defective Railings of 1 BER
Cabinet.
- Broken Office Chair. 1 BER
ER Department:
- Repaired clogged Urinal in Public Male 1 Operational
Restroom at ER-N.
- Repaired Bidet leak in Public Male Restroom 1 Operational
at ER-N.
- Repaired no power Convenience Outlet at 1 Operational
ER-P (COVID-19 Triage).
- Repaired clogged Urinal of Public Male 1 Operational
Restroom at ER-N.
- Repaired leak and replaced broken Faucet of 1 Operational
Sink at ER-P (COVID-19 Triage).
- Repaired leak and replaced broken Flexible 1 Operational
Hose of Restroom at ER-P (COVID-19
Triage).
- Repaired and re-taped wiring that cause 1 lot Operational
obstruction at ER-N.
- Assembled new Office Chair at ER-N. 1 Operational
- Replaced busted LED Driver Model: (8-12) 1 Operational
x1w of LED Square Panel Light at ER-N.
- Replaced broken wheel of Trolley at ER-P 1 Operational
(COVID-19 Triage).
- Broken Wheelchair at ER-N. 1 BER
General Laboratory Department:
- Repaired and replaced loosed Socket at 1 Operational
Histopathology Section.
- Repaired wiggled Swivel Chair at 1 Operational
Histopathology Section.
- Repaired Alcohol Dispenser leak. 1 Operational
- Checked and assessed defective Glass Door. 1 For checking
and repair of
Aluminum
Glass Installer
- Replaced broken Acoustic Board. 1 Operational
Ground Floor Area:
- Repaired short circuit LED Circular Light at 1 lot Operational
Hallway of Information Lobby.
- Repaired clogged Urinal at Ground Floor 1 Operational
Public Male Restroom beside Radiology
Department.
- Repaired clogged Toilet Bowl at 1 st Cubicle of 2 Operational
Ground Floor Public Female Restroom beside
Radiology Complex.
- Cleaned drainage at our Hospital beside St. 1 lot Operational
#DisiplinaMuna
Paul Hospital Cavite, Inc.
Housekeeping Department:
- Replaced LED Fluorescent Equivalent T8 at 2 Operational
6th Floor Line and Laundry Section.
- Shorted Capacitor of Washing Machine at 6 th 1 BER
Floor Linen and Laundry Section.
- Not working Washing Machine Dryer at 6 th 1 BER
Floor Linen and Laundry Section.
Human Resource Management Office (HRMO):
- Installed Hanging Cabinet. 1 Operational
- Replaced busted LED Driver Model: (8-12) 1 Operational
x1w of LED Square Panel Light.
ICT and Engineering Unit:
- Repaired and replaced valve of Pressure 1 Operational
Washer.
- Hyundai Elevator Services Phils., Inc. 6 Operational
personnel in conducting preventive
maintenance of our Elevator Nos. 1, 2, 3, 4, 5
and 6.
- Ericsson personnel in conducting Signal 1 lot Operational
Testing (Walktest) of Smart Signal Booster at
our Hospital.
- Hyundai Elevator Services Phils., Inc. 1 Operational
personnel in repair and installation of SMPS
900 GT, Serial No.: P2OE1411391 Board of
Elevator No. 1.
- Hyundai Elevator Services Phils., Inc. 1 Operational
personnel in repaired of Error 34 of Elevator
No. 4.
- Replaced busted LED Fluorescent Equivalent 1 Operational
T8 at Telecom Office.
Intensive Care Unit (ICU) Department:
- Defective motor and drive gear of Infusion 2 Operational
Pump No. 8, Serial No.: 81040117040038
and Infusion Pump No. 12, Serial No.:
81040117040058.
Isolation Ward:
- Repaired clogged Toilet Bowl of Restroom at 1 Operational
Droplet.
- Repaired clogged sink at Nurse Station. 1 Operational
- Relocated Water Dispenser at Pediatric Ward 1 Operational
to Isolation Ward.
- Replaced busted LED Circle Panel Pinlight, 3 Operational
5w at Male Pediatric Ward.
- Replaced broken Flexible Hose of Sink. 1 Operational
- Replaced busted LED Square Panel Light, 1 Operational
#DisiplinaMuna
12w at OB High risk Ward.
- Replaced busted LED Square Panel Light, 1 Operational
12w at Female Surgery Ward.
- Replaced busted LED Square Panel Light, 2 Operational
12w at COVID Ward.
- Replaced busted LED Driver Model: (8-12) 3 Operational
x1w of LED Square Directional Light at
Isolation Ward.
- Replaced busted LED Square Directional 1 Operational
Light at Isolation Ward.
- Replaced busted LED Circle Panel Pinlight, 5 Operational
5w at Isolation Ward.
- Replaced busted LED Square Panel Light 1 Operational
- Defective Thermostat and UV Light of Water 1 BER
Dispenser.
LR/DR/NICU Complex:
- Repaired and adjusted low water pressure of 1 Operational
Toilet Flush Bowl at Delivery Room.
- Repaired broken Blue Screen at Delivery 1 Operational
Room.
- Re-installed Alcohol Dispenser at Neonatal 1 Operational
Intensive Care Unit (NICU).
- Replaced loosed handle lock of Door Lock in 1 Operational
Receiving Area at Delivery Room.
- Replaced busted LED Square Directional 3 Operational
Light (Pathologic Area and Transitory Area) at
Neonatal Intensive Unit (NICU).
Medical Records Department:
- Repaired defective Metal Shelves. 1 Operational
- Repaired defective LED Square Directional 2 Operational
Light.
- Replaced busted LED Driver Model: (8-12) 1 Operational
x1w of LED Square Directional Light.
- Replaced defective Railings of Drawer. 1 Operational
Medicine Ward:
- Repaired clogged Sink at Female Medicine 1 Operational
Ward.
- Repaired 3 pcs defective Wheelchair. 3 Operational
- Repaired defective Stand Fan. 1 Operational
- Repaired and adjusted low water pressure of 1 Operational
Toilet Flush Bowl at Restroom of Family
Medicine Ward.
- Repaired clogged Toilet Bowl at Restroom of 1 Operational
Male Medicine Ward.
- Rewiring of Convenience Outlet at Patient 1 Operational
Bed Nos. 4 and 5 of Female Medicine Ward.
#DisiplinaMuna
- Replaced busted LED Driver Model: (8-12) 2 Operational
x1w of LED Square Directional Light at
Patient Bed Nos.: 1 and 4 of Male Medicine
Ward.
- Replaced busted LED Driver Model: (8-12) 5 Operational
x1w of LED Square Directional Light at Family
Medicine Ward.
- Replaced busted LED Driver Model: (8-12) 1 Operational
x1w of LED Square Directional Light at
Female Medicine Ward.
- Replaced busted LED Fluorescent Equivalent 1 Operational
T8x10w at Patient’s Bed of Family Medicine
Ward.
- Replaced busted LED Driver Model: (8-12) 5 Operational
x1w of LED Square Directional Light at
Female Medicine Ward.
- Replaced busted LED Circle Panel Pinlight, 4 Operational
5w.
- Replaced busted LED Square Directional 1 Operational
Light.
- Replaced busted LED Driver Model: DD (4-7) 8 Operational
x1w of LED Square Directional Light at Family
Medicine Ward.
- Defective Wheelchair. 2 BER
Molecular Laboratory Department:
- Repaired broken Office Chair. 1 Operational
- Replaced busted LED Square Panel Light, 4 Operational
12w.
Nursing Service Office (NSO):
- Repaired continuous water flow of Toilet 1 Operational
Flush Bowl at Restroom.
Nutrition and Dietetics Service:
- Replaced broken Faucet. 1 Operational
- Replaced broken Flexible Hose of Sink at 1 Operational
Kitchen.
OB Ward Department:
- Repaired low water pressure of Toilet Flush 1 Operational
Bowl at Public Male Restroom of OB Ward.
- Repaired clogged Sink at Public Male 1 Operational
Restroom of OB Ward.
- Replaced busted LED Driver Model: (8-12) 1 Operational
x1w of LED Circle Panel Light at Public
Female Restroom of OB Ward Annex.
- Replaced busted LED Circle Panel Light, 9w 3 Operational
at Hallway of OB Ward Annex.
- Replaced LED Driver Model: (8-12) x1w of 1 Operational
#DisiplinaMuna
LED Square Directional Light at Hallway.
- Replaced busted LE Square Panel Light, 12w 1 Operational
at Patient’s Bed No. 8 of OB Ward Annex.
Out Patient Department (OPD):
- Repaired and adjusted water pressure of 2 Operational
Toilet Flush Bowl at Female Restroom of 2 nd
Floor.
- Repaired and adjusted water pressure of 1 Operational
Toilet Bowl No. 2 at Public Female Restroom
of 2nd Floor.
- Disassembled Steel Cabinet/ Rack at Clinical 1 Operational
Department.
- Installed Bulletin Board at Clinical 1 Operational
Department.
- Installed Mirror at Clinical Department. 1 Operational
- Assembled 12 feet x 20 feet Tent beside 1 Operational
Central Triage of ER-P (COVID-19 Triage) of
ER Department as per request of Clinical
Department.
- Replaced busted LED Driver Model: (8-12) 5 Operational
x1w of LED Circle Panel Light at Restroom of
2nd Floor.
- Replaced busted LED Driver Model: DD (4-7) 2 Operational
x1w of LED Circular Light at 2nd Floor.
- Replaced busted LED Driver Model: (8-12) 1 Operational
x1w of LED Square Directional Light at 2 nd
Floor.
- Replaced busted LED Square Directional 4 Operational
Light (Internal Medicine Clinic, Family
Medicine Clinic and Ophthalmology Clinic) at
2nd Floor Outpatient Department.
- Defective Pump Motor of Alcohol Dispenser at 1 BER
Clinical Department.
- Broken Lock and Railing of Drawer at Clinical 1 BER
Department.
Pharmacy Department:
- Repaired detached Shelf. 1 Operational
- Transferred location of CCTV Camera. 1 Operational
- Installed additional LED Fluorescent 1 Operational
Equivalent T5.
- Installed additional Two Gang Universal 1 Operational
Convenience Outlet.
- Dismantled Hand Dryer. 1 Operational
Property and Supply Office (PSO):
- Replaced busted LED Driver Model: (8-12) 8 Operational
x1w of LED Square Directional Light.
#DisiplinaMuna
- Checked and assessed defective lights at the 30 Waiting for
office need for replacement of LED Square materials
Panel Light. needed
Radiology Department:
- Repaired broken Chair at Magnetic 2 Operational
Resonance Imaging (MRI) Section.
- Replaced busted LED Driver Model: (8-12) 10 Operational
x1w of LED Square Directional Light at
Radiologist’s Office.
Social Welfare Assistant (SWA) Office:
- Re-aligned roller of Cabinet. 1 Operational

Hospital Air-conditioning System:

Unit / Concerns Number Status

3rd Floor Area:


- Replaced defective pipe sensor TH2 and TH4 1 lot Operational
of Ceiling Cassette ACU at 3rd Floor Female
Doctor’s Quarter. Medical Records Department
and Property and Supply Office.
Administration Department:
- General cleaning of Wall Mounted ACU (Indoor 1 Operational
Unit) and re-insulation of piping at Chief of
Hospital Office.
CDRRM – Operation Center (OpCen):
- General cleaning of Wall Mounted ACU (Indoor 1 Operational
Unit) at Radio Room.
- Cleaned filters of Ceiling Suspended ACU. 2 Operational
- Cleaned drain pan of Ceiling Suspended ACU. 2 Operational
Dialysis Center:
- Repaired Error 2502 and reset blinking digital 1 Operational
panel of Ceiling Cassette ACU.
Doctor’s Quarter:
- Add refrigerant R410-A Freon and repaired low 1 Operational
cooling of Ceiling Cassette ACU at 4th Floor
Female Doctor’s Quarter.
- Relocated drain pipe line of Ceiling Cassette 1 Operational
ACU at 4th Floor Doctor’s Quarter.
- General cleaning of Wall Mounted ACU (Indoor 1 Operational
Unit) at 3rd Floor Male Doctor’s Quarter.
Dr. Ronaldo M. Mateo Operating Room Complex:
- Repaired not working Ceiling Cassette ACU 1 Operational
and reset trip off Circuit Breaker at OR2C.

#DisiplinaMuna
- Repaired malfunctioning ACU Controller of 1 Operational
Ceiling Cassette ACU.
- General cleaning of Wall Mounted ACU (Indoor 1 Operational
Unit) at Autoclave Room.
ER Department:
- Cleaned drain pipe line of Wall Mounted ACU in 1 Operational
Doctor’s Room (Outpost No. 15) at ER-P
(COVID-19 Triage).
General Laboratory Department:
- Repaired Error 2502 of Ceiling Cassette ACU 3 Operational
(Main Laboratory, Histopathology Section and
Extraction Room).
- General cleaning of Ceiling Cassette ACU 1 Operational
(Indoor Unit).
Ground Floor Area:
- Installed electrical power supply of 2 units Floor 2 Operational
Mounted ACU at Waiting Area of our Hospital.
ICT and Engineering Unit:
- General cleaning of Ceiling Suspended ACU 1 Operational
(Indoor Unit) at Oxygen Manifold System.
LR/DR/NICU Complex:
- Repaired Error 1102 of Wall Mounted ACU 3 Under
(Breastfeeding Area, Pathologic Area and observation
Nurse Station Complex) at Neonatal Intensive
Care Unit (NICU).
Medical Records Department:
- Repaired Error 6607 of Ceiling Cassette ACU. 1 Operational
Medicine Ward:
- General cleaning of Ceiling Cassette ACU 3 Operational
(Indoor Unit) at Family Medicine Ward.
Out Patient Department (OPD):
- General cleaning of Ceiling Suspended ACU at 1 Operational
2nd Floor.
- General cleaning of Window Type ACU at 1 Operational
Internal Medicine Clinic.
Radiology Department:
- Cleaned drain pipe line of Ceiling Suspended 1 Operational
ACU at CT Scan Section.
- Equipage Company, Inc. personnel in 1 Operational
installation of brand-new Condenser Fan Motor
of Climaveneta 8TR ACU No. 1 at Magnetic
Resonance Imaging (MRI) Control Room.

#DisiplinaMuna
ACU at City Hall and Field Offices:

Concerns Action Status


Taken

General cleaning of Wall Mounted ACU at Usaping Bayan 1 Operational


(UB) Office, City Hall Annex Bldg.
General cleaning of Window Type ACU at Commission on 1 Operational
Elections (Comelec), City Hall.
Cleaned drain pipe line of Wall Mounted ACU at City 1 Operational
Purchasing Office, City Hall.
Cleaned drain pipe line of Wall Mounted ACU at City 1 Operational
Legal Office, City Hall.
General cleaning of Wall Mounted ACU (Indoor Unit) at 1 Operational
City Civil Registrar’s Office, City Hall.
General cleaning of Wall Mounted ACU (Indoor and 1 Operational
Outdoor Unit) at Post Office, City Hall.
replaced defective Capacitor and general cleaning of wall 1 Operational
Mounted ACU (Outdoor Unit) at Bureau of Internal
Revenue (BIR) Office, City Hall.
General cleaning of Window Type ACU at City Civil 1 Operational
Registrar’s Office, City Hall.
Re-aligned Indoor Unit of Wall Mounted ACU at 1 Operational
Assessment of City Treasurer’s Office, City Hall.
General cleaning of Wall Mounted ACU (Indoor Unit) at 2 Operational
Human Resource Management Office (HRMO), City Hall.
Replaced busted ACU Plug of Wall Mounted ACU at City 1 Operational
Social Welfare and Development Office (CSWDO), Burol
II, City of Dasmariñas, Cavite.
General cleaning of Wall Mounted ACU (Indoor and 1 Operational
Outdoor Unit) at City Environment and Sanitation Unit
(CESU), Sampaloc IV, City of Dasmariñas, Cavite.
General cleaning of Wall Mounted ACU (Indoor and 1 Operational
Outdoor Unit) at Motorpool, Sampaloc IV, City of
Dasmariñas, Cavite
General cleaning of Wall Mounted ACU (Indoor and 1 Operational
Outdoor Unit) at City Agriculture Office, DCCI Bldg., San
Andres, City of Dasmariñas, Cavite
General cleaning of Wall Mounted ACU (Indoor and 2 Operational
Outdoor Unit at Regional Trial Court (RTC), Branch 128,
DasCA Bldg.
Stuck-up Fan Motor of Wall Mounted ACU (Office) at City 2 BER
Slaughter House, Central Market Ave., Zone 4, City of
Dasmariñas, Cavite need for replacement of Bearing
(608Z) due to beyond economical repair.
#DisiplinaMuna
General cleaning (Indoor and Outdoor Unit) and repaired 1 Operational
Outdoor Board of Wall Mounted ACU at City Health Office
(CHO) – 1.
General cleaning of Wall Mounted ACU (Indoor Unit) at 1 Operational
Public Attorney’s Office (PAO), DasCA Bldg.
General cleaning of Wall Mounted ACU (Indoor and 1 Operational
Outdoor Unit) at Quality Assurance (QA) of City Slaughter
House, Central Market Ave., Zone 4, City of Dasmariñas,
Cavite.
Checked and assessed not working Wall Mounted ACU at 1 For reprocess
Regional Trial Court (RTC) Branch 90, DasCA Bldg. need
for reprocess.
General cleaning of Wall Mounted ACU (Indoor and 1 Operational
Outdoor Unit) at Regional Trial Court (RTC) Branch 90,
DasCA Bldg.
Defective Control Board of Floor Mounted ACU at 1 BER
Aklatang Panlungsod ng Dasmariñas (APD), DasCA
Compound need for replacement of due to beyond
economical repair.
General cleaning of Wall Mounted ACU (Indoor Unit) at 2 Operational
Municipal Trial Court in Cities (MTCC), DasCA Bldg.
General cleaning of Floor Mounted ACU (Indoor Unit) at 1 Operational
Aklatang Panlungsod ng Dasmariñas (APD), DasCA
Compound.
Flushing of drain pipe line of Floor Mounted ACU at 1 Operational
Public Information Office (PIO), APD Bldg., DasCA
Compound.
Reset tripped off Circuit Breaker and set ACU remote of 2 Operational
Wall Mounted ACU at Alternative Learning System (ALS)
and Conference of Special Education (SpEd), Burol I.
General cleaning of Wall Mounted ACU (Indoor Unit) at 1 Operational
DepEd Office, Special Education (SpEd), Burol I.
Replaced Capacitor of Wall Mounted ACU at Dining Area 1 Operational
of Congressman’s Office, DasCA Bldg.
General cleaning of Wall Mounted ACU (Indoor Unit) at 1 Need for
Bahay Kalinga located at Victoria Reyes. replacement of
Evaporator
Blower Fan
General cleaning of Window Type ACU at Aklatang 2 Operational
Panlungsod ng Dasmariñas (APD), DasCA Compound.
General cleaning of Wall Mounted ACU (Indoor and 1 Operational
Outdoor Unit) at Head Office of City Assessor’s Office,
City Hall.
General cleaning of Wall Mounted ACU (Indoor and 1 Operational
Outdoor Unit) at Entrance of City Assessor’s Office, City
#DisiplinaMuna
Hall.
General cleaning of Wall Mounted ACU (Indoor and 1 Operational
Outdoor Unit) at Staff Office of City Assessor’s Office,
City Hall.
Repaired P7 Error and general cleaning of Wall Mounted 1 Operational
ACU (Outdoor unit) at Aklatang Panlungsod ng
Dasmariñas (APD), DasCA Compound.
General cleaning of Wall Mounted ACU (Indoor Unit) at 3 Operational
Alternative Learning System (ALS) and SpED Office of
City of Dasmariñas Center for Special Education,
Dasmariñas II Central School, Burol I.

Provided 25KVA and 150KVA Generator and Electrician during the conduct
of the following activities:

Events Venue Date

BBM – Sara Caravan at Dasmariñas City, Cavite. Tent Area, March 6, 2022
Dasmariñas
Integrated
High School
Installed Manual Transfer Switch (MTS) of Genset City Disaster March 8, 2022
Nos. 2 and 4. Risk
Reduction and
Management
Office
(CDRRMO)
Women’s Month Kick-Off Celebration 2022 Activity. Track Oval, March 8, 2022
De La Salle
Medical and
Health
Sciences
Institute
(DLSMHSI)
Blessing and Distribution of Multicabs to the 75 Tent Area, March 14,
Barangays of our City. Dasmariñas 2022
Integrated
High School
Seminar of watchers regarding Operation Quick Tent Area, March 20,
Count. Dasmariñas 2022
Integrated
High School
Blessing and Inauguration of Athletes’ Quarter. Dasmariñas March 21,
Integrated 2022

#DisiplinaMuna
High School
Blessing and Inauguration of Union Theological Philippine March 21,
Seminary (UTS) Blvd. that will connect Aguinaldo Christian 2022.
Highway and Governor’s Drive in our City located at University
Philippine Christian University (PCU). (PCU)
Mass Wedding. Promenade March 21,
Des 2022
Dasmariñas
Meeting with Congressman Elipidio F. Barzaga, Jr. Tent Area, March 24,
Dasmariñas 2022
Integrated
High School
Blessing and Distribution of Solar-Electric Vehicle to Tent Area, March 24,
different Homeowners Association. Dasmariñas 2022
Integrated
High School
Bugtong - Tanong Finals. Tent Area, March 24,
Dasmariñas 2022
Integrated
High School
Proclamation Rally of Team Dasma. Dasmariñas March 26,
Arena, Burol 2022
Main

Aside from these accomplishments, our Unit is also responsible for the
implementation of other special project throughout the City.

For information and reference.