You are on page 1of 2

WATEROUS COMPANY Issued: April, 1965

South St. Paul, Minnesota 55075 CL & CLS SERIES CENTRIFUGAL FIRE PUMP PERFORMANCE SHEET Revised: 5/17/21
(Speed and Power Data)

IMPELLER DIAMETER - 7-1/2 INCH EYE DIAMETER - 4-1/4 INCH


IMPELLER COMBINATIONS
SERIES-
PUMP TEST 70980 & 70981
PARALLEL
CLV & CLR CLS
NO. STAGES
GPM PSI RPM HP RPM HP RPM HP RPM HP RPM HP

500 150 4775 62 4773 64


(1893 L/min) (10 bar) (46 kw) (48 kw)
350 200 5125 64 5095 64
(1325 L/min) (14 bar) (48 kw) (48 kw)
250 250 5622 71 5563 72
(946 L/min) (17 bar) (53 kw) (54 kw)
500 165 4938 68 4948 73
(1893 L/min) (11 bar) (51 kw) (53 kw)

80 350 6600 95 6505 94


(303 L/min) (24 bar) (71 kw) (70 kw)

20 80 3069 9
(76 L/min) (6 bar) (7 kw)

100 100 3441 15


(379 L/min) (7 bar) (11 kw)

Pump Curve No. 650204 Page 1 of 2 Form No. F-1115


WATEROUS COMPANY
South St. Paul, Minnesota 55075 CL & CLS SERIES CENTRIFUGAL FIRE PUMP PERFORMANCE SHEET Revised: 3/10/98
(Lift and Elevation Data)

IMPELLER COMBINATIONS
PUMP 70980 & 70981
TEST CLS CLV, CLR & CLD

Connection Piping (” Hg)


Maximum Allowance for
INTAKE

10’ Lift @ 2000’ Alt.


HOSE DIA
(20 FT

10 Ft (3 m) Lift

10 Ft (3 m) Lift
Maximum Lift

Maximum Lift
Maximum Alt

Maximum Alt
[6 M]

Sea Level

Sea Level
GPM PSI LENGTH)

(Ft)

(Ft)
500 150 4 in. 13.8* 3300 3 15.8* 4600
(1893 L/min) (10 bar) (102 mm) (4.2 m) (1000 m) (76 mm) (4.8 m) (1,400 m)
500 150 4-1/2 in. 14.9* 5000 5 16.7* 6800
(1893 L/min) (10 bar) (1/4 mm) (5 m) (1524 m) (127 mm) (5 m) (2073 m)

*Based on the use of a 30’-0’’ intake hose


direct connection to pump intake

Data shown is generally applicable. Performance for a spe-


cific configuration of pump may vary from that shown. See
form F-1096 (latest revision).

Friction loss in hose and strainer is based on data in NFPA


Standard No. 1901, 1991 edition, Table 4-1.3.1(b)

Page 2 of 2 Form No. F-1115