TOTAL LOAD ( KW) 360 TOTAL LOAD (W) 360000 C.B SELECTION :- P=1.73*Irated*V*P.F V 400 P.F 0.8 Irated 650.2890173 I c.b = 1.25* Irated 812.8612717 C.B ( from catalogue ) from catalogue BAHRA 800
CABLE SELECTION :-
D1= Ambient temperature Derating factor from catalogue BAHRA AT 45 C 0.96
D2= Grouping factor from catalogue BAHRA AT 45 C 0.98 DF= D1*D2*D3*D4 0.9408 I Cable = I C.B / DF 864.0107054 2(3*185mm2) CABLE ( UNARMOURED ) from catalogue BAHRA CU/XLPE/PVC
VOLTAGE DROP CALCULATION:-
V.D = ((mv/amp/m)/1000) * I rated *L