Node: 2.
Description: . A3
S
Design Intent: H
Risk Matrix Severity. E
Deviation Causes Consequences Safeguards Recommendation
C L R Cat. A
1.1 No Flow into tank
1.2 No flow out of Tank 1. PCV-1101 Fail Closed dan menutup line 252-A-3" Kehilangan suplai Fuel Gas
ke Sub Header FG Scrubber V-1104
2. Manual Valve 4" A2RF tidak sengaja tertutup dan Kehilangan suplai Fuel Gas
menutup line 252-A-3" ke Sub Header FG Scrubber
V-1104
3. ILCV 1101A-2 Fail Closed 1. Meningkatnya level HP Separator V-1101-A, cairan 2 2 4
terbawa ke V-1104, meningkatkan tekanan V-1104,
cairan terbawa ke Flare Sub Header, level tinggi pada
Flare KO Drum (V-1107), cairan terbawa ke cerobong
Flare Proses, tumpah, terbakar pada Pool Fire (S)