Answer.
breakdown occurs.
Answer.
What is meant by condition monitoring?
Answer.
tested.
Answer.
regularly and a record kept of this, and any deterioration can be seen and
Answer.
Requirements for condition monitoring are; insulation tests, temperature
readings and vibration tests and an on going record of the results kept.
Answer.
Answer.
Alternator air ducting should be checked for blockages and that they are
pressure air?
Answer.
When cleaning windings with low-pressure air, care should be taken that
Answer.
Alternator slip rings should be checked for even wear and that carbon
brushes have free movement in their boxes. Correct brush pressure can
be checked a pull type spring balance ( normal pull around 1 – 1.5 kg is
lengths should be no less than 2cm or spring pressure will be too little,
Answer.
reasonable value which has become steady during the drying out period,
it’s windings should then be coated with high quality air drying
insulating varnish. Should the IR values remain low, this could mean the
made sure that the windings are suitably heated to prevent internal
Answer.
circuits, pilot lights and control circuits are involved, they may be
Answer.
Before starting work, the actual equipment should be checked with a live
line detector, not only between phases but also between phases and
earth.
Answer.
Answer.
Alignment of contacts are checked by removing the arc chutes on ACB’s
to expose the contact assembly. On some high voltage designs, the chute
Answer.
To dress copper contacts, a fine file or fine glass paper can be used.
Answer.
The maintenance carried out on silver plated contacts is very little but if
of contacts.
Answer.
Dash pots are checked for correct oil levels. Particular care should be
Answer.
What does dirt on motor insulation cause?
Answer.
Dirt on motor insulation causes two things, firstly it may in time cause
eventually a burn out. Secondly, the vent ducts may become clogged
Answer.
Answer.
A layer of dust with totally enclosed motors can cause overheating as
insulator.
Why must the air pressure be less than 1.75 bar when blowing out
motors?
Answer.
Air pressure must be less than 1.75 bar when blowing out motors so that
Answer.
bearings.
Answer.
Answer.
breakdowns.
What could cause damaged insulation of the stator winding’s insulation?
Answer.
Answer.
Answer.
Answer.
After changing bearings on a motor, checks that are made are; for signs
Answer.
Answer.
Bearings should be renewed as a planned maintenance policy, or per
manufacturers instructions.
Answer.
The procedure for a bearing that cannot be replaced, is that they should
paraffin, then cleaned in a jet of clean, dry compressed air. Once dried,
the bearings must be lightly oiled. Any traces of metal particles from the
Also carefully examine raceways and rolling elements for sins of wear
and damage.
Answer.
If a bearing sticks, it must be rewashed and inspected, if it sticks after
Answer.
roller elements, any signs of metal particles from the bearing or sticking
bearings.
Answer.
one third to half full, as over greasing causes churning and friction,
If the bearing housing has no vent hole what must be done before
regreasing?
Answer.
Answer.
The application that requires special greases for motor bearings are
when the motors are used for fan motors in refrigerated compartments
and laminated core, also make sure all core ventilating ducts are clear.
Answer.
revarnishing.
Answer.
Stator windings are usually dried out with low power electric heaters or
What tests are carried out before re-varnishing?
Answer.
Tests carried out before revarnishing are IR tests and if they remain high
Answer.
All moving contacts used in control gear have what is known as a wipe
Answer.
If the wipe action is lost from moving contacts, a build up of oxide could
Answer.
Answer.
contacts.
Answer.
Answer.
What should be checked in high vibration areas?
Answer.
Answer.
Answer.
When replacing lamps or tubes, it must be ensured that the supply is off.
What can arc flash cause personnel?
Answer.
Arc flash can cause personnel blindness, burns and can cause fires.
Answer.
Answer.
Answer.
With portable cargo lighting, it should be checked that cables and supply
Answer.
enclosure?
Answer.
If the lamps glass is cracked in a flame proof light fitting, a complete
Answer.
distortion of the flame path, damage seals and cause excessive stress on
lamp glasses.
Answer.
What is the maximum voltage regarded as reasonably safe for portable
power tools?
Answer.
What is the maximum shock voltage to earth for a centre tapped 110V
tool transformer?
Answer.
The maximum shock voltage to earth for a centre tapped 110V tool
transformer is 55V.
What is the first thing that must be done when finding a victim of
electric shock?
Answer.
The first thing that must be done when finding a victim of electric shock
Answer.
Two methods of how to do this are, switch off the supply or remove the
Answer.
Details of first aid to be carried out in the event of electric shock can be
Answer.
operate?
Answer.
Answer.
All fuses should be of the non-renewable cartridge type and capable of
supplies.
Answer.
value.
Answer.
windings.
Answer.
An earth return path must have low impedance so all of the earth fault
Answer.
The value that earth fault leakage breakers are set to trip, are at currents
as small as 40 –50mA.
Answer.
The normal range of welding current is from 50 – 600 Amps.
welders?
Answer.
Answer.
The type ‘B’ electrode holder is better than the type ‘A’ because no live
parts are accessible to the standard test finger and when the electrode is
fitted, it'’ non-coated end does not protrude from the electrode holder.
Answer.
Answer.
Answer.
Answer.
Answer.
The only way of guaranteeing the prevention of interference is keeping
as far away as possible equipment that causes interference but this is not
interference?
Answer.
Answer.
Answer.
Cables that should not be run together are sensitive and non-sensitive
cables.
Answer.
Answer.
prime mover, own fuel supply tank, starting equipment and switchboard,
Answer.
electrical failure.
Why are both an emergency generator and batteries recommended?
Answer.
the moment of total power failure there is not a black out, as a battery
Answer.
minimum of 3 hours.
Answer.
Testing of emergency power supplies are done weekly on a normal basis
where practical.
What are the special interlocks fitted to the main and emergency
Answer.
The special interlocks that are fitted to the main and emergency circuit
Answer.
Answer.
fuse in the auto start panel which supplies the undervoltage or under
frequency relay.
What is the only way to test the performance of the emergency power
supply?
Answer.
power.
What equipment is usually fed by batteries?
Answer.
Answer.
Two types of battery cell are the lead acid and the alkaline cell.
Answer.
Answer.
Answer.
Answer.
The two types of cell must be kept separate because rapid electrolyte
corrosion to metal work can take place and certain damage to batteries
can occur.
What does the value of the electrolyte specific gravity indicate in lead
acid batteries?
Answer.
the battery, i.e., SG of 1270 – 1285 when fully charged and 1100 when
discharged.
Answer.
charging?
Answer.
degrees C.
Answer.
The only indication of a fully charged alkaline cell is when the voltage
Answer.
If the cell plates are exposed to air, the life of the battery will rapidly
reduce.