You are on page 1of 1

PUMPS ( PS1 )

TOTAL LOAD ( KVA) 288.0


TOTAL LOAD ( KW) 360
TOTAL LOAD (W) 360000
C.B SELECTION :-
P=1.73*Irated*V*P.F
V 400
P.F 0.8
Irated 650.2890173
I c.b = 1.25* Irated 812.8612717
C.B ( from catalogue ) from catalogue BAHRA 800

CABLE SELECTION :-

D1= Ambient temperature Derating factor from catalogue BAHRA AT 45 C 0.96


D2= Grouping factor from catalogue BAHRA AT 45 C 0.98
DF= D1*D2*D3*D4 0.9408
I Cable = I C.B / DF 864.0107054
2(3*185mm2)
CABLE ( UNARMOURED ) from catalogue BAHRA
CU/XLPE/PVC

VOLTAGE DROP CALCULATION:-

V.D = ((mv/amp/m)/1000) * I rated *L


(mv/amp/m) from catalogue BAHRA 0.27
L ( cable length ) 35
V.D = ((mv/amp/m)/1000) * I rated *L 6.145231214
V.D 1.54%
V.D FOR 2 CABLES 0.77%

You might also like