TAIE Digital Controller OUT1


OUT2
AT
AL 1
OUT1 OUT2

OUT1 OUT2
OUT1 OUT2

AL 2

FY400/600/700/800/900
PRO

FY400 FY600 FY700 FY800 FY900


1 Notice
Please confirm the specification of controllers is to totally with your requirement before using it, also read this user’s manual in detail.
Danger
1. Danger! Electric Shock!
DON'T touch AC power wiring terminal when controller has been p owered!
Keep the power off until all of the wiring are completed!
Warning
1. Please confirm the AC power wiring to controller is correct, otherwise it would be caused aggravated
damage on controller. (FY400 connecting with Pin 1 and 6,FY600/700/800/900 with Pin 1 and 2).
2. Be sure to use the rated power supply(AC85~265V or DC24V), otherwise it would be caused aggravated damage on controller.
3. Please confirm wires are connected with correct terminal (Input, Output).
4. Use M3 screw-compatible crimp-on terminals with an insulation sleeve, as shown below
3.2mm 3.2mm
5.8mm or less

5.8mm or less

Torque : 0.4 N.m (4kgf.cm)

5. Avoid to install controller in following spaces :


I. A place where the ambient temperature may reach beyond the range from 0 to 50℃
II. A p l a c e w h e r e t h e a m b i e n t h u m i d i t y m a y r e a c h b e y o n d t h e r a n g e f r o m 5 0 t o 85% RH.
III. A place where the the controller likely to come into contact with water ,oil , chemicals ,steam and vapor.
IV. A place where the controller is subject to interface with static electricity ,magnetism and noise.
6. For thermocouple(TC) input ,use shield compensating lead wire .
7. For RTD input ,use shield wires which have low resistance and no resistance difference between the 3 wires.

2 External Dimension and Panel Cutout〈Unit:mm〉


+0.5
48 14 80 44.5 0

OUT1
OUT2

+0.5
FY400
AT

70 44.5
48
1
2 0
PRO

65
+0.5
90.5
96 14 80 0

OUT1 OUT2

+0.5
FY600 48 70 44.5
0

111
+0.5
14 80 68.5
72 0

+0.5
FY700 OUT1
72 94
68.5
0
OUT2

89
+0.5
44.5
48 14 80 0

+0.5
90.5
FY800
OUT1 OUT2

0
96 116

65
+0.5
90.5
14 80 0
96

+0.5
90.5
FY900 OUT1 OUT2 96 116 0

111
3 Parts Description
FY400 FY600 FY800 FY700/FY900
11 8 9 12 16 5 7 1 2 8 9 10 11 12 13 14 15
8
OUT1
9
1
OUT1 OUT2
OUT2

AT
10 1
2
AL 1
AL 2
11 9 10
PRO
11 2
12
OUT1
8 OUT1 OUT2

OUT1 OUT2
15 12 15
OUT1
16 OUT1

3 5 6 7 1 2 13 10 15 14 4 3 6 13 14
16
7
4 3 4 5 6 7

3 5 6
SYMBOL NAME FUNCTION SYMBOL NAME FUNCTION
Measured value Displays PV or various parameter OUT1 8 OUT1 lamp Lights when OUT1 is on (Green)
PV 1 (PV)display symbols (Red)
OUT2 9 OUT2 lamp Lights when OUT2 is on (Green)
Displays SV or various parameter Lights when Autotuning is activated
SV 2 Setting value AT 10 A u t o t u n i n g l a m p (Orange)
(SV)display set values (Green)
11 A l a r m 1 l a m p Lights when Alarm 1 is activated
AL1 (Red)
Used for parameter calling up and
SET 3 Set key
set value registration 12 A l a r m 2 l a m p Lights when Alarm 2 is activated
AL2 (Red)
Auto/Manual Switches between Auto(PID)
A/M 4 key output mode and Manual output 13 A l a r m 3 l a m p Lights when Alarm 3 is activated
AL3 (Red)
Shift digits when settings are
5 Shift key changed MAN 14 M anual output Lights when manual output is
lamp activated (Red)
Decrease numbers
6 Down key
(*Program Hold) (*Only for programmable controller)
PRO 15 *l aPmr opg r a m R u n n i n g *Flashes when program running
(Only for programmable controller)
Up key Increase numbers Output% Bar- Output% is displayed on 10-dot
7 (*Program Run) (*Only for programmable controller)
OUT1% 16
Graph display LEDs

4 Terminal Arrangement
FY400 FY700
A.Power Supply
A.Power Supply
1 15 8

2 16 9
AC 85~265V
AC 85~265V
DC 15 ~50V(Option) 3 17 10
DC 15 ~50V(Option)

H.CT Input 4 18 11 H.CT Input


5 19 12
15
11
6 20 13
CT
CT
12 7 21 14 16

B.Control Output C.Input


B.Control Output C.Input mA,V RTD TC,mV
OUT1 OUT2
mA,V TC,mV 11 11 11
RTD Relay SSR mA,V Relay SSR mA,V
OUT1 OUT2 12 12 12
5 3
Relay SSR mA,V Relay SSR mA,V
13 13 13
6 4
2
14 14 14
3 7

D.Alarm E.Retransmission

D.Alarm AL 1 AL 2 TRS
(Option) COM
(Use OUT1 & OUT2) 3 8 18
OUT1 OUT1 OUT1
(Option) AL 1 AL 2 (Proportional Motor
Valve Control) (Proportional Motor (1ΦZero Cross (1ΦPhase Angle NO 19
OUT1 OUT1 Valve Control) Control) Control) 4 9
2 13 11
(1ΦZero Cross (Proportional Motor AL 1
Control) Valve Control) 3 15 G1 15 G1
3 14 12 NC 10
G1 4 CLOSE 17 G2 16 K1

K1 CLOSE E.Retransmission F.Communication G.Communication F.Remote


5 OPEN 19 17 G2
TRS RS232 RS485 TTL RS232 RS485 TTL Remote SV
G2 OPEN RD Dx- RD 11 6 20 18 K2 RD Dx- RD 15
11 11 PROT 15 15 9
K2 COM SD 12 Dx+
12 SD 12 7 COM 20 SD 16 Dx+
16 SD 16 10

SG 13 SG 13 21 SG 17 SG 17
PROT
FY600/FY800 FY900
A.Power Supply A.Power Supply E.Retransmission
1 21 31 11
1 11 TRS
2 22 32 12
AC 85~265V 39
2 12
DC 15 ~50V(Option) 3 23 33 13
AC 85~265V
DC 15 ~50V(Option) 3 13 40
4 24 34 14
4 14
5 25 35 15
5 15 6 26 36 16
H.CT Input
6 16
H.CT Input 14
7 27 37 17 F.Remote
7 17 Remote SV
8 28 38 18
14 CT 14
8 18 9 29 39 19
CT 15 15
9 19 10 30 40 20

15 10 20
B.Control Output C.Input
OUT1 OUT1 mA,V RTD TC,mV
B.Control Output C.Input OUT1 Relay SSR mA,V (1ΦZero Cross (3ΦZero Cross 17 17 17
Control) Control)
mA,V RTD TC,mV
OUT1 OUT2 18 18 18
17 17 17 31 G1 31 RG1
Relay SSR mA,V Relay SSR mA,V
18 18 18 33 G2 33 RG2 19 19 19
6
39 35 TG1 20 20 20
19 19 19
7
OUT2 Relay SSR mA,V 40 D.Alarm
PROT 37 TG2
20 20 20 6
39 AL 1 AL 2 AL 3
7 6
D.Alarm E.Retransmission 40
PROT
AL 1 AL 2 AL 3 TRS OUT1 OUT1 7
(Option) (Proportional Motor (1ΦPhase (3ΦPhase
OUT1
6 12
Valve Control) Angle Control) Angle Control)

OUT1 OUT1 13 6 31 G1 31 G1
7 G.Communication
(Proportional Motor Valve (1ΦPhase Angle
Control) Control) 7 CLOSE 32 K1 32 K1 RS232 RS485 TTL
RD 14 Dx- 14 RD 14
6 7 K2 8 OPEN 33 G2 33 G2
SD Dx+ SD 15
15 15
7 CLOSE 8 G2 G.Communication 9 34 K2 34 K2
F.Remote
SG 16 SG 16
8 OPEN 9 K1 RS232 RS485 TTL Remote SV 10 COM 35 35 G3
Dx- RD
( Remote SV )
RD 14 14 14 14
36 36 K3 RS232 RS485
9 10 G1 PROT
SD Dx+ SD RD 31 Dx- 31
15 15 15 15 39
10 COM
SD 32 Dx+ 32
SG 16 SG 16 40
PROT
SG 33

5 Operations
1.Power ON: Controller wiil display as following 4.Change the Alarm value:
PV PV PV PV Change AL1 value to“5.0"( AL1 active ,if PV exceeds SV over 5.0)
SV SV SV SV

PV PV PV PV
OUT1 OUT2 AT
Y2 AL1 AL2 AL3 MAN PRO OUT1 OUT2 AT
OUT1 Y2 AL1 AL2 AL3 MAN PRO OUT2 AT
OUT1 OUT2
OUT1 Y2 AL1 AL2 AL3 MAN PRO OUT1 OUT2 AT
OUT1 OUT2 Y2 AL1 AL2 AL3 MAN PRO

0 20 40 60 80 100 0 20 40 60 80 100 0 20 40 60 80 100 0 20 40 60 80 100

< < < < SV SV SV SV


>
<
>

>
<

<
>
<

SET A/M SET A/M SET A/M SET A/M

OUT1 OUT2 AT
Y2 AL1 AL2 AL3 MAN PRO OUT1 OUT2 Y2 AL1 AL2 AL3 MAN PRO
AT OUT1 OUT2 AT
Y2 AL1 AL2 AL3 MAN PRO OUT1 OUT2 AT
Y2 AL1 AL2 AL3 MAN PRO

Light all LEDs and all Display input type Display range Ready for use 0 20 40 60 80 100 0 20 40 60 80 100 0 20 40 60 80 100 0 20 40 60 80 100

< < < > <


>

>
<
>

<

<
<

SET A/M SET A/M SET A/M


7 segment displays (0.0 ~ 400.0) SET A/M

2.Change the Set Value(SV): Change SV from 0.0 to 100.0 Press SET Key Press Key Press Key Press SET Key
To display parameter AL1 To change AL1 value Increase AL1 value Store the new value of AL1
PV PV PV PV

SV SV SV SV
* There are total 16 alarm mode types ,referenced as below:
OUT1 OUT2 AT
Y2 AL1 AL2 AL3 MAN PRO OUT1 OUT2 AT
Y2 AL1 AL2 AL3 MAN PRO OUT1 OUT2 AT
Y2 AL1 AL2 AL3 MAN PRO OUT1 OUT2 AT
Y2 AL1 AL2 AL3 MAN PRO

0 20 40 60 80 100 0 20 40 60 80 100 0 20 40 60 80 100 0 20 40 60 80 100


* To change Alarm mode ,press SET + key 5 seconds to enter
< < < < Level 3(Input Level) and then change the value of ALD1/ALD2/ALD3.
>

>

>

>
<

<

<

<

SET A/M SET A/M SET A/M SET A/M

Press Key Press Key Press Key Press SET Key


The SV number started to To select the hundreds digit. To change the number to 1. To store the new set value.
flash.The flashing digit
5.Alarm mode type (Referenced for ALD1/ALD2/ALD3)
indicates which digit can be set.
( :SV :Alarm set value)
3.Autotuning (AT): Deviation high alarm Segment End alarm
Band alarm
Use AT function to autimatically calculate and set the 01
with hold action*
OFF ON
04
(Only for Programmable controller)
(1) ALD1~3 , set 07
14
optimize PID value for your system. HIGH
PV
LOW
OFF ON OFF
HIGH
PV 07 (2) ALD1~3=Alarm Segment
(3) ALT1~3 defines as follows:
0 =flicker alarm
Deviation high alarm Process high alarm 99.59 =continued alarm
PV PV PV PV
with hold action* others =alarm ON time
11 OFF ON 05 OFF ON Program Run alarm
SV SV SV SV PV PV
HIGH LOW HIGH (Only for Programmable controller)
17 Run Stop
OUT1 OUT2 AT
Y2 AL1 AL2 AL3 MAN PRO OUT1 OUT2 AT
Y2 AL1 AL2 AL3 MAN PRO OUT1 OUT2 AT
Y2 AL1 AL2 AL3 MAN PRO OUT1 OUT2 AT
Y2 AL1 AL2 AL3 MAN PRO Deviation low alarm
Process high alarm ON OFF
0 20 40 60 80 100 0 20 40 60 80 100 0 20 40 60 80 100 0 20 40 60 80 100 with hold action* AL
< < < < 15
>

>

02
<

>

<
>

<
<

SET A/M SET A/M SET A/M SET A/M OFF ON


ON OFF
PV PV System failed alarm* (ON)
HIGH LOW HIGH
08 Normal Failed
Process low alarm
Press SET Key Press Key Press Key Press SET Key Deviation low alarm with hold action* OFF ON
AL
To display parameter AT. To change AT setting. Change AT to “YES" Start Autotuning process 12 ON OFF
06 ON OFF
PV System failed alarm* (OFF)
(AT lamp will be lighted on) HIGH
PV
LOW HIGH
Normal
Autotuning Autotuning 18 Failed
Deviation high/low alarm Process low alarm
ATVL=0 ATVL=20 with hold action*
ON OFF
AL
*Set ATVL to prevent overshoot occurred during 03 16
ON OFF ON ON OFF
autotuning process. PV PV Heater Break Alarm
LOW HIGH LOW HIGH 09
To set ATVL ,press SET key for 5 seconds to enter (HBA)
(Overshoot )
PV Level 2 (PID Level) and then change the value. Deviation high/low alarm 00 No alarm
10
SV SV 13 ON OFF ON
PV
SV - 20 LOW HIGH

PV *Hold action:
When Hold action is ON ,the alarm action is suppressed at start-up until the
measured value(PV) enters the non-alarm range.
100 100
% O O % O O
Output% OFF OFF Output% OFF OFF
0 N N 0 N N *System failed:
% % It means that the controller display error message with one of following :
ON/OFF Control PID Control ON/OFF Control PID Control
(Autotuning) (After Autotuning) (Autotuning) (After Autotuning) ”UUU1” or “NNN1” or “CJCE”
6 Parameter List
Levels
Level 3 (Input Level)
Diagram
Input type selection
Level 1
(User Level) * The controller returns to Level 1 if there Set
is no key operation within 60 seconds. Analog input low limit calibration Range:-1999 ~ 9999
LCK = 0000 (Used for mA and V input)
Press SET Key 5 seconds Press SET Key+ 5 seconds Set
* In any Level ,press A/M key
twice will return to Level 1.
Analog input high limit calibration Range:0 ~ 9999
(Used for mA and V input)
Set
Level 2 Level 3 Decimal point position 0000,000.0,00.00,0.000
Press SET (PID Level) (Input Level) Press SET Key+ 5 seconds
(Available for mA and V input)
Set
Key 5 seconds
Lower Set-Point Limit Scaling Low Limit
Set
Upper Set-Point Limit Scaling High Limit
Level 2 (PID Level) Set
Parameter
Description Range:0.0~200.0% Remote input low limit calibration Range:-1999 ~ 9999
Default Value Proportional band 1
(For output 1) ON/OFF control if set to 0 (0.0)
Set Set
Integral time 1 Range:0~3600 seconds Remote input high limit calibration Range:0 ~ 9999
Level 1 (User Level) (For output 1) PD control if set to 0
Set
Set
Process Value Alarm mode of AL1 Range:00~19
Derivative time 1 Range:0~900 seconds
Set Value Refer to “Alarm mode type"
Set (For output 1) PI control if set to 0
Set Set
Range:0~99 Min 59 Secs
Dead-band time Alarm time of AL1 0=Flicker Alarm,99:59=Continued
Output Limt Don't care Others=On delay time
Set Set (If ALD=07 , ALT means alarm on time)
Set
Autotuning Auto tuning offset value Range:0~USPL Alarm mode of AL2 The same with ALD1
Set Set
Set
Output 1 cycle time Range:0~150 seconds Alarm time of AL2 The same with ALT1
Alarm 1 set value
Relay output : 10
Set Set Voltage pulse output : 1 , mA output: 0 Set
Display
Heater current display ( Hysteresis for output 1 Alarm mode of AL3 The same with ALD1
) If P1=0
ON/OFF control
Range:0~1000
HBA set value
Set Set Set
Proportional band 2 Alarm time of AL3 The same with ALT1
Alarm 2 set value The same with P1
(For output 2)
Set Set
Set
Integral time 2 Hysteresis of all Alarm Range:0~1000
Alarm 3 set value The same with I1
(For output 2) Set
Set
Output 1 low limit calibration Range:0 ~ 9999
Display if output2 is provided

Derivative time 2
The same with D1 (Used for mA and V output)
(For output 2)
Set Set
Output 2 Cycle time Output 1 high limit calibration Range:0 ~ 9999
The same with CYT1 (Used for mA and V output)
Set
Display Set
Output 2 low limit calibration The same with CLO1
If P2=0 Hysteresis for output 2 (Used for mA and V output)
The same with HYS1
ON/OFF control
Set
Set
Control gap 1 Set point of output 1 (Heating side) Output 2 high limit calibration The same with CHO1
=SV - GAP1 (Used for mA and V output)
(For output 1)
Set
Set
Control gap 2 Set point of output 2 (Cooling side) Retransmission low limit calibration The same with CLO1
(For output 2) =SV + GAP2
Set
Set
Retransmission high limit calibration The same with CHO1
Function lock
Set
Set Full run time of proportional motor
( Used for proportional motor valve Range:5~200 seconds
Return to “P1"
Set control output)
Used for programmable controller 0=Not wait
Levels entering available
LCK Level 1 Level 2 Level 3 Parameters which can be changed to wait continued operation Others=Wait value
(User Level) (PID Level) (Input Level) Set
0000 ◎ ◎ ◎ All parameters (Factory set value)
1111 ◎ ◎ ----- All parameters
0100 ◎ ◎ ----- All parameters except Level 3 Set
◎ ◎ Communication Protocol MODBUS RTU /
0110 ----- Parameters in Level 1
Selection MODBUS ASCII /
0001 ◎ ◎ ----- SV" and “LCK" TAIE
0101 ◎ ◎ ----- Only “LCK" Set
Communication Bits O _ 81 / O _ 82 / E _ 81 /
Configuration
7 Error Displays Set
E _ 82

ID number Range:0 ~ 255


Set
IN1E : Input 1 Error 2400 / 4800 / 9600 /
Baudrate
19200 / 38400 bps
Check whether input loop is opened or wiring incorrect. Set
SV compensation Range:-1000~1000
CJCE :Cold Junction Compensation Failed
Set
Check the compensation diode outside controller. PV compensation Range:-100.0~500.0
UUU1 : PV is above USPL Set
Unit of PV & SV C(℃) / F(℉) / A(Analog)
Check whether the input value is correct or not.
Set
NNN1 : PV is below LSPL PV Filter PV will responese faster if
PVFT is smaller.
Check whether the input value is correct or not. Set
Reserved
ADCF :A/D Convert Failed
Set
Controller needs to be repaired. Action mode Heat / Cool

RAMF :RAM Failed Set


Control algorithm PID / Fuzzy
Controller needs to be repaired.
Set
Frequency 50 / 60HZ
Set
Return to “INP1"
8 Specifications
Standard Spec.
Model FY400 FY600 FY700 FY800 FY900
Dimension 48X48mm 96X48mm 72X72mm 48X96mm 96X96mm
Supply voltage AC 85~265V , DC24V (Optional)
Frequency 50/60 HZ
Power Consumption approx 3VA approx 4VA approx 3VA approx 4VA approx 4VA
Memory Non-volatile memory E 2 PROM
Measurement input. Sample time : 250ms,0.2% of FS
TC K , J , R , S , B , E , N , T , W , PL2 , U , L
Input

RTD PT100 , JPT100 , JPT50


mA dc 4~20mA , 0~20mA
Voltage dc 0~1V , 0~5V , 0~10V , 1~5V , 2~10V , -10~10mV , 0~10mV , 0~20mV , 0~50mV , 10~50mV
DP Position 0000 , 000.0 , 00.00 , 0.000 (available for mA or Voltage dc input)
Main control output
SPST type SPDT type SPDT type SPDT type SPDT type
Output 1

Relay
3A , 220V , electrical life : 100,000 times or more(under the rated load).
Voltage Pulse For SSR drive. ON:24V , OFF:0V , maximum load current:20mA.
mA dc 4~20mA , 0~20mA .Maximum load resistance:560 Ω
Voltage dc 0~5V , 0~10V ,1~5V ,2~10V. Maximum load current:20mA.
SPST type SPDT type SPST type SPDT type SPDT type
Alarm 1
A , 220V , electrical life : 100,000 times or more(under the rated load).
Control algorithms PID , P , PI , PD , ON/OFF(P=0) , FUZZY
PID range P:0~200% , I:0~3600 Secs , D:0~900 Secs
Isolation Output terminal (control output , alarm ,transmission) and Input terminal are isolated separately.
Isolated resistance 10M Ω or more between input terminals and case(ground) at DC 500V ,10M Ω or more between output terminals and case(ground) at DC 500V
Dielectric strength 1000V AC for 1 minute between input terminals and case(ground) ,1500V AC for 1 minute between output terminals and case(ground)
Operating temperature 0~50℃
Humidity range 20~90% RH
Weight FY400 approx 150g ,FY600/700/800 approx 225g , FY900 approx 300g.
Display Height PV:7mm SV:7mm PV:7mm SV:7mm PV:14mm SV:10mm PV:7mm SV:7mm PV:14mm SV:10mm

Optional Spec.
Model FY400 FY600 FY700 FY800 FY900
Programmable 2 Patterns with 8 segments each .
RAMP/SOAK The 2 patterns can be linked together as 16 segments use.
For heating and cooling control use.
Output 2
Relay , SSR , 4~20mA , 0~20mA , 0~5V , 0~10V , 1~5V , 2~10V
SPST type SPDT type SPDT type SPDT type SPDT type
Alarm 2
3A , 220V , electrical life : 100,000 times or more(under the rated load).
Available Available Available Available
Not available
Alarm 3 SPST type SPST type SPST type SPST type
3A , 220V , electrical life : 100,000 times or more(under the rated load).
Display range of heater current : 0.0~99.9A , Accuracy : 1%FS
Heater Break Alarm
(HBA)
Included CT : SC-80-T(5.8mm dia , 0.0~80.0A) or SC-100-T(12mm dia , 0.0~99.9A)
Alarm relay : AL1
Available for PV or SV transmission
Transmission
4~20mA , 0~20mA , 0~1V , 0~5V , 0~10V , 1~5V , 2~10V
Remote SV Input 4~20mA , 0~20mA , 0~1V , 0~5V , 0~10V , 1~5V , 2~10V
Protocol : MODBUS RTU , MODBUS ASCII , TAIE
RS232 , RS485 , TTL
Communication
Baud rate: 2400 , 4800 , 9600 , 19200 , 38400 bps
Data bits : 8 , Stop bit : 1 or 2bit , Odd or Even parity.
WaterProof/DustProof IP65
9 Order Information

Model & Suffix codes


Commu- Input Water/Dust
Model Output1 Output2 Alarm TRS Remote SV Type Power
nication Proof
FY400 1 0 1 0 0 0 02 A N
FY400 48x48mm 0 None 00 None 0 None 0 None 0 None 0 None See Input A AC 85~265V N None
FY600 96x48mm 1 11 Relay 1 1 Set 1 4~20mA 1 4~20mA 1 RS232 Codes D DC 24V W IP65
Relay
FY700 72x72mm 22 Voltage Pulse 2 2 Sets 2 0~20mA 2 0~20mA 2 RS485
FY800 48x96mm 2 Voltage Pulse
(SSR Drive) 3 3 Sets A 0~5V A 0~5V 3 TTL
96x96mm (SSR Drive)
FY900 3 4~20mA B 0~10V B 0~10V A RS232_MODBUS
(STANDARD) 3 4~20mA 3
4 0~20mA C 1~5V C 1~5V B RS485_MODBUS
4 0~20mA 4
48x48mm AA 0~5V D 2~10V D 2~10V
P FY400 A 0~5V BB 0~10V A HBA *
P FY600 96x48mm
B 0~10V
P FY700 72x72mm CC 1~5V B HBA + AL2
P FY800 48x96mm C 1~5V C HBA + AL2+AL3
P FY900 96x96mm D 2~10V DD 2~10V
(RAMP/SOAK 5 1φSCR ZERO CROSS CONTROL
Programmable)
6 3φSCR ZERO CROSS CONTROL
7 Motor valve control
8 1φSCR PHASE ANGLE CONTROL
9 3φSCR PHASE ANGLE CONTROL *
HBA:Heater Break Alarm(HBA must use AL1 as alarm relay)

* Block means option functions with additional charge

Combination of options and models O Available X Not available


Options RAMP/SOAK Output 1 Remote DC 24V
Model PROGRAM 1φSCR_Z 3φSCR_Z Motor valve control 1φSCR_P 3φSCR_P
Output2 Alarm2 Alarm3 HBA TRS Communication
SV Power
FY400 O O X O X X O O X O O O O O
FY600 O X X O O X O O O O O O O O
FY700 O O X O O X O O O O O O O O
FY800 O X X O O X O O O O O O O O
FY900 O O O O O O O O O O O O O O
* HBA function and Remote SV function can not be specified in the same model
Input type table
TYPE CODE RANGE TYPE CODE RANGE TYPE CODE RANGE TYPE CODE RANGE
K1 01 0.0~200.0℃(392.0℉) K2 02 0.0~400.0℃(752.0℉) K3 03 0~600℃(1112℉) AN1 61 -10~10mV
K
K4 04 0~800℃(1472℉) K5 05 0~1000℃(1832℉) K6 06 0~1200℃(2192℉) 62 -2~2V

J1 07 0.0~200.0℃(392.0℉) J2 08 0.0~400.0℃(752.0℉) J3 09 0~600℃(1112℉) 63 -5~5V


J
J4 10 0~800℃(1472℉) J5 11 0~1000℃(1832℉) J6 12 0~1200℃(2192℉) 64 -10~10V

R R1 13 0~1600℃(2912℉) R2 14 0~1769℃(3216℉) AN2 71 0~10mV


S S1 15 0~1600℃(2912℉) S2 16 0~1769℃(3216℉) AN3 76 0~20mV

B B1 17 0~1820℃(3308℉) AN4 81
LINEAR

0~50mV -1999~9999
TC

E 18 E2 or
E1 0~800℃(1472℉) 19 0~1000℃(1832℉) 82 0~20mA
-199.9~999.9
N N1 20 0~1200℃(2192℉) N2 21 0~1300℃(2372℉) 0~1V or
83
-19.99~99.99
T T1 22 0.0~400.0℃(752.0℉) T2 23 0.0~200.0℃(392.0℉) T3 24 0.0~350.0℃(662.0℉) 84 0~5V or
-1.999~9.999
W W1 25 0~2000℃(3632℉) W2 26 0~2320℃(4208℉) 85 0~10V

PLII PL1 27 0~1300℃(2372℉) PL2 28 0~1390℃(2534℉) 86 0~5KR

U U1 29 -199.9~600.0℃(999.9℉) U2 30 -199.9~200.0℃(392.0℉) U3 31 0.0~400.0℃(752.0℉) 87 0~2V

L L1 32 0~400℃(752℉) L2 33 0~800℃(1472℉) AN5 91 10~50mV


JP1 41 -199.9~600.0℃(999.9℉) JP2 42 -199.9~400.0℃(752.0℉) JP3 43 -199.9~200.0℃(392.0℉) 92 4~20mA
JPT
100 JP4 44 0~200℃(392℉) JP5 JP6 46
45 0~400℃(752℉) 0~600.0℃(1112℉) 93 1~5V

47
RTD

DP1 -199.9~600.0℃(999.9℉) DP2 48 -199.9~400.0℃(752.0℉) DP3 49 -199.9~200.0℃(392.0℉) 94 2~10mV


PT
100 DP4 50 0~200℃(392℉) DP5 51 0~400℃(752℉) DP6 52 0~600℃(1112℉)

JPT JP.1 53 -199.9~600.0℃(999.9℉) JP.2 54 -199.9~400.0℃(752.0℉) JP.3 55 -199.9~200.0℃(392.0℉)


50 JP.4 56 0~200℃(392℉) JP.5 0~400℃(752℉) JP.6 58
57 0~600℃(1112℉)

No.FYEV4 2005.12