APMR52115 Bulletin # 075/2021 A
INPUT DATA
Required Capacity 8 TR Leaving Wet Bulb Temperature 13.72 °C Altitude 0m
Return Air Flow Rate 1415.8 l/s Return Air DBT / WBT / RH 24 °C / 19 °C / 63% Ambient Temperature 46 °C
Fresh Air Flow Rate 70.8 l/s Fresh Air DBT / WBT / RH 46 °C / 20 °C / 6% Quantity 1
PERFORMANCE DATA
Calculated Capacity * 8.03 TR Compressor Power Input 10.45 kW
Sensible Capacity * 18.71 kW Sensible Heat Ratio 0.66
Entering Air Flow Rate 1486.6 l/s Air Face Velocity 1.65 m/s
Entering Air DBT / WBT / RH 25.05 °C / 19.05 °C / 57% EER @ AHRI Conditions 6.7
Leaving Air DBT / WBT / RH 14.67 °C / 13.69 °C / 90%
Air Pressure drop through Evap. Coil 41 Pa
* Capacity given is gross capacity which does not include the effect of evaporator fan motor heat.
PHYSICAL DATA
CONDENSER
Compressor Type Scroll Refrigerant R-410A Fan Code / Quantity D-550 / 2
Compressor Model ZP061 Quantity 2 Motor Size / Quantity 0.25 kW / 2
Rows / Fin Spacing 2 / 1.6 mm Coil Face Area 2.48 m² Fin Material Aluminum fins
EVAPORATOR
Coil Size (H x L) 635 mm x 1422 mm Rows / Fin Spacing 3 / 2.1 mm Fin Material Aluminum fins
External Static Pressure 500 Pa Total Static Pressure 580 Pa Motor Size 2.2 kW
Fan Model SYT 12-12 / 1 (Non Standard motor size, please consult SKM)
Rotational Speed 1219 rpm (RPM out of range, please consult SKM)
OCTAVE BAND IN-DUCT SOUND POWER LEVEL - SUPPLY FAN
Frequency Hz 63 125 250 500 1000 2000 4000 8000 Total
LwA dB(A) 56.9 69.6 70.3 74.4 77.1 76.3 72.1 65.8 82.1
ELECTRICAL DATA
Power Supply 380V-415V/3Ph/50Hz Compressor RLA LRA Cond. Fan Motor(each) FLA 0.87
Qty
Cond. Fan Motor(each) LRA 2.61
MCA 30 ZP061 (each) 2 11 64 Evap. Fan Motor FLA 4.8
MFA 50
Evap. Fan Motor LRA 27.1
Note :- • Power input mentioned here is at rated condition only, and should not be used for cable/fuse selection.
• MCA/MFA values given in the catalogue electrical data page should be refered for the same.
• For non standard units MCA/MFA values, please consult SKM engineering department.
• Evaporator motor electrical data is based on 4 poles, single speed.
Drawings
Loading Points
Unit A1 A2 A3 A4 Total
kg 112 138 110 115 475
Sound Data
SOUND PRESSURE LEVEL in dBA ref 2x10-5 Pa in free field
SPECTRUM PER OCTAVE BAND dB(A)
Note: Sound Pressure Level according to ISO 3744, full load operation at 95ºF (35ºC) ambient and 44ºF (6.7ºC) / 54ºF (12.2ºC) evaporator leaving and
entering water temperatures.