PACKAGED AIR CONDITIONERS PAC/2023/R0

March, 2023
APMR52115 Bulletin # 075/2021 A

Unit Tag PR/PAC/08TR/2023 Prepared By L3020-110-12658


Customer RAHUL KAUSHIK Reference
Project HYGIENIC PROECTS AT MUSCAT Print Date Sunday, 18 June, 2023

INPUT DATA
Required Capacity 8 TR Leaving Wet Bulb Temperature 13.72 °C Altitude 0m
Return Air Flow Rate 1415.8 l/s Return Air DBT / WBT / RH 24 °C / 19 °C / 63% Ambient Temperature 46 °C
Fresh Air Flow Rate 70.8 l/s Fresh Air DBT / WBT / RH 46 °C / 20 °C / 6% Quantity 1

PERFORMANCE DATA
Calculated Capacity * 8.03 TR Compressor Power Input 10.45 kW
Sensible Capacity * 18.71 kW Sensible Heat Ratio 0.66
Entering Air Flow Rate 1486.6 l/s Air Face Velocity 1.65 m/s
Entering Air DBT / WBT / RH 25.05 °C / 19.05 °C / 57% EER @ AHRI Conditions 6.7
Leaving Air DBT / WBT / RH 14.67 °C / 13.69 °C / 90%
Air Pressure drop through Evap. Coil 41 Pa

* Capacity given is gross capacity which does not include the effect of evaporator fan motor heat.

PHYSICAL DATA
CONDENSER
Compressor Type Scroll Refrigerant R-410A Fan Code / Quantity D-550 / 2
Compressor Model ZP061 Quantity 2 Motor Size / Quantity 0.25 kW / 2
Rows / Fin Spacing 2 / 1.6 mm Coil Face Area 2.48 m² Fin Material Aluminum fins

EVAPORATOR
Coil Size (H x L) 635 mm x 1422 mm Rows / Fin Spacing 3 / 2.1 mm Fin Material Aluminum fins
External Static Pressure 500 Pa Total Static Pressure 580 Pa Motor Size 2.2 kW
Fan Model SYT 12-12 / 1 (Non Standard motor size, please consult SKM)

Rotational Speed 1219 rpm (RPM out of range, please consult SKM)
OCTAVE BAND IN-DUCT SOUND POWER LEVEL - SUPPLY FAN
Frequency Hz 63 125 250 500 1000 2000 4000 8000 Total

Lw dB 82.9 85.6 78.9 77.6 77.1 75.1 71.0 66.9 89.0

LwA dB(A) 56.9 69.6 70.3 74.4 77.1 76.3 72.1 65.8 82.1

ELECTRICAL DATA
Power Supply 380V-415V/3Ph/50Hz Compressor RLA LRA Cond. Fan Motor(each) FLA 0.87
Qty
Cond. Fan Motor(each) LRA 2.61
MCA 30 ZP061 (each) 2 11 64 Evap. Fan Motor FLA 4.8
MFA 50
Evap. Fan Motor LRA 27.1

Note :- • Power input mentioned here is at rated condition only, and should not be used for cable/fuse selection.
• MCA/MFA values given in the catalogue electrical data page should be refered for the same.
• For non standard units MCA/MFA values, please consult SKM engineering department.
• Evaporator motor electrical data is based on 4 poles, single speed.

SKM Air Conditioning LLC Email : sales.skm@skmaircon.com


P.O. Box: 6004, Sharjah, UAE Tel: +971 6 5143333 1 Visit us at: www.skmaircon.com
Fax: +971 6 5143300
PACKAGED AIR CONDITIONERS PAC/2023/R0
March, 2023
APMR52115 Bulletin # 075/2021 A

Unit Tag PR/PAC/08TR/2023 Prepared By L3020-110-12658


Customer RAHUL KAUSHIK Reference
Project HYGIENIC PROECTS AT MUSCAT Print Date Sunday, 18 June, 2023

Drawings

Loading Points

Unit A1 A2 A3 A4 Total
kg 112 138 110 115 475

Sound Data
SOUND PRESSURE LEVEL in dBA ref 2x10-5 Pa in free field
SPECTRUM PER OCTAVE BAND dB(A)

63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz Total


@ 1 meter 53.4 51.2 41.5 66.1 69.1 68.7 60.3 52.4 73.3

Note: Sound Pressure Level according to ISO 3744, full load operation at 95ºF (35ºC) ambient and 44ºF (6.7ºC) / 54ºF (12.2ºC) evaporator leaving and
entering water temperatures.

Options : -

SKM Air Conditioning LLC Email : sales.skm@skmaircon.com


P.O. Box: 6004, Sharjah, UAE Tel: +971 6 5143333 2 Visit us at: www.skmaircon.com
Fax: +971 6 5143300

You might also like