PAGAMUTAN NG DASMARIÑAS

OFFICE OF THE ENGINEERING AND MAINTENANCE


Barangay Burol II, City of Dasmariñas, Cavite
Trunkline: (046) 481-4400 Loc. 771

For : Hon. Jennifer A. Barzaga


City Mayor

From : Reynor S. Calzado


Officer-In-Charge

Date : June 1, 2022

Re : Engineering & Maintenance Monthly Accomplishment Report –


May 2022

1. Reference: Office Memorandum Order No.: 244-S-2019 dated July 12, 2019.

2. In compliance to the above reference, respectfully submitting is the Monthly


Accomplishment Report of the Engineering and Maintenance Unit for the period
of May 1, 2022 to May 31, 2022.

3. For this period, this Unit continuously providing engineering related services in
the Pagamutan ng Dasmariñas and to LGU field offices that requires engineering
and electrical related assistance. Preventive Maintenance and corrective
measures are also being regularly performed to ensure 100% operability of the
following machines:

Pagamutan:

- Cistern of Pagamutan and Dasmariñas Community Affairs (DasCA)


Building
- Deep well and Water Care System
- Three (3) Water Fountains at DasCA Compound
- Six (6) elevators of Pagamutan
- Fire Distribution and Alarm System (FDAS) of Pagamutan
- Oxygen Manifold System
- Two (2) 500KVA Generators at Power Room
- Four (4) 5,000 Gallons Capacity Water Tanks at the Roof Deck
- Sewage Treatment Plant (STP) Facilities
- 196 units Air Conditioning Unit and 2 units Climaveneta
- Perimeter Lights at DasCA Compound

#DisiplinaMuna
Outside Pagamutan:

- All Air Conditioning Units installed at the City Hall and Field Offices
- Fifteen (15) elevators of Dasmariñas City
- Two (2) 150KVA Mobile Generators
- Generator installed at the City Hall and Slaughter House
- Six (6) sets of LED Signage installed at Welcome Arch
- Seventy-five (75) CCTV System installed at 75 units of Toyota FX issued
to Barangay
- Eighteen (18) units Mobile Police Outpost.

Hospital Medical Equipment:

Unit / Concerns Number Status

Dialysis Center:
- Defective BP Cuff of Sphygmomanometer. 1 BER
Dr. Ronaldo M. Mateo Operating Room Complex:
- Repaired loosed screw of Droplight. 1 Operational
- Repaired blinking OR Light and reset at OR2B. 1 Operational
- Repaired steam leak of Autoclave Machine. 1 Operational
- Repaired not working properly Cardiac Monitor. 1 Operational
- Repaired not functioning UV Machine. 1 Operational
ER Department:
- Repaired BP Cuff leak and defective BP 1 Operational
Apparatus at ER-N.
- Preventive maintenance of Defibrillator at ER- 3 Operational
N.
- Replaced busted bulb of Laryngoscope at ER-P 1 Operational
(COVID-19 Triage).
- Defective BP Cuff of Manual BP Apparatus at 2 BER
ER-N.
- Defective bulb of Laryngoscope at ER-P 1 BER
(COVID-19 Triage).
- Defective sensor of Pulse Oximeter at ER-N. 1 BER
- Not functioning CBG Machine at ER-P (COVID- 1 BER
19 Triage).
Isolation Ward:
- Broken Pulse Oximeter. 1 BER
LR/DR/NICU Complex:
- Replaced busted Shadowless Bulb of OR Light 1 Operational
at Delivery Room.
- Sterilizer leak at Delivery Room need for 1 BER
replacement of rubber gasket seal.
Medicine Ward:
#DisiplinaMuna
- Defective air release valve of Manual Blood 1 BER
Pressure Apparatus.
Nutrition and Dietetics Service:
- Repaired Vegetable Chiller which now for test 1 For monitoring
run monitoring.
Out Patient Department (OPD):
- Repaired defective BP Apparatus (Digital) at 2 nd 1 Operational
Floor.
- Defective BP Apparatus at Industrial Clinic. 1 BER
- Loosed thread of 3way valve of BP Apparatus. 1 BER
- Defective BP Apparatus (Aneroid) at 2nd Floor. 1 BER
- Defective Thermoscanner at 2nd Floor. 1 BER
Pediatric Ward:
- On-going reprocess of Pharmaceutical 1 On-going
Refrigerator. reprocess
- Defective Weighing Scale. 1 BER
Radiology Department:
- Repaired air leak of Oxygen Regulator at CT 1 Operational
Scan.

Hospital Facilities:

Location / Concerns Number Status

3rd Floor Area:


- Replaced busted LED Driver Model: (8-12) 2 Operational
x1w of LED Circular Light at Hallway.
4th Floor Area:
- Repaired Bidet leak at Public Female 1 Operational
Restroom.
th
5 Floor Area:
- Repaired and adjusted water pressure of 2 Operational
Toilet Bowl Nos. 3 and 4 at Public Male
Restroom.
- Repaired clogged Lavatory at Public Male 1 Operational
Restroom.
Administration Department:
- Installed LED Circle Panel Light, 9w at Chief 4 Operational
of Clinic Office.
- Checked and assessed materials needed for 1 lot Waiting for
the repainting of Chief of Clinics Office. materials
needed
- Replaced busted LED Circle Panel Light, 9w 1 Operational
at Restroom.

#DisiplinaMuna
Admitting and Information Office:
- General cleaning of Water Dispenser. 1 Operational
- Repaired Faucet leak of Water Dispenser. 1 Operational
Ambulance Center:
- Repaired defective Blinker of Siren for 1 Operational
Ambulance No. 2.
- Repaired defective Siren of Patient Transport 1 Operational
Vehicle (PTV) No. 5.
- Replaced defective voice coil of Siren 1 Operational
Ambulance No. 5 with Plate No.: SLG 208.
- Not working Inverter of Ambulance Nos. 15, 3 BER
16 and 17.
Animal Bite Center (ABC):
- Repaired and adjusted bracket of Glass Door 1 Operational
Jamb.
- Repaired broken Gang Chair. 1 Operational
- Repaired defective Glass Door wall angle. 1 Operational
Billing and Cashier Department:
- Broken Chair. 1 BER
Blood Bank Department:
- Repaired and replaced broken clip of Dangle 1 Operational
Light.
- Reset tripped off Circuit Breaker of power 1 lot Operational
supply.
- Replaced busted LED Driver Model: (8-12) 1 Operational
x1w of LED Square Panel Light.
- Replaced busted fuse of Automatic Voltage 2 Operational
Regulator (AVR).
- Defective Uninterrupted Power Supply (UPS) 1 BER
at Serology.
Cafeteria:
- Replaced busted LED Driver Model: (8-12) 3 Operational
x1w of LED Square Directional Light.
- Replaced LED Square Directional Light. 4 Operational
CDRRM – Operation Center (OpCen):
- Broken panel of LED Television. 1 BER
- Broken Monoblock Chair. 2 BER
- Broken Office Arm Chair. 4 BER
Cardio-respiratory Department:
- Repaired stuck-up Door Lock of Glass Door. 1 Operational
City Disaster Risk Reduction and Management
Office (CDRRMO):
- Replaced busted LED Circle Panel Light, 2 Operational
12w.
Dialysis Center:

#DisiplinaMuna
- Repaired and adjusted low water pressure of 1 lot Operational
Booster Pump.
- Repaired broken Trolley. 1 Operational
- Repaired broken Black Chair. 1 Operational
- Repaired broken Medical Trolley. 1 Operational
- Installed additional Convenience Outlet for 1 Operational
used of Water Dispenser and Alcohol
Dispenser.
- Synchronized Digital Clock at Waiting Area. 1 Operational
Doctor’s Quarter:
- Repaired and adjusted water pressure of 1 Operational
Toilet Bowl at Restroom of 4 th Floor Doctor’s
Quarter.
- Repaired overflowing Floor Drain at Restroom 1 Operational
of 4th Floor Doctor’s Quarter.
- Repaired and adjusted water pressure of 1 Operational
Toilet Bowl at 3rd Floor Female Doctor’s
Quarter.
- Replaced busted LED Square Directional 3 Operational
Light at 4th Floor Doctor’s Quarter.
Dr. Ronaldo M. Mateo Operating Room Complex:
- Repaired and reinstalled Door Knob at 1 Operational
Female Restroom.
- Repaired leak and clogged Washing Area at 1 Operational
Endoscopy Room.
- Repaired and adjusted low water pressure of 1 Operational
Toilet Bowl at Post Anesthesia Care Unit
(PACU).
- Reset tripped-off power supply of 1 lot Operational
Convenience Outlet.
- Replaced busted LED Driver Model: DD (4-7) 1 Operational
x1w of LED Square Directional Light at
Receiving Area.
- Replaced busted LED Fluorescent Equivalent 2 Operational
T8 at Corridor.
- Replaced busted LED Driver Model: DD (4-7) 1 Operational
x1w of LED Square Directional Light at
OR2C.
- Replaced busted LED Square Directional 1 Operational
Light at Nurse Station.
- Replaced busted LED Square Directional 1 Operational
Light at Central Supply Room (CSR).
- Replaced busted LED Circle Panel Light, 9w 1 Operational
at Receiving Area.
- Replaced busted LED Fluorescent Equivalent 1 Operational
T5 in Stockroom at Central Supply Room
#DisiplinaMuna
(CSR).
- Replaced busted LED Fluorescent Equivalent 1 Operational
T5 at OR2B Corridor.
Drug Testing Laboratory Department:
- Replaced busted LED Square Panel Light. 2 Operational
ER Department:
- Repaired defective Faucet of Public Male 1 Operational
Restroom at ER-N.
- Repaired loosed screw of Table Drawer at 1 Operational
ER-N.
- Repaired detached sidings of Computer Table 1 Operational
in Triage Area at ER-N.
- Repaired broken Examination Bed at ER-N. 1 Operational
- Repaired broken Black Bed at ER-P (COVID- 1 Operational
19 Triage).
- Installed insulator in Glass Panel at ER-N. 1 Operational
- Installed additional LED Fluorescent 1 Operational
Equivalent T5 at ER-P (COVID-19 Triage)
Tent.
- Relocation and set-up of Tent and Mobile 1 lot Operational
Outpost at ER-P (COVID-19 Triage).
- Replaced busted LED Driver Model: DD (4-7) 2 Operational
x1w of LED Square Directional Light at ER-N.
- Replaced broken Door Knob at Restroom of 1 Operational
ER-P (COVID-19 Triage).
- Replaced busted LED Square Directional 1 Operational
Light at ER-N.
- Replaced busted LED Driver Model: DD (4-7) 1 Operational
x1w of LED Square Directional Light in Code
Room at ER-P (COVID-19 Triage).
- Replaced busted LED Square Panel Light in 3 Operational
Code Room at ER-P (COVID-19 Triage).
- Broken Treatment Bed at ER-P (COVID-19 1 BER
Triage).
General Laboratory Department:
- Repaired defective Door Knob of Restroom. 1 Operational
- Repaired detached Trolley. 1 Operational
- Transferred LED Television for queuing 1 Operational
system in their entrance.
- Defective switching relay of Uninterrupted 1 BER
Power Supply (UPS).
- Damaged and missing parts of Drawer. 1 BER
Ground Floor Area:
- Hyundai Elevator Services Phils., Inc. 6 Operational
personnel in conducting preventive
maintenance of our Elevator Nos. 1, 2, 3, 4, 5
#DisiplinaMuna
and 6.
- Installed repaired SMPS Board at Elevator 1 Operational
No. 3.
- Repaired clogged Toilet Bowl at Ground 1 Operational
Public Male Restroom beside Radiology
Department.
- Repaired clogged Urinal at Ground Floor 3 Operational
Public Male Restroom beside Radiology
Department.
- Replaced busted LED Driver Model: DD (4-7) 1 Operational
x1w of LED Circular Light at Ground Floor
Hallway going to Ground Floor Public
Restroom.
- Repaired and replaced busted LED Lights 7 Operational
Diode of LED Circular Light at Canopy of
Hospital Entrance.
Housekeeping Department:
- On-going repair and installation of mechanical 1 On-going
of Iron Machine at Basement Linen and repair
Laundry Section.
Human Resource Management Office (HRMO):
- Replaced busted LED Square Panel Light. 1 Operational
- Replaced busted LED Square Directional 1 Operational
Light.
- Broken Chair. 3 BER
ICT and Engineering Unit:
- Repaired malfunction Freezer No. 3 at 1 For check-up
Morgue.
- Temporary shutoff of Freezer no. 1 due to 1 Temporary
overheat at Morgue. shutoff
- Replaced busted LED Fluorescent Equivalent 2 Operational
T5 at Sewerage Treatment Plant (STP).
Intensive Care Unit (ICU) Department:
- Repaired misaligned Hospital Bed. 6 Operational
Isolation Ward:
- Repaired loosed contact Wall Light of Male 2 Operational
Bed No. 6.
- Replaced busted LED Driver Model: DD (4-7) 1 Operational
x1w of LED Square Directional Light.
- Detached Wall Tiles at Restroom. 8 Waiting for
materials
needed
LR/DR/NICU Complex:
- Repaired clogged Scrub Sink at Delivery 1 Operational
Room.
- Repaired broken Stainless Chair at Delivery 1 Operational
#DisiplinaMuna
Room.
- Repaired detached wheel of Mayo Table at 1 Operational
Delivery Room.
- Synchronized Digital Clock at Delivery Room. 1 lot Operational
- Reset tripped off Circuit Breaker of 1 lot Operational
Convenience Outlet at Delivery Room.
- Broken Bed Frame at Delivery Room. 1 BER
Medicine Ward:
- Removed broken bed side railing of Patient’s 3 Operational
Bed.
- Checked and assessed installation of 1 lot Waiting for
additional Convenience Outlet at Medicine materials
Ward which listed materials needed for the needed
said installation.
- Replaced busted LED Square Directional 1 Operational
Light at Nurse Station.
- Replaced busted LED Driver Model: DD (4-7) 3 Operational
x1w of LED Square Directional Light.
- Replaced busted LED Square Directional 5 Operational
Light.
- Not working Electric Fan. 1 BER
Nursing Service Office (NSO):
- Repaired stock-up door lock of Door Knob. 1 Operational
Nutrition and Dietetics Service:
- Replaced short circuit LED Driver Model: DD 1 Operational
(4-7) x1w of LED Square Directional Light.
- Checked and assessed materials needed for 1 lot Waiting for
Office Table repair and repainting. materials
needed
- Cleaned condenser of Vegetable Refrigerator 1 For reprocess
at Kitchen and upon assessment need for and waiting for
reprocess due to clogged and not cooling materials
needed
OB Ward Department:
- Repaired clogged Sink at Public Male 1 Operational
Restroom of OB Ward Annex.
- Repaired clogged Urinal at Public Male 1 Operational
Restroom of OB Ward Annex.
- Repaired detached wheel of Trolley Tray at 1 Operational
OB Ward.
- Repaired loosed connection of Door Lock at 1 Operational
Public Female Restroom of OB Ward.
- Repaired clogged Drinking Fountain at OB 1 Operational
Ward Annex.
- Repaired clogged Toilet Bowl at Public 1 Operational
Female Restroom of OB Ward.
#DisiplinaMuna
- Repaired clogged Toilet Bowl No. 2 at Public 1 Operational
Female Restroom of OB Ward Annex.
- Repaired clogged Toilet Bowl at Public 2 Operational
Female Restroom of OB Ward Annex.
- Installed plastic cover at Window of OB Ward 1 Operational
Annex.
- Replaced busted LED Square Directional 3 Operational
Light at OB Ward.
Out Patient Department (OPD):
- Repaired detached Filing Shelves at Room 7 1 Operational
of 2nd Floor.
- Repaired detached Door Lock of Glass Door 1 Operational
at Industrial Clinic.
- Repaired leak of Bidet at Public Female 1 Operational
Restroom of 2nd Floor.
- Repaired wiggled Folding Chair at Industrial 1 Operational
Clinic.
- Repaired misaligned Glass Door at Industrial 1 Operational
Clinic.
- Repaired and adjusted water pressure of 1 Operational
Toilet Bowl at Public Female Restroom of 2 nd
Floor.
- Repaired clogged Sink at Public Female 1 Operational
Restroom of 2nd Floor.
- Repaired and adjusted water pressure of 1 Operational
Toilet Bowl at Public Male Restroom of 2 nd
Floor.
- Installed Picture Frame at Industrial Clinic. 1 Operational
- Replaced busted LED Square Directional 1 Operational
Light at Room 7 of 2nd Floor.
Pediatric Ward:
- Repaired leak and replaced Faucet at 1 Operational
Restroom.
- Repaired Toilet Bowl leak at Public Restroom 1 Operational
of Female Pediatric Ward.
- Repaired clogged Toilet Bowl of Restroom at 1 Operational
Female Pediatric Ward.
- Repaired overflowing Floor Drain of Restroom 1 Operational
at Nurse Station.
- Installed bracket support of Cabinet at Stock 1 lot Operational
Room.
- Replaced busted LED Driver Model: DD (4-7) 4 Operational
x1w of LED Square Directional Light at Male
Pediatric Ward.

Pharmacy Department:
#DisiplinaMuna
- Make additional holes for Computer Table. 1 Operational
- Replaced busted LED Square Panel Light. 1 Operational
Physical Therapy (PT) Rehabilitation Department:
- Repaired defective Alcohol Dispenser. 1 Operational
- Repaired broken Hospital Bed. 1 Operational
- Replaced busted LED Square Directional 3 Operational
Light.
Property and Supply Office (PSO):
- Replaced broken Door Knob at 2nd Floor 1 Operational
Stock Room.
- Replaced busted LED Driver Model: DD (4-7) 7 Operational
x1w of LED Square Directional Light at
Basement Stock Room.
Radiology Department:
- Repaired and adjusted water pressure of 1 Operational
Toilet Bowl at Restroom.
- Replaced broken Flexible Hose at Ultrasound 1 Operational
Section.
- Broken Office Chair. 1 BER
- Broken Folding Chair. 1 BER
- Broken Round Chair. 1 BER
Social Welfare Assistant (SWA) Office:
- Repaired broken microphone stand of Two- 1 Operational
way Speaker.
- Installed Window Blinds. 1 Operational
- Checked and assessed materials needed for 1 Waiting for
the installation of Window Blinds. materials
needed

Hospital Air-conditioning System:

Unit / Concerns Number Status

Administration Department:
- Installed LED Television at Chief of Hospital 1 Operational
Office.
Animal Bite Center (ABC) Department:
- Cleaned air filter of Wall Mounted ACU. 1 Operational
CDRRM – Operation Center (OpCen):
- General cleaning of Wall Mounted ACU (Indoor 1 Operational
Unit) at 6th Floor Radio Room.
- Repaired noisy and rectify air filter and cover of 2 Operational
Ceiling Suspended ACU.
City Disaster Risk Reduction and Management Office

#DisiplinaMuna
(CDRRMO):
- General cleaning of Window type ACU. 1 Operational
- General cleaning of Wall Mounted ACU (Indoor 1 Operational
and Outdoor Unit).
Doctor’s Quarter:
- Repaired Error 2502 and cleaned drain pipe 1 Operational
line and drain pump of Ceiling Cassette ACU at
4th Floor Doctor’s Quarter.
ER Department:
- General cleaning of Wall Mounted ACU (Indoor 1 Operational
Unit) of Doctor’s Quarter at ER-N.
- General cleaning of Wall Mounted ACU (Indoor 1 Operational
Unit) of Dining Area at ER-N.
- Cleaned air filter of Ceiling Cassette ACU at 2 Operational
ER-N.
- General cleaning of Ceiling Suspended ACU 2 Operational
(Indoor Unit) at ER-N.
- Cleaned drain pipe line of Ceiling Cassette 1 Operational
ACU on Hallway at ER-N.
- General cleaning of wall Mounted ACU (Indoor 1 Operational
and Outdoor Unit) of Mobile Outpost No. 18 at
ER-P (COVID-19 Triage).
General Laboratory Department:
- Re-piping of drain pipe line of Ceiling Cassette 1 Operational
ACU at Main Laboratory.
- Cleaned drain pan and drain pipe line, and 1 Operational
replaced drain pump of Ceiling Cassette ACU
at Main Laboratory.
- Repaired Error 2502 and cleaned drain pipe 1 Operational
line and drain pump of Ceiling Cassette ACU.
Ground Floor Area:
- General cleaning of Ceiling Concealed ACU 1 Operational
(Indoor Unit) at Information Lobby.
Human Resource Management Office (HRMO):
- General cleaning of wall Mounted ACU (Indoor 1 Operational
Unit).
Isolation Ward:
- Cleaned air filter of Wall Mounted ACU at 1 Operational
Droplet.
LR/DR/NICU Complex:
- Re-aligned drain pipe line of Ceiling Cassette 1 Operational
ACU at Operating Room (OR).
- Cleaned air filter of Ceiling Cassette ACU at 1 Operational
Delivery Room.
- Cleaned drain pipe line and drain pump of 1 Operational
Ceiling Cassette ACU at Operating Room.
#DisiplinaMuna
Medicine Ward:
- General cleaning of Ceiling Cassette ACU 1 Operational
(Indoor Unit).
- Cleaned drain pipe line and drain pump motor 1 Operational
of Ceiling Cassette ACU at Male Medicine
Ward.
OB Ward Department:
- General cleaning of Ceiling Cassette ACU 1 Operational
(Indoor Unit) at OB High Risk Ward.
- General cleaning of Ceiling Cassette ACU 1 Operational
(Indoor Unit) at OB Ward.
Out Patient Department (OPD):
- Cleaned air filter of Ceiling Suspended ACU at 1 Operational
Industrial Clinic.
- Cleaned air filter and cover of Wall Mounted 1 Operational
ACU at Orthopedic/Surgery Clinic of 2nd Floor.
- Cleaned drain pipe line of Wall Mounted ACU 1 Operational
at Internal Medicine of 2nd Floor.
- Replaced 2 pcs broken Fan Bearing 6201Z of 2 Operational
Ceiling Suspended ACU at 2nd Floor.
Pediatric Department:
- Cleaned drain pan and drain pump of Ceiling 1 lot Operational
Cassette ACU at Male Pediatric Ward.
- Cleaned drain pan and drain pump of Ceiling 1 lot Operational
Cassette ACU at Female Pediatric Ward.
- Reset Ceiling Cassette ACU. 1 lot Operational
Pharmacy Department:
- General cleaning of Ceiling Suspended ACU 1 Operational
(Outdoor Unit).
Property and Supply Office:
- General cleaning of Windows Type ACU at 2 nd 1 Operational
Floor Stock Room.
Radiology Department:
- Equipage Company, Inc. personnel in checking 2 BER
of our not functioning 2 units Climaveneta 8TR
ACU at Magnetic Resonance Imaging (MRI)
Control Room found out both Magnetic
Contactor burn out and need for replacement
due to beyond economical repair.
- Checked and assessed the burning smell which 2 Checked and
found out it was come from the burnout assessed
Magnetic Contactor at 8TR ACU at Magnetic
Resonance Imaging (MRI) Control Room and
waiting for the materials needed for
replacement.
Surgery Ward:
#DisiplinaMuna
- General cleaning of Ceiling Cassette ACU 1 Operational
(Indoor Unit) at Male Surgery Ward.
- General cleaning of Wall Mounted ACU (Indoor 1 Operational
Unit) at Female Surgery Ward.

ACU at City Hall and Field Offices:

Concerns Action Status


Taken

Repaired overflow flushing of drain pipe lines of Wall 2 Operational


Mounted ACU at City Budget Office, City Hall, Zone 4,
City of Dasmariñas, Cavite.
Replaced busted Contactor of Wall Mounted ACU at 1 Operational
Document Monitoring Unit, City Hall, Zone 4, City of
Dasmariñas, Cavite.
Cleaned drain pipe line of wall Mounted ACU at SPM 1 Operational
Nickol Austria, Jr. Office, City Hall, Zone 4, City of
Dasmariñas, Cavite.
General cleaning of wall Mounted ACU (Outdoor Unit) at 1 Operational
City General Services Office, City Hall, Zone 4, City of
Dasmariñas, Cavite.
General cleaning of Wall Mounted ACU (Indoor Unit) and 2 Operational
re-insulation of drain pipe line at Office of the City Mayor,
City Hall, Zone 4, City of Dasmariñas, Cavite.
Cleaned drain pipe line of Wall Mounted ACU at 1 Operational
Department of Interior and Local Government (DILG)
Office, City Hall, Zone 4, City of Dasmariñas, Cavite.
General cleaning of Window Type ACU (Indoor Unit) at 2 Operational
Office of the City Mayor, City Hall, Zone 4, City of
Dasmariñas, Cavite.
General cleaning of Wall Mounted ACU (Indoor Unit) at 2 Operational
Commission on Elections (COMELEC), City Hall, City
Hall, Zone 4, City of Dasmariñas, Cavite.
Recharged R22 Freon of Wall Mounted ACU at General 1 Operational
Service Office (GSO), City Hall, City Hall, Zone 4, City of
Dasmariñas, Cavite.
Recharged freon R410A and general cleaning of Wall 3 Operational
Mounted ACU (Indoor and Outdoor Unit) at Closed-Circuit
Television and Security (CCTV), City Hall, Zone 4, City of
Dasmariñas, Cavite.
Repaired Wall Mounted ACU which suddenly shutdown 1 Operational
using remote control at Public Employment Services
Office (PESO), City Hall, Zone 4, City of Dasmariñas,

#DisiplinaMuna
Cavite.
Reset Circuit Breaker of not functioning Wall Mounted 1 Operational
ACU at City Civil Registrar Office, City Hall, Zone 4, City
of Dasmariñas, Cavite.
Checked and assessed leak of Wall Mounted ACU at 1 lot Waiting for
Documents Monitoring Unit, City Hall, Zone 4, City of materials
Dasmariñas, Cavite need for re-insulation. needed
Checked and assessed Wall Mounted ACU leak at 1 Waiting for
Complaint’s ang Action Unit (CAU), City Hall Annex Bldg., materials
Zone 4, City of Dasmariñas, Cavite need for re-installation needed
of drain pipe line.
Cleaned air filter of Wall Mounted ACU at Day Care 1 Operational
Center Office at City Social Welfare and Development
Office (CSWDO), Burol II, City of Dasmariñas, Cavite.
General cleaning of Wall Mounted ACU at Solo Parent 1 Operational
Office at City Social Welfare and Development Office
(CSWDO), Burol II, City of Dasmariñas, Cavite.
General cleaning of Wall Mounted ACU (Indoor Unit) at 1 Operational
Motorpool, Sampaloc IV, City of Dasmariñas, Cavite.
Checked and assessed materials needed for the repair of 1 Operational
Wall Mounted ACU at Sports Development Office, DasCA
Bldg., Burol II, City of Dasmariñas, Cavite.
General cleaning of Condenser at Office of the City 1 Operational
Prosecutor, DasCA Bldg., Burol II, City of Dasmariñas,
Cavite.
General cleaning of Wall Mounted ACU (Indoor Unit) at 1 Operational
Office of the Clerk of Court, Municipal Trial Court in Cities
(MTCC), DasCA Bldg., Burol II, City of Dasmariñas,
Cavite.
Cleaned air filter of Window Type ACU at Central 1 Operational
Inspection Unit (CIU), CM Plaza Bldg., Don P. Campos
Ave., Zone 4, City of Dasmariñas, Cavite.
Cleaned air filter of Wall Mounted ACU at Central 1 Operational
Inspection Unit (CIU), CM Plaza Bldg., Don P. Campos
Ave., Zone 4, City of Dasmariñas, Cavite.
General cleaning of Wall Mounted ACU (Indoor Unit) at 1 Operational
Room 4, Prosecutor’s Office, DasCA Bldg., Burol II, City
of Dasmariñas, Cavite.
General cleaning and declogged drain pipe line of Wall 3 Operational
Mounted ACU (Indoor Unit) at Closed-Circuit Television
and Security Office, City Hall, City Hall, Zone 4, City of
Dasmariñas, Cavite.
General cleaning of Wall Mounted ACU (Indoor and 1 Operational
Outdoor Unit) and recharge of R410-A Freon at Nurse
Room of City Health Office (CHO) – 1, Dr. Leoncio

#DisiplinaMuna
Mangubat Bldg., D. Mangubat St., Zone II, City of
Dasmariñas, Cavite.
Checked and assessed Wall Mounted ACU leak at 1 lot Waiting for
Sanitation Department of City Health Office (CHO) – 1, materials
Dr. Leoncio Mangubat Bldg., D. Mangubat St., Zone II, needed
City of Dasmariñas, Cavite need for re-insulation of
piping.
General cleaning of Wall Mounted ACU (Indoor Unit) at 1 Operational
Branch 3, Municipal Circuit Trial Court in Cities (MTCC),
DasCA Bldg., Burol II, City of Dasmariñas, Cavite.
Declogged drain pipe line of Wall Mounted ACU at 1 Operational
Records Section of Prosecutor’s Office, DasCA Bldg.,
Burol II, City of Dasmariñas, Cavite.
Cleaned air filter and reset 3 units Window Type ACU at 3 Operational
Dasmariñas Social Hygiene Clinic of City Health Office
(CHO) -1, Galdiola St., Mabuhay Homes 2000 Subd.,
Phase III, Salawag, City of Dasmariñas, Cavite.
Defective compressor and outdoor board of Wall Mounted 1 BER
ACU at Computer Room of City Health Office (CHO) -1,
Dr. Leoncio Mangubat Bldg., D. Mangubat St., Zone II,
City of Dasmariñas, Cavite need for replacement due to
beyond economical repair.
General cleaning of Wall Mounted ACU (Indoor Unit) at 1 Operational
Doctor’s Room of City Health Office (CHO) -1, Dr.
Leoncio Mangubat Bldg., D. Mangubat St., Zone II, City of
Dasmariñas, Cavite.
General cleaning of Wall Mounted ACU (Indoor and 1 Operational
Outdoor Unit) at Lying-in Clinic Consultation of City
Health Office (CHO) -1, Dr. Leoncio Mangubat Bldg., D.
Mangubat St., Zone II, City of Dasmariñas, Cavite.

Provided 25KVA and 150KVA Generator and Electrician during the conduct
of the following activities:

Events Venue Date

Cavite 2.0 Ipanalo Na10 To Grand Rally Her New City of May 1, 2022
Excellency Vice President Maria Leonor “Leni” G. Dasmariñas
Robredo – Sen. Francis “Kiko” N. Pangilinan. Football Field,
Burol Main,
City of
Dasmariñas,
Cavite
Meeting with Congressman Elipidio F. Barzaga, Jr. Tent Area, May 3, 2022

#DisiplinaMuna
Dasmariñas
Integrated
High School
(DIHS), Burol
II, City of
Dasmariñas,
Cavite
Orientation of the operation quick count. Tent Area, May 3 – 4,
Dasmariñas 2022
Integrated
High School
(DIHS), Burol
II, City of
Dasmariñas,
Cavite
Assistance to Individuals in Crisis Situation (AICS) Tent Area, May 5, 2022
Distribution. Dasmariñas
Integrated
High School
(DIHS), Burol
II, City of
Dasmariñas,
Cavite
Green Ladies Induction. Tent Area, May 5, 2022
Dasmariñas
Integrated
High School
(DIHS), Burol
II, City of
Dasmariñas,
Cavite
Precinct Workers Seminar. Tent Area, May 6 - 7,
Dasmariñas 2022
Integrated
High School
(DIHS), Burol
II, City of
Dasmariñas,
Cavite
Standby Generator for National and Local Election Dasmariñas May 9, 2022
2022. Elementary
School (DES),
Don P.
Campos Ave.,
Zone 4, City of
Dasmariñas,
#DisiplinaMuna
Cavite
Standby Generator for National and Local Election Francisco E. May 9, 2022
2022. Barzaga
Elementary
School
(FEBS), D.
Mangubat St.,
Zone 2, City of
Dasmariñas,
Cavite
Standby Generator for National and Local Election Paliparan May 9, 2022
2022. National High
School,
Paliparan III,
City of
Dasmariñas,
Cavite
Iglesia Ni Cristo (INC) Evangelical Mission – Cavite Dasmariñas May 10, 2022
South. Arena, Burol
Main, City of
Dasmariñas,
Cavite
Meeting with Congressman Elipidio F. Barzaga, Jr. Tent Area, May 14, 2022
Dasmariñas
Integrated
High School
(DIHS), Burol
II, City of
Dasmariñas,
Cavite
Assistance to Individuals in Crisis Situation (AICS) Tent Area, May 19, 2022
Distribution. Dasmariñas
Integrated
High School
(DIHS), Burol
II, City of
Dasmariñas,
Cavite
Sunduan 2022 City May 27, 2022
Quadrangle,
City Hall, Zone
4, City of
Dasmariñas,
Cavite
Philippine National Police (PNP) License To Own and Tent Area, May 28, 2022
Process Firearms (LTOPF) Caravan. Dasmariñas
#DisiplinaMuna
Integrated
High School
(DIHS), Burol
II, City of
Dasmariñas,
Cavite
Senior Cruzan Tent Area, May 29, 2022
Dasmariñas
Integrated
High School
(DIHS), Burol
II, City of
Dasmariñas,
Cavite
Green E-skwela (Energy Sustainability Project for the Francisco E. May 30, 2022
Public Schools by the City Government of Barzaga
Dasmariñas). Integrated
High School
(FEBIHS),
Lagmay Cpd.,
Medinaville
Subd., San
Jose, City of
Dasmariñas,
Cavite
Distribution of Tablets. Tent Area, May 30, 2022
Dasmariñas
Integrated
High School
(DIHS), Burol
II, City of
Dasmariñas,
Cavite

Aside from these accomplishments, our Unit is also responsible for the
implementation of other special project throughout the City.

For information and reference.