Fundamentals of
Hardened Concrete

Blocks
Monolithic concrete with a compressive strength
in excess of 3500 pounds per square inch (psi)
is watertight, except at any irregularities in the
structural element. Typical locations where irreg-
ularities occur include overhead decks, floors,
updates and information
and walls that have cracks, honeycombs, joints,
mechanical/electrical penetrations, and form-tie on structural materials
supports. Hairline cracks in excess of 1/1000 of
an inch (i.e. 1 mil) commonly leak water if subject
to hydrostatic pressure. Water leakage rate and
volume, or quantity, is related to pressure and
crack width.
®
Concrete Cracking
When concrete is freshly cast, its temperature
is often between 60º and 90º F. Depending on
the in-situ form, materials, temperature, envi-

R E
U
Monolithic concrete with a compressive strength in excess
ronmental conditions, and composition of the righ
t
of 3500 PSI ispywatertight, except at any irregularities.

T
mix design, concrete hydration may generate Co
significant additional heat. Thermal expansion occur from outside to inside

C Proper Procedures and


of the semi-plastic structural element will occur face, allowing air or dissolved

e for Interception
U
and, depending upon local restraint, may cause oxygen in the water to interact
micro-cracking. with the steel, all three of the Protocol
n
ziGrouting
R
Depending on local restraints, minute small critical items are now available

T
cracks (defects within the cement/aggregate for corrosion to occur.
matrix typically so small they can’t be seen by a
In addition to corrosion, water
g
S
the naked eye) develop externally and inter- leakage can bring salt and vari-
nally. After the forms are removed, the concrete a
ous stray minerals that can exacerbate other issues By Brent Anderson, P.E.
continues to shrink from both cooling and loss
of water. This process varies with environmental m
within the concrete, e.g., sulfate attacks. External
issues with water leakage are many – ice buildup,
conditions and may create cracks capable of slip problems, treatment of contaminated water,
water leakage within hours of form removal, and potential mold issues.
and within days after wet curing. For most
structural elements less than 14 inches thick, Fundamentals of
it takes about 5 years for shrinkage to subside.
In this time, the cracks initiated by thermal
Interception Grouting
contraction become much larger. These cracks, Brent Anderson, P.E., is the
Directional Drilling
depending on reinforcing, sectional dimen- Moisture Control Solutions Team
sions, mix design, and restraint conditions, The objective of interception grouting is to Leader at Structural Technologies.
can be as large as 5 to 50 mils. If subjected make the concrete element monolithic. This He serves on ACI 332 Residential
to water under hydrostatic pressure, serious can be achieved by pressure injecting a resin- Concrete and previously served on
leakage will occur. ous material through one or both concrete ACI 515 Protective Coatings for
element faces (surface mounted ports), or by Concrete. Brent can be reached at
Ingredients for Corrosion
drilling at a 45-degree offset to the defect and banderson@structuraltec.com.
Corrosion in reinforced concrete requires three injecting into the defect in the center third
basic ingredients; oxygen, water, and an elec- of the concrete element section (interception
trolyte medium. Fundamental to corrosion grouting). The importance of drilling into the
mitigation is minimizing at least one of these center of the concrete element is that, during
three basic ingredients. grouting, the resinous material should flow
equally to the inside and outside face of the
Issues from Leakage
concrete section in a uniform manner. If drill-
One of the biggest concerns with water leakage in ing into the interior third of the section, grout
heavily reinforced concrete is that the time for the flow will not extend to the exterior. Drilling
onset of corrosion is shortened. It is well under- into the outer third of the section will unlikely
stood that if you eliminate oxygen and water from allow grout migration to the interior. By proper
the immediate environment around reinforcing placement of drill holes, grout flow will inter-
steel, corrosion is generally minimal and essen- sect from bottom-to-top or side-to-side with a
tially mitigated. When through-element cracks relatively high degree of reliability. Long-term

STRUCTURE magazine 23
Typical water leakage paths.

grouting solutions intercept the defect in These are often questions as to whether or not
the center; short-term solutions allow shal- some kind of acidic material (e.g., phosphoric ®
It is important to intercept the crack at the center

E
low drill depth holes. In addition to crack or muriatic) should be used. Generally, it is third so that the resinous material flows equally to
interception at the concrete element’s center an acceptable approach, but it should come the inside and outside face of the concrete section.

R
third, most quality contractors alternate with some safety precautions and the use of
directional drilling on each side. proper personal protective equipment to keep

U
acid away from the htface. small electric operated pumps, and high
Drill Hole Spacing yrig

T
Acid washing Copthe drill hole and the crack volume air driven or piston driven pumps.
Generally, the rule of thumb is that drill hole improves the bond ability of any type of resin Most hand and small electric driven pumps are

C
spacing should be one half to two-thirds the that is injected into the crack later. If the crack for single component resins. The larger piston

e
U
concrete element thickness. This allows an has debris and mineral deposits, the effective- pumps can be used for 1-3 components.
overlap of about 20 to 30 percent between ness of the grout will not be as monolithic
i n Small electric pumps require minimal

R
drill holes. Drill hole spacing up to the width as needed, and secondary or minor leakage maintenance. However, after several uses the
z
T
of wall element can be done if cracks are rela- could still occur. pumps are discarded and new ones are pur-
tively large – i.e. 50 to 100 mils wide.
g a chased. Others prefer to buy the large piston

S
Pressure
Interior and/or exterior steel can influence drive, both single and multi-ratio. What’s
the drilling angle based on its density and a
Interception grouting should be done in a way important is that these pumps have a capac-
location. Angles of 30º to 60º are not uncom-
mon provided that interception drilling is m
that the internal hydraulic pressures of the grout
never exceed the tensile strength of the concrete.
ity of ¼ gallon per minute and have pressure
capabilities up to 750 psi.
done in the wall center. Because cracks vary The tensile strength of concrete is 10% of the
Injection Packers
in direction, drilling should be 20 to 25 per- compressive strength. Most concrete that inter-
cent deeper for interception grouting than ception grouting will be performed on will have There are basically three types of injection
what the typical calculations dictate. Drill a tensile strength of 300 to 500 psi. It is recom- packers – button head, grease zerk, and ball
hole diameter is not critical and can be left mended not to use pumping grout pressures valve quick connect. The advantage of the
to contractor preference. in excess of 500 psi. In so doing, the concrete grease zerk packers is that they are inex-
surface may spall where the drill holes exist and/ pensive and can be discarded after one use.
Cleaning
or the pressure may hydraulically fracture the Button head packers are similar and usually
Just as important as intercepting the crack concrete and create additional cracks. discarded after one use. The ball valve quick
at the element midsection is cleaning the A word of caution, use of high viscosity connect packers are more expensive, but can
drill hole of debris prior to setting any ports. resins may lead to internal damage of the be reused multiple times. Another advantage
Injection drill holes should be blown out with concrete. High viscosity resinous materials of the ball valve is that you can open and
high pressure air and then flushed thoroughly are not as user friendly as low viscosity injec- close the valve to monitor water or grout flow.
with a water jet. Some contractors even push tion materials. For comparison, water has a Button head and ball valve quick connect
and flush a wire bristle brush down the drill viscosity of one centipoise – so grouts that packers generally do not restrict grout flow
hole and scrub the area of intersection to have values of 50 to 300 centipoises means and increase pump gauge pressure during
remove surface debris. that they are 50 to 300 times more viscous application. Disadvantages of zerk packers
than water. are that they cannot be opened and closed to
Crack Flushing
It is not uncommon for contractors who do monitor grout movement and they are very
The next important aspect is to put a port on not have a good understanding of viscosity restrictive to grout flow, requiring about 100
the surface and flush the crack. Flushing the and crack width to use resinous grouts with to 200 psi gauge pressure just to move most
crack is important for two reasons: 300 upwards to 500 centipoises and pressures grouts through them.
1) To push out any mineral deposits up to 3000 psi to accomplish placing resinous
(clay, silt) that may have accumulated material within the crack. Causes of Premature
in the crack, and
2) If water is pumped and does not make
Grout Delivery Grout Failure
it to the surface of the concrete, grout There are three types of delivery systems gen- There are 4 basic causes of premature grout
will not make it through either. erally utilized: small hand operated pumps, failure:

STRUCTURE magazine 24 September 2015


CONSTRUCTION CEMENT

FA S T ER
STRONGER
MORE DURABLE
3000 PSI IN 1 HOUR
®

E
To achieve the right mixing ratio of water to grout,
a multi-ratio pump should be used.

R
Most quality contractors alternate directional
drilling on each side.
contractors have found that the only

U
viable way to ighseal cracks with unreactive
t

T
1) Improper drilling and delivery pyr backside grouting method.
grouts isCothe
It is not uncommon for contractors to 3) Excessive wall movement

C
drill directly into the crack or too close to Excessive movement is most prevalent

ADVERTISEMENT–For Advertiser Information, visit www.STRUCTUREmag.org


e
U
the surface. By doing this, a seal is created when the concrete is subject to out-
that is 1/3 to ½ of the crack depth and door temperatures – i.e. exterior tanks,
i n Specified

R
water under hydrostatic pressure is still retaining walls, exposed foundations,
z Worldwide

T
within the concrete element. Very little etc. Most resins have some degree of
flexural movement causes leakage to recur. a
flexibility. It is not uncommon that
g
S
2) Inadequate mixing ratio of water to during warm to cold cycles, a 5 mil
grout during application a
crack will open to a 10 mil crack. Most
Most contractors are taught by manu-
facturers that pre-wetting the crack m resinous grouts, even though they are
called flexible, cannot sustain repeated
prior to urethane grout injection is all opening and closing of the crack and
that is needed to activate the material. will fail. Grout adhesion to the substrate
This would likely be the case of the wall may fail during expansion and contrac-
4 to 6-inches or less in thickness. Wall tion of the crack if surface contaminants
and floor sections greater than 12 inches on the grout sidewall are prevalent.
would not fit the criteria however, and 4) Chemical attack
a multi-ratio pump for injecting water Chemical attack is very common in the
reactive urethane grouts should be used. industrial environment, and this type
Some contractors prefer to use two small of issue usually takes several years to
ADVANCED TECHNOLOGY
electric pumps – one to inject urethane, work its way through the grout matrix. • High bond strength
one to inject water – and then rotate a Residue hydrocarbons within water will
few strokes of water to several strokes commonly attack many of the grout for- • Low shrinkage
of grout thinking they are getting good mulations. This is exacerbated if chemical
cross-polymerization of water to urethane. attack and thermal expansion/contrac-
• High sulfate resistance
While this may seem a viable solution tion are occurring simultaneously. • Great freeze thaw durability
because the first grout that comes to
the surface appears to be fully reacted, • Long life expectancy
it is very common to have areas of water
Conclusion
• 65% lower carbon footprint
deprived urethane grout within cracks It is important for engineers and contractors
and other defects. When these conditions alike to remember that the grout viscosity
are subjected to high temperatures in the needs to match up with the crack width, and
environment (in excess of 100 to140º the grout chemical resistance needs to match
Available in
Fahrenheit), it is common to see a brown, the exposure. The most successful grouting Bags and Bulk
unreacted urethane resin extrude from the contractors have a good knowledge of chemi-
cracks anywhere from 2 months to 2 years cal resistance and have good field experience
after the initial grouting. This urethane in developing techniques that allow them to 800-929-3030
resinous material has now contaminated get low viscosity grouts to migrate deeply
the crack for future injection. Many within finely cracked concrete.▪ ctscement.com
STRUCTURE magazine 25 September 2015